Thank you for buying this energy efcient water heater.
We appreciate your condence in our products.
ALL TECHNICAL AND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS
PURCHASED. IF YOU ARE UNSUCCESSFUL, CALL THE TECHNICAL SUPPORT PHONE NUMBER SHOWN ON THE WATER HEATER LABELING.
KEEP THIS MANUAL IN THE POCKET ON HEATER FOR FUTURE REFERENCE
WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.
PRINTED 0114 326464-000
• For Your Safety •
AN ODORANT IS ADDED TO THE GAS USED
BY THIS WATER HEATER.
1
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE.................................3
The proper installation, use and servicing of this water heater is extremely important to your safety and the safety of others.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and
others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important
that the meaning of each safety message is understood by you and others who install, use, or service this water heater.
This is the safety alert symbol. It is used to alert you to
potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible
injury or death.
DANGER indicates an imminently
DANGER
WARNING
CAUTION
hazardous situation which, if not avoided,
will result in injury or death.
WARNING indicates a potentially hazardous
situation which, if not avoided, could result
in injury or death.
CAUTION indicates a potentially hazardous
situation which, if not avoided, could result in
minor or moderate injury.
CAUTION used without the safety alert
CAUTION
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message, and
how to avoid the risk of injury.
symbol indicates a potentially hazardous
situation which, if not avoided, could result in
property damage.
APPROVALS
3
CAUTION
GENERAL SAFETY INFORMATION
PRECAUTIONS
DO NOT USE THIS WATER HEATER IF ANY PART HAS BEEN
UNDER WATER. Immediately call a qualied service agency to
inspect the water heater and to make a determination on what steps
should be taken next.
If the unit is exposed to the following, do not operate heater until all
corrective steps have been made by a qualied service agency.
1. External re.
2. Damage.
3. Firing without water.
GROUNDING INSTRUCTIONS
This water heater must be grounded in accordance with the National
Electrical Code and/or local codes. These must be followed in all
cases. Failure to ground this water heater properly may also cause
erratic control system operation.
This water heater must be connected to a grounded permanent
wiring system; or an equipment grounding conductor must be
run with the circuit conductors and connected to the equipment
grounding terminal or lead on the water heater.
HYDROGEN GAS FLAMMABLE
Explosion Hazard
Flammable hydrogen gases
may be present.
Keep all ignition sources away
from faucet when turning on
hot water.
Hydrogen gas can be produced in a hot water system served by
this water heater that has not been used for a long period of
time (generally two weeks or more). Hydrogen gas is extremely
ammable. To reduce the risk of injury under these conditions, it is
recommended that a hot water faucet served by this water heater
be opened for several minutes before using any electrical appliance
connected to the hot water system. If hydrogen is present there will
probably be an unusual sound such as air escaping through the pipe
as the water begins to ow. THERE SHOULD BE NO SMOKING
OR OPEN FLAME NEAR THE FAUCET AT THE TIME IT IS OPEN.
Verify the power to the water heater is turned off before performing any service procedures.
Read and understand this instruction
manual and the safety messages
herein before installing, operating or
servicing this water heater.
Failure to follow these instructions and
safety messages could result in death
or serious injury.
This manual must remain with the
water heater.
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Improper installation, use and service may result
in property damage.
Do not operate water heater if flood damaged.
•
Inspect anode rods regularly, replace if damaged.
•
Install in location with drainage.
•
Fill tank with water before operation.
•
Properly sized thermal expansion tanks are required on all
•
closed water systems.
Refer to this manual for installation and service.
Explosion Hazard
Overheated water can cause
water tank explosion.
Properly sized temperature and
pressure relief valve must be
installed in the opening provided.
4
GENERAL SAFETY INFORMATION
5
Fire or Explosion Hazard
Read instruction manual before
installing, using or servicing
water heater.
Avoid all ignition sources if you smell gas.
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Use only the gas shown on the water heater rating plate.
Keep ignition sources away from faucets after extended
periods of non-use.
Maintain required clearances to combustibles.
Do not expose water heater controls to excessive gas
pressure.
Do not obstruct water heater air intake
with insulating blanket.
Gas and carbon monoxide detectors
are available.
Install water heater in accordance with
the instruction manual.
Breathing carbon monoxide can cause brain damage or
death. Always read and understand instruction manual.
Breathing Hazard - Carbon Monoxide Gas
Property Damage Hazard
All water heaters eventually leak.
•
Do not install without adequate drainage.
•
CAUTION
GENERAL SAFETY INFORMATION
Fire Hazard
For continued protection against
risk of fire:
Do not install water heater on
carpeted floor.
Do not operate water heater if
flood damaged.
Electrical Shock Hazard
Turn off power to the water heater
•
before performing any service.
Label all wires prior to disconnecting
•
when performing service. Wiring errors
can cause improper and dangerous
operation.
Verify proper operation after servicing.
•
Failure to follow these instructions can
•
result in personal injury or death.
Fire and Explosion Hazard
Do not use water heater with any gas
other than the gas shown on the rating
plate.
Excessive gas pressure to gas valve can
cause serious injury or death.
Turn off gas lines during installation.
Contact a qualified installer or service
agency for installation and service.
6
INTRODUCTION
Thank You for purchasing this water heater. Properly installed and
maintained, it should give you years of trouble free service.
ABBREVIATIONS USED
Abbreviations found in this Instruction Manual include :
• ANSI - American National Standards Institute
• ASME - American Society of Mechanical Engineers
• AHRI - Air-Conditioning, Heating and Refrigeration Institute
• NEC - National Electrical Code
• CSA - Canadian Standards Association
QUALIFICATIONS
QUALIFIED INSTALLER OR SERVICE AGENCY
Installation and service of this water heater requires ability
equivalent to that of a Qualied Agency (as dened by ANSI below)
in the eld involved. Installation skills such as plumbing, air supply,
venting, gas supply and electrical supply are required in addition to
electrical testing skills when performing service.
ANSI Z223.1 2006 Sec. 3.3.83: “Qualied Agency” - “Any
individual, rm, corporation or company that either in person or
through a representative is engaged in and is responsible for (a)
the installation, testing or replacement of gas piping or (b) the
connection, installation, testing, repair or servicing of appliances
and equipment; that is experienced in such work; that is familiar
with all precautions required; and that has complied with all the
requirements of the authority having jurisdiction.”
If you are not qualied (as dened by ANSI above) and licensed or
certied as required by the authority having jurisdiction to perform
a given task do not attempt to perform any of the procedures
described in this manual. If you do not understand the instructions
given in this manual do not attempt to perform any procedures
outlined in this manual.
PREPARING FOR THE INSTALLATION
See the Installation Checklist and Troubleshooting on Page 50.
By using this checklist the user may be able to make minor
operational adjustments and avoid unnecessary service calls.
However, service and diagnostic procedures should only be
performed by a Qualied Service Agency.
NOTE: Costs to correct installation errors are not covered under
the limited warranty.
2. Be sure to turn off power when working on or near the electrical
system of the water heater. Never touch electrical components
with wet hands or when standing in water.
3. The installation must conform to all instructions contained in
this manual and the local code authority having jurisdiction.
These shall be carefully followed in all cases. Authorities having
jurisdiction should be consulted before installation begins if
there are any questions regarding compliance with local, state
or national codes.
In the absence of local codes, the installation must comply with
the current editions of the CAN/CSA-B149.1, the Natural Gas
and Propane Installation Code and CSA C22.1, the Canadian
Electrical Code. All documents are available from the Canadian
Standards Association, 8501 East Pleasant Valley Road,
Cleveland, OH 44131.
4. If after reading this manual you have any questions or do
not understand any portion of the instructions, call the toll
free number on the back cover of this manual for technical
assistance. In order to expedite your request, please have the
full Model, Serial and Series number of the water heater you
are working with available for the technician. This information is
located on the water heater’s rating plate.
5. Carefully plan the placement of the water heater. Examine
the location to ensure that it complies with the requirements
in Locating The Water Heater on Page 14 and the Rough In
Dimensions on Page 8..
1. Read the entire manual before attempting to install or operate
the water heater. Pay close attention to the General Safety
Information on Page 4 thru Page 6. If you don’t follow the safety
rules, the water heater may not operate safely. It could cause
property damage, injury and/or death.
This manual contains instructions for the installation, operation,
and maintenance of the water heater. It also contains warnings
throughout the manual that you must read and be aware of.
All warnings and all instructions are essential to the proper
operation of the water heater and your safety.
Detailed installation diagrams are also found in this manual.
These diagrams will serve to provide the installer with a
reference. It is essential that all venting, water piping, gas piping
and wiring be installed as shown.
Particular attention should be given to the installation of
thermometers at the locations indicated in the piping diagrams
as these are necessary for checking the operation of the water
heater.
The principal components of the water heater are identied in
Features And Components on Page10 & Page 11 in this manual.
Use this reference to locate and identify various components on
the water heater.
7
DIMENSIONS AND CAPACITY DATA
ROUGH IN DIMENSIONS: 50 GALLON UNIT
Figure 1: DIMENSIONS FOR 50 GALLON UNIT
ROUGH IN DIMENSIONS: 75 GALLON UNIT
Figure 1A: DIMENSIONS FOR 75 GALLON UNIT
Table 1 – ROUGH-IN-DIMENSIONS
UnitsABCDEFGHI
50G
75G
Top Inlet and Outlet: 50G - 3/4” NPT; 75G - 1” NPT
Side Inlet and Outlet: 3/4” NPT
Gas Inlet: 1/2” NPT
Inches66.7549.2522.0015.753.008.008.0062.0065.00
cm169.5125.0955.8840.007.6220.3220.32157.48165.1
Inches64.7145.6427.7516.003.718.007.9357.3658.98
cm164.4115.970.540.69.420.320.1145.7149.8
8
DIMENSIONS AND CAPACITY DATA
Table 2 – CAPACITY, GAS AND ELECTRICAL CHARACTERISTICS
All models - Maximum Supply Pressure: 14 inches W.C. (3.48kPa)
Minimum Supply Pressure for Natural Gas: 3.50” (.87kPa)
Minimum Supply Pressure for Propane Gas: 8.00” (1.99kPa)
Minimum pressure must be maintained under both load and no load (dynamic and static) conditions.
Table 3 – RECOVERY CAPACITIES
InputRecovery Capacities
Rating
(Btu/hr)
100,00029.3
Recovery capacity based on 96% thermal efciency.
Rating
(kW)
Temp.
Rise
F30405060708090100110120130140
C172228333944505661677278
GPH387291233194166145129116106979083
LPH14651102882734628549488439401367341314
9
**29
FEATURES AND COMPONENTS
50 GALLON UNIT
20
23
22
21
**14
21
30
32
18
16
1
12
**15
25
11
ACCESS PANEL
5
17
13
26, 27
24
33
19
18
35
Caution:
This access panel covers
a 2” NPT plug that was required
during the manufacturing of this
water heater. This 2” NPT ange is
not a cleanout tting, removing the
2” NPT plug and using this tting as
a cleanout could void your warranty.
31
9
34 (SEE
ACCESS
3
2
4
PANEL
CAUTION)
VACUUM RELIEF
VALV E
* CAUTION HARNESS HAS 120 VAC. IN OPERATION.
** See Planning the Vent System, Installation of Vent System and Condensate Piping for more information.
28
*INSTALL PER
LOCAL CODES
Figure 1B: 50 GALLON UNIT
10
**29
FEATURES AND COMPONENTS (CONT.)
75 GALLON UNIT
21
13
18
**14
21
20
23
22
**15
5
12
11
17
1
18
16
25
24
3
2
26, 27
31
4
33
19
9
35
32
30
* CAUTION HARNESS HAS 120 VAC. IN OPERATION.
** See Planning the Vent System, Installation of Vent System and Condensate Piping for more information.
34
VACUUM RELIEF
VALV E
28
*INSTALL PER
LOCAL CODES
Figure 1C: 75 GALLON UNIT
11
FEATURES AND COMPONENTS (CONT.)
1: Control Assembly
2: Blocked Intake Switch
3: Blocked Outlet Switch
4: Blower Prover Switch
5: Blower Assembly
6: Burner Assembly
7: Flame Sensor
8: Igniter Assembly
9: Junction Box
10: Gas Control Valve Assembly
11: Display Board
12: Top Plastic Enclosure
13: Display Enclosure
** 14: Exhaust Elbow Assembly
** 15: Condensate Tubing
16: Off/On Switch
17: Display Label
18: Hot Water Outlet
19: Gas Supply
20: Main Manual Gas Shutoff Valve
21: Union
22: Inlet Water Shutoff Valve
23: Cold Water Inlet
24: Inlet Dip Tube
25: T/P Relief Valve
26: Rating Plate
27: Labels
28: Drain Valve
** 29: Vent Terminal
30: Drain Pan
31: Anode Rod
32: Insulation
33: Temperature Probe
34: Access Door
35: Spark Module
12
CONTROLS AND SWITCHES
This model is provided with three pressure switches. These switches
are essential to the safe and proper operation of the unit. All switches
are wired in series. The controller is set up to shut the unit down
whenever there is a failure of any of the switches. It is important to
understand the purpose of each switch.
BLOCKED EXHAUST SWITCH
The Blocked Exhaust Switch is set up to shut the unit off when a buildup of positive pressure in the exhaust vent pipe occurs. This switch
is a positive pressure switch that requires an increase in pressure to
change the electrical contacts from normally closed to open. When
this switch prevents the unit from igniting, most likely the exhaust is
blocked by some means. Check to see if the condensate is allowed
to ow freely from the exhaust elbow and for obstructions in the
exhaust venting and exhaust vent terminal. Also verify that the vent
length does not exceed the maximum allowed as shown in the Vent
Section of this manual.
Blocked Exhaust
Switch
Blocked
Intake
Switch
Blower
Prover
Switch
50 GALLON UNIT
Blocked
Intake
Switch
Blower
Prover
Switch
BLOCKED INTAKE SWITCH
The Blocked Intake Switch is set up to shut the unit off when a
build-up of negative pressure in the intake air pipe occurs. This
switch is a negative pressure switch that requires an increase
in negative pressure to change the electrical contacts from
normally closed to open. The switch is connected to the pressure
tap on the PVC pipe connected to the inlet of the blower. When
this switch prevents the unit from igniting, most likely the intake
is blocked. Verify that the screen on the intake air connection
(conventional vent), the intake air pipe and termination (direct
vent installations) are free of obstructions that may prevent air
from entering the unit. Insure the screen on intake air connection
has been removed on direct vent installations, see “Figure 13:
AIR INTAKE SCREEN”. Also verify the intake air pipe length
does not exceed the maximum allowed as shown in the Vent
Section of this manual.
WATER HEATING ENABLE/DISABLE (ON/OFF) SWITCH
The Water Heating Enable/Disable (On/Off) Switch is a single-pole,
single-throw rocker switch. This switch provides 24V power to the
gas control valve.
SPARK IGNITER
The Spark Igniter is a device that ignites the main burner by spark.
When high voltage is applied to the igniter, spark is generated to
ignite the main burner.
75 GALLON UNIT
Figure: 2
BLOWER PROVER SWITCH
The Blower Prover Switch is provided on the heater to verify that
the fan is operating. It is a positive pressure switch whose electrical
contacts are normally open. When the fan increases the pressure in
the burner, the pressure switch will allow the electrical contacts to
close. The pressure switch is connected to the blower pressure tap
by a piece of tygon tubing. This tubing must be connected in order for
the switch to change the electrical contacts. The controller requires
that the electrical contacts on this air ow switch be open before it will
allow the blower to come on.
13
CAUTION
INSTALLATION CONSIDERATIONS
LOCATING THE WATER HEATER
Carefully choose a location for the new water heater. The
placement is a very important consideration for the safety of the
occupants in the building and for the most economical use of the
water heater.
Property Damage Hazard
All water heaters eventually leak.
•
Do not install without adequate drainage.
•
Whether replacing an existing water heater or installing the
water heater in a new location observe the following critical
points:
1. The water heater must be located indoors.
2. The water heater must not be located in an area where it
will be subject to freezing temperatures.
3. Locate the water heater so it is protected and not subject
to physical damage by a moving vehicle.
4. Locate the water heater on a level surface.
5. Locate the water heater near a floor drain. The water heater
should be located in an area where leakage of the tank or
connections will not result in damage to the area adjacent
to the water heater or to lower floors of the structure. When
such locations cannot be avoided, it is recommended that
a metal drain pan, piped to adequate drain, be installed
under the water heater. Drain pan should be fabricated
with sides at least 2” deep with diameter at least 2” greater
than diameter of heater. Pan must not restrict combustion
air flow.
6. Locate the water heater close to the point of major hot
water usage.
7. Locate the water heater close to a 120 VAC power supply.
See Power Supply on Page 18 for requirements.
8. Locate the water heater where an adequate supply of fresh
air for combustion and ventilation can be obtained. See
Combustion Air and Ventilation on Page 15.
9. Locate the water heater where the vent and intake air
piping, when installed, will remain within the maximum
equivalent lengths allowed. See Venting on Page 24.
10. Do not locate the water heater where noise (such as
the Combustion Blower) during normal operation will be
objectionable in adjacent areas.
11. Do not locate the water heater where the subsequent
installation of the vent (exhaust) or intake air terminations
would be objectionable due to noise at the termination(s).
This includes locations close to or across from windows
and doors. See Venting starting on Page 24.
Do not locate water heater areas where flammable liquids
(vapors) are likely to be present or stored (garages, storage
and utility areas, etc.): Flammable liquids (such as gasoline,
solvents, propane (LP or butane, etc.) and other substances
(such as adhesives, etc.) emit flammable vapors which can be
ignited by a gas water heater’s ignition device or main burner.
The resulting flashback and fire can cause death or serious
burns to anyone in the area.
Also, the water heater must be located and/or protected so it
is not subject to physical damage by a moving vehicle.
This water heater must not be installed directly on carpeting.
Carpeting must be protected by metal or wood panel beneath the
water heater extending beyond the full width and depth of the water
heater by at least 3” (7.6 cm) in any direction, or if the water heater
is installed in an alcove or closet, the entire oor must be covered
by the panel. Failure to heed this warning may result in a re hazard.
14
Minimum clearances between the water heater and combustible
construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from
the front and 18” (45.7 cm) from the top. (Standard clearance.) If
clearances stated on the heater differ from standard clearances, install
water heater according to clearances stated on the heater.
Adequate clearance 30” (76 cm) for servicing this water heater should
be considered before installation, such as changing the anode rods,
control system components and gas control valve.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to
replaceable and/or serviceable parts such as the thermostats, drain valve,
condensate drain, temperature-pressure relief valve, clean out opening,
and the vent connection (exhaust elbow).
When installing the heater, consideration must be given to proper
location. Location selected should be as close to the wall as practicable
and as centralized with the water piping system as possible.
• Do not apply insulation to the top of the water heater, as this will
interfere with safe operation of the blower assembly.
• Do not cover the control system LCD on top of the water heater.
• Do not cover the outer door, thermostat or temperature & pressure
relief valve.
• Do not cover the instruction manual. Keep it on the side of the
water heater or nearby for future reference.
• Do obtain new warning and instruction labels from the manufacturer
for placement on the blanket directly over the existing labels.
• Do inspect the insulation blanket frequently to make certain it does
not sag, thereby obstructing combustion air ow.
COMBUSTION AIR AND VENTILATION
A gas water heater cannot operate properly without the correct
amount of air for combustion. Do not install in a conned area such
as a closet, unless you provide air as shown in the Facts to Consider
About Location section. Never obstruct the ow of ventilation air. If
you have any doubts or questions at all, call your gas supplier. Failure
to provide the proper amount of combustion air can result in a re or
explosion and cause death, serious bodily injury, or property damage.
Figure 3: CLEARANCES
INSULATION BLANKETS
Insulation blankets are available to the general public for external use
on gas water heaters but are not necessary with these products. The
purpose of an insulation blanket is to reduce the standby heat loss
encountered with storage tank heaters. Your water heater meets or
exceeds the Energy Policy Act standards with respect to insulation and
standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you
should follow these instructions (For identication of components
mentioned below, see “Figure 1B: 50 GALLON UNIT” & “Figure 1C:
75 GALLON UNIT”. Failure to follow these instructions can restrict
the air ow required for proper combustion, potentially resulting in
re, asphyxiation, serious personal injury or death.
Figure 4: COMBUSTION AIR AND VENTILATION
If this water heater will be used in beauty shops, barber shops,
cleaning establishments, or self-service laundries with dry cleaning
equipment, it is imperative that the water heater(s) be installed
direct vent so that all air for combustion and ventilation is taken
from outdoors.
Propellants of aerosol sprays and volatile compounds, (cleaners,
chlorine based chemicals, refrigerants, etc.) in addition to being
highly ammable in many cases, will also react to form corrosive
hydrochloric acid when exposed to the combustion products of
the water heater. The results can be hazardous, and also cause
product failure.
15
UNCONFINED SPACE
An Unconned Space is one whose volume IS NOT LESS THAN
50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the
total input rating of all appliances installed in the space. Rooms
communicating directly with the space, in which the appliances are
installed, through openings not furnished with doors, are considered
a part of the unconned space.
FRESH AIR OPENINGS FOR CONFINED SPACES
The following instructions shall be used to calculate the size, number
and placement of openings providing fresh air for combustion,
ventilation and dilution in conned spaces. The illustrations shown
in this section of the manual are a reference for the openings
that provide fresh air into conned spaces only. DO NOT refer to
these illustrations for the purpose of vent installation. See Venting
Installation on Page 24 for complete venting installation instructions.
Makeup air requirements for the operation of exhaust fans, kitchen
ventilation systems, clothes dryers and replaces shall also be
considered in determining the adequacy of a space to provide
combustion, ventilation and dilution air.
UNUSUALLY TIGHT CONSTRUCTION
In unconned spaces in buildings, inltration may be adequate to
provide air for combustion, ventilation and dilution of ue gases.
However, in buildings of unusually tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.)
additional air must be provided using the methods described in the
Conned Space section that follows.
CONFINED SPACE
A Conned Space is one whose volume IS LESS THAN 50 cubic
feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input
rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion,
ventilation and dilution in conned spaces. The required size for
the openings is dependent on the method used to provide fresh
air to the conned space AND the total Btu/hr input rating of all
appliances installed in the space.
DIRECT VENT APPLIANCES
Appliances installed in a Direct Vent conguration that derive all
air for combustion from the outdoor atmosphere through sealed
intake air piping are not factored in the total appliance input Btu/hr
calculations used to determine the size of openings providing fresh
air into conned spaces.
EXHAUST FANS
OUTDOOR AIR THROUGH TWO OPENINGS
Figure: 5
The conned space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. The openings shall communicate directly with the
outdoors. See Figure 5.
Each opening shall have a minimum free area of 1 square inch per
4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating of all
appliances installed in the enclosure. Each opening shall not be
less than 100 square inches (645 cm2).
Where exhaust fans are installed, additional air shall be provided
to replace the exhausted air. When an exhaust fan is installed in
the same space with a water heater, sufcient openings to provide
fresh air must be provided that accommodate the requirements
for all appliances in the room and the exhaust fan. Undersized
openings will cause air to be drawn into the room through the water
heater’s vent system causing poor combustion. Sooting, serious
damage to the water heater and the risk of re or explosion may
result. It can also create a risk of asphyxiation.
LOUVERS AND GRILLES
The free areas of the fresh air openings in the instructions that
follow do not take in to account the presence of louvers, grilles or
screens in the openings.
The required size of openings for combustion, ventilation and
dilution air shall be based on the net free area of each opening.
Where the free area through a design of louver or grille or screen is
known, it shall be used in calculating the size of opening required to
provide the free area specied. Where the louver and grille design
and free area are not known, it shall be assumed that wood louvers
will have 25% free area and metal louvers and grilles will have 75%
free area. Non motorized louvers and grilles shall be xed in the
open position.
OUTDOOR AIR THROUGH ONE OPENING
Figure: 6
16
Alternatively a single permanent opening, commencing within 12
inches (300 mm) of the top of the enclosure, shall be provided.
See Figure 6. The water heater shall have clearances of at
least 1 inch (25 mm) from the sides and back and 6 inches (150
mm) from the front of the appliance. The opening shall directly
communicate with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces that freely
communicate with the outdoors and shall have a minimum free
area of the following:
1. 1 square inch per 3000 Btu/hr (733 mm2 per kW) of the total
input rating of all appliances located in the enclosure, and
2. Not less than the sum of the areas of all vent connectors in the space.
OUTDOOR AIR THROUGH TWO HORIZONTAL DUCTS
AIR FROM OTHER INDOOR SPACES
Figure: 8
The conned space shall be provided with two permanent
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. See Figure 8.
Figure: 7
The conned space shall be provided with two permanent horizontal
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure. The horizontal ducts shall communicate directly with the
outdoors. See Figure 7.
Each duct opening shall have a minimum free area of 1 square inch
per 2,000 Btu/hr (1100 mm2 per kW) of the aggregate input rating of
all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional
area as the free area of the openings to which they connect. The
minimum dimension of rectangular air ducts shall be not less than
3 inches.
Each opening shall communicate directly with an additional room(s)
of sufcient volume so that the combined volume of all spaces
meets the criteria for an Unconned Space.
Each opening shall have a minimum free area of 1 square inch per
1,000 Btu/hr (2200 mm2 per kW) of the aggregate input rating of
all appliances installed in the enclosure. Each opening shall not be
less than 100 square inches (645 cm2).
17
INSTALLATION REQUIREMENTS
CHEMICAL VAPOR CORROSION
Corrosion of the ueways and vent system may occur if air for
combustion contains certain chemical vapors. Such corrosion may
result in failure and risk of asphyxiation.
Spray can propellants, cleaning solvents, refrigerator and air
conditioning refrigerants, swimming pool chemicals, calcium
and sodium chloride (water softener salt), waxes, and process
chemicals are typical compounds which are potentially corrosive.
Do not store products of this sort near the heater. Also, air which is
brought in contact with the heater should not contain any of these
chemicals. If necessary, uncontaminated air should be obtained
from remote or outside sources. The limited warranty is voided
when failure of water heater is due to a corrosive atmosphere. (See
limited warranty for complete terms and conditions).
WATER PIPING
HOTTER WATER CAN SCALD:
Water heaters are intended to produce hot water. Water heated to
a temperature which will satisfy space heating, clothes washing,
dish washing, cleaning and other sanitizing needs can scald and
permanently injure you upon contact. Some people are more likely
to be permanently injured by hot water than others. These include
the elderly, children, the physically or developmentally disabled. If
anyone using hot water ts into one of these groups or if there is a
local code or state law requiring a certain temperature water at the
hot water tap, then you must take special precautions. In addition
to using the lowest possible temperature setting that satises your
hot water needs, a means such as a mixing valve should be used
at the hot water taps used by these people or at the water heater.
Valves for reducing point of use temperature by mixing cold and hot
water are also available:
This water heater shall not be connected to any heating
systems or component(s) used with a non-potable water heating
appliance.
All piping components connected to this unit for space heating
applications shall be suitable for use with potable water.
Toxic chemicals, such as those used for boiler treatment shall
not be introduced into this system.
When the system requires water for space heating at
temperatures higher than required for domestic water purposes,
a mixing valve must be installed.
These water heaters cannot be used in space heating
applications only.
POWER SUPPLY
The water heaters covered in this manual require a 120
VAC, 1Ø (single phase), 60Hz, 15 amp power supply and
must also be electrically grounded in accordance with local
codes or, in the absence of local codes, with the CSA C22.1,
the Canadian Electrical Code.
POWER FLUCTUATIONS AND ELECTRICAL NOISE
The water heater’s control system requires a source of
stable clean electricity for proper operation. Connecting the
water heater to a branch circuit that is subject to fluctuations
in voltage level or electrical line noise such as EMI (electro
magnetic interference) or RFI (radio frequency interference)
may cause erratic control system operation and malfunction.
A high quality power supply filter/suppressor must be
installed if the above conditions exist. Call the technical
support phone number listed on the back cover of this
manual for more information.
NOTE: Malfunctions caused by the power supply and the
costs to install power supply filters are not covered under
the limited warranty.
DEDICATED POWER WIRING AND BREAKERS
Dedicated power supply wires, ground wiring and dedicated
circuit breakers often prevent electrical line noise and
should be considered when installing the water heater.
Consult a Qualied Installer or Service Agency. Follow
manufacturer’s instructions for installation of the valves. Before
changing the factory setting on the thermostat, read the Temperature
Regulation section in this manual.
18
MIXING VALVES
Water temperature over 125°F (52°C)
can cause severe burns instantly
resulting in severe injury or death.
Children, the elderly and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting devices such as
mixing valves must be installed
when required by codes and to
ensure safe temperatures at fixtures.
Water heated to a temperature which will satisfy clothes washing,
dish washing, and other sanitizing needs can scald and cause
permanent injury upon contact. Short repeated heating cycles
caused by small hot water uses can cause temperatures at the
point of use to exceed the water heater’s temperature setting by
up to 20°F (11°C).
Some people are more likely to be permanently injured by hot water
than others. These include the elderly, children, the inrm and the
physically/mentally disabled. Table 4 shows the approximate timeto-burn relationship for normal adult skin. If anyone using hot water
provided by the water heater being installed ts into one of these
groups or if there is a local code or state law requiring a certain
water temperature at the point of use, then special precautions
must be taken.
In addition to using the lowest possible temperature setting that
satises the demand of the application a Mixing Valve should be
installed at the water heater or at the hot water taps to further
reduce system water temperature.
Mixing valves are available at plumbing supply stores. Consult
a Qualied Installer or Service Agency. Follow mixing valve
manufacturer’s instructions for installation of the valves.
In all cases, the following burn table must be used.
GAS PIPING
Make sure gas supplied is same type listed on model rating plate. The
inlet gas pressure must not exceed 14 inch water column (3.5 kPa) for
natural and propane gas (L.P.). The minimum inlet gas pressure shown
on rating plate is that which will permit ring at rated input.
SEDIMENT TRAPS
A sediment trap shall be installed as close to the gas inlet of the
water heater as practical at the time of water heater installation. The
sediment trap shall be either a tee tting with a capped nipple in the
bottom outlet or other device recognized as an effective sediment
trap.
Contaminants in the gas lines may cause improper operation of the
gas control valve that may result in re or explosion. Before attaching
the gas line be sure that all gas pipe is clean on the inside. To trap
any dirt or foreign material in the gas supply line, a sediment trap
must be incorporated in the piping. The sediment trap must be readily
accessible. Install in accordance with the Gas Piping section. Refer
to the current edition of the CAN/CSA-B149.1, the Natural Gas and
Propane Installation Code.
Table 4
Water Temperature
°F (°C)
110 (43.3)(normal shower temp.)
116 (46.7)(pain threshold)
116 (46.7)35 minutes45 minutes
122 (50)1 minute5 minutes
131 (55)5 seconds25 seconds
140 (60)2 seconds5 seconds
149 (65)1 second2 seconds
154 (67.8)instantaneous1 second
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15, 1978)
Time for 1st Degree Burn
(Less Severe Burns)
Time for Permanent
Burns
2nd & 3rd Degree
(Most Severe Burns)
Use pipe joint compound or teon tape marked as being resistant to
the action of petroleum [Propane (L.P.)] gases.
The water heater and its gas connection must be leak tested before
placing the water heater in operation.
The water heater and its individual Shut-off valve shall be disconnected
from the gas supply piping system during any pressure testing of that
system at test pressures in excess of 1/2 pound per square inch (3.5
kPa). It shall be isolated from the gas supply piping system by closing
its individual manual Shut-off valve during any pressure testing of the
gas supply piping system at test pressures equal to or less than 1/2
pound per square inch (3.5 kPa).
19
GAS SUPPLY SYSTEMS
Low pressure building gas supply systems are dened as those
systems that cannot under any circumstances exceed 14” W.C. (1/2
PSI Gauge). These systems do not require pressure regulation.
Measurements should be taken to insure that gas pressures are
stable and fall within the requirements stated on the water heater
rating plate. Readings should be taken with all gas burning equipment
off (static pressure) and with all gas burning equipment running at
maximum rate (dynamic pressure). The gas supply pressure must
be stable within 1.5” W.C. from static to dynamic pressure to provide
good performance. Pressure drops that exceed 1.5” W.C. may cause
rough starting, noisy combustion or nuisance outages. Increases or
spikes in static pressure during off cycles may cause failure to ignite
or in severe cases damage to water heater gas control valves. If
your low pressure system does NOT meet these requirements, the
installer is responsible for the corrections.
High Pressure building supply systems use pressures that exceed
14” W.C. (1/2 PSI Gauge). These systems must use eld supplied
regulators to lower the gas pressure to less than 14” W.C. (1/2 PSI
Gauge). Appliances require gas regulators that are properly sized
for the water heater input and deliver the rating plate specied
pressures. Gas supply systems where pressure exceeds 5 PSI often
require multiple regulators to achieve desired pressures. Systems in
excess of 5 PSI building pressure should be designed by gas delivery
professionals for best performance. Water heaters connected to gas
supply systems that exceed 14” W.C. (1/2 PSI Gauge) at any time
must be equipped with a gas supply regulator.
GAS PRESSURE REQUIREMENTS
All models require a minimum gas supply pressure of 3.5” W.C.(0.87
kPa) for natural gas and 8.0” W.C. (1.99 kPa) for propane. The
minimum supply pressure is measured while gas is not owing
(static pressure) AND while gas is owing (dynamic pressure). The
supply pressure (static and dynamic) should never fall below 3.5”
W.C.(0.87 kPa) for natural gas or 8.0” W.C. (1.99 kPa) for propane.
The supply pressure should be measured with all gas red water
heaters connected to the common main ring at full capacity. If the
supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins
to ow to the water heater then the supply gas system including the
gas line and/or the gas regulator may be restricted or undersized.
See Supply Gas Regulator section and Gas Piping section of this
manual. The gas control valve on all models has a maximum gas
supply pressure limit of 14” W.C.(3.48 kPa) The maximum supply
pressure is measured while gas is not owing (static pressure) AND
while gas is owing (dynamic pressure).
SUPPLY GAS REGULATOR
The maximum allowable gas supply pressure for this water heater
is 14 inches W.C. (3.5 kPa). Install a positive lock-up gas pressure
regulator in the gas supply line if inlet gas pressure can exceed 14
inches W.C. (3.5 kPa) at any time. Regulators must be sized/used
according to manufacturer’s specications.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or above
the input Btu/hr rating of the water heater they supply.
2. Positive lock-up gas pressure regulator(s) should be installed no
closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters)
from the water heater’s inlet gas connection.
3. After installing the positive lock-up gas pressure regulator(s) an
initial nominal supply pressure setting of 7.0” W.C.(1.74 kPa) for
Natural Gas and 11.0” W.C. (2.74 kPa) for Propane (LP) while
the water heater is operating is recommended and will generally
provide good water heater operation. Some additional adjustment
may be required later to maintain a steady gas supply pressure.
4. When installing multiple water heaters in the same gas supply
system it is recommended that individual positive lock-up gas
pressure regulators be installed at each unit.
All gas piping must comply with local codes and ordinances or
with the current edition of CAN/CSA-B149.1, the Natural Gas and
Propane Installation Code. Copper or brass tubing and ttings
(except tin lined copper tubing) shall not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi
(3.5 kPa), the damage to the gas control valve could result in a re
or explosion from leaking gas.
If the main gas line Shut-off serving all gas water heaters is used,
also turn off the gas at each water heater. Leave all gas appliances
shut off until the water heater installation is complete.
A gas line of sufcient size must be run to the water heater. Consult
the current edition of CAN/CSA-B149.1, the Natural Gas and
Propane Installation Code and your gas supplier concerning pipe
size.
There must be:
• A readily accessible manual shut off valve in the gas supply line
serving the water heater, and
• A sediment trap ahead of the gas control valve to help prevent dirt
and foreign materials from entering the gas control valve.
• A ground joint union of proper size between the manual shut off
valve and control valve to permit servicing of the unit.
Be sure to check all the gas piping for leaks before lighting the water
heater. Use a soapy water solution, not a match or open ame.
Rinse off soapy solution and wipe dry.
20
SPACE HEATING AND POTABLE WATER SYSTEM
Your water heater is equipped with inlet/outlet connections for use
in space heating applications (see Figure 9). If this water heater
is to be used to supply both space heating and potable (drinking)
water, the instructions listed below must be followed:
• Be sure to follow the manual(s) shipped with the air handler or
other type heating system.
• This water heater cannot be used in space heating applications
only.
• This water heater is not to be used as a replacement for an
existing boiler installation.
• Do not use with piping that has been treated with chromates,
boiler seal or other chemicals and do not add any chemicals to
the water heater piping
• If the space heating system requires water temperatures in excess
of 120°F, a mixing valve must be installed per the manufacturer’s
instructions in the potable hot water supply to limit the risk of scald
injury.
• Pumps, valves, piping and ttings must be compatible with
potable water.
• A properly installed ow control valve is required to prevent
thermosiphoning. Thermosiphoning is the result of a continuous
ow of water through the air handler circuit during the off cycle.
Weeping (blow off) of the temperature and pressure relief valve
(T & P relief valve) or higher than normal water temperatures are
the rst signs of thermosiphoning.
• The hot water line from the water heater should be vertical past
any mixing valve or supply line to the heating system to remove
air bubbles from the system Do not connect the water heater to
any system or components previously used with non-potable
water heating appliances when used to supply potable water.
• These water heaters cannot be used in space heating applications
only.
THERMAL EXPANSION
As water is heated, it expands (thermal expansion). In a closed
system the volume of water will grow when it is heated. As the
volume of water grows there will be a corresponding increase in
water pressure due to thermal expansion. Thermal expansion can
cause premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure build
up. This condition is not covered under the limited warranty. The
temperature-pressure relief valve is not intended for the constant
relief of thermal expansion.
A properly sized thermal expansion tank should be installed on all
closed systems to control the harmful effects of thermal expansion.
Contact a local plumbing service agency to have a thermal
expansion tank installed.
NOTE: To protect against untimely corrosion of hot and cold
water t t ing s, it is str o ngl y recomm end ed that di - elec t ric uni ons
or couplings be installed on this water heater when connected
to copper pipe, see Figure 10 also.
Figure: 9
CLOSED WATER SYSTEMS
Water supply systems may, because of code requirements or such
conditions as high line pressure, among others, have installed
devices such as pressure reducing valves, check valves, and back
ow preventers. Devices such as these cause the water system to
be a closed system.
Figure: 10
Figure 9 and Figure 10 show the typical attachment of the water
piping to the water heater. The water heater is equipped with 3/4
inch NPT water connections for 50 gallon unit and 1 inch NPT
water connections for 75 gallon unit..
NOTE: If using copp e r tu bing, sol d e r tubing to an ada p ter befo r e
attaching the adapter to the water heater connections. Do not
solder the water lines directly to the water heater connections.
It will harm the dip tube and damage the tank, T & P Valve and
Pipe Insulation (if supplied)
Fit pipe insulation over the incoming cold water line and the hot
water line. Make sure that the insulation is against the top cover of
the heater.Fit T & P valve insulation over valve. Make sure that the
insulation does not interfere with the lever of the T & P valve.
Secure all insulation using tape.
21
CAUTION
TEMPERATURE-PRESSURE RELIEF VALVE
This water heater is provided with a properly rated/sized and certied
combination Temperature-Pressure Relief Valve (T&P relief valve) by
the manufacturer. The valve is certied by a nationally recognized
testing laboratory that maintains periodic inspection of production of
listed equipment of materials as meeting the requirements for Relief
Valves for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4, and
the code requirements of ASME.
If replaced, the new T&P valve must meet the requirements
of local codes, but not less than a combination TemperaturePressure Relief Valve rated/sized and certied as indicated in
the above paragraph. The new valve must be marked with a
maximum set pressure not to exceed the marked hydrostatic
working pressure of the water heater (150 psi = 1,035 kPa) and
a discharge capacity not less than the water heater Btu/hr or kW
input rate as shown on the water heater’s model rating plate.
NOTE: In addition to the factory installed Temperature-Pressure
Relief Valve on the water heater, each remote storage tank
that may be installed and piped to a water heating appliance
must also have its own properly sized, rated and approved
Temperature-Pressure Relief Valve installed. Call the toll free
technical support phone number listed on the back cover of
this manual for technical assistance in sizing a TemperaturePressure Relief Valve for remote storage tanks.
Water Damage Hazard
Temperature-Pressure Relief Valve discharge
•
pipe must terminate at adequate drain.
T&P VALVE DISCHARGE PIPE REQUIREMENTS:
• Shall not be smaller in size than the outlet pipe size of the valve,
or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall not be exposed to freezing temperatures.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both the
Temperature-Pressure Relief Valve and the discharge pipe.
• Must terminate a maximum of six inches (15.2 cm) above a
oor drain or external to the building. In cold climates, it is
recommended that the discharge pipe be terminated at an
adequate drain inside the building.
• Shall not have any valve or other obstruction between the
temperature-pressure relief valve and the drain.
Burn hazard.
Hot water discharge.
Explosion Hazard
Temperature-Pressure Relief Valve
must comply with ANSI Z21.22CSA 4.4 and ASME code.
Properly sized temperaturepressure relief valve must be
installed in opening provided.
Can result in overheating and
excessive tank pressure.
Can cause serious injury or death.
For safe operation of the water heater, the TemperaturePressure Relief Valve must not be removed from its designated
opening nor plugged. The Temperature-Pressure Relief Valve
must be installed directly into the tting of the water heater
designed for the relief valve. Install discharge piping so that any
discharge will exit the pipe within 6 inches (15.2 cm) above an
adequate oor drain, or external to the building. In cold climates
it is recommended that it be terminated at an adequate drain
inside the building. Be certain that no contact is made with any
live electrical part. The discharge opening must not be blocked
or reduced in size under any circumstances. Excessive length,
over 30 feet (9.14 m), or use of more than four elbows can cause
restriction and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the
Temperature-Pressure Relief Valve and the tank. Do not connect
discharge piping directly to the drain unless a 6” (15.2 cm) air gap
is provided. To prevent bodily injury, hazard to life, or property
damage, the temperature-pressure relief valve must be allowed
to discharge water in adequate quantities should circumstances
demand. If the discharge pipe is not connected to a drain or other
suitable means, the water ow may cause property damage.
Keep clear of TemperaturePressure Relief Valve
discharge outlet.
The Temperature-Pressure Relief Valve must be manually
operated at least twice a year. Caution should be taken to
ensure that (1) no one is in front of or around the outlet of the
Temperature-Pressure Relief Valve discharge line, and (2)
the water manually discharged will not cause any bodily injury
or property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions in this
manual, and replace the Temperature-Pressure Relief Valve with
a properly rated/sized new one.
NOTE: The purpose of a Temperature-Pressure Relief Valve is to
prevent excessive temperatures and pressures in the storage tank.
The T&P valve is not intended for the constant relief of thermal
expansion. A properly sized thermal expansion tank must be
installed on all closed systems to control thermal expansion, see
Closed Water Systems and Thermal Expansion on Page 21.
If you do not understand these instructions or have any questions
regarding the Temperature-Pressure Relief Valve call the toll
free number listed on the back cover of this manual for technical
assistance.
22
CONDENSATE PIPING
This water heater is a condensing unit and requires a drain to be
located in close proximity to allow the condensate to drain safely.
The condensate drains from the unit at the exhaust tee located at
the bottom of the unit (see Figure 11). Condensate from this water
heater is mildly acidic. Please note that some local codes require
that condensate is treated by using a pH neutralizing lter prior to
disposal.
Caution must be used to ensure that the drain is free and clear of
debris and will not allow backow through the condensate hose.
Consideration must be given to avoid freezing of the condensate
lines which could result in excessive build up of condensate inside
the water heater.
freezing of the condensate
condensate drain does not create a slippery condition which could
lead to personal injury.
Condensation warning: this water heater is a condensing unit and
re q u ires a dr a i n to be lo c a ted in clo s e pr oxim i t y to allo w co n densat e
to dr ain sa f e ly. The con d e nsate dr ains fr o m unit at the ex h aust el bow
located at bottom of unit. Note: it is important that the condensate
hose not be elevated above the exhaust elbow, see Figure 11.
Condensate build-up will block the exhaust outlet, which will cause
improper operation.
Waterproof heat tape may be required to prevent
lines. Please ensure that the outlet of the
• Slope the condensate drain toward the inside oor drain or
condensate pump.
• The condensate drain line and connection to the drain piping
must comply with all local codes.
HIGH ALTITUDE INSTALLATIONS
This high efciency water heater is certied for use without
modication for an altitude of 10,100 feet (3,078 m). Consult the
factory for installation at altitudes over 10,100 feet (3,078 m).
Some gas utility companies derate their gas for altitude, making it
unnecessary to install high altitude orices. Call the local gas or
utility company to verify BTU content.
Due to the input rate reduction at high altitudes, the output rating
of the water heater is also reduced and should be compensated
for in the sizing of the equipment for applications.
FILLING THE WATER HEATER
Exhaust
Elbow
Figure: 11
The condensate drain line must be routed to a suitable drain. If
no oor drain is available or the drain is above the level of the
condensate line, install a condensate pump that is resistant
to the acidic condensate. These pumps are available from
local distributors. If the pump is not resistant to acidic water, a
condensate neutralizer must be used ahead of the pump. When
installing the drain line, note the following:
• Plastic pipe or tubing must be used to connect the condensate
drain to a suitable drain or condensate pump. Do not use copper
tubing, iron, or steel pipe for the condensate drain line.
• Condensate drain lines should be installed in conditioned areas
only. Drain lines installed in areas that are subject to freezing
temperatures should be wrapped with a nationally recognized/
listed heat tape and/or approved insulation for freeze protection.
Install per manufacturer’s instructions.
• Do not common drain with the temperature and pressure relief
valve or the condensate line from an air conditioner evaporator
coil.
Never use this water heater unless it is completely full of water.
To prevent damage to the tank, the tank must be lled with water.
Water must ow from the hot water faucet before turning ON gas
to the water heater.
To ll the water heater with water:
1. Close the water heater drain valve by turning the handle to the
right (clockwise). The drain valve is on the lower front of the
water heater.
2. Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open when the
water heater is in use.
3. To insure complete lling of the tank, allow air to exit by opening
the nearest hot water faucet. Allow water to run until a constant
ow is obtained. This will let air out of the water heater and the
piping.
4. Check all water piping and connections for leaks. Repair as
needed.
23
VENTING INSTALLATION
VENT INSTALLATION CONSIDERATIONS
This water heater can be vented using room air for intake
combustion air, or direct vented so that all intake air for combustion
comes from the outside through a sealed pipe.
This water heater may be installed in 4 separate orientations
depending on the requirements of the building and the water
heater. The installer must decide which method is most appropriate
for each installation. These orientations are:
1. Vertical Termination - vertical vent termination through
unenclosed or enclosed areas with roof penetration, refer to
Vertical Vent Terminal Installation on Page 30.
2. Through-the-Wall Termination - horizontal vent termination
directly through an outside wall, see “Figure 12: VENT
TERMINATION” on Page 26.
3. Horizontal Direct Vent - using Through-the-Wall Termination to
exhaust ue products and piping to bring combustion air to the
water heater from the outside. See “Figure: 14” on Page 27.
4. Vertical Direct Vent - using a vertical vent termination to
exhaust ue products and piping to bring combustion air to
the water heater from outside, see “Figure: 20” & “Figure: 21”
on Page 31.
Installation of this water heater must comply with the current edition
CAN/CSA B149.1 - Natural Gas and Propane Installation Code
which requires the vent system components be certied to ULC
S636.
This water heater has been design certied to be vented with
PVC/CPVC pipe and Polypropylene pipe certied and marked as
complying with ULC S636.
If the water heater is being installed as a replacement for an
existing power vented heater in pre-existing venting, a thorough
inspection of existing venting system must be performed prior
to any installation work. Verify that correct material as detailed
above has been used, and that the minimum or maximum vent
lengths and terminal location as detailed in this manual have been
met. Carefully inspect the entire venting system for any signs of
cracks or fractures, particularly at joints between elbows and other
ttings and straight runs of vent pipe. Check system for signs of
sagging or other stresses in joints as a result of misalignment of
any components in the system. If any of these conditions are found,
they must be corrected in accordance with the venting instructions
in this manual before completing installation and putting the water
heater into service.
NOTE: For water heaters in locations with high ambient
temperatures above 100°F (38°C) it is recommended that CPVC or
Polypropylene pipe and ttings be used.
All vent (exhaust) pipes must be pitched a minimum of a 1/4” per
foot back to the water heater to allow drainage of condensation.
Never operate the water heater unless it is vented to the outdoors.
The instructions in this section of the manual must be followed
to avoid choked combustion or recirculation of ue gases. Such
conditions cause sooting of the combustion chamber, burners and
ue tubes and creates a risk of asphyxiation.
For direct vent application where combustion air might be supplied
from extremely cold ambient through fresh air intake piping
system, it is recommended that a backow preventer be installed
at the intake vent terminal close to the blower before proceeding
with installation of the rest of the fresh air intake piping. Call the
technical support phone number listed on the back cover of this
manual for more information.
In cold climates any water vapor remaining in the ue gases will
condense into a cloud of vapor at the point where the vent system
exits the building. Special consideration is recommended, before
locating the vent termination near walkways, windows and building
entrances.
Direct venting into dead spaces such as alleys, atriums, and
inside corners can cause recirculation of ue gases. Recirculation
of ue gases will cause sooting, and icing of the combustion air
intake during severe cold weather. To prevent the recirculation
of ue gases, maintain as much distance as possible between
the combustion air intake and the exhaust vent terminal refer to
“Figure: 15” and “Figure: 16” on Page 28 & Page 29 respectively.
24
POLYPROPYLENE INSTALLATIONS
The water heater has been approved to be installed with
Polypropylene vent material as shown in Table 5 and Table 6. The
approved application of single wall, non-exible, non-concentric
Polypropylene vent material is offered by two specic manufacturers
(Centrotherm ECO Systems and DuraVent Polypropylene. These
listed products must be installed by following the vent manufacturer’s
instructions. Refer to “Table 7” on Page 26 to determine the maximum
pipe length and number of elbows that can be used.
Insulation should not be used on Polypropylene venting materials.
The use of insulation will cause increased vent wall temperatures,
which could result in vent pipe failure.
Use only the adapters and vent system listed in Tables below. DO
NOT mix vent systems of different types or manufacturers. Failure
to comply could result in severe personal injury, death, or substantial
property damage.
Table 5
M & G Duravent PolyPro
Nominal Pipe
Diameter
2”2PPS-ADPPS-PAC2PPS-LB2PPS-E902PPS
Flue Outlet Adapter
Adapter
Connector
Ring
Connector
90 Degree
Elbow
Polypropylene vent systems do not use cement to connect the pipe
and elbow sections but use a push together gasket seal method.
Do not attempt to connect Polypropylene with sealant cement. All
vent connections MUST be secured by the vent manufacturer’s joint
connector. The installer must use a specic vent starter adapter at
the ue connection. The adapter is supplied by the vent manufacturer
to adapt to its vent system.
In order to be in full compliance with ULC-S636 and to meet the
requirements of the water heater manufacturer, you must use the
metal joint connector rings, available from the Polypropylene vent
manufacturer, to stiffen the joints of 2”, and 3” diameter pipes.
Vent MaterialTerminal(s)
2PPS & 2PPS-BG for Exhaust;
2PPS-E90 & 2PPS-BG for Intake (Direct Vent
only)
3”3PPS-ADPPS-PAC3PPS-LB3PPS-E903PPS
Table 6
Centrotherm InnoFlue SW
Nominal Pipe
Diameter
2”
3”
Flue Outlet Adapter
ISAGL
0202
ISAGL
0303
Adapter
Connector
IAFC02IANS02ISELL0287ISVL02
IAFC03IANS03ISELL0387ISVL03
Ring
Connector
90 Degree
Elbow
3PPS & 3PPS-BG for Exhaust;
3PPS-E90 & 3PPS-BG for Intake (Direct Vent
only)
Vent MaterialTerminal(s)
ISVL02 & IASPP02 for Exhaust;
ISELL0287 & IASPP02 for Intake (Direct Vent
only)
ISVL03 & IASPP03 for Exhaust;
ISELL0387 & IASPP03 for Intake (Direct Vent
only)
25
VENT PIPE TERMINATION
The rst step is to determine where the vent pipe will terminate. See
Figures 12, “Figure: 13A”, and “Figure: 14”. The vent may terminate
thr o u gh a side w all as sh own in Fi gure 12 and “Figu r e: 14” or th r ough
the roof as shown in “Figure: 15” and “Figure: 16”.
The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
Natural Gas and Propane Installation Code (CAN/CSA-B149.1).
See “Figure: 15” and “Figure: 16”.
Instructions on proper installation through a sidewall are provided
in Figures 12, “Figure: 13A”, and “Figure: 14”.
Plan the vent system layout so that proper clearances are
maintained from plumbing and wiring.
Vent pipes serving power vented water heaters are classied by
building codes as vent connectors. Required clearances from
combustible materials must be provided in accordance with
information in this manual under FACTS TO CONSIDER ABOUT LOCATION and INSTALLING THE WATER HEATER, and with the
National Fuel Gas Code and local codes.
PLANNING THE VENT SYSTEM
Plan the route of the vent system from the exhaust elbow to the
planned location of the vent terminal.
1. Layout total vent system to use a minimum of vent pipe and
elbows.
2. This water heater is capable of venting ue gases in equivalent
The minimum vent length for each of the pipe size is one 90° elbow
plus 2’ and 7’ (0.61 m and 2.1 m) of straight pipe for air intake and
exhaust vent respectively and the appropriate termination.
NOTE: Th e equiva l e nt fe e t (m) of pip e li sted ab ove ar e excl u s ive
of the termination. That is, the termination, with an installed
screen, is assumed to be in the system and the remainder of
the system must not exceed the lengths and number of elbows
shown in Table 7.
If using 2” inch vent pipe: A 2” diameter vent pipe must be
inserted and glued to the exhaust elbow assembly.
If using 3” inch vent pipe: Two inches (5.1cm) of 2” diameter pipe
must be inserted and glued to the exhaust elbow assembly before
adding a 2’ x 3” reducer to acquire the desired pipe diameter. A
3” coupling (supplied locally-a schedule 40 DWV) vent terminal
must be obtained. A 3” diameter screen is supplied in the vent
kit.
2” Maximum
Pipe - ft. (m)
3” Maximum
Pipe - ft. (m)
INSTALLATION OF HORIZONTAL THROUGH THE
WALL VENT SYSTEM
If yo u are inst a l ling yo u r syst e m so that it vent s th r ough ro o f, plea s e
re f e r to se c t i on titl e d VERTIC A L VE NT TERMI N A L IN S TA L L AT I O N .
VENT TERMINAL INSTALLATION, SIDEWALL
1. I n stall th e vent te r m i nal by us ing the co ver pla t e as a tem p l ate to
mark the hole for the vent pipe to pass through the wall. BEWARE
OF CONCEALED WIRING AND PIPING INSIDE THE WALL.
2. If the Vent Terminal is being installed on the outside of a nished
wall, it may be easier to mark both the inside and outside wall.
Align the holes by drilling a hole through the center of the
template from the inside through to the outside. The template
can now be positioned on the outside wall using the drilled hole
as a centering point for the template.
3. A) MASONRY SIDE WALLS
Chisel an opening approximately one half inch (1.3 cm) larger
than the marked circle.
B) WOODEN SIDE WALLS
Drill a pi lot ho l e approx i mate l y one quar te r inch (0. 6 4 cm) ou t side
of the marked circle. This pilot hole is used as a starting point
for a saws-all or sabre saw blade. Cut around the marked circle
staying approximately one quarter inch (0.64 cm) outside of the
line. (This will allow the vent to easily slide through the opening.
The resulting gap will be covered up by the Vent Terminal cover
plate.) Repeat this step on inside wall if necessary.
Cut a length of pipe about 3.5 inches (8.9 cm) longer than the wall
thi c k n ess at th e open i n g. Glue th e ven t termi n a l to th i s sectio n of pipe .
Slide the wall plate over the pipe to stop against the vent terminal.
Place a bead of caulking (not supplied) around the gap between the
pipe and cover plate. Apply enough to ll some of the gap between
the pipe and wall. Place some of the caulking on the back of the plate
to hold it against the wall after installation. If the vent pipe is installed
up to the wall, with a coupling on the end against the wall opening,
the pipe with the vent terminal can be prepared for gluing before
inserting through the wall. Slide the pipe through the wall and insert
into the coupling on the other side of the wall, making sure that the
vent terminal ends up pointed in the correct position, see Figure 12.
Figure 12: VENT TERMINATION
26
DIRECT VENT TERMINAL INSTALLATION
The air intake provided on the unit contains an air intake screen to
prevent large particles from entering the unit.
Blower Air Inlet Assembly
Air Intake Screen
Figure 13: AIR INTAKE SCREEN
When the unit is to be setup as a direct vent, the air intake screen
must be removed. The air intake pipe may then be glued to the air
intake (see Figure 13) provided on the unit.
This unit consists of two terminals - an air intake terminal and an
exhaust vent terminal. The air intake terminal is a 2” 90° pvc elbow
with an air intake screen and the exhaust vent terminal is a 2” straight
pvc coupling with a mesh wire screen.
B.) WOODEN SIDE WALLS Drill a pilot hole approximately
one quarter inch outside of the marked circle. This
pilot hole is used as a starting point for a saws-all or
sabre saw blade. Cut around the marked circle staying
approximately one quarter inch outside of the line.
(This will allow the vent pipe to easily slide through
the opening. The resulting gap will be covered by the
vent terminal cover plates.) Repeat this step on the
inside wall if necessary.
2. Cut a length of pipe about 3.5” (8.9 cm) longer than the
wall thickness at the opening.
3. Glue the air intake terminal to the section of the pipe.
4. Slide the wall plate over pipe to stop against air intake terminal.
5. Place a bead of caulking (not supplied) around the gap between
the pipe and the wall. Place some of the caulking on the
back of the plate to hold it against the wall after installation.
6. If the air intake pipe is installed up to the wall, with a coupling on the
end against the wall opening, the pipe with the air intake terminal can
be prepared for gluing before inserting through the wall. Slide the
pipe through the wall and insert into coupling on the other side of
the wall, making sure that the air intake terminal ends up pointed in the
correct position (Figure 13A and Figure 14).
Note: to prevent exhausting products from circulating to the air intake
in windy/cold areas, the maximum practical distance between these
two terminals is recommended.
Figure: 13A
INSTALLATION SEQUENCE
1. After the points of termination have been determined,
use the cover plates as templates to mark the holes for
the vent pipes to be inserted through the wall. BEWARE OF
CONCEALED WIRING AND PIPING INSIDE OF WALL. If the
vent terminals are being installed on the outside of a nished
wall, it may be easier to mark both the inside and outside
wall. Align the holesby drilling a hole through the center of the
template from the inside through to the outside. The template
can now be positioned on the outside wall using the drilled holes
as a centering point for the template.
A.) MASONRY SIDE WALLS Chisel an opening approximately
1/2” (1.3 cm) larger than the marked circle.
Figure: 14
27
TERMINATION CLEARANCES SIDEWALL POWER VENT
POWER VENT
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
D
E
v
(using room air for combustion)
G
V
A
H
L
B
v
C
FIX ED
V
CLOSED
OPERABLE
V
F
B
OPERABLE
V
B
B
B
V
FIX ED
CLOSED
X
V
J
A
M
X
V
K
B
VENT TERMINALAIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
VX
Figure: 15
Vent terminal clearances for “Power Vent” installations. Power Vent congurations use room air for combustion.
Clearance above grade,
veranda, porch, deck or
A
balcony
Clearance to window
or door that may be
B
opened
CANADIAN INSTALLATIONS
12 inches (30 cm)
6 inches (15 cm) for appliances up to
10,000 Btu/hr (3 kW), 12 inches (30
cm) for appliances between 10,000
Btu/hr (3 kW) and 100,000 Btu/hr (30
kW), 36 inches (91 cm) for appliances
above 100,000 Btu/hr (30 kW)
1
Clearance to each side
of center line extended
H
above meter/regulator
assembly
Clearance to service
regulator vent outlet
I
CANADIAN INSTALLATIONS
3 feet (91 cm) within a height 15 feet
(4.5 m) above the meter/
regulator assembly
3 feet (91 cm)
1
Clearance to
permanently closed
C
window
Vertical clearance to
ventilated soft located
above the terminal
within a horizontal
D
distance of 2 feet (61
cm) from the center line
of the terminal
Clearance to
E
unventilated soft
Clearance to outside
F
corner
Clearance to inside
G
corner
12 inches (30 cm)*
12 inches (30 cm)*
12 inches (30 cm)*
2 feet (60 cm)*
18 inches (45 cm)*
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
† A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.
Clearance to a non
mechanical air supply
inlet into building or
J
combustion air inlet to
any other appliance
Clearance to a
mechanical air supply
K
inlet
Clearance above paved
sidewalk or paved
L
driveway located on
public property
Clearance under
veranda, porch, deck, or
M
balcony
28
6 inches (15 cm) for appliances up
to 10,000 Btu/hr (3 kW), 12 inches
(30 cm) for appliances between
10,000 Btu/hr (3 kW) and 100,000
Btu/hr (30kW), 36 inches (91cm)
for appliances above 100,000 Btu/
hr (30 kW)
6 feet (1.83 m)
7 feet (2.13 m)†
12 inches (30 cm) ‡
TERMINATION CLEARANCES SIDEWALL DIRECT VENT
(using outdoor air for combustion)
G
V
A
C
FIX ED
V
CLOSED
OPERABLE
V
F
B
V
B
B
B
OPERABLE
V
A
B
FIX ED
CLOSED
J
H
V
M
X
X
V
K
D
E
v
L
B
v
VENT TERMINALAIR SUPPLY INLETAREA WHERE TERMINAL IS NOT PERMITTED
VX
EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION
Figure: 16
Vent terminal clearances for “Direct Vent” installations. Direct Vent congurations use outdoor air for combustion.
DIRECT VENT
CANADIAN INSTALLATIONS
1
CANADIAN INSTALLATIONS
1
Clearance above grade,
veranda, porch, deck or
A
balcony
Clearance to window or
B
door that may be opened
Clearance to
permanently closed
C
window
Vertical clearance to
ventilated soft located
above the terminal within
D
a horizontal distance of
2 feet (61 cm) from the
center line of the terminal
Clearance to unventilated
E
soft
Clearance to outside
F
corner
Clearance to inside
G
corner
12 inches (30 cm)
6 inches (15 cm) for appliances
up to 10,000 Btu/hr (3 kW), 12
inches (30 cm) for appliances
between 10,000 Btu/hr (3 kW)
and 100,000 Btu/hr (30 kW), 36
inches (91 cm) for appliances
above 100,000 Btu/hr (30 kW)
6 inches (15 cm)*
12 inches (30 cm)*
12 inches (30 cm)*
2 feet (60 cm)*
18 inches (45 cm)*
Clearance to each side
of center line extended
H
above meter/regulator
assembly
Clearance to service
I
regulator vent outlet
Clearance to a non
mechanical air supply
inlet into building or
J
combustion air inlet to
any other appliance
Clearance to a
mechanical air supply
K
inlet
Clearance above
paved sidewalk or
L
paved driveway located
on public property
Clearance under
veranda, porch, deck,
M
or balcony
3 feet (91 cm) within a height 15
feet (4.5 m) above the meter/
regulator assembly
3 feet (91 cm)
6 inches (15 cm) for appliances up
to 10,000 Btu/hr (3 kW), 12 inches
(30 cm) for appliances between
10,000 Btu/hr (3 kW) and 100,000
Btu/hr (30 kW), 36 inches (91 cm)
for appliances above 100,000 Btu/
hr (30 kW)
6 feet (1.83 m)
7 feet (2.13 m)†
12 inches (30 cm) ‡
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
† A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.
29
VERTICAL VENT TERMINAL INSTALLATION
WHEN TERMINATING THROUGH A ROOF, THE FOLLOWING
SPECIFICATIONS PERTAINING TO TERMINAL LOCATION
MUST BE FOLLOWED.
1. Proper support must be provided for all pipe protruding through
the roof.
2. The vertical roof terminations should be sealed with a plumbing
roof boot or equivalent ashing.
3. The air intake termination and the exhaust vent termination
must penetrate the same side of roof.
4. The center line of the air intake termination and the center line
of the exhaust vent termination must be no closer than 24”
(61cm). See Figure 17 and Figure 18.
FLAT ROOF INSTALLATION
On at roof installations the air intake and the exhaust vent
terminations must be a minimum of 24 inches (60 cm) above any
parapet, vertical wall or structure within 10 feet (3 m) horizontally.
See Figure 19.
Figure: 19
Figure: 17
Figure: 18
30
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.