Parts List - Components.................................................................................................................33
Parts List - Options........................................................................................................................35
Parts Diagram - Components.........................................................................................................36
Parts Diagram - Freestanding Steel................................................................................................37
Parts Diagram - Insert Steel...........................................................................................................38
Installation Data Sheet..................................................................................................................39
2
Page 3
Safety Warnings & Recommendations
* This manual is designed for the technician in conjunction with the owner’s manual. *
Please read this entire Installation Manual before installing or operating your ENVIRO Pellet
Stove. Failure to follow these instructions may result in property damage, bodily injury or
even death. Any unauthorized modification of the appliance or use of replacement parts
not recommended by the manufacturer is prohibited. All national and local regulations and
European Standards shall be complied with when installing this appliance.
Caution: Do not connect to any air distribution duct or system.
Warning: Parts of the appliance, especially the external surfaces, will be hot to touch when
in operation so use due care and the fire gloves provided. Never place wood, paper, furniture,
drapes or other combustible materials within 80cm (31½”) of the front of the unit, 152 mm (6”) from
each side, and 76 mm (3”) from the back of the unit. Do not let children or pets touch it when it is hot.
To prevent the possibility of a fire, ensure that the appliance is properly installed by adhering to the
installation instructions. An ENVIRO dealer will be happy to assist you in obtaining information with
regards to your local building codes and installation restrictions.
FIRE EXTINGUISHER AND SMOKE DETECTION: All homes with a pellet burning stove should have
at least one fire extinguisher in a central location known to all in the household. Smoke detectors should
be installed and maintained in the room containing the stove when installing and operating a pellet
burning appliance. If it sounds the alarm, correct the cause but do not deactivate. You may choose to
relocate the smoke detection devise within the room; DO NOT REMOVE THE SMOKE DETECTOR FROM
THE ROOM.
CHIMNEY OR RUN AWAY FIRE: Call local fire department. Close the draft fully. Extinguish the fire
in the burn pot liner with a cup of water and close the door. Examine the flue pipes, chimney, attic, and
roof of the house, to see if any part has become hot enough to catch fire. If necessary, spray with fire
extinguisher or water from the garden hose. IMPORTANT: Do not operate the stove again until you are
certain the chimney and its lining have not been damaged.
FUEL: This pellet stove is designed and approved to only burn wood pellet fuel with up to 3% ash content.
Dirty fuel will adversely affect the operation and performance of the unit and may void the warranty.
Check with your dealer for fuel recommendations. THE USE OF CORDWOOD IS PROHIBITED BY
LAW. When filling fuel hopper, open lid on top of unit, check hopper for foreign objects, empty the
bag into the hopper, DO NOT OVER FILL, and ensure hopper lid closes completely. DO NOT use this
appliance as an incinerator. DO NOT use unsuitable and non recommended fuels, including liquid fuels.
KEEP ASH PAN FREE OF RAW FUEL. DO NOT PLACE UNBURNED OR NEW PELLET FUEL IN ASH PAN.
A fire in the ash pan may occur.
SOOT: Operation of the stove with insufficient combustion air will result in the formation of soot which
will collect on the glass, the heat exchanger, the exhaust vent system, and may stain the outside of the
house. This is a dangerous situation and is inefficient. Frequently check your stove and adjust the slider/
damper as needed to ensure proper combustion. See: “Slider/damper Setting”.
3
Page 4
Safety Warnings & Recommendations
CLEANING: There will be some build up of fly ash and small amounts of creosote in the exhaust. This
will vary due to the ash content of the fuel used and the operation of the stove. It is advisable to inspect
and clean the exhaust vent semi-annually or every two tons of pellets. The appliance, flue gas connector
and the chimney flue require regular cleaning. Check them for blockage prior to re-lighting after a
prolonged shut down period.
ASHES: Disposed ashes should be placed in a metal container with a tight fitting lid. The closed container
of ashes should be on a non-combustible surface, well away from all combustible materials pending final
disposal. If the ashes are disposed of by burial in soil or otherwise locally dispensed, they should be
retained in the closed container until all cinders have been thoroughly cooled.
IMPORTANT: The door and ash drawer cover must be kept closed except during ignition, refueling and
removal of residue material to prevent fume spillage.
GLASS: Do not abuse the glass by striking or slamming the door. Do not attempt to operate the stove
with broken glass. The stove uses ceramic glass. Replacement glass must be purchased from an ENVIRO
dealer. Do not attempt to open the door and clean the glass while the unit is in operation or if glass is
hot. To clean the glass, use a soft cotton cloth and mild window cleaner, gas or wood stove glass cleaner,
or take a damp paper towel and dip into the fly ash. This is a very mild abrasive and will not damage the
glass.
ELECTRICAL: The use of a surge protected power bar is recommended. The unit must be
grounded. The grounded electrical cord should be connected to a standard 220-240 volts (2.92-3.18
Amps), 50 hertz electrical outlet and also must be accessible. If this power cord should become damaged,
a replacement power cord must be purchased from the manufacturer or a qualified ENVIRO dealer. Be
careful that the electrical cord is not trapped under the appliance and that it is clear of any hot surfaces
or sharp edges. This unit’s maximum power requirement is 7000 watts.
OPERATION: The door and ash drawer cover must be kept closed securely when the unit is in operation
to prevent fume spillage and for proper and safe operation of the pellet stove. Also ensure all gaskets on
the door are checked and replaced when necessary.
CAUTION: When operating during adverse weather, if the unit exhibits dramatic changes in combustion
stop using the unit immediately.
INSTALLATION: Contact your local building or fire official to obtain a permit and any information on
installation restrictions and inspection requirements for your area. All local regulations, including those
referring to national and European Standards need to be complied with when installing this appliance.
Be sure to maintain the structural integrity of your home when passing a vent through walls, ceilings, or
roofs. It is recommended that the unit be secured into its position in order to avoid any displacement. This
appliance must be installed on a floor with an adequate load bearing capacity. If an existing construction
doesn’t meet these prerequisite, suitable measures (e.g. load distributing plate) shall be taken to achieve
it.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
4
Page 5
Safety Warnings & Recommendations
FRESH AIR: Outside Fresh Air connection is optional. Fresh Air must be connected to all units installed
in “Air Tight Homes” or where required by local codes.
Consider all large air moving devices when installing your unit and provide room air accordingly. NOTE:
Extractor fans when operating in the same room or space as the appliance, may cause problems. Limited
air for combustion may result in poor performance, smoking and other side effects of poor combustion.
The stove’s exhaust system works with negative combustion chamber pressure and a slightly positive
chimney pressure. It is very important to ensure that the exhaust system be sealed and airtight. The ash
pan and viewing door must be locked securely for proper and safe operation of the pellet stove.
Do not burn with insufficient combustion air. A periodic check is recommended to ensure proper
combustion air is admitted to the combustion chamber. Setting the proper combustion air is achieved by
adjusting the slider damper located on the left side of the stove.
Minor soot or creosote may accumulate when the stove is operated under incorrect conditions such as an
If you have any questions with regards to your stove or the above-mentioned information, please feel
free to contact your local dealer for further clarification and comments.
SINCE SHERWOOD INDUSTRIES LTD. HAS NO CONTROL OVER THE INSTALLATION OF
YOUR STOVE, SHERWOOD INDUSTRIES LTD. GRANTS NO WARRANTY IMPLIED OR STATED
FOR THE INSTALLATION OR MAINTENANCE OF YOUR STOVE. THEREFORE, SHERWOOD
INDUSTRIES LTD. ASSUMES NO RESPONSIBILITY FOR ANY CONSEQUENTIAL DAMAGE(S).
SAVE THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE
5
Page 6
Specifications
rating label location:
Freestanding: The rating label is located on the inside of the hopper lid.
Fireplace Insert and Built-In Heater: The rating label is located on the hopper cover.
SpecificationS:
*Note: Consumption will vary with the type of fuel used.
IMPORTANT: The above values were found during testing and may vary with the fuel type, climate, and installation style
FPI: 0.5g/kg
Gross Calorific value of Pellets (dry weight)
20.2 MJ/kg (8.68 BTU/lb)wood pellets - 6mm dia. - complying with draft standard AS/NZS 4014.6
FPI: 9.1 kW (31078 BTU/hr)
Average Particular Emissions (dry weight)Average Emissions RateAverage Efficiency
Class I IP-20AS/NZS 4012:1999, 4013:1999Residential Wood Pellet Heater
FPI: 31mg/MJ
Fuel type
FPI: 80%
FS: 5.3 kW (18100 BTU/hr)
FS: 26mg/MJ
FS: 76%
FPI: 5.8 kW (19808 BTU/hr)
FS: 2.6 kW (8879 BTU/hr)
FPI: 2.9 kW (9904 BTU/hr)
FS: 177°C (351°F)
FS: 1.4 kg/hr (3.09 lb/hr)*
FPI: 1.4 kg/hr (3.09 lb/hr)*
FS: 0.7 kg/hr (1.54 lb/hr)*
FPI: 0.7 kg/hr (1.54 lb/hr)*
FPI: 176°C (349°F)
FS: 119°C (246°F)
FPI: 115°C (239°F)
Table 1: Olympian Specifications.
6
Page 7
dimenSionS - freeStanding:
32 1/2"
(826mm)
Specifications
Figure 1: Olympian Freestanding Dimensions.
dimenSionS - fireplace inSert:
7
/8"
23
(605mm)
(326mm)
7
/8"
24
(632mm)
7
/8"
12
7
/8"
22
(583mm)
3
24
/
4
"
(629mm)
23 3/4"
(604mm)
Figure 2: Olympian Fireplace Insert Dimensions.
7
Page 8
Installation
deciding Whereto locateyour pellet appliance:
1. Do not install the stove in a bedroom or room where people sleep in.
2. Locate the stove in a large and open room that is centrally located in the house. This will optimize
heat circulation.
3. Check clearances to combustibles and for the least amount of interference to house framing, plumbing,
wiring, etc. Also refer to InStallatIon - ClearanCeSto CombuStIbleS - FreeStandIng, InStallatIon - alCoveClearanCeS - FreeStandIng, and InStallatIon - ClearanCeSto CombuStIbleS - FIrePlaCe InSert).
4. You can vent the stove with approved pipe through an exterior wall behind the unit or pass it through
the ceiling and roof. The stove can connect to an existing masonry or metal chimney (must be lined
if the chimney is over 6” (15 cm) diameter, or over 28 inches² (180 cm²) cross sectional area).
5. This unit must not be installed directly onto carpet. If it is to be installed on a carpeted area, a solid
surface (wood, metal or approved hearth pad) must be installed between the unit and the carpet.
6. This unit uses large quantities of air for combustion; outside Fresh Air connection is strongly
recommended. Fresh Air must be connected to all units installed in Mobile and “Air Tight Homes”
(R2000) or where required by local codes.
7. Do not obtain combustion air from an attic, garage or any unventilated space. Combustion air may be
obtained from a ventilated crawlspace.
8. The power cord is 8 feet (2.43 m) long and may require a grounded extension cord to reach the
nearest electrical outlet.
removing pellet Stove from pallet:
To remove your new stove from its pallet, remove the two (2) screws securing the bottom to the pallet.
Freestanding: One screw can be easily seen from behind but to access the second screw the ashpan must
be removed (refer to Figure 3).
Fireplace Insert: There is one screw on either side of the bottom (refer to Figure 4).
Figure 3: Removing FS From the Pallet. Figure 4: Removing FPI From the Pallet.
8
Page 9
Installation
clearanceSto combuStibleS - freeStanding:
These dimensions are minimum clearances but it is recommended that you ensure sufficient room for
serving, routine cleaning and maintenance.
Back wall
Adjacent
wall
3"
(76mm)
Minimum
6" (150mm)
6"
Side wall
(152mm)
3" (76mm)
Figure 5: Olympian on Floor
Protection.
Figure 6: Minimum Clearances to Combustibles for
Freestanding Olympian.
This pellet stove requires floor protection. The floor protection must be non-combustible, extending
beneath the stove the full width and depth of the unit including 6“ (150 mm) in front for ember
The fireplace insert must be installed into a masonry fireplace. This model includes a surround faceplate
and a pedestal. When installing this unit, ensure that the pedestal is removed from the inside of the
hopper and installed on the bottom of the unit. Refer to InStallatIon - InStallatIonoF PedeStaland levelIng
legS - FIrePlaCe InSert and InStallatIon - InStallIng HoPPer Coverand adjuStIng HoPPer HeIgHt - FIrePlaCe InSert
before proceeding.
From the body of the heater to the side wall: 8 inches (203 mm) minimum
From the body of the heater to the Facing on masonry fireplace: 8 inches (203 mm) minimum
From the body of the heater to the mantle: 13.25 inches (337 mm) minimum
inStallationof pedeStaland leveling legS - fireplace inSert:
There are two parts to the Olympian insert pedestal and they can be found inside the hopper. Place unit
on its back. Two (2) hex head screws are used on each side of the pedestal (refer to Figure 8). Using a
5
/16” wrench or socket attach the pedestal to the bottom of the unit.
OPTIONAL:
There are two (2) leveling legs and they can be found inside
the manual bag. Each leveling leg consists of a long bolt, a hex
nut, a washer, and a square bolt with clip (see Figure 9). For
installation of the leveling legs the unit should be on its back and
a ½” wrench is required for adjustments.
Install the square bolts into the square holes in the back corners
of the bottom. The square bolt should be inserted from inside the
unit so that the clip will be facing up.
Thread hex nut onto the bolt till it is
approximately 1” (25 mm) from the bolt head,
slide washer onto bolt. Thread the bolt into
the square nut so length of the bolt shown is
the approximately height needed for leveling.
When the unit is up right and the bolts can be
adjusted to the exact height required. To lock
the bolts at a height tighten the hex nut and
washer against the square bolt
The hopper cover initially comes upside-down on top of the hopper. To install the hopper cover flip the
cover over and fasten in place with four T-20 screws (see Figure 10).
The back height of this unit can be set to one (1) of three (3) heights; 19” (483 mm), 21⅛” (537
mm), 22¼” (565 mm). The hopper should be set to the maximum height that can be used in the
installation.
To change the height of the hopper back up or down, remove the seven (7) T-20 screws, three (3) on
each side and one (1) on the back. The screw placement is shown Figure 11. Move the hopper assembly
to the required setting and replace the screws. When the hopper back is in place it is recommended that
silicone is used to seal the bottom lip of the hopper back and sides
● Secure the heater to the floor using the holes in the pedestal of the appliance.
● Ensure the unit is electrically grounded to the chassis of your home (permanently).
WARNING: Do not install in a room people sleep in.
CAUTION: The structural integrity of the manufactured home floor, wall and ceiling/roof
must be maintained
• Outside fresh air is mandatory. Secure outside air connections directly to fresh air intake pipe and
secure with three (3) screws evenly spaced.
Hearth Pad
Flooring
Steel Frame
1
/
4" Lag bolts
securely fastened
Figure 12: Mobile Home Install Mounting.
Ground wire directly
connected to metal chassis.
11
Page 12
Installation
vent termination requirementS:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Table 2: Use in conjunction with Figure 13 for allowable exterior vent termination locations.
LetterMinimum ClearanceDescription
A24 in (61 cm)Above grass, top of plants, wood, or any other combustible materials.
B48 in (122 cm) Beside/below any door or window that may be opened. (18” (46 cm) if outside
fresh air installed.)
C12 in (30 cm)Above any door or window that may be opened. (9” (23 cm) if outside fresh air
installed.)
D24 in (61 cm)To any adjacent building, fences and protruding parts of the structure.
E24 in (61 cm)Below any eave or roof overhang
F12 in (30 cm)To outside corner.
G12 in (30 cm)To inside corner, combustible wall (vertical and horizontal terminations).
H3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly
I3 ft (91 cm)From any forced air intake of other appliance
J12 in (30 cm)Clearance to non-mechanical air supply inlet to building, or the combustion air
K24 in (61 cm)Clearance above roof line for vertical terminations.
L7 ft (2.13 m)Clearance above paved sidewalk or paved driveway located on public property.
To each side of center line extended above natural gas or propane meter/
regulator assembly or mechanical vent.
inlet to any appliance.
1. Do not terminate the
vent in any enclosed or
G
K
semi-enclosed areas such
as a carport, garage,
attic, crawlspace, narrow
walkway, closely fenced
area, under a sundeck
or porch, or any location
that can build up a
concentration of fumes
such as stairwells, covered
breezeway, etc.
2. Vent surfaces can become
B
D
F
Opens
B
Termination Cap
Air Supply Inlet
Figure 13: Use in conjunction with Table 2 for allowable exterior vent termination
Opens
A
G
I
Gas Meter
locations.
G
Restriction Zone
(Termination not allowed)
H
E
C
Opens
G
L
hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3. Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be
installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the
possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a
nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred
venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the
plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located
in the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior
of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no
guarantee against such incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
12
Page 13
Installation
exhauSt and freSh air intake locationS:
3
/4"
5
(146mm)
5
/8"
1
/16"
13
(332mm)
18
(473mm)
7
3
/16"
(87mm)
7
/8"
10
(277mm)
Figure 15: Olympian Insert Inlet and Outlet Location.
11 7/16"
(291mm)
1"
(25mm)
11
6
/16"
(170mm)
Figure 14: Olympian Freestanding Inlet and Outlet
Location.
EXHAUST Freestanding Insert
Base of unit to center of flue 18 ⅝” (473 mm) 9 1/16” (229 mm)
Side of unit to center of flue 6 11/16” (170 mm) 6 ⅛” (156 mm)
Center of unit to center of flue 5 ¾” (146 mm) 5 ¾” (146 mm)
5 3/4"
(146mm)
1"
(25mm)
1
6
/8"
(156mm)
1
/16"
9
(229mm)
FRESH AIR INTAKE.
Base of unit to center of intake 13 1/16” (332 mm) 3 7/16” (87 mm)
Side of unit to center of intake 11 7/16” (291 mm) 10 ⅞” (277 mm)
Center of unit to center of flue 1” (25 mm) 1” (25 mm)
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENTING MANUFACTURER
outSide freSh-air connection:
Outside fresh air is mandatory when installing this unit in
airtight homes and mobile homes.
A Fresh-air intake is strongly recommended for all
installations. Failure to install intake air may result in improper
combustion as well as the unit smoking during power failures.
When connecting to an outside fresh air source, do not use
plastic or combustible pipe. A 2” minimum (51 mm) ID (inside
diameter) steel, aluminum or copper pipe should be used. It is
recommended, when you are installing a fresh air system, to keep
the number of bends in the pipe to a minimum.
2" ID
(51 mm)
Figure 16: Outside Air Connection.
Outside
Wall
Optional
Elbow
13
Page 14
Installation
corner through Wall inStallation - freeStanding:
Fresh Air Intake
3" (7.5 cm)
Figure 17: Corner Installation.
Wall thimble
manufactured
by pellet vent
manufacturer.
3"
(7.5 cm)
horizontal exhauSt through Wall inStallation - freeStanding:
Vent installation: install vent at clearances specified by the vent manufacturer.
A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces,
or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired,
the installation must conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and
Equipment and with all local regulations, including those referring to regional and national. Only use
venting of L or PL type with an inside diameter of 3 or 4 inches (7.6 or 10.1 cm).
1. Place the appliance 15” (37.5 cm) away from the wall. If the stove is to be set on a hearth pad, set
the unit on it.
2. Locate the center of the exhaust pipe on the stove. Extend that line to the wall. Once you have located
the center point on the wall, refer to pellet vent manufacturer installation instructions for correct hole
size and clearance to combustibles.
3. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour
barrier in accordance with local building codes.
4. Install a length of vent pipe into the wall thimble. Try not to have joints inside the thimble. The pipe
should install easily into the thimble.
5. Connect the exhaust vent pipe to the exhaust pipe on the stove. Seal the connection with high
temperature silicone.
6. Install the fresh air intake (see outSIde FreSH aIr ConneCtIon).
7. Push the stove straight back, leaving a minimum of 3” (76 mm) clearance from the back of the stove
to the wall. Seal the vent pipe to the thimble with high temperature silicone.
8. The pipe must extend at least 12” (30 cm) away from the building. If necessary, bring another
length of pipe to the outside of the home to connect to the first section. Do not forget to place high
temperature silicone around the pipe that passes through the thimble.
14
Page 15
Installation
Exhaust Tube
3" (75mm) or 4" (100mm)
"PL" or "L" vent
Wall Thimble
45° Elbow with screen
or Termination Cap
Fresh Air Intake
High Temperature RTV
Silicone Required
Figure 18: Straight through wall Installation.
9. Install a vertical pipe, or if all requirements for direct venting are met, install vent termination.The
stainless steel cap termination manufactured by the vent manufacturer is recommended. However,
when the vent terminates several feet above ground level and there are no trees, plants, etc. within
several feet, a 45° elbow can be used as termination. The elbow must be turned down to prevent
rain from entering.
NOTE:
• It is recommended that horizontal through wall installations have 3 to 5 feet (91 to 152 cm) of
vertical pipe in the system to help naturally draft the unit in the event of extreme weather or a power
outage.
• Some horizontal through wall installations
may require a “T” and 3 to 5 feet (91 to 152
cm) of vertical pipe outside the building to
Wall framing
Horizontal frame
for thimble
help draft the unit. This may be required if
a proper burn cannot be maintained, after
the stove has been tested and the airflow
set. This is due to the back pressure in
the exhaust caused by airflow around the
Vent pipe
Termination
cap
structure.
• Follow vent manufacturer’s guidelines for
installation of venting. High temperature
sealant must be used when connecting
the vent pipe to the unit’s starter pipe.
Improper seals at the vent joints may cause
combustion byproducts to leak into the room
where installed - seal as required.
Wall thimble
Figure 19: Straight through Wall Installation - Side View.
A 45° elbow may be used in place of the termination
cap (or stainless steel termination hood).
Vertical section of vent pipe
Horizontal frame
for thimble
Wall strap
Clean
out tee
Figure 20: Through Wall with Horizontal Termination.
through concrete Wall With vertical riSe inStallationS - freeStanding:
Horizontal frame
for thimble
A 45° elbow may be used in place of the
termination cap (or stainless steel termination
hood).
This is the recommended installation to use
if there is a concrete or retaining wall in line
with exhaust vent on pellet stove.
The termination must be 12 inches (30 cm)
from the outside wall and 12 inches (30 cm)
above the ground.
Wall thimble
90°elbow
Wall framing
Vertical section
of vent pipe
Wall
thimble
Termination cap
Concrete Wall
16
Clean out tee
Figure 21: Vertical rise with Horizontal Termination.
Page 17
Installation
inSide vertical inStallationS - freeStanding:
1. Choose a stove location that is ideal. See the section “InStallatIon - deCIdIng WHereto loCateyour Pellet
aPPlIanCe.”
2. Place the unit on the
hearth pad (if installed on
a carpeted surface) and
space the unit in a manner
so when the pellet vent is
installed vertically, it will be
3” (76 mm) away from a
combustible wall.
3. Locate the center of the
fresh air intake pipe on the
unit. Match that center with
the same point on the wall
and cut a hole about 2” (51
mm) in diameter.
4. Install the fresh air intake
pipe.
5. Install the tee with clean
out.
6. Install the pellet vent
upward from there. When
you reach the ceiling, make
sure that the vent goes
through the ceiling fire stop.
Maintain a 3” (76 mm)
distance to combustibles
and keep attic insulation
away from the vent pipe.
Maintain an effective vapor
barrier.
Rain cap - ensure cap is at
least 2 feet (610mm) above
the roof at the lowest point
Storm collar
Roof flashing
Roof rafter
Fire stop with
Support Collar
Ceiling joist
Vertical vent pipe
Clean out tee with
Pipe adapter
7. Finally, extend the pellet
vent to go through the roof
flashing.
8. Ensure that the rain cap
is approximately 24” (610
mm) above the roof.
NOTE:
All vent sections must maintian 3"
(76 mm) clearances to combustibles.
Figure 22: Inside Vertical Installation.
17
Page 18
Installation
outSide vertical inStallationS - freeStanding:
To accomplish a outside vertical pipe installation, follow steps 1 through 5 in the “InSIde vertICal InStallatIonS
- FreeStandIng” section and then finish it by performing the following (refer to Figure 23).
1. Install a tee with clean out on the outside of the house.
2. Install PL vent upward from the tee. Make sure that you install support brackets to keep the vent
straight and secure.
3. Install ceiling thimble and secure the flashing as you go through the roof.
4. Ensure that the rain cap is approximately 24” (610 mm) above the roof.
Rain cap
Flashing
24"
(61 cm)
3"
(7.5cm)
Figure 23: Outside Vertical Installation.
3" (7.5 cm)
Clearance
Support
bracket
Tee with
cleanout
Type "L"
vent
Fresh air
intake
18
Page 19
Installation
hearth mount inStallation - freeStanding:
Damper Removed
or Fastened Open
Mantel
Minimum 8" (20 cm)
from top of stove
Clean-out
Fresh-air intake
should com from
chimney. If holes
lready exist fresh-air
intake can be taken
through back of the
fireplace or through
the ash dump.
Figure 24: Hearth Mount - Side View.
SEISMIC RESTRAINT:
All installation scenarios for the Enviro
Olympian require the use of hold-down
anchors (one on each side)
Combustible FloorMasonry Fireplace
Min 6"
(150 mm)
Floor
Protection
1. Lock fireplace damper in the open
position.
2. Install a positive flue connector at the
fireplace dampers.
3. Connect a clean-out tee or a 90°
elbow to the exhaust pipe.
4. Install flexible stainless steel liner or
listed pellet vent to the top of the
chimney.
Rain cap
Storm collar
Seal plate
(cover plate)
Existing masonry
flue
Fixing to Concrete Floor:
Minimum M8 expansion anchors (M10
recommended) or min M8 epoxy- set
anchors.
Approved Anchors: Expansion AnchorsRamset Dynabolt and Trubolt, Hilti HAS.
Epoxy-set Anchors – Ramset Epcon, Ramset
Chemset and Hilti HVU.
Fixing to Timber Floor Framing:
Minimum 14g x 60 screws (6.3mm diameter)
or M10 X 90 coach-screws. These shall be
fixed a minimum of 40mm into the centreline of the existing floor joists. If screws
cannot be installed directly into an existing
floor joist, solid blocking between joists (min
size 90x45) shall be provided.
The Olympian can be equipped with an externally mounted exhaust blower (PART #50-492). This
optional kit will include all components necessary to install the exhaust blower on any external vertical
wall surface.
Choose a location for your stove that meets the requirements stated in this manual and allows installation
with the least amount of interference to house framing, plumbing, wiring, etc.
Included in the exterior mounted exhaust blower kit are:
1 - Exhaust blower housing box.
1 - Blower cover plate.
1 - Hardware bag
1. Open the left side of the unit and the back grill and
disconnect the Exhaust Blower wires from the harness.
Remove the exhaust blower by undoing the six (6) ¼ hex
head sheet metal screws that fasten the blower to the
housing.
2. Remove the back grill from the exterior exhaust vent
housing and remove the round cover plate installed on the
blower housing.
3. Install the round cover plate over the gasketed opening in
the stove where the exhaust motor was removed from.
Left side with cab side
removed
Exhaust motor must be
replaced with cover
4. Install the exhaust blower motor in the Exterior Vent
Housing Box onto the exhaust blower housing.
5. Follow the procedures for InStallatIon - HorIzontal exHauSttHrougH Wall InStallatIon - FreeStandIng. Place the unit in
the desired location. Cut the hole in the wall at the desired
location. Install a wall thimble.
6. Drill holes in the wall thimble in the corresponding locations
for wire and fresh air if needed. Install wire clamps and
feed wire through the hole in the thimble into the house.
Tighten clamp on wire and attach green ground wire (at
the symbol) with the screw and star washer provided.
7. Attach a short or an adjustable section of 3” of double wall
pellet vent through the wall thimble to the stove. Seal all
joints with silicone. Maintain clearances to combustibles.
8. Apply silicone to the pipe in the Exhaust Box, slide the
pipe into the exhaust vent. Mount the Exhaust Box to the
house. Reinstall the back grill on the Exterior Vent Housing
Box. Apply normal venting practices when installing the
vertical vent pipe.
9. Connect the wires in the stove. Re-install the Left side and
Back Grill on the stove.
10. Set the Slider Damper as described in the InStallatIon - SlIder/damPer SettIng“ section.
Exhaust motor
Complete assembly - Exterior
blower & housing
Figure 26: Exterior Exhaust Blower.
20
Page 21
Installation
NOTE:
Ensure that all vent connections are installed by placing three (3) screws evenly spaced and a small bead
of high temperature silicone at each chimney connection. Also ensure that all vertical vent sections are
properly supported and that all clearances to combustibles are maintained in accordance with the vent
manufacturer’s specifications.
Install an amour coated electrical cable from the exhaust blower housing, through the wall thimble, and
attach to the pre-drilled hole in the left hand rear hopper pillar. Hook up to wires from the wiring harness
for the exhaust blower. All electrical connections must be in accordance with local code requirements (see
WIrIng dIagram).
21
Page 22
Installation
through Wall vertical inStallation With exhauSt bloWer - freeStanding:
Refer to InStallatIon - InStallatIonWItH exterIor mounted exHauSt bloWer - FreeStandIngand InStallatIon -
outSIde vertICal InStallatIonS - FreeStandIng. Ensure that vent pipe is properly secured to wall using wall
straps. Maintain clearances to combustibles on vent pipe as well as unit.
The Fireplace insert model requires a surround faceplate and a pedestal. When installing this unit, ensure
that the pedestal is removed from the inside of the hopper and installed on the bottom of the unit (Refer
to InStallatIon - InStallatIonoF PedeStaland levelIng legS - FIrePlaCe InSert).
Adjust hopper height (see InStallatIon - InStallIng HoPPer Coverand adjuStIng HoPPer HeIgHt - FIrePlaCe InSert)
and assemble surround panel (see Installation - InStallatIonand removaloF Control PanelIn tHe SurroundPanel - FIrePlaCe InSert and Installation - aSSemblyand InStallatIonoF InSert Surround PanelS - FIrePlaCe InSert)
before starting installation.
A noncombustible hearth pad
must cover combustible flooring
underneath, as well as 6” (150 mm)
in front of the heater and 6” (150
mm) to the side of the heater
1. Install the hearth pad.
Rain Cap
Flexible or Rigid 6"
Stainless Steel Liner
Fresh-air intake
Steel Plate or Flashing
2. Lock the fireplace damper in the
open position.
3. Install a positive flue connector at
the fireplace damper.
4. Connect a tee or 90° degree elbow
Flexible stainless
steel pipe connection
Damper Removed
or Fastened Open
Mantel
Minimum 8" (20 cm)
from top of stove
to the exhaust pipe.
5. This fireplace insert must be
Surround Panel
installed with a continuous
chimney liner of 3 or 4” diameter
extending from the fireplace insert
to the top of the chimney. The
liner must conform to type 3
requirements of CAN/ULC S635.
6. (Recommended) Install fresh air
intake either through the back
of the fireplace or through the
positive flue connector.
Clean-out tee
If holes already exist
fresh-air intake can
be taken through the
back of the fireplace
or through the ash
dump.
Figure 29: Installation of Fireplace Insert.
Masonry Fireplace
Min 6"
(150 mm)
Floor
Protection
Combustible Floor
When installing the insert into a masonry fireplace DO NOT remove any bricks or masonry, with the
following exception; masonry or steel, including the damper plate, may be removed from the smoke shelf
and adjacent damper frame if necessary to accommodate a chimney liner. Provided that their removal
will not weaken the structure of the fireplace and chimney, and will not reduce protection for combustible
materials to less than that required by the national building code.
When installing the fireplace insert into a zero clearance fireplace, DO NOT cut or modify any factory
firebox parts. If the fireplace insert does not fit into a zero clearance fireplace we recommend you use
an ENVIRO freestanding model and install as a hearth mounted unit. Install a 3” (76 mm) flex pipe from
the stove to the top of the chimney (see “InStallatIon - HeartH mount InStallatIon - FreeStandIng”).
23
Page 24
Installation
inStallationand removalof control panelin the Surround panel - fireplace inSert:
When installing the circuit board control panel into the surround panel, the surround does not need to be
assembled. The circuit board will be found in the firebox.
Place the circuit board control panel on the backside of the right
surround panel so the hinge is on the outside and the top and
bottom holes on the control panel line up with those on the
surround. Attach using two (2) T-20 screws through the front of
the surround into the circuit board control panel (see Figure 30).
After the surround has been assembled and is ready to be
installed on the unit plug the wiring harness into the control panel
(see Figure 31).
REMOVAL:
When maintenance is required on the unit the surround must be
removed. Pull the surround straight up till it stops then pull it out
about 4” (10 cm) and rest the surround on top of the unit while
the control panel is removed or disconnected.
If electrical connection is required for the maintenance remove
the circuit board control panel from the surround.
Plug
If electrical connection is not required for the maintenance remove
Figure 30: Right
Panel - Front.
the wiring harness from the bottom of the circuit board control.
The trim set for your surround panel must be installed before installing the surround panel onto the unit,
if not already done.
1. To assemble the surround panels, lay the panels face down
on a soft flat surface and align the outer edges of the sides
with the top panel. Using four (4) T-20 screws up through the
side panels into the top (see Figure 32).
2. Place the assembled
surround panel
around the stove;
align the slots with
the screw heads.
Push surround in
then down to engage
the surround slots
on the mounting
screws (see Figure
33). Make sure the
top surround panel
sits flat behind the
stove top.
TO AVOID PERSONAL INJURY DO NOT REMOVE OR REPLACE TRIMS WHEN PELLET STOVE IS HOT!
KIT COMPONENTS:
QuantityDescription
2Upper Cabinet Trim
2Lower Cabinet Trim
1Top Trim
3Louver
4#8 nut plated (spares)
TOOLS REQUIRED:
Upper
Cabinet Trim
Lower
Cabinet Trim
#8 Hex Nut (x8)
Left Cabinet
Side
#8 Stud (x8)
● T-20 screwdriver ●11/32” socket
REMOVAL OF SIDE TRIMS:
Figure 34: Right cab side with upper and lower cabinet trims.
When stove is off and cool, open the door. Remove the two (2) screws on the right cab side (at top and
bottom of front flange) and the two (2) screws on the left cab side (one above and one below hinge). The
cab sides have hinges at the back so they can swing open when the screws have been removed.
Remove the trims that will be replaced by unfastening the #8 hex nuts (four (4) for each piece of trim)
by hand. Carefully remove the trim from the studs.
REPLACEMENT OF SIDE TRIMS:
Place the new trim pieces on their corresponding studs
Top Front
and finger tighten the #8 hex nuts (four (4) for each
piece of trim). Refer to Figure 34.
Close both cab sides and replace the two (2) screws on
each side.
REMOVAL OF TOP TRIM:
#8 Stud (x6)
Top Trim
With door open, undo the two (2) screws on the
underside of the top there are visible under the angled
corners. Open the hopper lid, remove the two (2)
screws that are found attached to the top under the
hopper lid. Pull top forward, lift the top front piece off
the stove and turn it over. Remove the six (6) #8 hex
nuts and pull the trim off the studs.
Figure 35: Top front with top trim
#8 Hex Nut (x6)
Hand Tighten Only
REPLACEMENT OF THE TOP TRIM:
Place the new trim on its corresponding studs (see Figure 35) and finger tighten the six (6) #8 hex
nuts.
Replace top front on top of the stove, remembering to hook the two (2) front tabs under the corresponding
tabs on the stove. Replace the two (2) screws on the top under the hopper lid then close lid. Replace the
two (2) screws under the corner lips above the door. Align top then tighten screws.
25
Page 26
Figure 36: Door with louvers.
Installation
REMOVAL OF LOUVER BAR SET:
Door must be open. The three (3) arrows in Figure 36 point to
three (3) of the nuts that hold the louvers on. There are three
nuts on each end. Remove the six nuts by hand; if the nuts are
tight, a
pull one end of the louver up over the stud. If it is difficult to
remove the louver, push on one side from the front, then pull
the other end off the second stud.
REPLACEMENT OF LOUVER BAR SET:
Place one slotted end of new louver over a stud, then slide the
other slot over the corresponding stud; replace the nuts and
hand tighten. Close door when all three louvers are replaced.
Clean all plated surfaces before starting the stove. See
CleanIng Plated SurFaCeS in routIne CleanIngand maIntenanCe in the
Owner’s Manual.
11
/32” socket can be used. When removing the louvers,
plated door inStallation:
TO AVOID PERSONAL INJURY DO NOT REMOVE OR REPLACE COVER WHEN PELLET STOVE IS HOT!
TOOLS REQUIRED:
●11/32” socket or wrench
REMOVAL OF DOOR COVER:
When stove is off and cool, open the door. Remove the four (4)
#8 hex nuts around the inside of the glass retainer shown in
Figure 37.
Remove door cover from door by gently sliding the studs out of
the holes. If it is difficult to remove the cover, the glass retainer
may be pinching the threads on the studs. Slightly loosen the
four (4) screws (by each of the studs).
REPLACEMENT OF DOOR COVER:
Slide new door cover into place and hand tighten the four (4)
#8 hex nuts around the inside of the glass retainer. Ensure the
four screws are also hand tight and close door.
Clean all plated surfaces before starting the stove. See
CleanIng Plated SurFaCeS in routIne CleanIngand maIntenanCe in the
Owner’s Manual.
Figure 37: Inner side of Olympian door.
26
Page 27
Installation
Removejumper
wireandinstall
thermostatwireshere.
thermoStat inStallation:
1. Install the wall thermostat in a location that is not to close too the unit but will effectively heat the
desired area.
2. Install a 12 or 24 Volt Thermostat using an 18 x 2
gauge wire from the unit to the thermostat.
If the unit has been placed in the HI / LOW mode, the unit
will be taken to a low or idle setting when the thermostat
is not calling for heat. When the thermostat calls for
heat, the unit will go to the setting that is displayed on
the control board Heat Indicator. If the heating load is
not great enough when the stove is on low, the high limit
switch will turn the stove off and the switch will have to
be manually reset. To reset the high limit switch, remove
the right cabinet side. The switch is found behind the
Figure 38: Thermostat wire placement.
Slider/damper Set-up:
THE SLIDER / DAMPER MUST BE SET AT TIME OF INSTALLATION, IT IS USED TO REGULATE
THE AIRFLOW THROUGH THE PELLET STOVE.
control panel. Avoid setting off the high limit switch.
A Qualified Service Technician or Installer must set the Slider Damper.
The slider damper is used to regulate the airflow through the pellet stove and is located behind the left
cab side (refer to Figure 39). The door must be open for the cab side to be removed on all models. On
freestanding model loosen the two T-20 torx screws, one above and one below hinge, swing open left
panel to access. On insert model remove the two (2) T-20 torx screws on the front, one above and one
below hinge, and the one T-20 at the top of the cab side under the top front.
The combustion exhaust blower is a variable speed blower controlled by the heat output button. This
blower will decrease the vacuum pressure inside
Exhaust Blower
the stove and as the heat output button is turned
down. The vacuum pressure inside the firebox
will increase as the combustion exhaust blower
increases in speed (higher heat output setting).
Exhaust
Channel
If the fire should happen to go out and the heat
output indicator has been set on the lowest
Slider
Damper
setting, the Slider Damper should be pushed in
slightly, decreasing the air in the firebox.
If, after long periods of burning, the fire builds
up and overflows the burn pot or there is a build
up of clinkers, this would be a sign that the pellet
have been removed in order
Note: Some parts
to see components more clearly.
Figure 39: Slider / Damper
quality is poor, this requires more primary air, the
slider damper must be pulled out to compensate.
Pulling the slider damper out gives the fire more
air.
27
Page 28
Installation
The easiest way to make sure that an efficient flame is
achieved is to understand the characteristics of the fire.
• A tall, lazy flame with dark orange tips requires more
air – Open slider (pull out) slightly.
• A short, brisk flame, like a blowtorch, has too much air
– Close slider (push in) slightly.
• If the flame is in the middle of these two
characteristics with a bright yellow/orange, active
flame with no black tips then the air is set for proper
operation (see Figure 40).
SPECIAL NOTES:
Pellet quality is a major factor in how the Pellet stove will
operate. If the pellets have a high moisture content or
ash content the fire will be less efficient and has a higher
possibility of the fire building up and creating clinkers
(hard ash build-up).
Figure 40: Efficient Flame.
Taking a reading of vacuum pressure inside the firebox
with a magnehelic gauge can be used to set the slider
for best combustion. The slider damper should be set
only on a hot stove (operating for thirty (30) minutes
or more) by placing a Magnahelic Pressure Gauge in the
firebox. The reading can be taken from the ⅛” (3 mm)
hole located in the front of the firebox under the door
(see Figure 41). The best settings are a reading of
approximately 0.10 inches of water column on the
high fire setting. Some fuels may require higher or
lower settings.
Figure 41: Hole for Pressure test with Magnehelic
Gauge.
28
Page 29
Troubleshooting
DO NOT:
● Service the stove with wet hands. The stove is an electrical appliance, which may pose a shock hazard
if handled improperly. Only qualified technicians should deal with possible internal electrical failures.
● Do not remove from the firebox any screws without penetrating oil lubrication.
WHAT TO DO IF:
1. The stove will not start.
2. The stove will not operate when hot.
3. The exhaust blower will not function normally.
4. Light # 2 on Heat output bar flashing.
5. Auger light flashes but auger motor does not turn at all
6. The 200 °F (93 °C) high limit temperature sensor has tripped.
7. The convection blower will not function normally.
8. Igniter- the pellets will not light.
9. Control settings (Heat Level) has no effect on the fire.
10. The stove keeps going out.
*NOTE: All troubleshooting procedures should be carried out by qualified technicians or
installers.
1. The stove will not start.
Make sure the stove is plugged in and the wall outlet is supplying power..
If the Control Board has been placed in the ON /OFF thermostat mode, then turn the thermostat up to
call for heat.
Check the Heat Level Indicator. - If the # 2 light is flashing (see the # 2 light is flashing)
Check the fuse on the circuit board.
If the unit still does not start, contact your local service dealer for service.
2. The stove will not operate when hot.
Check the Heat Level Indicator if a fire is not detected, or if the fire has gone out the #3 light will
flash because the Exhaust Temperature Sensor’s contacts have opened.
Check the hopper for fuel.
Incorrect air damper setting. - Excessive air may consume the fire too quickly before the next drop of
fuel, leaving completely unburned fuel in the burn pot liner. - Insufficient air will cause build up, further
restricting the air flow through the Burn Pot Liner. This in turn will cause the fuel to burn cold and very
slowly. Fuel may build up and smother the fire. In this case clean the burn pot. (NOTE: unit may
require a change to the vent system or installation of fresh air to correct Air to Fuel ratio
problems).
Combustion Blower failure. - The Combustion Blower is not turning fast enough to generate the proper
vacuum in the fire box. Visual Check – is the blower motor turning.
Check the Exhaust Blower voltage across the blower wires (>=220V on #5 setting and >= 150V on
#1 setting). – Replace the Circuit Board if the Voltage reading is less than 150 V. with a line voltage
>220 V AC.
Check Vacuum levels in the exhaust channel by bypassing the Vacuum Switch, then remove the Vacuum
hose from Vacuum Switch. Check exhaust vacuum readings by placing the open end of the Vacuum
Hose on a Magnahelic Gauge (readings must be above .10” W.C. on low fire).
If the motor fails to reach a 0.10” W.C. readings, then replace the Combustion Blower.
29
Page 30
Troubleshooting
Poor Quality Fuel – Insufficient energy in the fuel to produce enough heat to keep the stove burning
or operational.
Exhaust Temperature Sensor failure. – Bypass sensor located on Exhaust Blower if stove now operates
properly, the unit may require cleaning or a new sensor. Contact your local dealer for service.
Check the fuse on the circuit board.
3. The exhaust motor will not function normally.
Open the left side access panel; check all connections against the wiring diagram.
See “2. The stove will not operate when hot.” section.
4. Light # 2 on Heat output bar flashing
(The Vacuum Switch contacts have opened for more than 15 sec.)
Pinch, break or blockage in Vacuum Hose - Check hose for pinch points or damage, replace or re-route
as required. Blow out Vacuum Hose
Blocked Hose Barb on Exhaust Channel - Use a paper clip to clean out Hose Barb or remove the Vacuum
Hose from the Vacuum Switch and blow into the hose to remove blockage.
Blocked exhaust / venting system - Have stove and venting cleaned and inspected.
Severe negative pressure in area where unit is installed - Check the operation by opening a window,
does this solve the problem? If it does, install fresh air intake to unit or room. Venting system may
require vertical section to move termination into a low pressure zone.
Vacuum Switch failure - Bypass the vacuum switch, if this corrects the problem check for above
problems before replacing the Vacuum Switch.
Damage to gray wires between Circuit Board and Vacuum Switch - Inspect wires and connectors
Combustion Blower failure - The Combustion Blower is not turning fast enough to generate the proper
vacuum in the Exhaust Channel. Visual Check; is the blower motor turning? Check the Exhaust Blower
voltage across the blower wires (>=220V on #5 setting and >= 150V on #1 setting). – Replace the
Circuit Board if the Voltage reading is less than 150 V. with a line voltage >220 V AC.
Check Vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the Vacuum
hose from Vacuum Switch. Check exhaust vacuum readings by placing the open end of the Vacuum
Hose on a Magnahelic Gauge. (readings must be above .10” W.C. on low fire).
If the motor fails to reach a 0.10” W.C. readings, then replace the Combustion Blower
To reset Circuit Board after a trouble code - push the ON/OFF button
5. Auger light flashes but auger motor does not turn at all.
If the Auger gear box does not turn but the motor’s armature does try to spin then the auger is jammed.
– Try to break apart jam by poking at the jam through the drop tube. If this fails then empty the hopper
and remove the Auger Cover **Remember to re-seal the cover after installation**
Check the fuse on the circuit board.
6. The 200 °F ( 93 °C) high limit temperature sensor has tripped.
Reset sensor and determine cause – was it Convection Blower failure
Check the fuse on the circuit board.
30
Page 31
Troubleshooting
7. The convection blower will not function normally.
Clean all grill openings at the back and below unit .
Press the fan button; does the fan come on? Press again to verify that the blower turns on; if, not
contact your local dealer for service.
8. Ignitor- the pellets will not light.
Everything else in the stove operates but the ignitor will not light the pellets.
Make sure the burn pot liner is up tight and square to the ignitor tube by pushing the burn pot back
against the ignitor tube.
Check to see if the exhaust blower is operating. If not, contact your local dealer for service.
Check the fuse on the circuit board.
NOTE: The ignitor should be bright orange in color. If not replace the ignitor.
9. Control settings (Heat Level) has no effect on the fire.
NOTE: If the system light is flashing the Control Board has complete control of the unit. When the units
system light becomes solid then control of the unit is given back to the operator.
If there is no control of the Heat Level button make sure the thermostat is calling for heat.
Call your local dealer for service.
10. The stove keeps going out.
If the stove goes out and leaves fresh unburned pellets or cigarette-like ashes in the burn pot liner, the
fire is going out before the stove shuts off.
Check to see that the Slider / Damper is in the correct position (set with a magnehelic gauge).
Turn the Heat Level up slightly (poor quality pellets will require slightly higher settings).
Set the auger trim till the #1 and #5 lights are illuminated.
If the stove goes out and there are partially burned pellets left in the burn pot liner, the stove has shut
down due to a lack of air, exhaust temperature, or power failure.
Adjust the Slider / Damper.
Check to see if the stove needs a more complete cleaning.
Turn the Heat Level up slightly (poor quality pellets will require slightly higher settings).
Did the power go out?
Contact your local Dealer for service.
31
Page 32
Wiring Diagram
Optional Exterior
Exhaust Blower
Thermostat
Armor Cable Supplied
Black
Combustion
Blower
Power
Cord
115V
Black
220V
Brown
White
White
Blue
Ground
115V
White
220V
Blue
Grey
Grey
Brown
Brown
Red
White
Vacuum
Switch
Exhaust
Temperature
Sensor
Black
Black
Red
Red
Connect
Thermostat
Here
5 Amp
Fuse
Black
White
Orange
Orange
Purple
Blue
Yellow
Red
Grey
Grey
Brown
Brown
Com
monHot
Ignitor
Convection
Temperature
Sensor
Yellow
White
Orange
Orange
Purple
White
Auger
Motor
High Limit
Temperature
Sensor
Convection
Blower
32
Page 33
Parts List - Components
Reference #DescriptionPart #
1120 °F (49 °C) Ceramic Fan Temperature SensorEC-001