Installation Data Sheet...............................................................................................................38
2
Page 3
Introduction
IMPORTANT SAFETY DATA:
Please read this entire Owner’s Manual before installing or operating your ENVIRO Pellet
Stove. Failure to follow these instructions may result in property damage, bodily injury or
even death. Any unauthorized modification of the appliance or use of replacement parts not
recommended by the manufacturer is prohibited.
Contact your local building or fire official to obtain a permit and any information on installation restrictions
and inspection requirements for your area. All local regulations, including those referring to national and
European Standards need to be complied with when installing this appliance.
To prevent the possibility of a fire, ensure that the appliance is properly installed by adhering to the
installation instructions. An ENVIRO dealer will be happy to assist you in obtaining information with
regards to your local building codes and installation restrictions.
The stove’s exhaust system works with negative combustion chamber pressure and a slightly positive
chimney pressure. It is very important to ensure that the exhaust system be sealed and airtight. The
ash pan and viewing door must be locked securely for proper and safe operation of the pellet stove.
Operating with door open could cause a fire inside the house as well as the release of carbon monoxide
into the living space.
Carbon monoxide is a colorless and odorless gas, to prevent it from poisoning you or your family know the
symptoms of carbon monoxide poisoning: headache, dizziness, weakness, sleepiness, nausea, vomiting,
and confusion. Carbon monoxide reduces the blood’s ability to carry oxygen. Low blood oxygen levels can
result in loss of consciousness and death.
Do not burn with insufficient combustion air. A periodic check is recommended to ensure proper combustion
air is admitted to the combustion chamber. Setting the proper combustion air is achieved by adjusting
the slider damper located on the left side of the stove.
When installing the stove in a mobile home, it must be electrically grounded to the steel chassis of the
home and bolted to the floor. Make sure that the structural integrity of the home is maintained and all
construction meets local building codes.
Consider all large air moving devices when installing your unit and provide room air accordingly. NOTE:
Extractor fans when operating in the same room or space as the appliance, may cause problems. Limited
air for combustion may result in poor performance, smoking and other side effects of poor combustion.
Soot or creosote may accumulate when the stove is operated under incorrect conditions such as an
extremely rich burn (black tipped, lazy orange flames).
Be sure to maintain the structural integrity of your home when passing a vent through walls, ceilings, or
roofs. It is recommended that the unit be secured into its position in order to avoid any displacement. This
appliance must be installed on a floor with an adequate load bearing capacity. If an existing construction
doesn’t meet these prerequisite, suitable measures (e.g. load distributing plate) shall be taken to achieve
it.
FRESH AIR: Outside Fresh Air connection is optional. Fresh Air must be connected to all units installed in
Mobile Homes and Air Tight Homes (R2000) or where required by local codes.
If you have any questions with regards to your stove or the above-mentioned information, please feel
free to contact your local dealer for further clarification and comments.
3
Page 4
Introduction
SAFETY WARNINGS AND RECOMMENDATIONS:
Caution: Do not connect to any air distribution duct or system. Do not burn garbage or flammable fluids
such as gasoline, naphtha or engine oil. Unit hot while in operation. Keep children, clothing and furniture
away. Contact may cause skin burns.
Warning: Parts of the appliance, especially the external surfaces, will be hot to touch when in operation
and due care will need to be taken. Never place wood, paper, furniture, drapes or other combustible
materials within 80cm (31½”) of the front of the unit, 20cm (7⅞”) from each side, and 10cm (4”) from
the back of the unit. Do not let children or pets touch it when it is hot.
To prevent the possibility of a fire, ensure that the appliance is properly installed by adhering to the
installation instructions. An ENVIRO dealer will be happy to assist you in obtaining information with
regards to your local building codes and installation restrictions.
FIRE EXTINGUISHER AND SMOKE DETECTION: All homes with a pellet burning stove should have
at least one fire extinguisher in a central location known to all in the household. Smoke detectors should
be installed and maintained in the room containing the stove when installing and operating a pellet
burning appliance. If it sounds the alarm, correct the cause but do not deactivate. You may choose to
relocate the smoke detection devise within the room; DO NOT REMOVE THE SMOKE DETECTOR FROM
THE ROOM.
CHIMNEY OR RUN AWAY FIRE: Call local fire department (or dial 911). Close the draft fully. Examine
the flue pipes, chimney, attic, and roof of the house, to see if any part has become hot enough to catch
fire. If necessary, spray with fire extinguisher or water from the garden hose. IMPORTANT: Do not
operate the stove again until you are certain the chimney and its lining have not been damaged.
FUEL: This pellet stove is designed and approved to only burn wood pellet fuel with up to 3% ash
content. Dirty fuel will adversely affect the operation and performance of the unit and may void the
warranty. Check with your dealer for fuel recommendations.
THE USE OF CORD WOOD IS PROHIBITED BY LAW.
SOOT and FLYASH: Formation and Need for Removal - The products of combustion will contain small
particles of flyash. The flyash will collect in the exhaust venting system and restrict the flow of flue gases.
Incomplete combustion, such as occurs during startup, shutdown, or incorrect operation of the room
heater will lead to some soot formation which will collect in the exhaust venting system. The exhaust
venting system should be inspected at least once every year to determine if cleaning is necessary.
CREOSOTE: When wood is slowly burned it produces tar and other organic vapours and these combine
with expelled moisture to form creosote. The creosote vapours condense in the relatively cool chimney
flue associated with a slow burning fire. As a result, creosote residue accumulates on the flue lining.
When ignited this creosote can result in an extremely hot chimney fire.
CLEANING: There will be some build up of fly ash and small amounts of creosote in the exhaust. This
will vary due to the ash content of the fuel used and the operation of the stove. It is advisable to inspect
and clean the exhaust vent semi-annually or every two tons of pellets.
ASHES: Disposed ashes should be placed in a metal container with a tight fitting lid. The closed container
of ashes should be on a non-combustible floor on the ground, well away from all combustible materials
pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispensed, they
4
Page 5
Introduction
should be retained in the closed container until all cinders have been thoroughly cooled.
ELECTRICAL: The use of a surge protected power bar is recommended. The unit must be grounded.
The grounded electrical cord should be connected to a standard 110-120 volts, nominal average 2.0 Amps (4.1
Amps peak), 60 hertz electrical outlet and also must be accessible. Ensure the polarity to the outlet the unit will
be plugged into is correct as incorrect polarity can affect the unit’s operation. If this power cord should become
damaged, a replacement power cord must be purchased from the manufacturer or a qualified ENVIRO dealer. Be
careful that the electrical cord is not trapped under the appliance and that it is clear of any hot surfaces or sharp
edges. This unit’s maximum power requirement is 184 watts (600 watts peak).
GLASS: Do not abuse the glass by striking or slamming the door. Do not attempt to operate the stove with
broken glass. The stove uses ceramic glass. Replacement glass must be purchased from an ENVIRO dealer. Do not
attempt to open the door and clean the glass while the unit is in operation or if glass is hot. To clean the glass, use
a soft cotton cloth and mild window cleaner, gas or wood stove glass cleaner, or take a damp paper towel and dip
into the fly ash. This is a very mild abrasive and will not damage the glass.
FLAMMABLE LIQUIDS: Never use gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar
liquids to start or “freshen up” a fire in the heater. Keep all such liquids well away from the heater while it is in use.
SMOKE DETECTOR: Smoke detectors should be installed and maintained in the structure when installing and
operating a pellet burning appliance.
OPERATION: The ash pan and door must be closed securely for proper and safe operation of the pellet stove.
Also ensure all gaskets on the door are checked and replaced when necessary.
KEEP ASH PAN FREE OF RAW FUEL.
Do not lace unburned fuel or new fuel in ash pan. A fire in the ash pan may occur.
INSTALLATION: Be sure to maintain the structural integrity of your home when passing a vent through walls,
ceilings, or roofs. It is recommended that the unit be secured into its position in order to avoid any displacement.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
FRESH AIR: Outside Fresh Air connection is optional. Must be connected to all units installed in Mobile and “Air
Tight Homes” (R2000) or where required by local codes. Consider all large air moving devices when installing your
unit and provide fresh air accordingly. Limited air for combustion may result in poor performance, smoking and
other side effects of poor combustion.
If you have any questions with regards to your stove or the above-mentioned information, please feel free to
contact your local dealer for further clarification and comments.
SINCE SHERWOOD INDUSTRIES LTD. HAS NO CONTROL OVER THE INSTALLATION OF YOUR STOVE,
SHERWOOD INDUSTRIES LTD. GRANTS NO WARRANTY IMPLIED OR STATED FOR THE INSTALLATION
OR MAINTENANCE OF YOUR STOVE. THEREFORE, SHERWOOD INDUSTRIES LTD. ASSUMES NO
RESPONSIBILITY FOR ANY CONSEQUENTIAL DAMAGE(S).
SAVE THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE
5
Page 6
Introduction
RATING LABEL LOCATION:
The rating label is located on the back of the ash pan access cover.
PELLET QUALITY:
Pellet quality is important, please read the following:
Your Enviro pellet stove has been designed to burn wood pellets only. Do not use any other
type of fuel, as this will void any warranties stated in this manual.
The performance of your pellet stove is greatly affected by the type and quality of wood
pellets being burned. As the heat output of various quality wood pellets differs, so will the
performance and heat output of the pellet stove.
CAUTION: It is important to select and use only pellets that are dry and free of dirt or any impurities
such as high salt content. Dirty fuel will adversely affect the operation and performance of the unit
and will void the warranty. Pellet Fuel Industries (P. F. I.) has established standards for wood pellet
manufacturers. We recommend the use of pellets that meet or exceed these standards. Ask your dealer
for a recommended pellet type.
P. F. I. PELLET STANDARDS:
Fines (fine particles)......1% maximum through a ⅛” screen
Bulk Density..................40 pound per cubic foot minimum
Size..............................¼” to 5/16” diameter ½ – 1½” long maximum
Ash Content..................1% maximum (Premium grade)
..................3% maximum (Standard grade)
Moisture Content...........8% maximum
Heat Content.................approximately 8200 BTU per pound minimum
ASH: The ash content of the fuel and operation of your stove will directly determine the frequency of
cleaning. The use of high ash fuels may result in the stove needing to be cleaned daily. A low ash fuel
may allow longer intervals between cleaning.
CLINKERING: [clinkers are silica (sand) or other impurities in the fuel that will form a hard mass during
the burning process]. This hard mass will block the air flow through the Burn Pot Liner and affect the
performance of the stove. Any fuel, even approved types, may tend to clinker. Check the Burn-Pot Liner
daily to ensure that the holes are not blocked with clinkers. If they become blocked, remove the liner
(when the unit is cold) and clean/scrape the clinkers out. Clean the holes with a small pointed object if
required. Refer to the section Routine Cleaning and Maintenance.
PELLET FEED RATES: Due to different fuel densities and sizes, pellet feed rates may vary. This may
require an adjustment to the slider damper setting or to the auger feed trim setting on low.
Since Sherwood Industries Ltd. has no control over the quality of pellets that you use, we assume no
liability for your choice in wood pellets.
Store pellets in a dry area at least 36” (1 m) away from the pellet stove.
6
Page 7
Installation
Remove
DECIDING WHERETO LOCATEYOUR PELLET APPLIANCE:
1. Check the “Clearances to Combustibles” section for proper spacing.
2. Do not obtain combustion air from an attic, garage or any unventilated space.
Combustion air may be obtained from a ventilated crawlspace.
3. Do not install the stove in a bedroom.
4. You can vent the stove through an exterior wall behind the unit or connect it to an
existing masonry or metal wood stove chimney (must be lined if the chimney is over 6”
(15 cm) diameter, or over 28 inches² (180 cm²) cross sectional area). An interior vent
can be used with approved pipe passing through the ceiling and roof.
5. Locate the stove in a large and open room that is centrally located in the house. This
will optimize heat circulation.
6. The power cord is 8 feet (2.43 m) long and may require a grounded extension cord to
reach the nearest electrical outlet.
7. Stove must sit on a non-combustible pad that extends six inches in front of the door or
the included hearth pad (50-2929).
UNPACKINGAND REMOVING PELLET STOVE FROM PALLET
1. Start by removing the crating and unit bag, you will need a pry bar and hammer to remove the crating. A
sawzall can be used to cut the staples as well.
2. Loosen six screws securing Back Grill, once loose slide downwards and remove.
3. Use a 5/16” wrench or socket to remove the shipping bolts holding the unit to the pallet.
Figure 1: Shipping Bolt Removal
7
Page 8
Installation
ASSEMBLY
1. First install the hearth pad if you plan on using it. You
may have to unscrew feet to raise unit up. Tilt the unit
so it is balancing on the back feet, slide the hearth pad
under the unit while making sure the side mounting
tabs are on the outside of the base flange. once holes
are aligned secure with provided T-20 thread rolling
screws. See Figure 2.
Figure 3: Cabinet Side Install
3. Now Install Ash Shelf and Louvers. Ash Shelf is
mounted using two T-20 thread roller screws. The
Louvers are installed by inserting into slots cut into
louver mounting brackets located above the door.
If properly aligned the louvers should catch on the
bracket tabs and sit at a 15 degree angle.
Figure 2: Hearth Pad Install
2. Next install the Cabinet Sides. There are six screws
for mounting each cabinet side. Start by installing
screws at front top of the panels, Do not fully tighten
screws. Now get the back top screws started. Now
install the rest of the screws and tighten them down.
See Figure 3.
8
Figure 4: Louver and Ash Shelf Install
Page 9
Installation
36in
(91.5 cm)
48in
(122 cm)
30in
(76 cm)
A
E
D
C
B
CLEARANCESTO COMBUSTIBLES:
IMPORTANT: The P3 must have a Hearth Pad when installing the unit on a combustible floor. The included
hearth pad meet all the requirement of a proper hearth pad. If you do not use the included hearth pad a certified
non combustible Hearth Pad with a minimum R Value of at least 0.84 must be placed underneath the unit and
extend six inches in front of the unit measured from the glass. If the P3 is installed on carpet the use of a solid non
combustible Hearth Pad must be used under leveling legs.
These dimensions are minimum clearances but it is
recommended that you ensure sufficient room for servicing,
routine cleaning and maintenance.
A. Side wall to unit 8 inches (20 cm)
B. Back wall to unit 5.5 inches (14 cm)
C. Back wall to Chimney Connector 4in inches (10cm)
D. Corner to unit 3 inches (7.5 cm)
E. Glass to Hearth Pad 6 inches (15 cm)
Figure 5: Minimum Install Clearances
ALCOVE CLEARANCES:
The unit may be installed in an alcove if desired.
These minimum clearances to combustibles must
be maintained at all times. Be sure to leave room
for servicing, routine cleaning, and maintenance.
These are inside dimensions.
Minimum Alcove Width 36 inches (91.5 cm)
Minimum Alcove Height 48 inches (122 cm)
Minimum Alcove Depth 30 inches (76 cm)
Figure 6: Minimum Alcove Clearances
9
Page 10
Installation
Air Supply Inlet
Gas Meter
Restriction Zone
(Termination not allowed)
Termination Cap
G
G
Opens
Opens
Opens
D
F
B
B
A
I
H
K
G
G
L
C
E
VENT TERMINATION REQUIREMENTS:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Table 1: Use in conjunction with Figure 6 for allowable exterior vent termination locations.
LetterMinimum ClearanceDescription
A24 in (61 cm)Above grass, top of plants, wood, or any other combustible materials.
B48 in (122 cm) Beside/below any door or window that may be opened. (18” (46 cm) if outside
fresh air installed.)
C12 in (30 cm)Above any door or window that may be opened. (9” (23 cm) if outside fresh air
installed.)
D24 in (61 cm)To any adjacent building, fences and protruding parts of the structure.
E24 in (61 cm)Below any eave or roof overhang
F12 in (30 cm)To outside corner.
G12 in (30 cm)To inside corner, combustible wall (vertical and horizontal terminations).
H3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly
I3 ft (91 cm)From any forced air intake of other appliance
J12 in (30 cm)Clearance to non-mechanical air supply inlet to building, or the combustion air
K24 in (61 cm)Clearance above roof line for vertical terminations.
L7 ft (2.13 m)Clearance above paved sidewalk or paved driveway located on public property.
To each side of center line extended above natural gas or propane meter/
regulator assembly or mechanical vent.
inlet to any appliance.
. Do not terminate the vent in any
1
enclosed or semi-enclosed areas
such as a carport, garage, attic,
crawlspace, narrow walkway,
closely fenced area, under a sun
deck or porch, or any location
that can build up a concentration
of fumes such as stairwells,
covered breezeway, etc.
2. Vent surfaces can become
hot enough to cause burns
if touched by children. Noncombustible shielding or guards
Figure 7: Use in conjunction with Table 1 for allowable exterior vent termination locations.
may be required.
3. Termination must exhaust above
the inlet elevation. It is recommended that at least five feet of vertical pipe be installed outside when the appliance is vented
directly through a wall, to create some natural draft to prevent the possibility of smoke or odor during appliance shut
down or power failure. This will keep exhaust from causing a nuisance or hazard from exposing people or shrubs to high
temperatures. In any case, the safest and preferred venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the plants and
nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located in the vicinity of
termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior of the house
might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no guarantee against such
incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
10
Page 11
Installation
2" ID
(51 mm)
Optional
Elbow
Outside
Wall
10.5in
(26.5 cm)
6.625in
(17 cm)
2.125 in
(5.5 cm)
OUTSIDE FRESH AIR CONNECTION:
Outside fresh air is mandatory when installing this
unit in airtight homes (R2000) and mobile homes.
A Fresh-air intake is strongly recommended for all
installations. Failure to install a fresh air intake may result
in improper combustion as well as the unit smoking during
power failures.
When connecting to an outside fresh air source, do not use
plastic or combustible pipe. A 2” minimum (51 mm) ID
(inside diameter) steel, aluminum or copper pipe should be
used. It is recommended, when you are installing a fresh
air system, to keep the number of bends in the pipe to a
minimum.
EXHAUSTAND INTAKE LOCATIONS:
Figure 8: Outside Air Connection.
EXHAUST
Base of unit to center of flue 10.5 in (265 mm)
Center of unit to center of flue 0 in (0 mm)
[at center of unit]
FRESH AIR INTAKE
Base of unit to center of intake 6.625 in (170 mm)
Center of unit to center of intake 2.125 in (53 mm)
IMPORTANT: When attaching the exhaust venting
system to the unit or when joining vent sections three
screw must be used at each joint. If vented horizontally,
joints shall be made gas tight with aluminum foil duct
tape.
Figure 9: P3 Inlet and Outlet Location.
11
Page 12
Installation
ENVIRO P3
1
/4” Lag Bolts
Securely Fastened
Ground Wire Directly
to Metal Chassis
Hearth Pad
Flooring
Steel Frame
3" (75mm)
3"
(75mm)
Wall thimble
manufactured
by pellet vent
manufacturer.
MOBILE HOME INSTALLATION:
● Secure the heater to the floor using the two
holes in the pedestal.
● Ensure the unit is electrically grounded to
the chassis of your home (permanently).
● Do not install in a room people sleep in.
● Outside fresh air is mandatory. Secure
outside air connections directly to fresh air
intake pipe and secure with three screws
evenly spaced.
CAUTION: THE STRUCTURAL
INTEGRITY OF THE MANUFACTURED
HOME FLOOR, WALL AND CEILING/
ROOF MUST BE MAINTAINED.
CORNER THROUGH WALL INSTALLATION:
Minimum clearances must be maintained
for a corner installation as shown in
figure 11.
Figure 10: Mobile home installation.
12
Figure 11: Corner Installation.
Page 13
Installation
Non-combustible
floor protection.
Existing floor
(combustible)
6"
(15 cm)
4"
(10 cm)
Wall
thimble
45°
elbow
12"
(30.5 cm)
Exhaust Tube
3" (75mm) or 4" (100mm) "PL" or "L" vent
Wall Thimble
45° Elbow with screen or
Termination Cap
High Temperature RTV
Silicone Required
Fresh Air Intake Tube
HORIZONTAL EXHAUST THROUGH WALL INSTALLATION:
Vent installation: install vent at clearances specified by the vent manufacturer.
A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces, or a floor,
or ceiling. Where passage through a wall or partition of combustible construction is desired, the installation shall
conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and Equipment. Only use venting of
L or PL type with an inside diameter of 3 or 4 inches (7.6 or 10.1 cm).
1. Choose a location for your stove that meets
the requirements stated in this manual and
allows installation with the least amount of
interference to house framing, plumbing,
wiring, etc.
2. Install a non-combustible hearth pad
(where necessary).
3. Place the appliance 15” (37.5 cm) away
from the wall. If the stove is to be set on
a hearth pad, set the unit on it, and adjust
the leveling legs.
4. Locate the center of the exhaust pipe on
the stove. Extend that line to the wall.
Once you have located the center point on
the wall, refer to pellet vent manufacturer
installation instructions for correct hole
size and clearance to combustibles.
5. Install the wall thimble as per the
instructions written on the thimble.
Maintain an effective vapour barrier in
accordance with local building codes.
6. Install a length of 3” (75 mm) or 4” (100
mm) vent pipe into the wall thimble. The
pipe should install easily into the thimble.
7. Connect the exhaust vent pipe to the
exhaust pipe on the stove. Seal the
connection with high temperature silicone.
8. Push the stove straight back, leaving a
minimum of 4” (10 cm) clearance from the
back of the stove to the wall. Seal the vent
pipe to the thimble with high temperature
silicone.
9. The pipe must extend at least 12” (30 cm)
away from the building. If necessary,
bring another length of pipe (PL type) to
the outside of the home to connect to the
first section. Do not forget to place high
temperature silicone around the pipe that
passes through the thimble.
Figure 12: Straight through wall Installation.
Figure 13: Venting to use with straight through wall Installation.
13
Page 14
Installation
Wall framing
Wall thimble
Termination cap
Vertical section of vent pipe
Horizontal frame for thimble
Clean out tee
90° elbow
Wall strap
Wall framing
Wall thimble
Termination cap
Vertical section
of vent pipe
Horizontal frame
for thimble
90° elbow
Concrete Wall
Clean out tee
10. Install a vertical pipe, or if all requirements for direct venting are met, install vent termination. The stainless steel
cap termination manufactured by the vent manufacturer is recommended. However, when the vent terminates
several feet above ground level and there are no trees, plants, etc. within several feet, a 45° elbow can be used
as termination. The elbow must be turned down to prevent rain from entering.
NOTE:
• It is recommended that horizontal through wall installations have 3 to 5 feet (91 to 152 cm) of vertical pipe in the
system to help naturally draft the unit in the event of extreme weather or a power outage.
• Some horizontal through wall installations may require a “T” and 3 to 5 feet (91 to 152 cm) of vertical pipe outside
the building to help draft the unit. This may be required if a proper burn cannot be maintained, after the stove
has been tested and the airflow set. This is due to the back pressure in the exhaust caused by airflow around the
structure.
• Follow vent manufacturer guidelines for installation of venting. High temp sealant must be used when connecting
vent pipe to the unit’s starter pipe. Improper seals at the vent joints may cause combustion by-products to leak
into the room where installed - seal as required.
THROUGH WALL VERTICAL RISE HORIZONTAL TERMINATION INSTALLATION - FREESTANDING:
A termination cap is always recommended for this type of install but a stainless steel termination hood or a 45°
elbow may be used in place of the cap.
Figure 14 is the recommended installation set up, venting length is negligible.
Figure 15 is the installation to use if there is a concrete or retaining wall in line with exhaust vent on a pellet stove.
The termination must be 12” (30 cm) from the outside wall and 12” (30 cm) above the ground.
Figure 14: Venting horizontally with rise.
14
Figure 15: Venting with concrete wall behind unit .
Page 15
INSIDE VERTICAL INSTALLATIONS:
2 ft
(600 mm)
Rain Cap (ensure cap is
at least 3ft above the
roof at the lowest point)
Roof Flashing
Roof Rafter
Fire Stop with
Support Collar
Ceiling Joist
Vertical Vent Pipe
Clean Out Tee with
Pipe Adapter
NOTE: All vent sections must
maintain 3 inches (7.5 cm)
clearances to combustibles.
Rain cap
Flashing
24"
(61 cm)
4"
(10 cm)
Tee with
cleanout
3" (7.5 cm)
Clearance
Support
bracket
Type "PL"
vent
Installation
1. Choose a stove location that is ideal. See the section
“DECIDING WHERETO LOCATEYOUR PELLET APPLIANCE.”
2. Place a non-combustible hearth pad where
necessary.
3. Place the unit on the hearth pad (if installed on a
combustible surface) and space the unit in a manner
so when the pellet vent is installed vertically, it will
be 3” (7.5 cm) away from a combustible wall.
4. Install the tee with clean out.
5. Install the pellet vent upward from there. When
you reach the ceiling, make sure that the vent goes
through the ceiling fire stop. Maintain a 3” (7.5 cm)
distance to combustibles and keep attic insulation
away from the vent pipe. Maintain an effective
vapor barrier.
6. Finally, extend the pellet vent to go through the
roof flashing.
OUTSIDE VERTICAL INSTALLATIONS:
To accomplish a outside vertical pipe installation, follow
steps 1 through 5 in the “INSIDE VERTICAL INSTALLATIONS -
FREESTANDING” section and then finish it by performing the
following (refer to Figure 17).
1. Install a tee with clean out on the outside of the house.
2. Install PL vent upward from the tee. Make sure that
you install support brackets to keep the vent straight
and secure.
3. Install ceiling thimble and secure the flashing as you
go through the roof.
4. Ensure that the rain cap is approximately 24” (600
mm) above the roof.
7. Ensure that the rain cap is approximately 24” (600
mm) above the roof.
Figure 16: Inside Vertical Installation.
Figure 17: Outside Vertical Installation.
15
Page 16
HEARTH MOUNT INSTALLATION:
Min 6" (150 mm)
Optional Hearth
or Other
Floor Protection
Combustible FloorMasonry Fireplace
10" (25.4 cm) Mantel
Minimum 8" (20 cm)
from top of stove
Flexible vent connector
(use this 5 foot [152cm]
section of pipe to vent
past fireplace damper or
small shelf)
Installation
Refer to Figures 18 and 19.
1. Install the hearth pad.
2. Lock the fireplace damper in the open
position.
3. Install a positive flue connector at the
fireplace dampers or seal the chimney at
the top.
4. Connect a tee to the exhaust pipe.
5. Install flexible stainless steel liner or listed
pellet vent to the top of the chimney.
Figure 18: Freestanding hearth mount installation.
16
Figure 19: Freestanding hearth mount installation overview.
Page 17
Installation
EXTERIOR MOUNTED EXHAUST BLOWER (20-070):
The P3 can be equipped with an externally mounted exhaust blower.
This optional kit includes all components necessary to install the exhaust
blower on any vertical wall surface.
Choose a location for your stove that meets the requirements stated in
your manual and allows installation with the least amount of interference
with house framing, plumbing, wiring, etc. Make sure unit is unplugged.
Included in the Exterior Mounted Exhaust Blower Kit are:
1 - Exhaust blower housing box.
1 - Blower cover plate.
1 - Hardware bag
Figure 21: Exterior Blower Kit.
Figure 20: Exterior Blower Kit.
1. Remove the left hand cabinet side by removing the six mounting
screws down the front. Loosen the three screws, slide the
cabinet side forward and remove panel.
2. Loosen the six screws that hold the back grill in place. Lift the
back grill off the screws.
3. Disconnect the Exhaust blower wires from the wire harness.
Remove the exhaust blower motor from the housing; six screws.
Cover hole in housing with cover plate provided (see Figure 21).
4. Remove the cover from the exterior exhaust blower housing
box.
5. Install the exhaust blower housing box into the pipe placed
through the wall thimble, seal with high temperature silicone.
Fasten the box to the wall with (4) four screws, seal edges of
box to wall with clear silicone.
Figure 22: Exterior Blower Kit section view.
6. Drill a hole through the wall thimble plate for the electrical wires.
Pass the armored cable through the wall thimble. Use the strain
relief provided. Do not pass cable through vent hole.
7. Install the Exhaust Blower motor into the external exhaust
blower housing box. Make the electrical connections to the wire
harness and exhaust blower.
8. Replace the cover on the exterior Exhaust Box and the back grill
of the stove and ensure the screws are tightened down.
9. Install vertical pipe as instructed in appropriate section.
17
Page 18
Installation
Electrical Cable
90° Elbow
45°Elbow with Rodent
screen or stainless
steel termination hood
2ft (610mm) Riser
Pipe Adaptor
Exterior Blower
and Housing
Wall Strap
To supply power to
the exhaust blower
THROUGH WALL WITH EXTERIOR BLOWER KIT INSTALLATION - HORIZONTAL TERMINATION:
NOTE:
Figure 23: Through Wall Installation with Exterior Blower Kit.
Ensure that all interior vent connections are sealed by placing a small bead of high temperature silicone around
each chimney connection.
Also ensure that all vertical vent sections are properly supported and that all clearances to combustibles are
maintained in accordance with the vent manufacturer’s specifications.
Figure 24: Through Wall Installation with Exterior Blower Kit; Side View.
Install the amour coated electrical cable from the exhaust blower housing, through the wall thimble plate and
attach to the pre drilled hole in the left hand rear hopper pillar. Hook up to wires from the exhaust blower wiring
harness.
All electrical connections must be in accordance to local code requirements
18
Page 19
Roof Sheathing
Rain Cap
Roof Flashing
Roof Rafters
Ceiling Joists
Vent Pipe
Exterior Wall
Sheathing
Outside Vent
Termination
Installation
TYPICAL THROUGH WALL WITH EXTERIOR BLOWER KIT INSTALLATION - VERTICAL TERMINATION:
Follow the previous pages for through wall
installations. Ensure that vent pipe is properly
secured to wall using wall straps. Maintain clearances
to combustibles on vent pipe as well as unit.
Figure 25: Through Wall Installation with Exterior Blower Kit;
Vertical Termination.
THERMOSTAT INSTALLATION:
1. Install the wall thermostat in a location that is not to close too the unit but will effectively heat the
desired area.
2. The Right Cabinet Side will need to be removed to
access the Control Board. Once the side has been
removed you can remove three screws securing the
Control Board Cover.
3. Now that the board can be accessed, wire the
Thermostat using to the Control Board using an
18 gauge, 2 connector wire from the unit to the
thermostat.
Figure 26: Thermostat wire placement.
19
Page 20
Specifications
15 1/2"
(389 mm)
5 1/2"
(143 mm)
20 1/2"
(526 mm)
35"
(886 mm)
18"
(460 mm)
17 1/2"
(444 mm)
24"
(615 mm)
20"
(508 mm)
DIMENSIONSAND SPECIFICATIONS:
Weight (with full hopper): 275 lb (125 Kg)
Hopper Capacity: up to 62 lb (28 Kg)
Voltage: 110 - 120 V
Max Current: 4.1 Amps
Consumption on High: 3.1 lb/hr (1.4 Kg/hr)*
Consumption on Low: 1.3 lb/hr (0.6 Kg/hr)*
(Note: Consumption will vary with the type of
fuel used.)
20
Figure 27: Dimensions of P3.
Page 21
Operating Instructions
Auto
CONTROL BOARD FUNCTIONS:
1. POWER BUTTON: This is the green button with the power symbol, it is used
to turn the unit on and off. When the power is on and the blue LED beside the
button will be illuminated. The LED will flash during the start-up cycle. Once startup cycle is complete the power LED will stay on.
2. AUTO BUTTON: Located below the Power button, when pressed this activates
Auto or “Comfort” mode. LED beside button will be illuminated when active.
3. THERMOSTAT BUTTON: Located below the Auto Button. This is for external
thermostat control. LED beside button will be illuminated when active.
4.ARROW BUTTONS: The Arrow Buttons are used to adjust heat level and trim
settings.
START-UP: When the unit is turned on it will go into a start-up cycle while trying
to light a fire. During start-up you have no control over the settings. The Power
LED will flash until start-up is complete. You can adjust heat levels or toggle the
different modes during start-up but these adjustments will not come into affect
until the start-up cycle is complete.
MANUAL MODE: Once the start-up cycle is completed you will be in either Manual
mode or Auto mode. When in Manual mode the Power LED is illuminated and
AUTO LED is not. Use the Arrow buttons to adjust heat level from L1-L5.
AUTO MODE: Press the Auto button to activate Auto or “Comfort” mode. When
activated the Power and Auto LED’s will be illuminated. Use the Arrow buttons
to adjust from C1-C9. Each setting corresponds to a different temperature set
point. The stove will automatically adjust to hold this temperature. As the room
temperature gets close to the set point the fire will decrease in size. If room
temperature is above the set point for a certain amount of time the stove will shut
down and go into Suspend mode.
SUSPEND MODE: Once a stove has gone into Suspend mode the fire will go
out. This means the room has heated up beyond the Auto set point. Once
temperature in the room drops below the Auto set point the stove start back up and run until the room gets to
hot once again. When in suspend mode the Auto LED will flash.
THERMOSTAT MODE: This can only be used in Manual mode, and is for external thermostat control. A external
thermostat can be wiring to the main control board. When activated the LED beside the Thermostat Button will
be illuminated.
FEED/COMBUSTION TRIM: To adjust the Feed Trim you must be in Manual mode heat level 1. Press the
hidden button located under the down arrow. The Display will then change from P (Program) to A (Auger) to C
(Combustion) with a two second delay between changes. When the display shows an A use the arrows to adjust
the feed trim. To adjust the combustion fan trim wait until the display shows C then use the arrows to adjust.
SERVICE INDICATOR:If you see the “S1” on the LED display this is a maintenance recommended indicator. The
“S1” will come on when your stove has run for so many hours. It is recommended that you contact your local
dealer for component inspection and servicing. Pellet stoves require regular maintenance to keep running
efficiently.
AUTOMATIC SAFETY FEATURESOF YOUR PELLET STOVE:
Figure 28: Circuit Board
Control Panel Decal.
A. The stove will shut off if the fire unexpectedly goes out, once exhaust temperature drops below 120°F (49°C),
you will see an E3 code on the LED display.
B. The stove has a high temperature safety switch. If the temperature on the hopper reaches 200°F (93°C), the
auger will automatically stop and the stove will shut down. The LED display will show an E4 error code, see
Troubleshooting section. If this happens, call your local dealer to reset the 200°F (93°C) high limit switch. ALSO FIND THE REASONS WHY THE UNIT OVERHEATED. This code can also be cause by leaving the hopper lid
open, there is a magnetic safety switch.
C) The unit is equipped with a vacuum switch to monitor the venting pressure; if it becomes blocked the vacuum
switch will turn off the auger and there will be an E2 error code on The LED Display.
21
Page 22
Operating Instructions
Damper
`OPERATION YOUR PELLET STOVE:
PRE-BURN INSTRUCTIONS: The burn pot liner holes must be clear and the liner installed properly against the ignitor tube for proper operation. Check the hopper for enough pellets to start the unit.
DO NOT OPERATE THE UNIT WITH THE DOOR OR ASH PAN OPEN.
TO START: Press the Power button. The stove will turn on. The LED beside the Power button will flash
to indicate a start-up cycle. The Heat Level is shown on the LED display, you can change the Heat Level
and mode but these adjustments will not take affect until the start-up cycle is complete. If this is the first
time the unit has been started or the unit has run out of fuel, the auger will need to be primed. You may
need restart the unit if an E3 error occurs, to do this just press the Power button again. Once you see
pellets start to drop the auger is primed.
TO OPERATE: When a fire has been established, the Power LED will turn solid (after approximately 10
- 15 minutes) and the current settings will now take affect.
The convection blower (room air blower) will turn on once the start-up cycle is complete. The speed of
this blower is automatically controlled and is based off the heat level setting.
TURNING YOUR PELLET STOVE OFF:
To turn off your Pellet stove just press the Power button. This will not shut off the stove instantly, it will
go intoa shut down cycle and take approximately 5 minutes for the fire to burn out. The fans will stay
running until the unit has cooled sufficiently.
NEVER unplug a unit that is running!
DO NOT unplug unit while Combustion fan is running.
Unplugging may cause smoke to be released into the home.
DAMPER SET-UP:
DAMPER MUST BE SET AT TIME OF INSTALLATION. This is used to regulate the airflow through
the pellet stove, this is key to an efficient clean burn. See figure 29.
If the pellets being burnt are of poor quality there is a higher chance of clinker build up and over time
the fire may build up and overflow the burn pot. Poor quality pellets will require more primary air to help
complete the burn, the slider damper must be pulled
out to compensate. Pulling the slider damper out gives
the fire more air. It is crucial to make sure the burn
pot is clean and that no holes are blocked for proper
combustion. It is recommended to get the stove hot
then set the damper at heat level 1, this is the most
sensitive setting.
There are two ways to set the damper. You can visually
set the damper if you have experience.
• A tall, lazy flame with dark orange tips requires more
air – Open slider (pull out) slightly.
• A short, brisk flame, like a blowtorch, has too much
air – Close slider (push in) slightly.
• If the flame is in the middle of these two characteristics
with a bright yellow/orange, active flame with no
black tips then the air is set for proper operation,
refer to Figure 30.
22
Figure 29: Slider/Damper Adjustment
Page 23
Operating Instructions
Hole
For less experienced installers or owners a magnehelic gauge can be used to determine the proper
Damper setting. A magnehelic gauge will accurately measure the pressure in your firebox. There is a
small hole on underneath the ash lip on the right side of the firebox front, see figure 31. You
want a reading of .10-.13 WC (25-32 Pa) depending on pellet quality.
The combustion exhaust blower is a variable speed blower controlled by heat level setting. This blower
will decrease the vacuum pressure inside the stove as the heat level output is decreased.
SPECIAL NOTES:
Pellet quality is a major factor in how the Pellet stove will operate. If the pellets have a high moisture
content or ash content the fire will be less efficient and has a higher possibility of the fire building up
and creating clinkers (hard silica ash build-up).
Overfiring should not occur if stove is operating properly, if stove looks like it is buring unusually high
turn off the unit with the power button, DO NOT unplug. There is a built in safety switch if unit gets too
hot from overfiring it will shut down automatically.
Figure 30: Efficient Flame.
Figure 31: Magnehelic Test Hole.
GUIDELINES FOR FINE-TUNING FOR FUEL QUALITY:
Due to fuel quality the damper and control board trims may need to be fine-tuned to achieve optimal
conditions. Trims are access by pressing hidden button below the down arrow when in L1.
1. If ash builds up in the unit on all settings, the slider damper rod should be pulled out in small
increments to give the unit more air.
2. If the unit has excesses ash build-up in the liner on the lower feed settings, the Combustion Blower
Trim should be increased one setting at a time until the problem improves (Factory Setting is #3).
3. If the fire is going out on low because the airflow is too great, the Combustion Blower Trim can be
lowered one setting at a time.
4. If the stove has excesses ash build-up in the liner on the higher settings the damper can be opened
until the problem improves.
5. If you need more heat and the fuel has long pellets, the majority are over 1” (2.5cm) in length, the
Feed Rate Trim can be increased.
23
Page 24
Routine Cleaning and Maintenance
Burn Pot Liner
Ignitor Tube
Air Intake Tube
Burn Pot
Ignitor Hole
The following list of components should be inspected and maintained routinely to ensure that the
appliance is operating at its’ optimum and giving you excellent heat value:
2-3 Days / WeeklySemi-annually or 2 Tons of Fuel
Burn Pot and LinerExhaust Vent
Heat Exchanger TubesAir Intake
Ash Pan Blower Mechanisms
Door GlassHeat Exchanger Tubes
Inside FireboxBehind Firebox Liners & Covers
Ash Pan and Door GasketsAll Hinges
Door LatchPost Season Clean-up
TOOLS REQUIRED TO CLEAN UNIT:
Torx T-20 Screwdriver, 5/16” wrench or socket, Brush, Soft
Cloth, Vacuum with fine filter bag
BURNER POT AND LINER (2-3 days)
Figure 32: P3 Burn pot and Liner
Every two to three days (when the unit is cold), remove the burn-pot liner from the stove. Using a
metal scraper, remove material that has accumulated or is clogging the liner’s holes. Then dispose of
the scraped ashes from the liner and from inside the burn-pot. Place the burn-pot back into the stove,
making sure that the pipes are properly inserted into the burn pot. Place the liner back into the burn-pot,
making sure that the ignitor hole in the liner is aligned with the ignitor tube (shown in Figure 32). Push
the liner up against the ignitor tube.
If after long periods of burning, the fire continually builds up and overflows the burn pot or there is a
build up of clinkers, this is an indication that the pellet fuel quality is poor, the stove may need cleaning,
or the air adjusted. Check the stove for ash build up (clean if required) and adjust the damper to produce
the proper clean combustion.
HEAT EXCHANGER TUBES (2-3 days)
A rod is located in the center of the stove just above the door behind the top louvers, see Figure 35. This
rod is to be pulled up and down a few times (ONLY WHEN THE UNIT IS COLD) in order to clean away
any fly ash that may have collected on the heat exchanger tubes. As different types of pellets produce
different amounts of ash, cleaning of the tubes should be done on a regular basis to enable the unit to
run efficiently. Do pull on rod excessively if it is not sliding. If stuck inspect rod for bend and try and free
up scraper plate from inside firebox.
ASH PAN AND DOOR GASKETS (weekly)
After extended use the gasket may come loose. To repair this, glue the gasket on using high-temperature
fiberglass gasket glue available from your local dealer. This is important to maintain an airtight assembly.
24
Page 25
Routine Cleaning and Maintenance
Loosen the four (4) screws, rotate
counter-clockwise & remove.
Loosen the screw &
rotate the cover
(left & right sides)
Vacuum
Air Wash
Vacuum
compartment
Empty
Ash Pan
DOOR GLASS CLEANING (2-3 days)
Cleaning of the glass must only be done when stove is cold. Open the door. The glass can be cleaned by
wiping down the outside and inside of the glass with a soft dry cloth.
If the glass has build up that can not be removed
with only the cloth, clean the glass using paper
towel and a gas appliance glass cleaner, this
may be purchased through most dealers. If a
gas appliance glass cleaner is not available, use
a damp paper towel dipped in fl y ash to clean
the glass. After the glass has been cleaned use
the dry soft cloth to wiping down the outside
and inside of the glass.
ASH PAN (weekly)
This part is located behind the bottom door. To
remove the ash pan, open the cover from the
right hand side, and lift the ash pan up and out.
Dump the ashes into a metal container stored
away from combustibles. Monitor the ash level
every week. Remember that different pellet fuels
will have different ash contents. Ash content is
a good indication of fuel efficiency and quality.
Refer to “SAFETY WARNINGS AND RECOMMENDATIONS” for
disposal of ashes. Vacuum the inside of the ash
pan compartment inside the pedestal including
the hole at the top back of the compartment.
Replace the ash pan ,close the latch, and close
pedestal door. DO NOT PLACE UNBURNED
OR RAW PELLET FUEL IN ASH PAN.
Figure 33: P3 Open
AIR INTAKE (semi-annually)
Inspect periodically to be sure that it is
not clogged with any foreign materials.
EXHAUST PASSAGES (Semi-annually)
To prevent build up of fly-ash all the
exhaust passages must be cleaned
and vacuumed.
Clean behind clean-out covers:
• Open ash box cover.
• Remove ash box.
• Using a 5/16” socket, loosen the six
screws in the ash box compartment;
four on the back.
• Rotate the back cover counter
clockwise.
•
Figure 34: P3 Clean-Out Covers.
25
Page 26
Routine Cleaning and Maintenance
Scaper
Rod
Remove
• To remove and rotate the side covers
to open them.
• Vacuum out all three 3 chambers.
• Close all the clean-out covers and
tighten the screws.
HEAT EXCHANGER TUBES (2-3 days)
• The heat exchanger tubes are located
behind the Louver assembly. To access
Heat Exchanger Scraper Rod, remove
middle two louvers by tipping up and
pulling out.
• Pull out the Scraper Rod shown in
Figure 35 in order to remove any fly
ash that may have collected on the
heat exchanger tubes. This will allow
for optimal heat transfer to convection
air.
REMOVAL OF FIREBOX PANELS
Figure 35: P3 Heat Exchanger Tubes
• Open the door, remove the door, burn
pot and burn pot liner.
• Lubricate all screws with penetrating
oil.
• Remove the four screws that hold the
side panels in place.
• With the tip of a flat screwdriver, gently
lift up the side panels and remove the
side panels.
• Pull the center panel out.
• Vacuum thoroughly.
• Re-install panel by inserting center
panel.
• Place the side panels back into the
firebox locking them into place and
re-install the two screws on each side.
• Clean thoroughly.
Note: Screws that secure left side
panel also secure hinge bracket
which holds cast door. Remove door
before unscrewing.
26
Figure 36: P3 Firebox Panels
Page 27
Routine Cleaning and Maintenance
FIREBOX (weekly)
The paint on the steel firebox panels may peel. This is due to extreme conditions applied to the paint and is in no
way covered by warranty. Brush and vacuum up all soot and flyash from firebox.
AIR WASH (semi-annually)
Vacuum out the air wash passages at the top of the glass (see Figure 33). We recommend that a soft brush nozzle
head is used on the vacuum.
EXHAUST VENT (semi-annually)
This vent should cleaned every year or after two tons of pellets. We recommend contacting your dealer for
professional cleaning. To clean the vent pipe, tap lightly on the pipe to dislodge any loose ash. Open the bottom of
the “T” to dump the ash, then vacuum as much of the ash out of the vent pipe as possible. Failure to clean exhaust
venting can result in a serious creosote fire.
BLOWER MECHANISMS (semi-annually)
Unplug the stove then open the right and left side panels to access the two blowers. Vacuum all dust from motors.
DO NOT lubricate the motors. Check gaskets and replace if needed.
HINGES
Check to make sure all hinges are working properly. You may use high temp anti-sieze on door hinges for smoother
operation.
POST SEASON CLEAN-UP
Once you are finished using the pellet appliance for the season, unplug the stove for added electrical protection. It
is very important that the stove be thoroughly cleaned and serviced. Pellet should be regularly service for optimum
efficiency and prolonged life.
DOOR GLASS REPLACEMENT
Never run a stove with broken glass, new glass must be purchased and installed by a Enviro dealer. The door
glass is made of high temperature “PYROCERAM” ceramic glass. The proper glass size is 13” x 9.5” x 0.2” (5mm).
To replace the glass, unscrew and remove the seven retainer screws. Carefully remove the glass and any broken
pieces using protective gloves. High temperature fiberglass tape should be used around the glass on the sides
and bottom. Place glass with fiberglass tape around outside into cast door, there should be no gasket at the top.
Use the same retainers to secure the glass in place, make sure glass is properly seated in the cast door before
tightening screws. Do not strike or slam door shut this can cause glass to break. The use of substitute glass
materials is prohibited use only part 50-2942.
27
Page 28
Troubleshooting
DO NOT:
● Service the stove with wet hands. The stove is an electrical appliance, which may pose a shock hazard if handled
improperly. Only qualified technicians should deal with possible internal electrical failures.
● Do not remove any screws from the firebox without penetrating oil lubrication.
WHAT TO DO IF:
1. The stove will not start.
2. E2 on LED Display.
3. E3 on LED Display.
4. E4 on LED Display.
5. The Exhaust Blower will not function normally.
6. The Auger is not feeding pellets.
7. The Convection Blower will not function normally.
8. The Igniter not working.
9. Control settings (Heat Level) has no effect on the fire.
*NOTE: All troubleshooting procedures should be carried out by qualified technicians or installers.
1. The stove will not start.
• Make sure the stove is plugged in and the wall outlet is supplying 115-120V AC power.
• If the Control Board has been is set to Thermostat mode, turn the thermostat up to call for heat.
• Check the LED display for error codes. - If Display reads E2,E3, or E4 use Troubleshoot sections.
• Check the fuses on the circuit board.
• If the unit still does not start, contact your local service dealer for service.
2. E2 on LED Display (The Vacuum Switch contacts have opened for more than 1:00 min)
• Pinch, break or blockage in Vacuum Hose - Check hose for pinch points or damage, replace or re-route as
required. Blow out Vacuum Hose with compressed air.
• Blocked Hose Barb on Exhaust Channel - Use a paper clip to clean out Hose Barb or remove the Vacuum Hose
from the Vacuum Switch and blow into the hose to remove blockage.
• Blocked exhaust / venting system - Have stove and venting cleaned and inspected.
• Air Damper is closed or set to low - open damper slightly.
• Severe negative pressure in area where unit is installed - Check the operation by opening a window, does this
solve the problem? If it does, install fresh air intake to unit or room. Venting system may require vertical section
to move termination into a low pressure zone.
• Vacuum Switch failure - Bypass the vacuum switch, if this corrects the problem check for above problems before
replacing the Vacuum Switch.
• Damage to gray wires between Circuit Board and Vacuum Switch - Inspect wires and connectors
• Combustion Blower failure - If the Combustion Blower is not turning fast enough to generate the proper vacuum
in the Exhaust Channel. Visually Check if the blower motor is turning, check the Exhaust Blower voltage across
the blower wires (>=115V on #5 setting and >= 82V on #1 setting). – Replace the Circuit Board if the Voltage
reading is less than 82 V. with a line voltage >115 V AC.
• Check Vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the Vacuum hose
from Vacuum Switch. Check exhaust vacuum readings by placing the open end of the Vacuum Hose on a
Magnehelic Gauge. (readings must be above .09” WC on low fire).
• If the motor fails to reach a 0.09” WC readings, then replace the Combustion Blower
To reset Circuit Board after a trouble code - press Power button.
28
Page 29
Troubleshooting
3. E3 on LED Display (Proof of Fire Failure)
• If a fire is not detected, or if the fire has gone out the display will read E3 because the exhaust temperature is
too low causing Exhaust Temperature Sensor’s contacts to open.
• Check the hopper for fuel. Auger may need to be primed if stove has run out of pellet or being fired for the
first time.
• Incorrect air damper setting. - Excessive air may consume the fire too quickly before the next drop of fuel,
leaving completely unburned fuel in the burn pot liner. - Insufficient air will cause build up, further restricting
the air flow through the Burn Pot Liner. This in turn will cause the fuel to burn cold and very slowly. Fuel may
build up and smother the fire. In this case clean the burn pot. (NOTE: unit may require a changes to the
vent system or installation of fresh air intake to correct Air to Fuel ratio problems).
• Combustion Blower failure. - The Combustion Blower is not turning fast enough to generate the proper vacuum
in the fire box. Visual Check – is the blower motor turning.
• Check the Exhaust Blower voltage across the blower wires (>=114V on #5 setting and >= 82V on #1 setting).
– Replace the Circuit Board if the Voltage reading is less than 82 V. with a line voltage >114 V AC.
• Check Vacuum levels in the exhaust channel by bypassing the Vacuum Switch, then remove the Vacuum hose
from Vacuum Switch. Check exhaust vacuum readings by placing the open end of the Vacuum Hose on a
Magnehelic Gauge (readings must be above .10” WC on low fire).
• Poor Quality Fuel – Insufficient energy in the fuel to produce enough heat to keep the stove burning or
operational.
• Exhaust Temperature Sensor failure. – Bypass the sensor located on Exhaust Blower, if stove now operates
properly, the unit may require cleaning or a new sensor. Contact your local dealer for service.
• Check the fuse on the circuit board.
4. E4 on LED Display (High Limit or Lid Switch Failure)
• If unit has been running normally and you now have an E4 this could be a High Limit switch. This is a safety
feature, if the hopper gets to hot the unit will shut off. The High limit switch is located the right side of the
hopper near the bottom.
• If the high limit has tripped something is wrong with the unit, possibly a component failure or a hopper fire has
occurred.
• Slowly open the hopper lid, if you see and smoke at all keep it closed. A fire extinguisher or water can be used
to put out a fire.
• If there is no smoke the Hopper Lid switch may not be engaged or there has been a component failure. The
components will need to be tested, contact an Enviro dealer. The High limit switch is a manual reset switch and
a small red button on the back of the switch will need to be manually pressed in order for the unit be started
again.
• To check Hopper Lid switch make sure Hopper Lid is fully closed, If you think it is properly closed, open and
close the lid, you should hear an audible click form magnetic Hopper Lid switch located in control board area.
• If no click is heard check that magnet on underside of Hopper Lid is still magnetic. This is a strong magnet.
• If magnet is good, alignment is out or switch is bad.
• Test switch for audible click with another magnet, switch is right above LED Display on control board.
5. The Combustion Blower will not function normally.
• If the Combustion “Exhaust” Blower is not functioning properly the stove will most likely will give an E2 or E3
error code.
• Check the wiring against the wiring diagram to make sure everything is connected properly.
• The fan can be directly hooked up to power to check motor.
NOTE: DO NOT attempt any electrical troubleshooting without knowledge of electrical systems,
make sure unit is not plugged in. It is recommended to call an authorized Enviro dealer or service
technician.
29
Page 30
Troubleshooting
6. Auger is not Feeding Pellets.
• If this is the first time starting the unit or during the previous burn the unit ran out of pellets the Auger will need
to be primed. You may get an E3 while auger is filling with pellets, just press the power button again. Once the
Auger is full of pellets it will start dropping them into the burn pot.
• If Auger is primed and no pellets are dropping remove the Rear Grill to see Auger motor, you will see the auger
collar and set screw rotating if the Auger is operating properly.
• If the motor’s armature tries to spin but the auger shaft doesn’t then the auger is jammed. – Try to break apart
jam by poking at the jam through the drop tube. If this fails then empty the hopper and remove the Auger
Cover **Remember to re-seal the cover with silicone after clearing jam**
• Check the set screw locking the motor shaft to the auger shaft. This needs to be tightened to the flat on the
motor shaft for proper rotation.
• Check the fuses on the main circuit board.
7. The Convection Blower will not function normally.
• The Convection fan should come on when the unit is started. Speed is automatically controlled, the higher the
heat level the higher the convection fan voltage will be.
• Check Wiring against wiring diagram.
• AC wall voltage can be directly hooked up to fan to test motor.
• Check that blade spins with very little friction.
• Check fuses on main circuit board.
8. Ignitor not working
• If pellets are feeding and the combustion blower is working your stove should light a fire or at least start
smoking.
• Make sure the burn pot and burn pot liner are correctly installed square to the Ignitor and air tube.
• If stove errors out before lighting open door and carefully check to see it pellets around the Ignitor hole are
warm - If not remove ignitor and test, replace if it does not heat up.
• If the air damper is closed to much or Combustion Blower is not working the stove will not light.
• Check the fuses on the main circuit board.
9. Control settings (Heat Level) has no effect on the fire.
• If the LED beside the Power button is flashing the Control Board has complete control of the unit. This means
the unit is in start-up mode, once the start-up cycle is complete the light will go solid.
• If running in Auto or “Comfort mode” and the LED light beside the Auto button is flashing the unit is in suspend
mode because it has overshot the set point. Once temperature drops below the set point the stove will turn
back on.
Minimum clearances to combustible materials; conventional or mobile home./ Les
dégagements minimums aux matériels combustibles; la maison
conventionnelle ou mobile.
A) Sidewall to unit / De mur lateral à l'unité 8" (200 mm)
B) `to unit / De mur du fond à l'unité 5.5" (140 mm)
C) Backwall to Chimney Connector / 4" (100 mm)
Paroi arrière au connecteur de cheminée
D) Corner to unit / Du coin à l'unité 3" ( 75 mm)
E) If supplied Hearth Pad is used no floor protection is required. If unit is installed
on a combustible floor and the supplied Hearth Pad is not used the floor must
be protected by a certified non-combustible Hearth Pad extending 6 inches (150
mm) in front of the glass. /Si fourni Foyers Pad est utilisé aucune protection de
plancher est requise. Si l'appareil est installé sur un plancher combustible et le
foyer Pad fourni n'est pas utilisé le sol doit être protégé par une plaque de foyer
non combustible certifié s'étendant de 6 pouces (150 mm) à l'avant du verre.
ALCOVE
Largeur / Width Minimum
36" (915 mm)
Hauteur / Height Minimum
48" (1220 mm)
Profondeur / Depth Minimum
30" (760 mm)
ENVIRO MODEL / MODELE ENVIRO:
P3
INPUT Rating: 8,000 to 30,000 BTU/Hr
LISTED ROOM HEATER, PELLETIZED FUEL ONLY
SUITABLE FOR MOBILE HOME INSTALLATION (CONCU POUR MAISON MOBILES)
REPORT #
US Environmental Protection Agency, certified to comply July 1, 1990, particulate
emission standards.
(États-Unis Environnemental Protection Agence, a certifié pour conformer au Juillet 1,
1990, les normes de particules d'émission.)
Conforms to ASTM 1509-12, Certified to ULC S627-00
This pellet appliance has been tested and listed for use in manufactured homes in accordance with
Oregon Administration Rules 814-23-900 through 814-23-909. Install and use only in accordance
with the Manufacture’s installation and operating instructions. Contact local building or fire officials
about restrictions and installation inspection in your area. Do not connect this unit to a chimney flue
serving another appliance. See local building codes and manufacturer’s installation instructions for
precautions required for passing a chimney through a combustible wall or ceiling. Do not obstruct
space under heater. Electrical rating: 120 volts, 60 hz, 4.1 Amps. Route cord away from the heater.
/
Cet appareil de boulette a été teste et repertoirie pour une utilisation dans les maisons pre
fabriquées conf ormément aux reglements l’A dministration d’Oregon Go uverne, 814-33-900 à
814-23-909. Installer et uli tiser uniq uement co nformément aux instruction s d’insta lltion et
d’utilisation du fabricant. Contacter les autories locales de la construction ou de la protection
incendie pour vous informer sur les restrictions et l’inspection d’installtion dans votre region. Ne
branchez pas cette unité sur un conduit de cheminée utilse pour un utre appereil. Consultez les
codes de construction locaux et les instructions du fabricant pour les précautions necessaires pur
faire passer une cheminée a travers un mur ou un plafold combustible. Ne pas obstruer l'espace
sous chauffe.Le classement électrique : 120 volts, 60 hz, 4.1 Amplis. Maintenez le fil a l’ecart de
l’apperreil de chauffage.
For Use With Only Pelletized Wood fuels. Operate only with viewing door and ash removal door
tightly closed. Only replace broken glass with dealer certified ceramic glass. Listed type PL 3 inch
(75 mm) or 4inch (100 mm) venting is required for installation. Other components required for
installation: A listed pellet vent cap, Hearthpad; a listed single wall chimney liner may be used.
Inspect and clean Exhaust Venting System frequently.
/
Pour l'usage avec les combustibles sous forme de boulets uniquement. Fonctionner seulement
avec la vue de porte et la porte d'enlèvement de cendre ont fermé. Seulement remplacer le verre
avec le verre de ceramique. Les composants ont exigé pour l'installation: 3 pouce (75 mm) ou 4
pouce (100 mm) a énuméré le conduit de PL complète avec les composants.
Les installations de
mont de foyer ; un paquebot de cheminée de mur de seul énuméré peut être utilisé.
MANUFACTURED BY /
FABRIQUE PAR
:
SHERWOOD INDUSTRIES LTD.
VICTORIA BC CANADA
CAUTION:
-Hot while in operation.
-Do not touch, keep children
clothing and furniture away.
-Contact may cause skin
burns. See nameplate and
instructions.
ATTENTION:
-Hot en cours de fonctionnement.
-Ne pas toucher, maintenir les
enfants des vêtements et des
meubles.
-Le contact peut provoquer des
brûlures de la peau. Voir plaque
signalétique et les instructions.
C-14328
Certied for use in Canada & USA /
Certié pour installation au
Canada et aux Etats-Unis.
4001609
DO NOT REMOVE THIS LABEL
/ N'ENLEVEZ PAS CETTE ETIQUETTE
CAUTION: Moving Parts May Cause Injury. Do Not Operate Unit With Rear Grill
Removed or Cabinet Sides Removed.
ATTENTION: Pièces en mouvement peut causer des blessures. Ne pas l'appareil avec
grille arrière supprimé ou Sides Cabinet supprimé.
CAUTION: Hot Parts. Do Not Operate With Rear Grill Removed or Cabinet Sides
Removed.
ATTENTION: les pièces chaudes. Ne pas utiliser avec grille arrière supprimé ou Sides
Cabinet supprimé.
DANGER: Risk of Electric Shock. Disconnect Power Before Servicing. Refer to Owners
manual for Electrical and Wiring Connection Diagrams.
DANGER: Risque de choc électrique. Débrancher l'alimentation avant l'entretien.
Reportez-vous au manuel Propriétaires de Schémas de raccordement électrique et de
câblage.
CAUTION: Operate this unit only with teh hopper lid closed. Failure to do so may result
in emssions of product of combustion fro m the hopper under certain conditions.
maintain hopper seal in good condition. Do not overfill the hopper.
LIGHTING INSTRUCTIONS:
- Press and release the green on / off button located under hopper lid.
- Set the mode and heat output to the desired setting.
- Make sure to close Hopper Lid.
TO TURN THE UNIT OFF:
- Press the green on / off button, when off the -- will be displayed.
(Refer to owners manual for detailed instructions)
INSTRUCTIONS POUR L’ALLUMAGE:
- Presse et relaease le vert sur / de bouton situé sous la trémie couvercle.
- Une fois le feu a commence, a regle le production de chaleur au montage desire.
- Assurez-vous de fermer couvercle de trémie.
POUR ETEINDRE L’UNITE:
Appuyez sur le vert bouton on / off, quand au large de la -- sera affiché.
(Referez-vous au guide de l’utilisateur pou un mode d’emploi detaille.)
DATE OF MANUFACTURE /
DATE DE FABRICATION:
J F M A M J J A S O N D 2014 2015 2016 2017 2018
Rating Label
Page 37
37
Page 38
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
MODEL:___________________________________
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________ (dd/mm/yyyy)
DATE OF INSTALLATION:___________(dd/mm/yyyy)
MAGNEHELIC AT INSTALL:___________________
INSTALLER’S SIGNATURE:
_________________________________________
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
38
Page 39
Notes
39
Page 40
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
40
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
www.enviro.com
July 3rd, 2012
C-14329
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.