Enviro HPF 06, HPF 08, HPF 10, HPF 12, HPF 14 Installation, Operation & Maintenance Instructions Manual

...
HP SERIES FAN COILS
INSTALLATION, OPERATION & MAINTENANCE
(HPP Plenum Return Shown)
Supersedes ET115.24-NOM1 (615)
HP SERIES
Form ET115.24-NOM1 (519)
INTRODUCTION
E
NVIRO-TEC fan coils represent a prudent investment which can, with proper installation, operation, and regular maintenance, give trouble­free operation and long service.
Your equipment is initially protected under the manufacturer’s standard warranty; however, this warranty is provided under the condition that the steps outlined in this manual for initial inspection, proper installation, regular periodic maintenance, and everyday operation of the equipment be followed in detail.
This manual s of any actual work being done on the equipment. Should any questions arise, please contact your local Sales Representative or the factory BEFORE proceeding.
The equipment covered by this manual is available with a vast variety of options and accessories. Consult the approved unit submittal, order acknowledgement, and other manuals for details on the options and accessories provided with the equipment on each project.
hould be fully reviewed in advance
FORM ET115.24-NOM1 (519)
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or se­rious injury.
SAFETY PRECAUTIONS
The equipment covered by this manual is designed for safe and reliable operation when installed and operated
within its design specication limits. To avoid personal
injury or damage to equipment or property while installing or operating this equipment, it is essential
that qualied, experienced personnel perform these
functions using good judgment and safe practices. See the following cautionary statements.
ELECTRICAL SHOCK HAZARDS. All power must be disconnected prior to installation and serving this equip­ment. More than one source of power may be present. Disconnect all power sources to avoid electrocution or shock injuries.
MOVING PARTS HAZARDS. Mo­tor and Blower must be disconnected prior to opening access panels. Motors can start automatically, disconnect all power and control circuits prior to servicing to avoid serious crushing or dismemberment injuries.
CAUTION identies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution. Usually an instruction will be given, together with a brief explanation.
NOTE is used to highlight additional information which may be helpful to you.
Check that the unit assembly and com­ponent weights can be safely supported by rigging and lifting equipment.
All assemblies must be adequately secured during lifting and rigging by temporary supports and restraints un­til equipment is permanently fastened and set in its nal location.
All unit temporary and permanent supports must be capable of safely supporting the equipment’s weight and any additional live or dead loads that may be encountered. All supports must be designed to meet applicable local codes and ordinances.
All fastening devices must be designed to mechanically lock the assembly in place without the capability of loosen­ing or breaking away due to system operation and vibration.
HOT PARTS HAZARD. Electric Re­sistance heating elements must be dis­connected prior to servicing. Electric Heaters may start automatically, dis­connect all power and control circuits prior to servicing to avoid burns.
2
Protect adjacent ammable materials when brazing. Use ame and heat pro­tection barriers where needed. Have re extinguisher available and ready for immediate use.
ENVIRO-TEC
FORM ET115.24-NOM1 (519)
TABLE OF CONTENTS
INTRODUCTION .................................................................................................................................................1
SAFETy SyMbOLS & PRECAUTIONS ..............................................................................................................2
CODE COMPLIANCE ..........................................................................................................................................4
RECEIPT AND INITIAL INSTALLATION .............................................................................................................4
UNPACKING & INSPECTION .............................................................................................................................4
HANDLING & INSTALLATION ............................................................................................................................5
DRAIN PANS .......................................................................................................................................................5
RETURN AIR LOCATION ....................................................................................................................................6
FAN REMOVAL ....................................................................................................................................................6
PLENUM bOX SERVICE PANEL ........................................................................................................................6
PLENUM bOX REMOVAL ...................................................................................................................................7
COIL HANDING ...................................................................................................................................................7
COILS ...................................................................................................................................................................7
PIPING CONNECTIONS ......................................................................................................................................7
DUCTWORK CONNECTIONS .............................................................................................................................8
ELECTRICAL CONNECTIONS ...........................................................................................................................8
CONTROL ENCLOSURE ....................................................................................................................................8
TELESCOPING bOTTOM PANEL ......................................................................................................................9
START-UP ............................................................................................................................................................9
COOLING/HEATING SySTEM ............................................................................................................................9
MOTOR & FAN DATA ........................................................................................................................................10
AHRI STANDARD RATINGS .............................................................................................................................10
INSPECTION & START-UP CHECKLIST .......................................................................................................... 11
AIR SySTEM bALANCING ...............................................................................................................................12
WATER SySTEM bALANCING ........................................................................................................................12
CONTROLS OPERATION .................................................................................................................................12
PHySICAL DATA ...............................................................................................................................................12
MOTOR/bLOWER ASSEMbLy .........................................................................................................................12
FAN ASSEMbLy ................................................................................................................................................13
COIL ...................................................................................................................................................................13
UNIT WEIGHT DATA .........................................................................................................................................14
ELECTRIC RESISTANCE HEATER ASSEMbLy ..............................................................................................14
ELECTRICAL WIRING & CONTROLS ..............................................................................................................14
ELECTRIC HEAT SELECTION CHART (AMPS) ..............................................................................................15
FACE AREA, FREE AREA AND FILTER SIZES ...............................................................................................16
VALVES & PIPING .............................................................................................................................................16
DRAIN ................................................................................................................................................................16
FILTERS ............................................................................................................................................................16
FILTER REPLACEMENT ...................................................................................................................................16
REPLACEMENT PARTS ...................................................................................................................................17
HP SERIES COIL CONNECTION SIZES ..........................................................................................................18
ECM VARIAbLE SPEED
MOTOR bALANCING INSTRUCTIONS .....................................................................................................19
FAN CALIbRATION WITH ECM MOTOR ...................................................................................................20
TROUbLE SHOOTING GUIDELINES ........................................................................................................21
CHECKING ECM CAbLES .........................................................................................................................22
ECM 3-SPEED (CONSTANT TORQUE)
TROUbLESHOOTING GUIDELINES .........................................................................................................23
CHECKING ECM CAbLES .........................................................................................................................24
TROUbLESHOOTING GUIDE FOR FAN COIL RELAy bOARD .....................................................................26
EXAMPLE WIRING DIAGRAMS .......................................................................................................................29
INSTRUCTIONS FOR REMOTE THERMOSTAT OR REMOTE 3-SPEED SWITCH ........................................32
APPENDIX .........................................................................................................................................................33
ENVIRO-TEC
3
FORM ET115.24-NOM1 (519)
CODE COMPLIANCE
This equipment has been manufactured and certied in
accordance with UL 1995-Standard for Safety, Heating and Cooling Equipment (CAN/CSA C22.2 NO 236­M90) and bears the Electrical Testing Laboratories (ETL) Mark under ETL File No: 3036742-002.
RECEIPT AND INITIAL INSTALLATION
NO ATTEMPT SHOULD BE MADE
TO HANDLE, INSTALL, OR SER-
VICE ANY UNIT WITHOUT FOL-
LOWING SAFE PRACTICES RE-
GARDING MECHANICAL EQUIP-
MENT.
All power must be disconnected before any in-
stallation or service should be attempted. More than one power source may be supplied to a unit. Power to remote mounted control devices may not be supplied through the unit. Never wear
bulky or loose tting clothing when working on
any mechanical equipment. Gloves should only be worn when required for proper protection from heat or other possible injury. Safety glasses or goggles should always be worn when drill­ing, cutting, or working with chemicals such as refrigerants or lubricants.
Never pressurize any equipment beyond specied
operating pressures. Always pressure test with
an inert uid or gas such as clear water or dry
nitrogen to avoid possible damage or injury in the event of a leak or component failure during testing.
Always protect adjacent flammable material
when welding or soldering. Use suitable heat shield material to contain sparks or drops of
solder. Have re extinguisher available for use
when welding or brazing.
The manufacturer assumes no responsibility for personal injury or property damage resulting from improper or unsafe practices during the handling, installation, service, or operation of any equipment.
UNPACKING & INSPECTION
All units are carefully inspected at the factory throughout the manufacturing process under a strict detailed quality assurance program, and where possible, all major components and subassemblies are carefully tested for
proper operation and veried to be in full compliance
with the factory manufacturing documents. Customer furnished components such as control valves, switches and DDC controls are not factory tested.
Each unit is carefully packaged for shipment to avoid damage during normal transport and handling. The equipment should always be stored in a dry place in the proper orientation as marked on the carton.
All shipments are made F.O.B. factory and it is the responsibility of the receiving party to inspect the equipment upon arrival. Any obvious damage to the carton and/or its contents should be recorded on the bill
of lading and a claim should be led with the freight
carrier.
After determining the condition of the carton exterior,
carefully remove each unit from the carton and inspect for hidden damage. At this time check to make sure that “furnished only” items such as switches, thermostats, etc. are accounted for. Any hidden damage should be recorded and immediately reported to the carrier and a
claim led as before. In the event a claim for shipping damage is led, the unit, shipping carton, and all packing
must be retained for physical inspection by the freight carrier. All equipment should be stored in the factory­shipping carton with internal packing in place until installation.
At the time of receipt, the equipment type and arrangement should be verified against the order documents. Should any discrepancy be found, the local
Sales Representative should be notied immediately
so that the proper action may be instituted. Should any question arise concerning warranty repairs, the factory must be notified BEFORE any corrective action is taken. Where local repairs or alterations can be accomplished, the factory must be fully informed as
to the extent and expected cost of those repairs before
work is begun. Where factory operations are required, the factory must be contacted for authorization to return equipment and a Return Authorization Number will be issued. Unauthorized return shipments of equipment and shipments not marked with an authorization number will be refused. In addition, the manufacturer will not
accept any claims for unauthorized expenses.
4
ENVIRO-TEC
FORM ET115.24-NOM1 (519)
HANDLING & INSTALLATION
While all equipment is designed for durability and fabricated for sturdy construction and may present a rugged appearance, great care must be taken to assure that no force or pressure be applied to the coil, piping or drain stub-outs during handling. Also, depending on the options and accessories, some units could contain delicate components that may be damaged by improper handling. Wherever possible, all units should be maintained in an upright position and handled by the chassis as close as possible to the mounting point locations.
In the case of a full cabinet unit, the unit must obviously
be handled by the exterior casing. This is acceptable
providing the unit is again maintained in an upright position and no impact forces are applied that may damage internal components, access panels, or painted surfaces. The equipment covered in this manual IS NOT suitable for outdoor installations or hazardous/
explosive environments. The equipment should never be
stored or installed where it may be subjected to a hostile
environment such as rain, snow, extreme temperatures
or corrosive or chemical laden atmospheres.
During and after installation, special care must be taken to prevent foreign material such as paint, plaster, and drywall dust from being deposited in the drain pan or on the motor or blower wheels. Failure to do so may have serious adverse effects on unit operation and in the case of the motor and blower assembly, may result in immediate or premature failure. All manufacturers’ warranties are void if foreign material is allowed to be deposited on the motor or blower wheels of any unit. Some units and/or job conditions may require some form of temporary covering during construction.
FOR SEISMIC CERTIFIED INSTALLATION, REFERENCE ENVIRO-TEC SEISMIC INSTALLATION DOCUMENT.
DRAIN PAN
The optional sloped, insulated drain pan can be equipped with a secondary drain connection. Standard drain pans
are externally insulated, single wall galvanized steel.
The drain pan is easily removable for cleaning. The pan can be turned around 180 degrees for drainage on the opposite side of the valve package(s) while capturing condensate from both the coil and the valve package(s).
The optional auxiliary drip pan to catch condensed
moisture from valves and piping is easily attachable to
the drain pan. The drain pan is equipped with external
slots and is to be sloped toward the outlet connection prior to start-up. Care must be taken to insure that the unit drain pan does not slope away from the outlet connection.
AUXILIARY DRAIN PANS
While the manufacturer does not become involved in the design and selection of support methods and components, it should be noted that unacceptable system operating characteristics and/or performance might result from improper or inadequate unit structural support. In addition, adequate clearance must be provided for service and removal of the equipment and its accessory components. Anchoring the equipment in place is accomplished by using the mounting points provided and positioning the unit to maintain the unit on a LEVEL plane. All units are supplied with hanging holes for use with all thread rods.
ENVIRO-TEC
The auxiliary drain pan mounts directly to the unit drain pan using (2) #10 x 1/2” screws.
After the connections are completed, the system should then be tested for leaks. Since some components are not designed to hold pressure with a gas, hydronic systems should be tested with water.
5
FORM ET115.24-NOM1 (519)
All water coils must be protected from
“H” MUST BE AT LEAST
freezing after initial lling with water.
Even if the system is drained, unit coils
may still hold enough water to cause
damage when exposed to temperatures
below freezing.
Refrigerant systems should be tested with dry nitrogen rather than air to prevent the introduction of moisture into the system. In the event that leaking or defective components are discovered, the Sales Representative
must be notied BEFORE any repairs are attempted.
All leaks should be repaired before proceeding with the installation.
After system integrity has been established the piping should be insulated in accordance with the project
specications. ALL chilled water piping and valves or
refrigerant suction piping not located over drain pans must be insulated to prevent damage from sweating.
This includes factory and eld piping inside the unit
cabinet.
RETURN AIR LOCATION
This unit is equipped with a eld reversible rear or
bottom ducted air return for plenum style units. To change the return air location, remove the reversible
plenum box panel and the lter rack. Rotate both the reversible panel and lter rack 180 degrees. Replace the reversible panel in the old lter rack position and fasten using the supplied screws. Fasten the lter rack to
the location where the reversible panel was and replace
the lter(s) as described above.
Bottom Return
The drain should always be connected and piped to an acceptable disposal point. For proper moisture carry­off, the drain piping should be sloped away from the unit at least 1/8” per foot. A drain trap may be required by local codes and it is strongly recommended for odor containment.
Condensate Trap
1 INCH PLUS CASING STATIC PRESSURE
X
H
“X” MUST BE AT LEAST 1 INCH
Trap detail for positive cabinet
static pressure
Rear Return
FAN REMOVAL
This fan assembly is easily removable by unscrewing the (4) ¼-20 nuts from the fan deck and sliding the fan assembly off of the weld studs. Disconnect motor wiring. Reassemble fans and torque nuts to 30 in/lbs.
PLENUM BOX SERVICE PANEL
The service panel on the plenum box is easily removable
by removing the screws located on the sides and bottom of the service panel.
6
ENVIRO-TEC
FORM ET115.24-NOM1 (519)
PLENUM BOX REMOVAL
In most cases this unit is fully serviceable without the
need for removal of the plenum box. However should the need arise, the plenum box is easily removable by removing the screws attaching the plenum box to the
sides, top and rear of the coil casing.
COIL HANDING
This unit features a eld reversible coil assembly should
the need arise upon installation to change the handing of the coil. To change the coil handing, remove the plenum
box (if applicable) from the coil by removing all screws to the coil casing. Next, remove the fan(s), fan deck,
and top and bottom casings from the coil. Rotate the coil. Replace the bottom coil casing in the top coil casing position and the top coil casing in the bottom coil casing position and reattach the fan deck, fan(s) and plenum
box (if applicable) in the original locations.
The leaving air side of the n pack will remain the same after changing the coil handing.
COILS
All fan coils are available in 2 or 4 pipe congurations. Heating and cooling coils are eld reversible for right
or left side connections. On units with water coils, the
maximum water pressure applied to the unit should never exceed 300 PSIG at 200°F. On units with steam heating coils, the maximum steam pressure applied to the unit should never exceed 15 PSIG. The drain
piping and steam trap should be sized and routed to
allow for proper condensate ow. (Minimum ambient temperature 35°F. Coils may freeze.)
PIPING CONNECTIONS
Toxic residues and loose particles resulting from manufacturing and eld piping techniques such as joint compounds, soldering ux, and metal shavings may be present in the unit and the piping system. Special con­sideration must be given to system cleanliness when connecting to solar, domestic or potable water systems.
Submittals and Product Catalogs detailing unit operation, controls, and connections should be thoroughly reviewed BEFORE beginning the connection of the various cooling and/or heating mediums to the unit.
All accessory valve packages should be installed as required, and all valves should be checked for proper operation.
If coil and valve package connections are to be made with “sweat” or solder joint, care should be taken to assure that no components in the valve package are subjected to a high temperature which may damage seals or other materials. Many two-position electric control valves, depending on valve operation, are provided with a manual-opening lever. This lever should be placed in the “open” position during all soldering or brazing operations. Valve bodies should be wrapped with a wet rag to help dissipate heat encountered during brazing. Use a brazing alloy to make connections such as BCup-
2. Soft solder is not recommended.
If the valve package connection at the coil is made with a union, the coil side of the union must be prevented from twisting (“backed up”) during tightening to prevent damage to the coil tubing. Over-tightening must be avoided to prevent distorting the union seal surface
and destroying the union. In the case of eld installed
valves and piping, the chilled water valve cluster (or
expansion valve on DX units) should be installed in
such a way that any dripping or sweating is contained
in the auxiliary drain pan or other device. Valves and TXV’s should be secured or supported to avoid damage
to coil headers or distributor tubes.
ENVIRO-TEC
7
FORM ET115.24-NOM1 (519)
DUCTWORK CONNECTIONS
All ductwork and/or supply and return grilles should be installed in accordance with the project plans and
specications. If not included on the unit or furnished
from the factory, ENVIRO-TEC supply and return grilles are available in a variety of types.
All units must be installed in non-combustible areas. Some models are designed to be connected to ductwork
with a MINIMUM amount of external static pressure.
Consult the approved submittals and the product catalog
for unit external static pressure limitations.
Units provided with outside air for ventilation should have some form of low temperature protection to prevent coil freeze-up. Outside air should be pretreated for best results.
It should be noted that none of these methods would adequately protect a coil in the event of power failure. The safest method of freeze protection is to use glycol
in the proper percent solution for the coldest expected
air temperature. Consult glycol supplier literature for correct solution ratios.
The manufacturer assumes no responsibility for undesirable system operation due to improper design, equipment or component selection, and/or
installation of ductwork, grilles, and other eld supplied
components.
voltage, fan and heater amperage and required circuit ampacities. The unit-wiring diagram shows all unit and
eld wiring. Since each project is different and each
unit on a project may be different, the installer must be familiar with the wiring diagram and nameplate on the unit BEFORE beginning any wiring. This unit is
not acceptable for installation in hazardous/explosive
areas.
CONTROL ENCLOSURE
The optional electrical control enclosure provides access to the electrical compartment. This compartment houses all electric heat and control components. Terminal strips are furnished for simple power and control wiring connections. Multiple knockouts allow wiring entries from either side of the compartment.
All components furnished for eld installation, by either
the factory or the controls contractor should be located and checked for proper function and compatibility. All internal components should be checked for shipping damage and all electrical connections should be tightened to minimize problems during start-up.
Any devices such as fan switches or thermostats
that have been furnished from the factory for eld
installation must be wired in strict accordance with the applicable wiring diagrams. Failure to do so could result in personal injury or damage to components and will void all manufacturers’ warranties.
ELECTRICAL CONNECTIONS
ELECTRICAL SHOCK HAZARDS.
All power must be disconnected prior
to installation and serving this equip-
ment. More than one source of power
may be present. Disconnect all power
sources to avoid electrocution or shock
injuries.
The electrical service to the unit should be compared to the unit nameplate to verify compatibility. The routing and sizing of all conduit, and the type and sizing of all wiring and other electrical components such as circuit breakers, disconnect switches, etc. should be determined by the individual job requirements and should not be based on the size and/or type of connection provided on the equipment. All installations should be made in compliance with all governing codes and ordinances. Compliance with all codes is the responsibility of the installing contractor. The unit nameplate lists the unit electrical characteristics such as the required supply
The fan motor(s) should never be controlled by any wiring or device other than the factory furnished switch or thermostat/switch combination, without factory authorization.
All eld wiring should be done in accordance with governing codes and ordinances. Any modication of
the unit wiring without factory authorization will result in voiding of all factory warranties and will nullify any agency listings.
The manufacturer assumes no responsibility for any
damages and/or injuries resulting from improperly eld
installed or wired components.
8
ENVIRO-TEC
FORM ET115.24-NOM1 (519)
TELESCOPING BOTTOM PANEL
The telescoping bottom panel allows for fully recessing the unit while permitting service access into the ceiling
plenum. The architectural ceiling panel is nished with
a durable powder coat paint.
Portions of the inlet louver not directly below unit inlet may require cover­ing in the eld on applications where inltration of ceiling plenum air into space is undesired. Telescoping skirt and collar assembly must be eld ad­justed to assure a proper t between lter frame and louvered inlet panel assembly. Refer to assembly submittal drawings for specic dimensions.
The initial step in any startup operation should be a nal
visual inspection. All equipment, plenums, duct-work, and piping should be inspected to verify that all systems are complete and properly installed and mounted, and that no debris or foreign articles such as paper or drink cans are left in the units or other areas. Each unit should be checked for loose wires, free blower wheel operation,
and loose or missing access panels or doors. Except as
required during start-up and balancing operations, no fan coil units should be operated without all the proper ductwork attached, supply and return grilles in place, and all access doors and panels in place and secure.
A clean lter of the proper size and type must also be
installed. Failure to do so could result in damage to the equipment or building and furnishings, and/or void all manufacturers’ warranties.
Fan coils are not intended for temporary heat/cool or ventilation. Units are not designed or equipped to operate in dusty construction environments. Operation of the units in conditions outlined above could result in damage to the equipment or building and furnishings and/or void all manufacturer’s warranties.
START-UP
Before beginning any start-up operation, the start­up personnel should familiarize themselves with the unit, options and accessories, and control sequence to understand the proper system operation. All personnel should have a good working knowledge of general start-up procedures and have the appropriate start-up and balancing guides available for consultation.
COOLING/HEATING SYSTEM
Prior to the water system start-up and balancing, the
chilled/hot water systems should be ushed to clean
out dirt and debris, which may have collected in the piping during construction. During this procedure, all unit service valves must be in the closed position. This prevents foreign matter from entering the unit and clogging the valves and metering devices. Strainers should be installed in the piping mains to prevent this material from entering the units during normal operation.
During system filling, air venting from the unit is accomplished by the use of the standard manual or
optional automatic, air vent tting installed on the coil. In the case of the manual air vent tting, the screw
should be turned counterclockwise no more than 1-½ turns to operate the air vent. Automatic air vents may be unscrewed one turn counterclockwise to speed initial venting but should be screwed in for automatic venting after start-up operations.Check to ensure that no leaks are prevalent at the coils, coil connections, piping packages, etc.
ENVIRO-TEC
9
FORM ET115.24-NOM1 (519)
The air vent provided on the unit is not intended to replace the main system air vents and may
POWER
QT QS WPD INPUT
FNF / FNP 06
•410 700 17800 14000 3.71.6 290
FNF / FNP 08
•410 900 23500 18500 4.91.9 410
FNF / FNP 10
•410 110029400 22900 6.02.2 470
FNF / FNP 12
•410 140043000 31800 8.74.2 560
FNF / FNP 14
410 175047 100 36250 9.63.0 715
FNF / FNP 16
410 200051 000 41000 10.52.0 830
FNF / FNP 18
410 220053 000 42000 11.02.2 850
FNF / FNP 20
410 230056 000 44000 11.42.5 870
WATER
Flow Rate
GPM
COOLING CAPACITY
AIRFLOW
COIL
PSC ECM
FLA
3-Phase N eutral
Current
FLA
3-Phase N eutral
Current
FLA
3-Phase N eutral
Current
FLA
3-Phase N eutral
Current
FLA
3-Phase N eutral
Current
FLA
3-Phase N eutral
Current
High (1) 1/6 2.6 1.1 0.9
Medium (1) 1/ 8 2.1 0.9 0.8
Low (1) 1/10 1.8 0.6 0.7
High (1) 1/4 3.8 1.6 1.3
Medium (1) 1/ 6 3.3 1.0 0.8
Low (1) 1/ 8 2.6 0.8 0.7
High (1) 1/4 4.9 2.2 1.9
Meduim (1) 1/ 5 4.1 1.5 1.2
Low (1) 1/ 6 3.2 1.1 0.8
High (2) 1/6 5.2 2.2 1.8
Medium (2) 1/ 8 4.2 1.8 1.6
Low (2) 1/10 3.6 1.2 1.4
High (2) 1/4 7.6 3.2 2.6
Medium (2) 1/ 6 6.6 2.0 1.6
Low (2) 1/ 8 5.2 1.6 1.4
High (2) 1/4 9.8 4.4 3.8
Medium (2) 1/ 5 8.2 3.0 2.4
Low (2) 1/ 6 6.4 2.2 1.6
High (2) 1/4 9.8 4.4 3.8
Medium (2) 1/ 5 8.2 3.0 2.4
Low (2) 1/ 6 6.4 2.2 1.6
High (2) 1/4 9.8 4.4 3.8
Medium (2) 1/ 5 8.2 3.0
2.4
Low (2) 1/ 6 6.4 2.2 1.6
UNIT
SIZE
FAN
SPEED
MOTOR HP
(Quantit y)
# OF
FANS
AMPs @ 120/ 1/60
AMPs @ 208- 230/1/ 60
AMPs @ 277/ 1/60
PSC
ECM
ECM 3- Speed
PSC
ECM
ECM 3- Speed
PSC
ECM
ECM 3- Speed
4.5
2.6
4.5
08
(1) 1/ 315.0
8.7
4.8
8.3
8.3
2.8
4.8
2.8
4.8
2.606(1) 1/ 315.0
8.7
4.8
2.6
4.5
10
(1) 1/ 315.0
8.7
4.8
8.3
2.8
2.8
4.8
2.8
4.8
2.6
4.5
5.6
9.7
5.2
9.0
5.2
9.0
4.5
12
(2) 1/ 3210.0
17.3
9.6
16.6
5.6
9.7
4.8
2.8
4.8
2.6
4.5
2.6
9.0
5.2
9.0
16
(2) 1/ 3210.0
17.3
9.6
16.6
16.6
5.6
9.7
5.6
9.7
5.214(2) 1/ 3210.0
17.3
9.6
5.2
9.0
18
(2) 1/ 3210.0
17.3
9.6
16.6
5.6
5.6
9.7
5.6
9.7
5.2
9.0
5.6
9.7
5.2
9.0
5.2
9.0
9.0
20
(2) 1/ 3210.0
17.3
9.6
16.6
5.6
9.7
9.7
5.6
9.7
5.2
9.0
5.2
not release air trapped in other parts of the system. Inspect the entire system for potential air
traps and vent those areas as required, independently. In addition, some systems may require
repeated venting over a period of time to properly eliminate air from the system
Motor & Fan Data
NOTES:
1. Motor electrical data is nameplate data. Actual data will vary with application.
2. Motors nameplated for 208-230/1/60. Data is at 230 volts.
3. ECM motors operated on 208/1/60 power result in reduced airow.
AHRI Standard Ratings
MODEL /
SIZE
HPF/HPP
HPF/HPP HPF/HPP HPF/HPP HPF/HPP HPF/HPP HPF/HPP
HPF/HPP
NOTES:
1. Based on 80°F DB and 67°F WB EAT, 45°F EWT, 10°F temperature rise, high fan speed. Motor type is PSC and motor voltage is
115/1/60. Airow under dry coil conditions. All models tested at 0.05” external static pressure.
2. Airow rate CFM on sizes 14 through 20 exceed maximum ratings in AHRI 440 and are therefore not certied.
AHRI 440
CERTIFIED
Rows FPI
CFM
(Dry Flow)
(BTUH) (BTUH) ft-wg (WA TTS )
10
ENVIRO-TEC
Loading...
+ 23 hidden pages