Enviro G39GI Owner's Manual

Page 1
WARRANTY REGISTRATION
enviro.com/warranty
G39GI
DIRECT VENT FIREPLACE - IPI
OWNER’S MANUAL
WARNING: If the information in this manual is not followed exactly, a
re or explosion may result causing property damage, personal injury
or loss of life. Installation and service must be performed by a qualied
Version Française: www.enviro.com/fr.html
installer, service agency or the gas supplier.
CERTIFIE D TO/CERTI FIÉ AUX : ANSI Z21.88-2017
: CSA 2.33-2 017
: C SA 2.17- 2017
50-3625
1
Page 2
Safety Precautions
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other ammable vapours and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a qualied
installer, service agency or the gas supplier.
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
This appliance may be installed in an after-market permanently located,
manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certied kit is used.
Only doors certied with the appliance shall be used
Massachusetts installations (Warning): This product must be installed by a licensed plumber or
gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code
requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed; only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon
monoxide detector is required in all rooms containing gas red direct vent appliances. The replace damper must be removed or welded in the open position prior to installation of a replace insert.
2
Page 3
Safety Precautions
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.

A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall
individuals.
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER, PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas-red appliances must be installed in accordance with their instructions. Carefully read all the instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for a permit prior to commencing the installation.
NOTE: Failure to follow these instructions could cause a malfunction of the replace, which could result in death,
serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a qualied
service person. The appliance should be inspected before
the rst use and, at least, annually by a qualied service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative the control compartments, burners and circulating air passageways of the appliance be kept clean.
• Due to high temperatures, the appliance should be located out of high trafc areas and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when in
the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is required if there is a risk for
individuals in the house. To restrict access to a replace
or stove install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces. Any safety screen, guard, or barrier removed for servicing an appliance must be replaced prior to operating the appliance.
• Clothing or other ammable materials should not be
placed on or near the appliance.
• A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and shall be installed for the protection of children and other at-risk
individuals. If the barrier becomes damaged, the barrier
shall be replaced with the manufacturer’s barrier for this appliance.
FOR YOUR SAFETY
• Installation and service must be performed by a qualied
installer, service agency or gas supplier.
• This installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
• To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
• To prevent injury, if the pilot or pilot and burners have gone out on their own, open the glass door and wait 5 minutes to air out before attempting to re­light the stove.
• Always keep the area around these appliances clear of combustible material, gasoline and other ammable liquids
and vapours.
• These appliances should not be used as a drying rack for clothing or for hanging Christmas stockings/decorations.
• Due to the paint curing on the stove, a faint odor and slight smoking will likely be noticed when the stove is rst used.
Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another room or inside the building. Make sure the specied vent
pipe is used, properly sized and of adequate height to
provide sufcient draft. Inspect the venting system annually
for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance with the diagrams in this booklet, or failure to use only
parts specically approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or qualied service person.
• Never use solid fuels such as wood, paper, cardboard, coal, or any ammable liquids, etc., in this appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system or any gas control which has been under water.
• Do not abuse the glass by striking it or slamming the door
shut.
• If the G39 unit is pulled out of its installation, and the vent-
air intake system is disconnected for any reason, ensure that the vent-air intake pipes are reconnected and re-sealed in accordance to the instructions noted in
- DIrect Vent
InItIal InstallatIon
3
Page 4
Table of Contents
Safety Precautions .............................................................................................................................. 2
Codes And Approvals ........................................................................................................................... 5
Specications ...................................................................................................................................... 6
Dimensions: .................................................................................................................................................6
Rating Label & Lighting Instructions Location: ................................................................................................6
Operating Instructions. ....................................................................................................................... 7
Lighting and Instructions:..............................................................................................................................7
Remote Control Operations:...........................................................................................................................8
System Description:.......................................................................................................................................8
Technical Data:.............................................................................................................................................8
Remote Transmitter:......................................................................................................................................8
Integrated Fireplace Controller (IFC):.............................................................................................................9
Operating Procedure:...................................................................................................................................10
Pilot Light: ................................................................................................................................................. 13
Air Shutter (Venturi): .................................................................................................................................. 13
Normal Sounds During Operation:................................................................................................................13
Maintenance And Service .................................................................................................................. 14
Routine Maintenance: ................................................................................................................................. 14
Cleaning The Glass: .................................................................................................................................... 14
Cleaning The Firebox: ................................................................................................................................. 14
Replacing The Glass: ..................................................................................................................................14
Cleaning Decorative Surfaces: .....................................................................................................................15
Surround Panel Removal: ........................................................................................................................... 15
Door Cover Removal: .................................................................................................................................. 16
Glass Door Removal: .................................................................................................................................16
Media Tray Removal: .................................................................................................................................. 17
Burner Removal:.........................................................................................................................................17
Fuel Conversion: ........................................................................................................................................18
Initial Installation ............................................................................................................................. 20
Introduction: ..............................................................................................................................................20
Unit Install Preparation: .............................................................................................................................. 20
Placement and Framing: ............................................................................................................................. 22
Finishing a Fireplace: .................................................................................................................................. 23
Cool Surface Activation:...............................................................................................................................24
Cool Surface Install Options:....................................................................................................................... 26
Flat Wall Installation: .................................................................................................................................. 29
Recess Installation: ....................................................................................................................................30
Corner Installation: .................................................................................................................................... 31
Floor Protection: ........................................................................................................................................ 32
Mantel Requirements: .................................................................................................................................32
Minimum Venting Requirements: ................................................................................................................. 33
Flex Venting: ..............................................................................................................................................34
Clearances & Non-Combustible : .................................................................................................................35
TV Installation Considerations: .................................................................................................................... 36
Direct Vent: ...............................................................................................................................................37
Vent Termination Restrictions: ..................................................................................................................... 37
General Venting Clearances: ........................................................................................................................ 38
Approved Venting Parts: ............................................................................................................................. 39
Allowable Co-Axial Vent Congurations: ....................................................................................................... 40
Exhaust Restrictor Setting: .......................................................................................................................... 42
Horizontal Termination: ............................................................................................................................... 43
Vertical Termination: ................................................................................................................................... 44
Gas Line Connection and Testing: ................................................................................................................ 46
Electrical Requirements: .............................................................................................................................47
Glass Media Installation: ............................................................................................................................. 48
Trouble Shooting ............................................................................................................................... 49
Parts List ........................................................................................................................................... 50
Options List ....................................................................................................................................... 50
Parts Diagram .................................................................................................................................... 51
Warranty.............................................................................................................................................53
4
Page 5
Codes And Approvals
DIRECT VENT ONLY: This type is identied by the sufx DV. This appliance draws all of its air for
combustion from outside the dwelling, through a specially designed vent pipe system.
This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above
sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
This appliance has been tested by INTERTEK and found to comply with the established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (G39; NATURAL GAS, PROPANE GAS)
TESTED TO: ANSI Z21.88-2017/CSA 2.33-2017 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-2017 GAS FIRED APPLIANCES FOR HIGH ALTITUDES
This ENVIRO G39 Fireplace:
• Has been certied for use with either natural gas or propane (see rating label).
• Is not for use with solid fuels.
• Is approved for a bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall
thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current installation code CAN/CGA B149.1 in Canada or ANSI Z223.1/NFPA 54 in the USA.
• Must be properly connected to an approved venting system and not connected to a chimney ue serving a separate solid-fuel burning appliance.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned
on for the rst time, it should be turned onto high without the fan on (if equipped) for the rst 4 hours. This will cure the paint, glass, gasket material and other products used in the manufacturing process. It is advisable to
open a window or door, as the unit will start to smoke and can irritate
some people. After the unit has gone through the rst burn, turn the unit
off including the pilot, let the unit get cold then remove the glass door
and clean it with a good gas replace glass cleaner, available at your local ENVIRO dealer.
5
Page 6
G39 Dimensions:
3
39
4
1008
42
1066
Specifications
3
27
4
703
1
3
18
18
4
478
1
34
2
877
4
464
41
1041
3
29
4
1
34
4
870
24
610
757
1
35
4
895
6
152
1
18
4
465
1
30
4
768
37
940
ELECTRICAL
3
38
1
2
1
6
2
163
4
58
4
984
1
39
4
997
2
GAS
1 4
58
1
5
4
134
Figure 1. G39 Dimensions
RatinG LabeL & LiGhtinG instRuctions Location:
Remove the surround completely to access the rating label and lighting instructions. The sheet is attached to a length of chain and are never to be tampered with or removed. All important information for your
replace is on this label as well as the model specic serial number which you will need for warranty
information. The sheet is located inside the cabinet under the gas valve.
6
Page 7
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.
LiGhtinG anD instRuctions:
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This appliance is equipped with an ignition device which automatically lights the pilot. Do not try to light the pilot by hand. B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department.
OPERATING INSTRUCTIONS
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
1. STOP! Read the safety information above on this label.
2. Read the owner's manual including the section on "Remote Control" operation.
3. Set the thermostat to the lowest setting.
4. Turn off all electric power to the appliance.
5. Do not attempt to light the pilot by hand.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.
7. Turn on all electric power to the appliance.
8. Using the remote control, set thermostat to desired setting, or press the ON/OFF key on the remote. "ON" will be indicated on the display of the remote and an audible "beep" will be heard at the unit to indicate the command has been received.
9. This appliance is equipped with a completely automatic ignition and lighting control. The control will attempt to light the pilot several times if necessary. If it is unsuccessful, it will discontinue operations. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
Blue LCD Display
ON/OFF Key
THERMOSTAT Key
UP/DOWN Arrow Key
MODE Key
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting, or press the ON/OFF Key. "OFF" will be indicated on the display and an audible "Beep" will be heard at the unit to indicate the command has been received.
2. Turn off all electric power to the appliance if service is to be performed.
C-12455
Figure 2. Lighting Instruction Label
7
Page 8
Operating Instructions
Blue Back lit LCD display
UP/DOW N Arrow Key
ON/OFF Key
THERMOSTAT Key
MODE Key
Remote contRoL opeRations:
Proame 2 is a modular remote control system that directs the functions of the replace. The Proame 2 remote transmitter is congured to control the on and off function of the main burner. The systems also allows your to modulate the ame level and fan speed
system DescRiption:
The Proame 2 Remote Control System consists of two (2) elements:
1. Proame 2 Transmitter.
2. Integrated Fireplace Controller (IFC) and a wiring harness to connect to the gas valve and stepper
motor.
ATTENTION!
- TURN “OFF” THE MAIN GAS SUPPLY OF THE APPLIANCE DURING INSTALLATION OR MAINTENANCE OF THE IFC.
- TURN “OFF” MAIN GAS SUPPLY TO THE APPLIANCE PRIOR TO REMOVING OR REINSERTING
THE BATTERIES IN THE BATTERY HOLDER
technicaL Data:
Transmitter (Remote Control):
Supply voltage: 4.5 V (three 1.5 V AAA batteries) Radio frequency: 315 MHz
Integrated Fireplace Controller (IFC):
Supply voltage: AC IN - 120 V / 60 Hz Battery Backup IN - 6 Vdc - 200mA (four 1.5 V AA batteries) Spark voltage / frequency: >10kV / 1Hz Comfort modulating fan: 120 V / 60 Hz / 2A Ember lights: 120 V / 60 Hz / 850mA [total] Top light: 120 V / 60Hz / 200mA
Remote tRansmitteR:
The Proame 2 uses a streamline design remote transmitter to allow the user to interact with the system. The simple button layout and LCD display offer a user friendly experience. The MODE key is used to cycle through different features and the THERMOSTAT key is used to manage thermostatic functions. The transmitter is
powered by three (3) AAA type batteries.
8
Figure 3: Proame 2 Transmitter.
Page 9
Low battery alarm
Key Lock
Room
Temperature
Dimmer ON
Set Point
Temperature/Level/State
Flame ON
Thermostat OFF/ ON/SMART
Comfort fan
Transmission
Split Flow
Aux ON
CPI mode
Operating Instructions
WARNING: Fire Hazard. Can cause severe injury or death. The Transmitter causes ignition of the appliance. The appliance can turn on suddenly. Keep away from the appliance burner when operating
the remote system.
Figure 4: Proame 2 Transmitter LCD Screen.
CAUTION: Property Damage Hazard. Excessive heat can cause property damage. The appliance can stay lit for many hours. Turn off the appliance if it is not going to be attended for any length of time. Always place the Transmitter where children cannot reach it.
inteGRateD FiRepLace contRoLLeR (iFc):
The IFC is the master controller for your replace control system known as Proame 2. This unit will control all aspects of the replace by receiving commands from the remote transmitter. This controller is powered by 120VAC but can also run off a (4) AA battery back-up if there is a power outage. Only main burner control can be used while
operating with the battery back up; auxiliary components, such as the convection fan, cannot be used. Use the reset
button (see Figure 5) to synchronize the remote transmitter to the IFC for the rst time, or after batteries have been
replaced.
Reset Button
Figure 5: Integrated Fireplace Controller
9
Page 10
Operating Instructions
opeRatinG pRoceDuRe:
Initializing The System
Install the four (4) supplied AA batteries into the IFC battery holder. The remote transmitter should come from the manufacturer with the batteries already installed. Press the reset button on the IFC (see Figure 5) and listen for three (3) beeps. Press the ON key on the remote transmitter and listen for another beep sequence.
Once the command has been accepted then the system is initialized and ready for use.
Note: Other remote transmitters may interfere with the system if you have another within the vicinity.
Temperature Indication Display
Press the Thermostat key and the Mode key
simultaneously while the system is OFF. The remote transmitter will indicate which temperature scale is
being displayed (°C or °F). Repeat this sequence to
change the scale (see Figure 6).
Turn on the Appliance
Press the ON/OFF key on the remote transmitter; the display will illuminate and show all active icons. A single beep from the IFC will conrm the command from the remote and the start up sequence will begin. The spark electrode will ignite the pilot ame which will engulf the ame sensor hook. After the sensor reaches sufcient temperature, the main burner valve will open and the ame will ignite moments after.
Note: If the pilot takes too long to ignite there may be air in the gas line. The system will enter a 5 minute lock-out and cancel the start-up procedure if too many spark attempts have been made. If pilot cannot light after 3 lock-out cycles then contact your gas tter.
Continuous Pilot Mode
Press the Mode key with the replace turned off. Use the UP/DOWN key to cycle between intermittent pilot ignition (IPI) and continuous pilot ignition (CPI). Press the mode key to make your selection and the IFC will beep to conrm your command.
Note: It is recommended to use CPI mode
when the temperature outside is below 50°F (10°C) to keep the vent sufciently heated to assist with warm-up procedure. Using CPI will
also eliminate excessive condensation on the
glass during start-up.
Figure 6: Temperature Scale Display
Turn off the Appliance
Press the ON/OFF key on the transmitter to turn the replace off. The IFC will conrm your command with a single beep. The pilot light (IPI) and the main burner will turn off. The pilot will remain lit if the replace is in CPI
mode. Room temperature information will still be displayed on the remote when the unit is off.
10
Figure 7: CPI Pilot Mode.
Page 11
Room Temperature
Set Temperature
Thermostat ON
Flame Off
Flame Level 1
Flame Level 5
Maximum Flame Level
Operating Instructions
Room Thermostat (Transmitter Operation)
The remote transmitter acts as a room thermostat. The thermostat can be set to a desired temperature to control the comfort level in a room.
Press the THERMOSTAT key to activate this function. The transmitter display will indicate the thermostat is ON and the set temperature can be adjusted with the UP/DOWN key. The ame will cycle on and off to
regulate temperature in this mode.
Smart Thermostat (Transmitter Operation)
The remote acts as a smart thermostat. Press the THERMOSTAT key until SMART is displayed. The
smart thermostat function has the ability to modulate
the ame level with reference to the set point. The ame will level down when the actual temperature
approaches the set temperature.
Figure 8: Thermostat Function
Remote Flame Control
The Proame 2 remote control system has six (6) ame levels. Adjust the ame level using the UP/ DOWN key; each time the button is pressed the IFC will beep to conrm your command. The remote display will show which level the ame is currently
at.
Figure 9: Smart Thermostat Function
Figure 10: Flame Control
11
Page 12
Operating Instructions
Fan Control
The Proame 2 remote control system has six (6)
fan speed levels. Adjust the fan speed using the
UP/DOWN key; each time the button is pressed the IFC will beep to conrm your command. The
remote display will show which level the fan speed is currently at.
Figure 11: Fan Control
Key lock
This function will lock the keys to avoid unsupervised operation. Press the MODE and UP key simultaneously to activate this function. Repeat this sequence to
deactivate. A lock icon will be displaced on the screen when activated.
Low Battery Power Detection
A low battery icon will be displayed on the remote transmitter when the batteries
are low. It is advisable to change the batteries at this point before all power is
lost from the remote.
There is no icon on the remote transmitter indicating low battery power for the
IFC. The IFC will emit a beep when the ON/OFF key is pressed indicating the
batteries are low.
The system will need to be initialized after battery replacement (see
the system). The life span of the batteries depends on various factors such as
battery quality, ignition attempts, remote usage, and power outage duration.
InItIalIzIng
Figure 12: Key Lock
Figure 13: Low Battery
12
Page 13
piLot LiGht:
Operating Instructions
The pilot ow adjustment is set to maximum at the factory
Flame Sensor
and should not need to be adjusted. The pilot ame should
.375
cover ⅜” to ½” (10 to 13mm) of the ame sensor (see Figure
16). However, should the need arise, turn the adjustment
-.500
(10-13mm)
screw to alter the pilot gas ow.
Figure 16. Pilot Light
aiR shutteR (VentuRi):
The air shutter plays a very important role in ame appearence and combustion quality. The shutter
adjusts how much air gets mixed with the gas before it ignites; adjustments can be made to accomodate
various climates and vent congurations.
Remove surround to access the air shutter. Find the lever underneath the rebox (see Figure 17). Moving the lever inward (closed) will make the ame appear more yellow and tall; moving the lever outward (open) will make the ames appear more blue and short.
Typically natural gas ames will require
the shutter to be more closed.
Typically LP ames will require the shutter to be more open.
If you cannot attain a healthy ame by making
air shutter adjustments, you may have the incorrect restrictor setting or venting problem.
+
_
If the ame is very ickery, fast moving, and
low then increase the restriction.
If the ame is very tall, lazy, and dirty then
decrease the restriction.
Figure 17. Air Shutter Location
Air Shutter Lever
More details can be found in the venting section of this manual.
Caution: Wear heat resistent gloves when making adjustments to the air shutter. Perform adjustments after 15 minutes.
noRmaL sounDs DuRinG opeRation:
Table 1: Normal Sounds
Component Normal Sound Description
Main Unit Creaking when heating up or cooling down
Burner Light pop or poof when turned on or off
Temperature Sensor Clinking when it senses to turn the blower on or off
Pilot Flame Quiet whisper while the pilot ame is on
Blower / Fan Air movement that increase and decreases with the speed of the blower
Gas Control Valve Dull click when turning on or off, this is the valve opening and closing
13
Page 14
Maintenance And Service
Routine maintenance:
Run through the following procedures to ensure the system is clean and working properly at least once
a year. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not blocked by anything. The pilot ame should be blue with little or no yellow tips.
WARNING: Failure to position parts in accordance with this manual, or failure to use only parts specically
approved with this appliance may result in property damage or personal injury.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied agency.
cLeaninG the GLass:
With the replace cooled, remove the surround panel and glass door (See maIntenance anD serVIce - surrounD Panel remoVal and maIntenance anD serVIce - glass Door remoVal). Check the gasket material
on the back of the glass, making sure that it is attached and intact.
During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all gas replaces. This condensation can allow dust and lint to cling to the glass surface which requires
periodic cleaning.
Initial paint curing of the appliance can leave a slight lm behind the glass, a temporary problem. The
glass will need cleaning about two weeks after installation.
Use a mild glass cleaner and a soft cloth. Abrasive cleaners will damage the glass and painted
surfaces. Depending on the amount of use, the glass should require cleaning no more than two or three
times a season.
WARNING: Do not clean the glass when it is hot.
cLeaninG the FiRebox:
Carefully remove the glass, they are fragile. Gently remove all the media and place on a paper towel. Vacuum the bottom of the rebox thoroughly. Carefully clean any dust off the glass and remove any lint from the burner and pilot. At this time, inspect the burner tube for cracking or severe warping. If a problem is suspected, contact the dealer. Check the glass for deterioration or large amounts of soot; a
small amount on the bottom side of the glass is normal. Replace the glass as shown in the
InstallatIon - log set InstallatIon section. If new/more media is required, contact your nearest ENVIRO
dealer.
seconDary
RepLacinG the GLass:
The glass in the replace is a low emissivity tempered glass. If the glass is damaged in any way, a factory
replacement is required (see Parts lIst). Wear gloves when handling damaged glass door assembly
to prevent personal injury. Do not operate with the glass front removed, cracked or broken. Removal and replacement of the glass from the door must be done by a licensed or qualied service person.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
To remove the door (see maIntenance anD serVIce - glass Door remoVal). The replacement glass will come with a new gasket installed. Remove any silicone remnants from the door. Apply high temperature around the perimeter of the door and install the new piece of glass with gasket. Apply even pressure to the glass to allow the silicone to adhere to the gasket material.
14
Page 15
Maintenance And Service
cLeaninG DecoRatiVe suRFaces:
Painted and porcelain faces should be wiped with a damp cloth periodically. If a plated face has been purchased, it should be unpackaged carefully to avoid getting anything on the surface of the nish, including cleaners, polish and nger prints. It is important to note that ngerprints and other marks can leave a permanent stain on plated nishes. To avoid this, give the face a quick wipe with denatured alcohol on a soft cloth BEFORE lighting the replace. Never clean the face when it is hot. Do not use other cleaners as they may leave a residue, which can become permanently etched into
the surface.
suRRounD paneL RemoVaL:
WARNING: Do not attempt to remove the surround panel until the unit has completely
cooled.
There are four mounting hooks that hold the surround into position (see Figure 18). To remove the
surround, it is easiest to grab with both hands on either side and lift up and bring outward. Upon installation, some adjustment from left to right may be needed to center the surround.
Figure 18. Surround Removal
15
Page 16
Maintenance And Service
DooR coVeR RemoVaL:
To remove the door cover, remove the two (2) wing nuts using your ngers then lift up and outward.
Wing nuts are only for shipping and do not need to be reinstalled.
WARNING: Do not touch or attempt to remove the glass door if the replace is not completely cold.
Figure 19. Door Cover Removal
GLass DooR RemoVaL:
To remove the glass door use a 3/8 socket to remove the 3 upper bolts ,rotate outward, and lift. To
replace the door simply reverse the order; do not over tighten the bolts or they may strip.
WARNING: Do not touch or attempt to remove the glass door if the replace is not completely cold.
WARNING: Never operate the replace with the glass door removed.
16
Figure 20. Glass Door Removal
Page 17
Maintenance And Service
The burners will need to be removed for maintenance and fuel conversion. Follow the procedure carefully.
Proceed only when the unit has completely cooled down.
meDia tRay RemoVaL:
1. Remove the surround panel (see maIntenance anD serVIce - surrounD Panel remoVal).
2. Remove the door cover (see
3. Remove the glass door (see maIntenance anD serVIce - glass Door remoVal)
4. Remove glass media (if installed).
5. Remove the upper tray hat by removing the two (2) upper T-20 screws.
6. Remove the seven (7) remaining T-20 screws securing the glass media tray
(see Figure 21). Lift up and out.
maIntenance anD serVIce - Door coVer remoVal).
Figure 21. Media Tray Removal
buRneR RemoVaL:
1. Remove the glass media tray (see maIntenance anD serVIce - meDIa tray remoVal).
2. Remove the six (6) appropriate T-20 screws securing the burner. Lift burner up and out. The remaining T-20
screws in the burner do not need to be removed.
Figure 22. Front Burner Removal
17
Page 18
Maintenance And Service
FueL conVeRsion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualied service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a re, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualied service agency is responsible for the proper installation of this kit. The installation is not proper or complete until the operation of the converted appliance is checked as specied in the manufacturer’s instructions supplied with the kit.
Kit Parts List for G39GI Model:
1 - Burner Orice LP [DMS #52] NG [#36 DMS] as marked 1 - Stepper Motor w/ Hardware 1 - Installation Instruction Sheet 4 - Conversion Labels
Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are
missing, contact your dealer, distributor or courier company to have them replaced before starting this installation.
conVeRsion Kit instaLLation:
1. Disconnect the gas supply completely as well as any electrical power source before proceeding.
2. Remove surround panel, door cover, glass door, media tray, and burner (see maIntenance anD serVIce section of Owner’s Manual).
3. Convert the existing burner orices with the ones provided in this kit using a 3/8 inch deep socket.
WARNING: BE SURE TO INSTALL THE CORRECT ORIFICE INTO THE CORRECT PORT
Pilot
Head
Orice
Slide
Figure 23: Pilot Assembly
18
Figure 24: Orice Location
Page 19
Maintenance And Service
4. Convert the existing pilot orice using a 7/16 inch wrench. Loosen the pilot head and move the orice slider to the opposite side. A red dot on the exposed side will indicate the pilot is set to LP. Retighten pilot, if head does not reach proper orientation in the snug position then contact your Enviro dealer (see Figure 30).
5. Convert the gas valve:
a) Remove the existing stepper motor using a T20 screwdriver (see Figure 31).
b) Remove the rubber diaphragm and spring within; do not reuse.
c) Install the new stepper motor with integrated diaphragm assembly using longer hardware. d) Plug new motor into the control module (IFC).
Figure 25: Pilot Orientation
Stepper
Regulator
Pilot Adjustment
Screw
Manifold
Pressure Tap
Figure 26: Gas Valve Diagram
Inlet
Pressure Tap
6. Reinstall burner, media tray, burner media, logs (if applicable), glass door, and door cover (see maIntenance anD serVIce section of Owner’s Manual).
7. Purge any air from gas line and reconnect to unit.
8. Use a small brush and apply a warm soapy water solution to all gas connections. If a gas leak is present, bubbling will occur. Gas leaks can be repaired by using a gas approved pipe thread sealant. WARNING:
NEVER USE AN OPEN FLAME WHEN TESTING FOR GAS LEAKS.
9. Reconnect electrical power to the unit.
10. Light the pilot and recheck for leaks in the aluminum pilot line. If a leak is evident, contact your ENVIRO
dealer for a pilot line replacement. WARNING: DO NOT ATTEMPT TO FIX THIS LINE, IT MUST BE
REPLACED IF DAMAGED. The pilot should properly cover the ame sensor. If adjustment is necessary, turn the adjustment screw in the valve (see Figure 26) clockwise to decrease and counter-clockwise to increase until the correct ame is achieved (see Figure 16).
11. Start the main burner and verify full range of adjustment using the remote. Conrm the inlet and manifold gas pressures are within the acceptable range using a manometer (see I connectIon anD testIng). If this unit has been installed at an altitude higher than 2000ft (610m) it is
required to de-rate the unit accordingly.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
12. MAKE SURE that the conversion labels provided are installed on or close to the rating label to signify
that the unit has been converted to a different fuel type.
nItIal InstallatIon - gas lIne
19
Page 20
Initial Installation
QUALIFIED INSTALLERS ONLY
intRoDuction:
This section of the owner’s manual is for the use of qualied technicians only. There are several installation
safety guidelines that must be adhered to; carefully read the safety precautions at the front of this manual.
unit instaLL pRepaRation:
Review the diagram below to familiarize yourself with the parts included with the unit. Please review the
following instructions carefully to ensure the unit is prepared properly before installation.
1
3
2
4
5
Diagram 1: Additional Parts
Item Number Item Description Quantity
1 Non-Combustible Board 1
2 Cool Surface System Bezel 1
3 Stud Anchors 4
4 Extended Finishing Edge Side 2
5 Extended Finishing Edge Top 1
20
Table 2: Additional Parts
Page 21
Initial Installation
QUALIFIED INSTALLERS ONLY
Nailing Flange:
There are four (4) nailing anges to secure the unit to the framing, they are assembled at from
the manufacturer. Remove the upper T-20 screw and rotate each nailing ange upward until the bare nailing ange hole lines up and reinstall the T-20 screw. Bend the ange 90 degrees making it ush with the cabinet face.
Figure 27: Nailing Flange Flat Figure 28: Nailing Flange Assembled
Non-combustible board:
Install the supplied non-combustible facing board with eight (8) supplied 8-32 x.75 fasteners
using a 1/4 inch socket. These screws can be found in the manual bag, remove them and install the board. Line up the holes and drill fasteners into the board until the screw head is ush with
facing board. CAUTION: DO NOT DRILL INTO THE BOARD ANY FURTHER OR IT MAY CRACK. This board is mandatory unless the
contact you ENVIRO dealer.
cool surface system is activated, if it is damaged
Figure 29: Non-combustible board
21
Page 22
Initial Installation
pLacement anD FRaminG:
QUALIFIED INSTALLERS ONLY
76 ½”
(1,943mm)
Natural Gas*
18¼”
(464mm)
Figure 30: G39 Minimum Framing
Table 3: G39 Minimum Framing
42”
(1,067mm)
41½”
(1,054mm)
Minimum Framing Dimensions
1/4
Depth 18 Width 41
464mm
1/2
1054mm
Header Height 42” 1067mm
1/2
Enclosure Ceiling (Natural Gas) 76
Enclosure Ceiling (Propane) 80
1943mm
1/2
2045mm
*NOTE: Minimum enclosure ceiling height is increased when Fireplace has been converted to propane.
The location for the replace can be raised, at oor level, or installed in a corner. There are minimum
framing measurements for each situation. The basic rough opening should have the following dimensions
(see Figure 23). The replace must be placed on a strong and level surface.
The gas line must be run to the right side of the replace, there is a 3/8 NPTM tting to connect the gas line to. The electrical wiring must be brought to the left side. The location of the replace should be chosen so
there will be at least a 36 inches (914 mm) clearance from drapes, doors and other combustible materials.
22
Page 23
Initial Installation
QUALIFIED INSTALLERS ONLY
FinishinG a FiRepLace:
There are multiple ways to finish a G39 fireplace. Here is what you need to know to properly install the
desired finishing material.
There are three finishing edge options.
1. Outer Finishing Edge (Short) - This finishing edge comes
mounted to the unit with screws. This finishing edge is 0.5” deep and will accommodate finishing materials up to 0.875” in
thickness. The surround panel will sit on the inside of this finish-
ing edge. This means the finishing edge is offset 0.25” from the
surround panel creating a border. This option will not cover the cut edge of the finishing material so it needs to be finished in an aesthetically pleasing way.
2. Outer Finishing Edge (Long) - This finishing edge comes
wrapped in foam on top of the unit. This finishing edge is 1” deep and will accommodate finishing materials of 1” or more in thickness. The 0.5” Finishing edge installed on the unit will
need to be removed and replaced with this trim. The surround panel will sit on the inside of this finishing edge. This means the
finishing edge is offset 0.25” from the surround panel creating
a border. This option will not cover the cut edge of the finishing material so it needs to be finished in an aesthetically pleasing way. This is ideal for thicker finishes like stone.
Figure 31: Outer nishing edge
removal / replacement
3. Inner Finishing Edge - This finishing edge is integrated into cabinet of the fireplace. The Outer Finishing
(Short) will need to be removed. The surround panel once installed will overlap the inner finishing edge. This means the surround panel will hide the edge of the finishing material. This ideal for finishing materials 0.75”
or less and the it is desired to hide.
Surround Border
Outer Edge
Inner Edge
Figure 32: Finishing edges
23
Page 24
Initial Installation
QUALIFIED INSTALLERS ONLY
Combustible material may be brought up to any finishing edge ONLY if the Cool Surface System (CSS) has been correctly activated allowing heat in the chase to be vented. This system keeps the front
wall cool enough for any combustible materials. The supplied non-combustible board can still be used but is not
mandatory when the CSS is activated, combustible material may overlap in this situation.
If the CSS has NOT been activated (Traditional Install) you
directly above the fireplace extending up the front wall 9” from the top finishing edge, it is recom-
mended to use the supplied non-combustible board. Combustible material must NOT be brought up to the top finishing edge. Also combustible material CANNOT overlap the non-combustible board on a traditional installation.
39.25
34.55
Figure 33: Outer Finishing Edge Dims
NOTE: These are exact dimension add tolerance when cutting nishing material to ensure t around the nishing edge. This is especially important when using the inner edge. The surround will overlap the inner edge by 0.375” and hide the cut edge.
MUST use a non-combustible material
37.95
33.95
Figure 34: Inner Finishing Edge Dims
cooL suRFace actiVation:
WARNING: IT IS ESSENTIAL THAT THE CHASE IS VENTED IN A MANNER THAT RELIEVES THE
ADDITIONAL HEAT ENTERING THE CHASE. ENSURE ONE OF THE AVAILABLE FRAMING OPTIONS HAVE BEEN CONSTRUCTED IN ACCORDANCE WITH THIS MANUAL. FAILURE TO DO SO CAN CREATE AN OVERHEATING SITUATION THAT COULD LEAD TO BUILDING FIRE.
Ensure your chase has been constructed in a
manner that vents the chase into the same
room. It is not permitted to vent the chase into an adjoining room. The CSS bleeds heat off the replace into the chase as opposed to
climbing up the front face. This dramatically lowers the front wall temperatures allowing the placement of delicate objects above
the replace. Review the guidelines in the
previous sections to ensure your install is in
accordance with the framing specications. Follow these instructions to active the CSS
feature. The non-combustible board included
with the replace is no longer required when using CSS.
Activation - Remove CSS plug using 1/4”
deep socket or at head screwdriver.
The CSS system is now activated.
24
CSS Plug
Figure 35: CSS Plug Removal
Page 25
Initial Installation
QUALIFIED INSTALLERS ONLY
Standard Install: the Non-combustible is
mandatory. Image shows single layer nishing material using the short nishing edge.
1
"
2
13mm
Supplied Non-combustible Board
Cool Surface System (CSS) Install: Image shows the short nishing edge, combustible can be brought right down to the nishing edge.
1
"
2
13mm
Combustible (ex. Drywall)
Standard Extended Install: Using the supplied
long nishing edge, non-combustible material may be layered on top of the supplied Non­combustible board. Supplied board not needed for thick non-combustible nishes like rock.
Supplied Non-combustible Board
7
"
8
9”
229mm
MIN
Extended Finishing Edge
13mm
MIN
Non-combustible Finishing Material
Cool Surface System Extended Install: Using
the supplied long nishing edge, combustible material may be layered on top of the supplied
Non-combustible board. Supplied board is not needed for thicker combustible nishes.
7
"
8
13mm
MIN
Combustible Finishing Material
Extended Finishing Edge
25
Page 26
Initial Installation
QUALIFIED INSTALLERS ONLY
cooL suRFace instaLL options:
This replace is manufactured with a built-in heat distribution kit, referred to as the Cool Surface System (CSS). The purpose of the CSS is to dramatically reduce the front wall temperatures above your replace. This is very useful when delicate objects such as a TV or artwork are mounted above the unit. Using this feature will also allow you to use combustible facing materials right up to the nishing edge. It is extremely important these instructions are followed meticulously. If not installed correctly this could be very dangerous and could lead to building re. If the CSS is activated it is crucial that the chase is vented in accordance to this manual. There are a few different options available to nish the CSS.
Option 1: Front Discharge (ush wall installations) - Construct the framing in a way that provides a
1/
minimum 41
2 inch (1054mm) by 2 inch (51mm) gap at the top of the facing wall. It is essential that these
dimensions are respected and not deviated away from them when using combustible materials inside or outside the chase (see Figure 36).
Note: If you wish to construct the CSS air discharge part way up a tall wall then it is essential to build a
false ceiling inside the chase at the desired height to direct the rising heat out of the gap.
1
"
1
38mm
MAX
"
2
1
76 "
2
1943mm
MIN (NG)
1
80 "
2
2045mm
MIN (LP)
2"
51mm
MIN
1
"
41
2
1054mm
MIN
CSS Air Discharge
Non-Combustible board mandatory for CSS Install.
1
39
"
4
997mm
9"
229mm
NOT
73
1740mm
MIN
Figure 36: CSS Front Discharge
26
Page 27
Initial Installation
QUALIFIED INSTALLERS ONLY
Option 2: Open Chase (built-out installations) - This could be considered the most discreet option
when considering the CSS. The chase must be constructed in a way that stops short of the ceiling, leaving
it totally vented above. Minimum framing dimensions must be followed when constructing this option and not to deviated from them when using combustible materials. Consider Optional 3: Valance to work in conjunction with this option.
6"
152mm
Minimum
Wall Mounted Object
2"
51mm
Minimum
Figure 37A: Option 2
2" MIN
Figure 37B: Open Chase Iso View
Option 3: Valance - A valance may be desired to accentuate or hide the CSS outlet. Consider framing
option 1 or 2 to utilize the valance feature. This is an optional decorative feature that covers up the CSS
outlet gap. Minimum opening and valance dimensions must be followed to ensure safe heat dissipation.
Combustible materiel is acceptable when constructing the valance. It is acceptable to wrap the valance around the three sides of a built out chase (Option 2).
Minimum
6"
152mm
Minimum
4"
102mm
1"
25mm
Maximum
Wall Mounted Object
152mm
Minimum
Figure 38A: Valance Install
6"
2"
51mm
Figure 38B: Valance Iso View
27
Page 28
Initial Installation
QUALIFIED INSTALLERS ONLY
Option 4: Bezel - The included bezel may be desired to accentuate the CSS outlet. This installation will also cover the edge of the nishing material at the cutout. Construct the framing in a way that provides
1
/2” (1054mm) by 2” (51mm) cutout to mount the bezel. The top of the cutout must be 1 1/2” from
a 41 the top of the chase. It is essential that these dimensions are followed and not to deviated from them when using combustible materials inside the chase (see Figure 39).
Note: If you wish to construct a similar cutout part way up a tall wall then it is essential to build a false
ceiling inside the chase at the desired height to direct the rising heat out of the gap.
1
0 to 1
2
38mm
"
Maximum
CSS Bezel Included With Unit
51mm
2
"
Figure 39A: Option 3 Bezel
Figure 39B: Bezel Iso View
Optional: False Ceiling - If your ceiling dimension is greater than the minimum (See gure 36) You
may want the CSS Air discharge lower on the wall. To do this a false ceiling is required to properly evacuate the heat from the chase. (See Figure 40).
False Ceiling
2"
51mm
Minimum
Figure 40A: False Ceiling
28
Figure 40B: False Ceiling Iso View
Page 29
Initial Installation
QUALIFIED INSTALLERS ONLY
FLat WaLL instaLLation:
These are the minimum allowable dimensions required to safely operate the replace. Plan your entire
installation before proceeding. These are minimum dimensions associated with natural gas only; adjust the ceiling dimensions by adding 6” (152 mm) if using propane.
4"
102mm
MIN
12"
305mm
4"
102mm
1
82
"
2 2096mm MIN (LP)
1
76
"
2
1829mm
MIN (NG)
16
419mm
1
"
2
1
10
"
2
266mm
45"
1144mm
Figure 41: Flat Wall Installation
29
Page 30
Recess instaLLation
Initial Installation
QUALIFIED INSTALLERS ONLY
These are the minimum allowable dimensions required to safely operate the replace. Plan your entire
1/2
installation before proceeding. The maximum allowable depth for a recess in 3
” (90mm) + Finishing
material thickness.
4"
102mm
MIN
1
3
"
2
1
13
"
2
343mm
39.5"
1003mm
MIN (NG)
1
82
"
2
2096mm
MIN (LP)
89mm
1
76 "
2
1943mm
MIN (NG)
48"
1219mm
30
Figure 42: Recess Installation
Page 31
Initial Installation
QUALIFIED INSTALLERS ONLY
coRneR instaLLation:
These are the minimum allowable framing dimensions required to safely operate the replace in a corner install. Plan your entire installation before proceeding.
5
33
"
8
853mm
3
21
"
25mm
1"
4
554mm
1
68
"
4
1733mm
Figure 43. Corner Installation
14
368mm
15"
382mm
1"
25mm
1
"
2
45°
47
1206mm
1
"
2
31
Page 32
Initial Installation
1 2 3 4 5 6 7 8 9 10 11 12 13 14
M A NTEL H E I G H T
M A NTEL D E P T H
Minimum Mantle Clearances
8” MANTEL
4”MANTEL
52”
51”
50”
49”
48”
47”
46”
44”
45”
12” MANTEL
QUALIFIED INSTALLERS ONLY
FLooR pRotection:
The replace must be placed on a solid and level oor; plywood is recommended for basic installations.
A protective hearth is not required but highly
recommended for the longevity of sensitive ooring materials in front of the replace.
If masonry is to be used, prepare the necessary
foundation for the masonry load. When masonry construction is being used, a lintel must be used over
top of the replace to support the added weight.
Consider the height of hearth nish material (stone, brick, etc.) when building a replace platform. The bottom of the replace must be level with nished
hearth.
WARNING: DO NOT OBSTRUCT THE BOTTOM
AIR GAP WITH FLOORING MATERIAL. RAISE THE FIREPLACE TO MATCH FLOOR
THICKNESS.
manteL RequiRements:
Figure 44: Air Gap Warning
1
2
[13mm]
"
First determine what mantel height or depth you would like and use the graph to determine the minimum
corresponding dimension. Mantel graph dimensions are measured from the bottom of the replace, if you
1/
wish to reference the mantel height from the tiling edge subtract 34
2” (876mm) from the mantel height
depicted on the graph. If you plan to install a TV above your replace refer to the appropriate section for available options. It is acceptable to install a combustible mantel over top of the non-combustible board.
If you are activating the
cooL suRFace system you are eligible to subtract 6” (152mm) from
the mantel height shown in this diagram.
32
Diagram 2: Mantel Graph
Page 33
Initial Installation
QUALIFIED INSTALLERS ONLY
minimum VentinG RequiRements:
This appliance uses a 4” (102mm) exhaust / 6 5/8” (168mm) air intake vent pipe system. For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the minimum vertical length can create difculty in burner start-up and sooting. Allow several minutes for the ame to stabilize after ignition under extreme vent congurations. It is recommended for vent lengths that pass
through unheated spaces (garages, attics, crawl spaces) be insulated to minimize condensation.
NOTE: Measure your total vent height on the unit before a hole is cut into the exterior wall;
account for
1
/4” (25mm) of rise for every 12” (305mm) of run to determine your thimble
height.
NOTE: Center of thimble dimension is based on 12”+6” sections of vertical rise for Natural Gas (NG) installs and
18
464mm
1
"
4
12”+12” sections for units converted to
Propane (LP).
72"
1829mm
MIN (NG)
66"
1677mm
MIN (LP)
60"
1524mm
MIN (NG)
Figure 45: Minimum Vent (NG)
33
Page 34
Initial Installation
QUALIFIED INSTALLERS ONLY
FLex VentinG:
This replace is only certied to work with certain BDM Pro-Form and Duravent exible direct venting systems. Not all rigid venting congurations are allowable when using ex venting. Only horizontally terminated applications will work with a vertical rise between 12” (305mm) and 78” (1981mm) measured
from the top of the unit.
If your vertical rise is between 18” (457mm) and 30” (762mm) use 50-3461 5ft kit.
If your vertical rise is between 30” (762mm) and 78” (1981mm) use 50-3462 10ft kit.
Important Information:
-Do not bend over 90 degrees.
-All horizontal runs should have a minimum 1/4” (6mm) rise per foot for optimal performance.
-Do not allow the inner ex pipe to contact the outer pipe, keep it pulled tight and use spacer springs.
-Spacers are required at the start, middle, and end of each elbow to ensure the gap is maintained.
-Do not add any extensions to the preset kits, if more length is required, use rigid pipe.
Step 1. Install supplied thimble into exterior
wall framing and seal with an approved sealant.
Step 2. Termination already comes secured
to the ex venting, do not detach. Insert spacer springs around inner
pipe and space out evenly. Feed venting through thimble from the exterior.
Step 3. Secure termination cap to exterior
wall using supplied screws. Use an approved sealant around the perimeter of the cap.
Step 4. Apply a liberal bead of sealant
around the perimeter of the replace vent collar then attach ex venting. Secure the inner exhaust pipe rst,
then the outer, using self-taping screws.
Flex Cap
Flex Vent
Flex Thimble
66"
1677mm
MIN (LP)
60"
1524mm
MIN (NG)
Approved Flex Vent Kits:
BDM Pro-Form 5ft kit (50-3461)
BDM Pro-Form 10ft kit (50-3462)
Duravent 4ft section (46DVA-48FF)
Duravent 10ft section (46DVA-120FF)
34
Figure 46. Flex Vent Install
Page 35
Initial Installation
QUALIFIED INSTALLERS ONLY
cLeaRances & non-combustibLe :
When installing the replace as a zero clearance replace the correct clearances and materials must be
used.
aboVe unit: The supplied noncombustible board is required above the unit up to the header 9” MIN.
However this not required if the Cool Surface System has been properly installed.
heaDeR: The header can be made up of wood 2x4 construction at or above the top standoffs.
beLoW unit: Is is recommended the replace sit a solid and level piece of 3/4” plywood.
aDjacent/siDeWaLL: There must be a minimum distance of 7” (178mm) from the nishing edge of
the replace to an adjacent wall composed of combustible material.
manteL: It is not necessary to install a mantel, but if one is desired the guidelines as shown in “InItIal I
nstallatIon - mantel requIrements”.
FLooR: The unit must be raised to accommodate ooring thickness. Always ensure convective air gaps around the unit remain unobstructed. Combustible ooring can be used but make sure to review the maximum allowable temperature for your specic ooring material. Since every home and installation is unique, temperatures should be veried at the time of install. A hearth should be installed if temperatures
exceed the manufacturers maximum allowable temperature.
Framing
Header
Non Combustible Board
Drywall
Sidewall
7”
[178mm]
COMBUSTIBLE
NON COMBUSTIBLE
9”
[229mm]
Figure 47. Typical Facing Layout
35
Page 36
Initial Installation
QUALIFIED INSTALLERS ONLY
tV instaLLation consiDeRations:
Use of the Cool Surface System is highly recommended when mounting a TV or delicate artwork above the replace. If the system is not desired, some considerations must be made to ensure above objects
are protected from the heat. A recess, mantel, or a combination of both will be needed for heat protection.
During testing temperatures did not exceed 120F over ambient in a 3
no guarantee that these temperatures will not harm the longevity of your TV. Make sure to consult your TV manufacture’s specications to nd the maximum allowable operating temperature. Since every home and installation is unique, temperatures should be veried at the time of install. A TV should not be installed if
temperatures exceed the manufacturers maximum allowable temperature.
Mantel Only Installation: Always maintain minimum clearances (see Figure 48). The total depth of the TV
and wall mount will determine the minimum allowable mantel depth. This is required for a standard installations
and highly recommended for CSS installations.
Recess Installation: Always maintain minimum clearances (see Figure 49). The total depth of the TV and
wall mount as well as the recess depth will determine the minimum whether or not a mantel is recommended.
A mantel may not be needed if the TV and Mount are low prole enough.
A mantle is not mandatory but highly recommended for protection of a TV. If choosing to not use a mantel you should place the TV as high up the wall as possible. Please consult the TV manufacture’s specications to nd the maximum allowable operating temperature. Temperatures should be conrmed on site after an extended burn.
1/2
” deep recess. There is
See “
InItIal InstallatIon - mantel clearances” and “InItIal InstallatIon - recess InstallatIon” for more
information.
Min:
1
2
"
2
64mm
Mantel Thickness Min:
Maintain minimum 2 1/2" TV screen distance
-See mantel instructions for further information
19mm
Min: 2" gap
50mm
3
"
4
Air gap behind TV Min: 1 1/2" [38mm] (typically provided by wall mount)
Non-Combustible Board (supplied)
Min: 2" gap
50mm
Mantel Thickness Min:
19mm
1
Min:
2
"
2
64mm
Under Side of Mantel Min:
3
"
4
13
343mm
1
"
2
Air gap behind TV Min: 1 1/2" [38mm] (typically provided by wall mount)
Non-Combustible Board (supplied)
Figure 48. Minimum TV Install
36
Figure 49. Recess Minimum TV Install
Page 37
Initial Installation
QUALIFIED INSTALLERS ONLY
DiRect Vent:
WARNING:
- Follow the venting instructions exactly for safe and proper appliance operation.
- Use Mill Pac or high temp RTV silicone for all venting aconnections.
- Risk of re, explosion, or asphyxiation if improper venting setup.
-Risk of re, do not allow loose materials or insulation to contact vent pipe. Remove insulation
to allow installation of thimble and maintain clearances to combustible materials.
This appliance uses a 4” (102mm) exhaust / 6 5/8” (168mm) air intake vent pipe system. For safe and proper operation of the appliance follow the venting instructions exactly. Deviation from the minimum vertical length can create difculty in burner start-up and sooting. Allow several minutes for the ame to stabalize after ignition under extreame vent congurations. It is recommended for vent lengths that
pass through unheated spaces (garages, attics, crawl spaces) be insulated to minimize condensation.
Use atleast three (3) screws at each vent connection. Check periodically that the vents are unrestricted,
especially the exterior vent cap.
Vent teRmination RestRictions:
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 50. Vent Termination Restrictions, refer to Table 4
Letter Canadian Installation
A 12 in (30 cm) Clearance above grade, verandah, porch, deck, or balcony.
B 12 in (30 cm) Clearance from window or door that may be opened.
C 12 in (30 cm)* Clearance from permanently closed window (to prevent
D 14 in (36 cm) Vertical clearance to ventilated soft located above the
E 12 in (30 cm) Clearance to unventilated soft.
F 12 in (30 cm)* Clearance to outside corner.
G 12 in (30 cm)* Clearance to inside corner.
H 3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly
I 3 ft (91 cm) 3 ft (91 cm)* Radial clearance around service regulator vent outlet.
1
Air Supply Inlet
Table 4: Vent Termination Clearances
US Installation
3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly*
Gas MeterG
2
condensation).
terminal, within a horizontal distance of 2 ft (60 cm) from
center line of terminal.
Clearance to each side of center line extended above me­ter/regulator assembly.
Restriction Zone
(Termination not allowed)
Description
K
A
37
Page 38
Initial Installation
x”
x”
QUALIFIED INSTALLERS ONLY
J 12 in (30 cm) Clearance to non-mechanical air supply inlet to building, or
K 6 ft (1.83 m) 3 ft (91 cm) above if within 10
L 7 ft (2.13 m
M 12 in / 30 cm
N 12 in (30 cm)* Clearance horizontally to any surface (such as an exterior
O 12 in (30 cm) Clearance above roof line for vertical terminations.
1
In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates.
t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings
and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
)t
+
ft (3 m) horizontally
7 ft (2.13 m)
12 in / 30 cm*
*t
+
the combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
Clearance above paved sidewalk or paved driveway located
on public property.
Clearance under verandah, porch, deck, or balcony.
wall) for vertical terminations.
Clearances must be in accordance with local installation codes and requirements of the gas supplier.
NOTE: Venting terminals shall not be recessed into walls or siding.
GeneRaL VentinG cLeaRances:
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a horizontal vent pipe, the clearance to combustibles should be 3” (76 mm) above and 1” (25 mm) on the sides and bottom. When combustible materials are directly above a 90° elbow, 3” (76 mm) of clearance is necessary.These are basic vent clearance and are used once outside the appliance chase enclosure.
Table 5. Vent Pipe Minimum Clearances
Hard
Pipe
Vertical Pipe to
the Side Walls
1”
(25mm)
Horizontal Pipe to
the Sides & Bottom
1”
(25 mm)
Above an Elbow
Not Above the Unit
3”
(76 mm)
Above Horizontal
Vent Pipe
3”
(76 mm)
Wall Frame 8”
(203mm) or less
3” top
(76mm)
See certied thimbles in venting section and frame accordingly (see Figure 51). A thimble will assure
the proper support and spacing requirements for the vent pipe as it passes through the exterior wall.
Installations in Canada require that a wall thimble be used
for passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.
The venting conguration depends on the locations of walls,
ceilings, and studs. However, the pipes cannot be of arbitrary
length and arrangement. Certain guidelines have been set in “
InItIal InstallatIon - allowable co-axIal Vent confIguratIons
because the length of the vertical and horizontal sections
dramatically affects the burning efciency of the replace.
WARNING:
-This gas appliance must be direct vented and can’t be connected to a chimney ue serving a separate solid-burning appliances.
-Venting terminals cannot be recessed into a wall or siding.
Figure 51. Thimble Framing
38
Page 39
Initial Installation
QUALIFIED INSTALLERS ONLY
appRoVeD VentinG paRts:
Manufacturer Trade Name Nominal Sizes
ICC EXCELDirect 4” - 6
M&G Dura-Vent Direct Vent Pro 4” - 6
Selkirk DIRECT-TEMP 4” - 6
Selkirk AMP DV 4” - 6
This replace has been tested and certied for use with M&G DuraVent DirectVent Pro, ICC EXCEL Direct, Selkirk DIRECT-TEMP, and Selkirk AMP DV venting systems. Refer to the table below for part numbers
of commonly used parts for both venting systems. For more venting parts please visit the respective manufacturers’ website.
WARNING: Do not mix parts from different vent manufacturers’ systems.
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a DirectVent Pro starting collar in conjunction with EXCELDirect venting systems. Use of this system with the DirectVent Pro starting collar is deemed acceptable and does not affect the Intertek listing of the appliance.
Table 7: Vent Part Numbers (must state if galvanized or black wanted)
Direct Vent Pro EXCELDirect DIRECT-TEMP AMP DV Description
46DVA-06 4DL6 4DT-06 6” pipe length
46DVA-09 4DL9 4DT-09 9” pipe length
46DVA-12 4DL1 4DT-12 4D12 12” pipe length
46DVA-16 4DT-16 18” pipe length
46DVA-24 4DL2 4DT-24 4D2 24” pipe length
46DVA-36 4DL3 4DT-36 4D3 36” pipe length
46DVA-48 4DL4 4DT-48 4D4 48” pipe length
46DVA-60 60” pipe length
46DVA-E30 30° elbow, black
46DVA-E45 4DE45 4DT-EL45 4D45L 45° elbow, black
46DVA-E90 4DE90 4DT-EL90 4D90L 90° elbow, black
46DVA-VSS, DVA-BVS VSS 4DT-VS, VSK 4DHVS, DVSK Vinyl siding standoff/sheild
46DVA-WT, 46DVA-WTU 4WT 4DT-WT 4DWT Wall thimble
46DVA-SC SQSC, SC 4DT-SC 4DSC Storm collar
46DVA-WFS 4DT-FS Wall Fire stop
46DVA-FS
46DVA-IS
46DVA-WS 4WS 4DT-WS/B 4DWS Wall strap/support/band
46DVA-VCH 4SVT 4DT-VT 4DVC High wind vertical termination
46DVA-17TA 11” to 17” pipe, adjustable
46DVA-24TA
46DVA-F6 6EFA 4DT-AF6 4DF Flashing, 0/12 to 6/12 roof pitch
46DVA-F12 6EFB 4DT-AF12 4DF12 Flashing, 7/12 to 12/12 roof pitch
46DVA-FF 6EF Flat Roof Flashings
46DVA-CFK 4MF Masonary Flashing
4CS 4DT-FS 4DFSP Ceiling Fire stop
4AS 4DT-AIS 4DAIS12, AIS36 Attic Insulation Shield
4DLA30 16.5” to 29” pipe , adjustable
4DLS1 1 7/8” to 9” slip length pipe
4DLS2 1 7/8” to 21” slip length pipe
Table 6: Approved Vent Manufacturers
4D7 7" pipe length
4D7A 3" to 5" pipe, adjustable
4DT-AJ12 4D12A 4" to 10" pipe, adjustable
4D16A 3" to 14" pipe, adjustable
4D26A 3" to 24" pipe, adjustable
4DT-TL14 14" to 22" pipe, telescopic
4DT-TL36 38" to 70" pipe, telescopic
4DT-MCK 4DRCKM Masonry Conversion Kit
5/
8
5/
8
5/
8
5/
8
17” to 24” pipe, adjustable
39
Page 40
Initial Installation
QUALIFIED INSTALLERS ONLY
aLLoWabLe co-axiaL Vent conFiGuRations:
40’
(12.2m)
35’
(10.7m)
RESTRICTOR 5
RESTRICTOR 5
NG Vent
Position
30’
(9.14m)
25’
(7.62m)
RESTRICTOR 4
RESTRICTOR 4
20’
(6.1m)
15’
(1.52m)
RESTRICTOR 3
RESTRICTOR 3
10’
(3.05m)
This shows the range of venting options using either vertical or horizontal terminations; any layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal as they restrict air movement. The total length of horizontal vent pipe
can not exceed 20 feet (6.1m) and
the total vertical vent length can not
exceed 40ft (12.2m). Any combination
of rise and run can be used as long as it lays within the shaded area (a total
of three (3) 90˚ elbows or six (6) 45˚ elbows can be used. In addition to what is shown, if a 90˚ elbow is used in the horizontal plane, 3 feet (91.4cm)
must be subtracted from the allowable
horizontal run (for each 45˚ elbow, 1½ feet (45.7cm) must be subtracted).
Restrictor Setting: Find the point on the graph where your vent configuration will terminate. Remember
to consider elbows in the HORIZONTAL
plane account for horizontal distance as stated above. Use the corresponding exhaust restrictor setting indicated on
the graph. See the following section in this manual for restrictor details. Your
climate and altitude may alter what restrictor is required for your particular application.
6’
(1.83m)
RESTRICTOR 2
RESTRICTOR 2
18”
(0.46m)
12”
(0.30m)
18”’
(1.83m)
Figure 52. Natural Gas Vent Graph
40
RESTRICTOR 1RESTRICTOR 1
6’
(1.83m)
15’
(4.57m)
High wind guard required for all vertical vent runs with no horizontal run.
ICC EXCELDirect TM-SVTS M&G Duravent Pro 46DVA-VWG
20’
(6.1m)
Page 41
40’
(12.2m)
Initial Installation
QUALIFIED INSTALLERS ONLY
ONLY use this venting diagram if your replace has been converted to LP.
35’
(10.7m)
30’
(9.14m)
25’
(7.62m)
20’
(6.1m)
RESTRICTOR 5
RESTRICTOR 5
RESTRICTOR 4
RESTRICTOR 4
LP Vent
Position
Restrictor Setting: Find the point on the graph where your vent configuration will terminate. Remember to consider elbows
in the HORIZONTAL plane account for
horizontal distance as stated above. Use the corresponding exhaust restrictor setting
indicated on the graph. See the following
section in this manual for restrictor details.
Your climate and altitude may alter what
restrictor is required for your particular application.
High wind guard required for all vertical vent runs with no horizontal run.
ICC EXCELDirect TM-SVTS M&G Duravent Pro 46DVA-VWG
15’
(1.52m)
10’
(3.05m)
6’
(1.83m)
2’
(0.61m)
RESTRICTOR 1
RESTRICTOR 1
4’
(1.83m)
RESTRICTOR 3
RESTRICTOR 3
RESTRICTOR 2
RESTRICTOR 2
15’
(4.57m)
20’
(6.1m)
Figure 53. LP Vent Graph
41
Page 42
Initial Installation
DETAIL
A
SCALE
2 : 5
QUALIFIED INSTALLERS ONLY
exhaust RestRictoR settinG:
WARNING: Improperly set restrictor setting can cause overheating issues which can lead to building re.
It may be necessary to adjust the exhaust restrictor in order to control combustion quality and ame
appearance. There are six different restrictor settings.
Determine what restrictor setting you require using the vent graphs in “
o-axIal Vent confIguratIons. The restrictor is set to 1 when the at edge of the dial is vertical (see Figure
c
55). Rotate the dial counter-clockwise to increase the restriction level successively until the appropriate setting is achieved. When the at edge is horizontal the restrictor level is at its maximum (see Figure 54). The proper setting is crucial for an efcient burn and best possible ame appearance.
It may be necessary to deviate from the recommended setting as different altitudes and climates can vary the operation of the replace. With LP fueled replaces, it is always a good idea to offer slightly less
restriction for higher altitudes to reduce the risk of sooting over an extended period.
Step 1. Remove surround panel to gain access to restrictor control.
Step 2. Use a 7/16 socket with long extension to adjust the restrictor dial according to the vent graph.
Step 3. Allow unit to warn up sufcently and make adjustment as needed.
Step 4. Allow unit to cool down and reinstall surround panel.
InItIal InstallatIon - allowable
42
Figure 55. Restrictor Setting 1Figure 54. Restrictor Setting 6
Page 43
9.00
B
Initial Installation
QUALIFIED INSTALLERS ONLY
hoRizontaL teRmination:
1. A minimum of 18”(NG) or 24”(LP) vertical rise before an elbow is required when
horizontally terminating with an approved venting cap.
2. Horizontal pipes must not be level. For every 12” (305 mm) of horizontal travel there
should be at least ¼” (6.4 mm) of vertical rise. Never allow the vent to run downward, as
this could cause high temperatures or even present the possibility of a re.
3. The exterior of the horizontal vent termination must not be blocked or obstructed.
4. If the vent termination is not
being attached to wood, the four wood screws provided should be replaced with material appropriate fasteners.
Wall Thimble Fire Stop
Horizontal Termination
5. For buildings with vinyl siding,
Wall Framing
a vinyl standoff should be installed between the vent cap
Elbow
and the exterior wall. Attach the vinyl siding standoff to the
horizontal termination. Note
that the termination screws
Exhaust Pipe
onto the at portion of the
standoff which provides an air space between the wall and
Combustion Air Outer Pipe
the vent termination. The air gap prevents excessive heat from possibly melting the vinyl siding.
6. Horizontal pipes must be supported every 3’ (914 mm).
Plumber’s “all round” strap will sufce.
Figure 56. Horizontal Vent Termination
7. When running horizontal pipe, clearances to combustibles must be maintained 1” (25 mm) sides, 1” (25 mm) bottom, 3” (76 mm) top, and 3” (76 mm) above elbow.
Step 1. Set the replace in the desired location. Check to determine if wall studs will be in the way when
the venting system is attached. If this is the case, the location of the replace may have to be
adjusted or the venting may have to be offset.
Step 2. Many direct vent pipe sections are designed with special twist-lock connections. Dry t the
desired combination of pipe and elbows to the appliance adaptor.
Step 3. With the pipe in the correct position and attached to the replace, mark the wall for a hole as
directed by specied wall thimble dimensions. Cut and frame the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is made of a non-combustible material
(i.e. masonry or concrete) a minimum 7 1/2” (191mm) hole is acceptable.
43
Page 44
Initial Installation
QUALIFIED INSTALLERS ONLY
Step 4. The vent pipe must extend into the vent cap at least 1¼” (320 mm). Secure the connection
between the vent cap and the pipe by attaching the two (2) sheet metal straps, which extend from the vent cap assembly to the outer wall of the vent pipe. Bend any remaining portion of
the strap back towards the vent cap.
Step 5. Position the horizontal vent termination in the center of the thimble and attach to the exterior
wall with the four screws provided. The arrow on the vent termination must be pointing up. Run a bead of high-temp silicone around the edges of the vent cap to make a seal with the wall.
Ensure the proper clearances to combustibles have been maintained.
VeRticaL teRmination:
Step 1. Check “InItIal InstallatIon - VentIng
clearances” for required clearances to
combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible
surfaces. Do not pack air spaces with
insulation.
Elbow Strap
Vertical
Termination
Storm Collar
Flashing
Step 2. Set the replace in the desired location.
Roofing nails
Drop a plumb bob down from the ceiling to the replace ue exit and
mark the location where the vent will
penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob
from the roof to the hole and mark the spot where the vent will penetrate the
roof. Determine if ceiling joists, roof
rafters, or other framing will obstruct the venting system. Relocate the
replace or offset the venting to avoid
cutting load bearing members.
Figure 57. Vertical Vent Termination
Step 3. To determine the length of pipe required, measure room height, ceiling thickness, and vertical
rise in an attic or second story. Firestops are required at each oor level beyond the rst oor ceiling support/wall thimble cover or cathedral ceiling support box. If an offset is required to avoid obstructions, use a pair of 45 degree elbows. For proper support, use elbow straps with
offsets. Use wall straps for long vertical runs. Attic insulation shield is required in attic.
Step 4. Measure roof pitch. Select the proper ashing and storm collar and determine the height above
the roof (see Figure 57). A non-corrosive pipe material must be used for all exterior pipe lengths. Seal nail heads with silicone.
44
Page 45
Initial Installation
H
Dimension ‘H’ obtained from table below
45° elbows (x2)
Wall strap
Plumbers tape connected to wal strap
QUALIFIED INSTALLERS ONLY
Table 8: Minimum ‘H’ for Figure 56.
Roof Pitch Minimum Height (H)
Feet Meters
Flat to 7/12 1 0.3
Over 7/12 to 8/12 1.5 0.46
Over 8/12 to 9/12 2 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4 1.22
Over 12/12 to 14/12 5 1.52
Over 14/12 to 16/12 6 1.83
Over 16/12 to 18/12 7 2.13
Figure 58: Height of Vertical Termination;
Reference Table 8
NOTES:
1. If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe every 3’ (914 mm) using wall straps to avoid excessive stress on the elbows.
Over 18/12 to 20/12 7.5 2.29
Over 20/12 to 21/12 8 2.44
2. Use 45° degree elbows instead of 90° degree elbows when ever possible. The 45° degree elbow offers less restriction to the ow of ue gases and intake air.
Figure 60: Use of Wall Straps.
Figure 59: Multi-Story Vent Pipe Installation
45
Page 46
Initial Installation
QUALIFIED INSTALLERS ONLY
Gas Line connection anD testinG:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.
GAS LINE CONNECTION
• This replace is equipped with a certied exible pipe located on the right side of the unit terminating in a 3/8” Male NPT tting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI Z223.1.
• The efciency rating of this appliance is a product thermal efciency rating determined under
continuous operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be disconnected from the gas supply piping system during any pressure testing where the pressure
exceeds ½ PSIG (3.45 KPa) or damage will occur
to the valve.
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or
less than ½ psig (3.45 KPa).
Always check for gas leaks with a soap and water solution after completing the required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the top right of the valve shown in Figure 56.
•Turn set screw 1 turn counter clockwise to loosen,
•Place
•Check pressures using a manometer.
•When nished, release pressure, remove hose & tighten set screw.
5
/16” (8 mm) I.D. hose over pressure tap system.
Stepper
Regulator
Pilot Adjustment
Screw
Pressure Tap
Figure 61: Fully Labeled Gas Valve.
Inlet
Pressure Tap
Manifold
Main Orice DMS# 36 DMS #52
Manifold Pressure 3.6” W.C. (0.89 KPa) 10.0” W.C. (2.49 KPa)
Min. Manifold Pressure 1.6” W.C. (0.39 KPa) 6.4” W.C. (1.59 KPa)
Max Supply Pressure 7.0” W.C. (1.74 KPa) 11.0” W.C. (2.74 KPa)
Min. Supply Pressure 4.5” W.C. (1.12 KPa) 10.4” W.C. (2.59 KPa)
Max BTU/hr Input 30,000 BTU/hr (8.79 KW) 30,000 BTU/hr (8.79 KW)
Min. BTU/hr Input 19,000 BTU/hr (5.57 KW) 23,000 BTU/hr (6.74 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
46
Table 9: Pressure and BTU Information.
Natural Gas Propane
Page 47
Initial Installation
QUALIFIED INSTALLERS ONLY
eLectRicaL RequiRements:
WARNING: The replace must be electrically connected and grounded in accordance with
local codes or, in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code Part 1, Safety Standards For Electrical Installations, or The National Electrical Code ANSI / NFPA 70 in the US.
WARNING: Disconnect electrical power supply before working on receptacle wiring.
CAUTION: When servicing controls, label all wires prior to disconnection. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing. If any of the original wire supplied with the appliance must be replaced, it must be replaced with 18 AWG wire with a temperature rating of 105°C.
Transmitter
Convection Fan
IFC
Main
Harness
To Battery Holder
885 Gas Valve
Main
On/Off
IPI Pilot
Flame Sensor
Spark Electrode
Power Cord
Figure 62: Proame 2 Wiring Diagram
47
Page 48
Initial Installation
QUALIFIED INSTALLERS ONLY
GLass meDia instaLLation:
Step 1. Remove surround panel and glass door (see “maIntenance anD serVIce” section).
Step 2. Spread the glass media provided out on the media tray. Create a thin and uniform layer over
the tray bed. Caution: Avoid excessive amount of media in front of the pilot.
Pilot
48
Figure 63: Glass Media Install
Page 49
Troubleshooting
Table 10: Troubleshooting
Problem Possible Cause Solution
· Turn the system off by pressing the ON/OFF button on
the transmitter
· After approximately 2 seconds press the ON/OFF button
on the transmitter again.
Locking conditions
Main burners will not start
Reset the Proame IFC board
The pilot ame has gone out · See “Pilot will not remain lit”
The remote control is not working correctly
The thermostat is disconnected or set too high
Problem with thermopile circuit
· In the manual ame control mode, use the down arrow button to reduce the ame to off, indicated by the word OFF displayed on the transmitter LCD screen.
· Wait approximately 2 seconds and press the up arrow
button, the ignition sequence will start.
· Replace the batteries
· Set the thermostat to a lower temperature
· Check gas line pressure
· Check wiring to thermostat for breaks
· Check for ame impingement on thermopile
Flame lifting
Blue Flames
Glass fogs up
Flames are burning
“dirty” or
sooting
Leak in vent pipe · Check for leaks in vent connections
Improper vent conguration · Check vent conguration with manual
· Check to see if terminal is on correctly
Terminal may be re-circulating ue
gases
The heater has just been started
Improper air shutter adjustment · Adjust air shutter – contact your dealer
Normal condition: after the
appliance warms up the glass will be clear.
The logs are placed incorrectly · Check log positioning
Improper air shutter adjustment
Incorrect rating input
· May need to install high wind termination cap.
· Contact dealer
· Normal during start up: ame will yellow as the replace
heats up
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
· Increase primary air by opening the air shutter and/or by
opening the vent restrictor
· Check for proper venting and blockage of the vent
termination
· See also “Burners will not remain lit”
· Check manifold pressure and clock input rating for over­ring
49
Page 50
Parts List
4 G39 Safety Screen 50-3578
7 G39 Non-Combusble Board 50-3635
11 Porcelain Liners 50-3498
- G39 Door Complete (ceramic) 50-3564
Table 11: Parts List
Reference # Part Descripon Part #
1 Convecon Fan Only 50-3577 2 Glass Burner Pan 50-3586 3 S.I.T IPI Valve 50-2682
5 PSE IPI Pilot Assembly 50-3026 6 G39 Door Complete (tempered) 50-3583
- G39 Door Glass w/ Gasket ONLY (tempered) 50-3584
8 Enamelled Media Tray 50-3637 9 Integrated Fireplace Controller (IFC) 50-3312 10 Proame 2 Remote Transmier 50-3028
Table 12: Opons List
12 G39 Slim Face - Black Painted 50-3430
- G39 Slim Face - Grey Powdercoat 50-3431
- G39 Slim Face - Bronze Powdercoat 50-3537
- G39 Slim Face - Silver Powdercoat 50-3432
- G39 Slim Face - Nickel Plated 50-3570
- G39 Slim Face - Copper Plated 50-3569
- G39 Forgeworks Face - Midnite Bronze 50-3501
- G39 Driwood Log Set 50-3575
- BDM Flex Vent Kit - 5FT 50-3461
- BDM Flex Vent Kit - 10FT 50-3462
- 12 oz. Can of Metallic Black Touch Up Paint PAINT-12-MB
50
Page 51
Parts Diagram
1
2
3
5
6
4
11
12
10
9
8
7
51
Page 52
Notes
52
Page 53
Warranty for Enviro Gas Products
Sherwood Industries Ltd. (Sherwood”) hereby warrants, subject to the terms and conditions herein set forth, this product against defects in material and workmanship during the specified warranty period starting from the date of original purchase at retail. In the event of a defect of material or workmanship during the specified warranty period, Sherwood reserves the right to make repairs or to assess the replacement of a defective product at Sherwood’s factory. The shipping costs are to be paid by the consumer. All warranties by Sherwood are set forth herein and no claim shall be made against Sherwood on any oral warranty or representation.
Conditions
 A completed warranty registration must be submitted to Sherwood within 90 days
of original purchase via the online warranty registration page or via the mail-in warranty registration card provided. Have the installer fill in the installation data sheet in the back of the manual for warranty and future reference.
 This warranty applies only to the original owner in the original location from date of
install.
 The unit must have been properly installed by a qualified technician or installer, and
must meet all local and national building code requirements.
 The warranty does not cover removal and re-installation costs.
 Sherwood Industries Ltd. reserves the right to make changes without notice.
 Sherwood Industries Ltd. and its employees or representatives will not assume
any damages, either directly or indirectly caused by improper usage, operation, installation, servicing or maintenance of this appliance.
 A proof of original purchase must be provided by you or the dealer including serial
number.
 This warranty does not cover any discoloration of the safety screen mesh.
Exclusions
An expanded list of exclusions is available at www.enviro.com/help/warranty.html
This warranty does not cover:
 Damage as a result of improper usage or abuse.
 Damage caused from over-firing due to incorrect setup or tampering.
 Damage caused by incorrect installation.
To the Deale r
 Provide name, address and telephone number of purchaser and date of purchase.
 Provide date of purchase. Name of installer and dealer. Serial number of the
appliance. Nature of complaint, defects or malfunction, description and part # of any parts replaced.
 Pictures or return of damaged or defective product may be required.
To the Distrib utor
 Sign and verify that work and information are correct.
Sherwood Industries Ltd.
6782 Oldfield Road, Victoria, BC . Canada V8M 2A3
Online warranty registration: www.enviro.com/warranty/
Category One Year Two Year Limited Lifetime (7yr)
1,2
Parts
(unit serial number required)
Firebox Liner Panels
3
Firebox
Heat Exchanger
Burner
Ceramic Logs
Ceramic Glass
Pedestal / Legs
4
5
(excluding finish)
Door Assembly
Surround Panels
Exterior Panels
(excluding finish)
(excluding finish)
Electrical Components
Exterior Surface Finishing
Labour
1
Whereas warranty has expired, replacement parts will be warrantied for 90 days from part purchase date. Labour not included.
 
Unit serial number required.
2
Westport Fan Kit covered for up to 5 years from purchase date. Labour not included. Unit serial required.
3
Excluding damage to the finish caused by improper setup of the appliance, or color changes.
4
Log set and panels excludes wear and tear or breakage caused by cleaning or service.
4
Glass is covered for thermal breakage. Photos of box, inside of door, and unit serial # must be supplied for breakage due to shipping.
6
Exterior Surface finishing covers plating, enamel or paint and excludes colour changes, chipping, and fingerprints.
Travel costs not included.
 
   
  
Up to 5 years
Apr 2 018
53
Page 54
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
MODEL:___________________________________
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________ (dd/mm/yyyy)
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
_________________________________________
DATE OF INSTALLATION:___________(dd/mm/yyyy)
NATURAL GAS (NAT) PROPANE(LPG)
INLET GAS PRESSURE:_________in wc
MAIN BURNER ORIFICE:__________# DMS
PILOT ORIFICE #_________OR________in diam.
INSTALLER’S SIGNATURE:
_________________________________________
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
www.enviro.com
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
August, 2018
C-15561
54
Loading...