WARNING: If the information in this manual is not followed exactly, a
re or explosion may result causing property damage, personal injury
or loss of life. Installation and service must be performed by a qualied
4001609
Version Française: www.enviro.com/fr.html
installer, service agency or the gas supplier.
1
50-3520
Page 2
Safety Precautions
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other ammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Leave the building immeadiately.
• Immeadiately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
- Installation and service must be performed by a qualied
installer, service agency or the gas supplier.
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certied kit is used.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or
gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code
requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed;
only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon
monoxide detector is required in all rooms containing gas red direct vent appliances. The replace
damper must be removed or welded in the open position prior to installation of a replace insert.
2
Page 3
Safety Precautions
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and shall
individuals.
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER,
PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas-red appliances must be installed in
accordance with their instructions. Carefully read all the
instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for a
permit prior to commencing the installation.
• NOTE: Failure to follow these instructions could cause
a malfunction of the replace, which could result in death,
serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your
re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a qualied
service person. The appliance should be inspected before
the rst use and, at least, annually by a qualied service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative the control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• Due to high temperatures, the appliance should be
located out of high trafc areas and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when
in the same room as the appliance. Toddlers, young
children and others may be susceptible to accidental
contact burns. A physical barrier is recommended if there
are at risk individuals in the house. To restrict access to a
replace or stove install an adjustable safety gate to keep
toddlers, young children and other at risk individuals out of
the room and away from hot surfaces. Any safety screen,
guard, or barrier removed for servicing an appliance must
be replaced prior to operating the appliance.
• Clothing or other ammable materials should not be
placed on or near the appliance.
• A barrier designed to reduce the risk of burns from the
hot veiwing glass is provided with this appliance and shall
be installed for the protection of children and other at-risk
individuals. If the barrier becomes damaged, the barrier
shall be replaced with the manufacturer’s barrier for this
appliance
FOR YOUR SAFETY
• Installation and service must be performed by a qualied
installer, service agency or gas supplier.
• This installation must conform to local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1.
• To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
• To prevent injury, if the pilot or pilot and burners
have gone out on their own, open the glass door and
wait 5 minutes to air out before attempting to relight the stove.
• Always keep the area around these appliances clear of
combustible material, gasoline and other ammable liquids
and vapours.
• These appliances should not be used as a drying rack for
clothing or for hanging Christmas stockings/decorations.
• Due to the paint curing on the stove, a faint odor and slight
smoking will likely be noticed when the stove is rst used.
Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another
room or inside the building. Make sure the specied vent
pipe is used, properly sized and of adequate height to
provide sufcient draft. Inspect the venting system annually
for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts specically approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or qualied service person.
• Never use solid fuels such as wood, paper, cardboard, coal,
or any ammable liquids, etc., in this appliance.
• Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system or
any gas control which has been under water.
• Do not abuse the glass by striking it or slamming the door
shut.
• If the EX32 unit is pulled out of its installation, and the
vent-air intake system is disconnected for any reason,
ensure that the vent-air intake pipes are reconnected and
re-sealed in accordance to the instructions noted in
Installation Data Sheet...................................................................................................44
4
Page 5
Codes And Approvals
DIRECT VENT: This type is identied by the sufx DV. This appliance draws all of its air for combustion from
outside the dwelling, through a specially designed vent pipe system.
This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas Association
guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000
(610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level. Refer also to local authorities
or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high altitude
rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
• This appliance has been tested by INTERTEK and found to comply with the established VENTED GAS
FIREPLACE HEATER standards in CANADA and the USA as follows:
DIRECT VENTED GAS FIREPLACE INSERT HEATER
TESTED AND LISTED TO: ANSI Z21.88-2016/CSA 2.33-2016 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 (R2009) GAS FIRED APPLIANCES FOR HIGH ALTITUDES BY OMNI-TEST LABORATORIES
CSA P.4.1-2015 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This ENVIRO EX32 Fireplace Insert:
• Has been certied for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a permanent wall thermostat
for bedroom installations. Consult the authority having local jurisdiction in your area. IN USA: see current ANSI
Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current installation code CAN/CGA B149 in
Canada or ANSI Z223.1/NFPA 54 in the USA.
• Must be properly connected to an approved venting system and not connected to a chimney ue serving a
separate solid-fuel burning appliance.
• Is not approved for closet or recessed installations.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned on for
the rst time, it should be turned onto high without the fan on for the rst 4
hours. This will cure the paint, logs, gasket material and other products used in
the manufacturing process. It is advisable to open a window or door, as the unit
will start to smoke and can irritate some people. After the unit has gone through
the rst burn, turn the unit off, let the unit get cold then remove the glass door
and clean it with a good gas replace glass cleaner, available at your local ENVIRO
dealer. See “Door remoVal” and “CleanIng the glass” sections.
COLD CLIMATES:
NOTE: In cold climates, additional insulation may be used on some venting. It is
recommended in cold climates to wrap the exhaust and intake venting for the nal
few feet before termination.
5
Page 6
19
13
16
"
504
28
5
8
" [728]
14
7
8
"
377
25
5
16
" [643]
27
1
2
" [699]
18
1
8
" [460]
13
3
16
"
336
14
1
4
"
363
17
5
8
" [447]
21
3
16
"
538
16" [406]
18
1
2
"
469
Specifications
Rating LabeL Location:
The rating label is located in the bottom of the unit.
Dimensions:
*Shown with
Contemporary
surround*
instaLL Depth:
The EX32 has a minimum install depth of 16” (406mm). The table below shows what depth of
install is required with each surround panel.
Surrround PanelRequired Install Depth
Contemporary
Extruded Plus
Borderview Plus
Modern Plus
6
Figure 1: EX32 Exterior Dimensions.
Extruded
Borderview
Table 1: Install Depths
16” (406mm)
17 1/4” (438mm)
Page 7
Specifications
39
5
8
"
41
5
8
"
25"
27
3
8
"
Figure 2: EX32 Contemporary Surround with Base Shelf and Riser.
Table 2: EX32 Options Dimensions.
Contemporary SurroundExtruded Surround
Height25” (635mm)25” (635mm)
7
Width39
Trimmable
Surround
/8” (1013 mm)39 7/8” (1013 mm)
HeightWidth
38” (965mm)46” (1168mm)
Base ShelfBase Shelf Riser
Height1 ⅝” (41mm)2 ⅛” (54mm)
Width41
DepthBottom 4 ⅞” (112mm); Top 3
5
/8” (1057mm)40 1/4” (1022mm)
13
/16” (97mm)3 11/16” (94mm)
Table 3: Elite Surround Options
Surround Borderview PlusBorderview Plus
Height26.125” (665mm)26.125” (665mm)
Width40” (1016mm)40” (1016mm)
SurroundBorderview Plus 4-SidedModern Plus
Height31” (785mm)25.375” (645mm)
Width40” (1016mm)38.5” (725mm)
SurroundExtruded PlusE30 Hearth Riser
Height26.125” (665mm)2” (50mm)
Width40” (1016mm)43.5” (1105mm)
7
Page 8
Operating Instructions
For Your Safety, Read Safety Precautions And Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION
MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
LightinganD tuRning off instRuctions:
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to
light the pilot by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fire department.
OPERATING INSTRUCTIONS
C. Use only your hand to push in or
turn the gas control knob. Never
use tools. If the knob will not push
in or turn by hand, don’t try to
repair it, call a qualified service
technician. Force or attempted
repair may result in a fire or
explosion.
D. Do not use this appliance if any
part has been under water.
Immediately call a qualified service
technician to inspect the appliance
and to replace any part of the
control system and any gas control
which has been under water.
1. STOP! Read the safety information above on this label.
2. Read the owner's manual including the section on
"Remote Control" operation.
3. Set the thermostat to the lowest setting.
4. Turn off all electric power to the appliance.
5. Do not attempt to light the pilot by hand.
6. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas, STOP!
Follow "B" in the safety information above on this label.
If you don't smell gas, go to the next step.
7. Turn on all electric power to the appliance.
8. Using the remote control, set
thermostat to desired setting, or
press the ON/OFF key on the
remote. "ON" will be indicated on the
display of the remote and an audible
"beep" will be heard at the unit to
indicate the command has been
received.
Blue LCD Display
9. This appliance is equipped with a
completely automatic ignition and
lighting control. The control will
attempt to light the pilot several
times if necessary. If it is
unsuccessful, it will discontinue
operations. If the appliance will
not operate, follow the
instructions "To Turn Off Gas To
Appliance" and call your service
technician or gas supplier.
ON/OFF Key
Blue LCD Display
Thermostat Key
Mode Key
ON/OFF Key
THERMOSTAT Key
UP/DOWN Arrow Key
MODE Key
UP/Down
Arrow Key
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting, or press the ON/OFF Key. "OFF" will be indicated on the display
and an audible "Beep" will be heard at the unit to indicate the command has been received.
2. Turn off all electric power to the appliance if service is to be performed.
C-12455
8
Figure 3: Lighting instruction label.
Page 9
Operating Instructions
VentuRi aDjustment:
The venturi adjustment lever is located on the right side of the unit, below the door (see Figure 4).
The venturi allows the amount of air coming into the replace to be adjusted in order to accommodate
different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot
ame is burning normally and none of the burner ports are plugged. Let the replace burn for roughly
fteen (15) minutes and then examine the ames. The ideal ame will be blue at the base and light
orange above. The ames should be of medium height. If
the ames look like this, no venturi adjustment is needed.
If the ames are fairly short and mostly blue, the replace
Less Air
Figure 4: Adjusting the venturi air setting.
More Air
is getting too much air. Therefore, the air shutter should
be closed (push left) slightly until the correct ames are
achieved. Flames that are very orange, with tall dark
stringy tips are not getting enough air. Open (push right)
the venturi until the ames clean up. If the venturi is
opened, then closed all the way, and the correct ames
cannot be attained, turn off the gas and contact the
dealer.
Warning: Incorrect venturi adjustment may lead to improper combustion, which is a safety hazard.
Contact the dealer if there is any concern about the venturi adjustment.
Operating Instructions
noRmaL sounDs DuRing opeRation:
ComponentSound & Reason
Fire BoxCreaking when heating up or cooling down.
BurnerLight pop or poof when turned off; this is more common with LP units.
Pilot FlameQuiet whisper while the pilot ame in on.
Blower / FanAir movement that increases and decreases with the speed of the blower.
Gas Control ValveDull click when turning on or off, this is the valve opening and closing.
IFCBeeps when remote control buttons are pressed.
Table 4: Normal Sound
Remote contRoL opeRations:
The Proame 2 GTMFLSA is a modular remote control system that directs the functions of the EX32.
The Proame 2 GTMFLSA is congured to control the on/off main burner operation, its ame levels and
provides on/off and Smart thermostatic control of the appliance. The system controls a remotely actuated
top light, as well as bottom lights and fan speed each through six (6) levels.
9
Page 10
Operating Instructions
Blue Back lit LCD display
UP/D O W N Arrow Key
ON/OFF Key
THERMOSTAT Key
MODE Key
system DescRiption:
The Proame 2 Remote Control System consists of two (2) elements:
1. Proame 2 Transmitter.
2. Integrated Fireplace Controller (IFC) and wiring harness to connect to the gas valve, stepper motor
battery holder, convection fan, and lights.
ATTENTION!
- TURN “OFF” THE MAIN GAS SUPPLY OF THE APPLIANCE DURING INSTALLATION OR
MAINTENANCE OF THE IFC.
- TURN “OFF” MAIN GAS SUPPLY TO THE APPLIANCE PRIOR TO REMOVING OR REINSERTING
THE BATTERIES IN THE BATTERY HOLDER
technicaL Data
Transmitter (Remote Control):
Supply voltage: 4.5 V (three 1.5 V AAA batteries)
Radio frequency: 315 MHz
Integrated Fireplace Controller (IFC):
Supply voltage: AC IN - 120 V / 60 Hz
Battery Backup IN - 6 Vdc - 200mA (four 1.5 V AA batteries)
Spark voltage / frequency: >10kV / 1Hz
Comfort modulating fan: 120 V / 60 Hz / 2A
Auxiliary: 120 V / 60 Hz / 5A
tRansmitteR:
The Proame 2 Transmitter is a remote control with a blue backlit lcd display. It uses a streamline design with
a simple button layout and informative lcd readout (Figure 5). The Transmitter is powered by three (3) AAA
type batteries. A Mode Key is provided to Index between the features and a Thermostat Key is used to turn
on/off or index through Thermostat functions (Figure 5 & 6).
Figure 5: Proame 2 Transmitter.
10
Page 11
Low battery alarm
Key Lock
Room
Temperature
Dimmer ON
Set Point
Temperature/Level/State
Flame ON
Thermostat OFF/
ON/SMART
Comfort fan
Transmission
Split Flow
Aux ON
CPI mode
Operating Instructions
[NotusedoN eX32]
integRateD fiRepLace contRoLLeR (ifc):
The Proame 2 IFC (Figure 7) connects directly to the gas valve, stepper motor, pilot, covection fan, and accent
lights with wiring harnesses. The IFC is mainly powered by 120 VAC but can also run off a battery backup four
(4) AA type batteries for shorter periods of time. The IFC accepts commands via radio frequency from the
Transmitter to operate the appliance in accordance with the particular Proame 2 system conguration. The
IFC has a red reset button at the front right corner that is used is to synchronize the Transmitter when using
the for the rst time, or after the batteries have been replaced.
Figure 6: Proame 2 Transmitter LCD Screen.
Reset Button
Figure 7: Integrated Fireplace Controller
11
Page 12
Operating Instructions
RoomTemperature
SetTemperature
ThermostatON
opeRating pRoceDuRe:
Initializing The System For The First Time
Install the four (4) AA batteries into the IFC battery holder. Note the polarity of the battery and insert into the battery
bay as indicated on the body of the battery holder. Press and release the reset button (see Figure 7).
The IFC will “beep” three (3) times to indicate that it is ready to synchronize with a Transmitter. Install the three (3)
AAA type batteries in the Transmitter battery bay, located on the base of the Transmitter. With the batteries already
installed in the Transmitter, push the ‘ON’ button. The IFC
will “beep” four (4) times to indicate the Transmitter’s
command is accepted and sets to the particular code of
that Transmitter. The system is now initialized.
Temperature Indication Display
With the system in the “OFF” position, press the
Thermostat Key and the Mode Key at the same time.
Look at the LCD screen on the transmitter to verify that
a °C or °F is visible to the right of the Room Temperature
display (see Figure 8).
Turn on the Appliance
Press the ON/OFF Key on the Transmitter. The Transmitter display will show all active Icons on the screen. A single
“beep” from the Receiver will conrm reception of the command and will commence to rst ignite the pilot light,
followed by the main burner. This should take about 10 seconds to complete.
Figure 8: Remote Control Display in Farenheit and Celcius.
Turn off the Appliance
Press the ON/OFF Key on the Transmitter. The Transmitter LCD display
will only show the room temperature and Icon (see Figure 9). A single
“beep” from the IFC conrms reception of the command and both the
pilot light (if the unit is not set to continuous pilot) and main burner will
turn off.
Room Thermostat (Transmitter Operation)
The Remote Control can operate as a room thermostat. The thermostat
can be set to a desired temperature to control the comfort level in a
room. To activate this function, press the Thermostat Key (see Figure
5). The LCD display on the Transmitter will change to show that the
room thermostat is “ON” and the set temperature is now displayed (see
Figure 9). To adjust the set temperature, press the Up or Down Arrow
Keys until the desired set temperature is displayed on the LCD screen
of the Transmitter.
Smart Thermostat (Transmitter Operation)
The Smart Thermostat function adjusts the ame height in
accordance to the difference between the set point temperature
and the actual room temperatures. As the room temperature
gets closer to the set point the Smart Function will modulate
the ame down. To activate this function, press the Thermostat
Key (Figure 5) until the word “SMART” appears to the right
of the temperature bulb graphic (Figure 10). To adjust the
set temperature, press the Up or Down Arrow Keys until the
desired set temperature is displayed on the LCD screen of the
Transmitter.
Figure 9: Remote Control Displays
Set Temperature.
Figure 10: Remote Control’s Smart Flame Function.
12
Page 13
Operating Instructions
FlameOff
FlameLevel1
FlameLevel5
MaximumFlameLevel
FlameOff
FlameLevel1
Remote Flame Control
The Proame 2 GTMF has six (6) ame levels. With the system on, and the ame level at the maximum in the
appliance, pressing the Down Arrow Key once will reduce the ame height by one step until the ame is turned off.
The Up Arrow Key will increase the ame height each time it is pressed. If the Up Arrow Key is pressed while the
system is on but the ame is off, the ame will come on in the high position (refer to Figure 11 below). A single “beep”
will conrm reception of the command.
Figure 11: Remote Control’s Flame Levels.
Fan Control
The EX32 comes with a convection fan that can be
controlled with the Transmitter. The fan speed can be
adjusted thorugh six (6) speeds. To control the fan
press the MODE key (Figure 5) to index to the fan
control icon (Figure 12). Use the UP/DOWN arrow
keys to turn on, off, or adjust the fan speed (Figure
12). A single beep from the IFC will conrm the
command has been received
Ember Lights Control
The ember lights at the front of the replace can
be controlled with the Transmitter. The lights can
be adjusted thorugh six (6) levels. To adjust the
brightness of the lights press the MODE key (Figure
5) to index to the light control icon (Figure 13). Use
the UP/DOWN arrow keys to turn on, off, or adjust
the brightness (Figure 13). A single beep from the
IFC will conrm the command has been received.
Figure 12: Fan Control
Figure 13: Bottom Light Control
13
Page 14
Operating Instructions
Split Flow Control
This function is not used on the EX32 and can be
disregarded.
Top Light Control
For added ambiance the EX32 also has a light at the
top of the replace that can be controlled with the
Transmitter. The light is non-adjustable but can be
turned on and off as desired. To control the top light
press the MODE key (Figure 5) to index to the AUX
control icon (Figure 15). Use the UP/DOWN arrow
keys to turn the light on or off. A single beep from
the IFC will conrm the command has been received.
The top light is most noticable when the ame is set
to the lowest setting. It can also be left on when the
ame is off (see remote Flame Control section) to
highlight the log set.
Figure 14: Split Flow Control
Figure 15: Aux (Top Light) Control
Key lock
This function will lock the keys to avoid unsupervised operation. To activate this
function, press the MODE and UP keys at the same time and the a lock will appear
(see Figure 16). To de-activate this function, press the MODE and UP Keys at the
same time.
14
Figure 16: Remote Control
Locked.
Page 15
Operating Instructions
Low Battery Power Detection
Transmitter: The life span of the remote control batteries depends on various factors:
quality of the batteries used, the number of ignitions of the appliance, the number of
changes to the room thermostat set point, etc. When the Transmitter batteries are
low, a Battery Icon will appear on the LCD display of the Transmitter (see Figure
17) before all battery power is lost. When the batteries are replaced this Icon will
disappear.
IFC: The life span of the IFC batteries depends on various factors during a prolonged
power outage: quality of the batteries used, the number of ignitions of the appliance,
the number of changes to the room thermostat set point etc. When the IFC batteries
are low, No “beep” will be emitted when it receives an On/Off command from the
Transmitter. This is an alert for a low battery condition for the IFC. When the batteries
are replaced the “beep” will be emitted from the Receiver when the ON/OFF Key is
pressed (See InItIalIzIngthe systemForthe FIrst tIme).
Switching to Continuous Pilot Mode
When the replace is turned off press the mode
key to index to the constant pilot (CPI) mode icon
(see gure 6). Pressing the up arrow key will select
Continuous Pilot Ignition (CPI) and pressing the down
arrow key will return to IPI. Once a selection is made
the IFC will beep once to conrm it had received the
command. NOTE: It is recommended to use the
continuous pilot mode during the winter when
the outside temperature is below 50°F (10°C)
to keep the chimney properly heated for updraft
during burner ignition. Continuous pilot mode also
keeps the rebox warm which eliminates both heat
loss to cold air that is trapped inside the rebox as
well as excessive exhaust vapour condensation on
the door glass.
NOTE: USE OF CPI PILOT MODE NOT PERMITTED IN BC OR AB
Figure 18: CPI Pilot Mode
Figure 17: Low Battery
Indicator.
WARNING: Fire Hazard. Can cause severe injury or death. The IFC causes ignition of the appliance.
The appliance can turn on suddenly. Keep away from the appliance burner when operating the remote
system.
WARNING: Shock Hazard. Can cause severe injury or death. This device is powered by line voltage. Do
not try to repair this device. In no way is the enclosure to be tampered with or opened. Disconnect from
line voltage before performing any maintenance.
CAUTION: Property Damage Hazard. Excessive heat can cause property damage. The appliance can stay
lit for many hours. Turn off the appliance if it is not going to be attended for any length of time. Always
place the Transmitter where children cannot reach it.
15
Page 16
Maintenance And Service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specically approved with this appliance, may result in property damage or personal injury.
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not
blocked by anything. The pilot ame should be blue with little or no yellow on the tips.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied person.
cLeaning the painteD suRfaces:
Painted surfaces should be periodically wiped with a damp cloth when the unit is cool.
gLass DooR RemoVaL:
16
Figure 19-A: Door Spring Latch Locations
Figure 20: Door Removal
Figure 19-B: Door Latch Release.
The glass door of the replace is retained at the top
by two spring latches as shown in Figure 18. Release
the latches by placing the hooked end of the door
tool in the hole on the door latch mechanism (see
Figures 19-A,B) and pulling the latch forward then
out to the side. When the two (2) latches have been
released, tilt the top of the door forward and lift up
to remove the door (Figure 20). To re-install the
glass door simply reverse the procedure.
Warning: Do not touch or attempt to remove the
glass if the replace is not completely cool.
Never operate the replace with the glass
removed.
CAUTION GLASS MAY SEPARATE FROM DOOR.
Page 17
Maintenance And Service
cLeaning the gLass:
When the replace is cool, remove the glass door. See maIntenanCeanD serVICe - glass Door remoVal.
Check the gasket material on the back of the glass, making sure that it is attached and intact.
During a cold start up, condensation will form on the glass. This is a normal condition with all replaces.
However, this condensation can allow dust and lint to cling to the glass surface. Initial paint curing of the
appliance can leave a slight lm on the glass. The glass will need cleaning after the replace has cooled
off from the rst burn and about two weeks after rst burn. Use a mild glass cleaner and a soft
cloth. Abrasive cleaners will damage the glass and painted surfaces. Depending on the amount
of use, the glass should require cleaning no more than two or three times a season. Do not clean the
glass when it is hot.
cLeaning the fiRebox:
Remove the logs carefully, as they are very fragile. Gently remove all the embers and rock wool and
place on a paper towel. Vacuum the bottom of the rebox thoroughly. Carefully clean any dust off the
logs and remove any lint from the burner and pilot. At this time, inspect the burner tube for cracking or
severe warping. If a problem is suspected, contact the dealer. Check the logs for deterioration or large
amounts of soot; a small amount on the logs is normal. Replace the logs and embers as in the seConDary
InstallatIon - log setanD ember InstallatIon section. If new/more embers and rock wool are required,
contact your nearest ENVIRO dealer.
RepLacing the gLass:
The glass in the replace is a high temperature ceramic. If the glass is damaged in any way, a factory
replacement is required (see Parts lIst). Wear gloves when handling damaged glass door assembly
to prevent personal injury. Do not operate with the glass front removed, cracked or broken. Removal
and replacement of the glass from the door must be done by a licensed or qualied service person.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
Remove the door (see page 16). The replacement glass will come with a new gasket installed. Remove
any silicone remnants from the door. Apply high temperature silicone to the two vertical faces of the
door and install the new piece of glass with gasket (be sure to maintain edge clearances). Apply even
pressure to the glass to allow the silicone to adhere to the gasket material.
check piLotanD buRneR fLames:
Periodically do a visual check of the pilot ames. One ame should encompass the ame sensor and the
other should burn over the burner ports (see Figure 24, page 21). Also check that the burner is operating
correctly, refer to Venturi Adjustment section.
17
Page 18
Maintenance And Service
buRneR RemoVaL:
The burner may need to be removed for a few reasons, including cleaning under the burner,
converting the unit to a different gas type, or to replace the burner altogether. Proceed only
when the unit has completely cooled down.
1. Remove the glass door as shown in
maIntenanCeanD serVICe - glass Door
remoVal.
2. Carefully remove the log set and embers
as shown in seConDary InstallatIon - log
set InstallatIon.
3. Remove the four log tray screws using a
T20 screwdriver, then remove the log tray.
4. Unscrew the two rear burner screws
using a T20 screwdriver.
5. Unscrew the front center burner bolt
using a 5/32” Allen key.
6. Slide the burner to the left and then lift
up to remove it.
To re-install the burner repeat the steps
above in reverse.
Log Tray
Burner
Figure 21: Burner Removal.
18
Page 19
Maintenance And Service
A
embeR Lights - buLb RepLacement:
The front ember light assembly consists of 5 halogen bulbs. Over time, should one of these bulbs
require replacement follow the steps below for the proper procedure. Proceed only when then
replace has been turned off and has completely cooled down.
Note: Gloves should be worn to avoid
skin contact with halogen bulb. Oil on
the bulb from skin contact will greatly
reduce the life span of the bulb.
1. Using the transmitter, turn off the
ember lights (see page 13)
2. Remove the burner as outlined in
maIntenanCeanD serVICe - burner
remoVal.
3. Remove the light tray by simply lifting
up and out.
4. Replace the burnt out bulb with the
extra bulb supplied with the replace.
Light Tray
5. Use the transmitter to conrm all bulbs
light up.
6. Re-install the light tray and burner.
Figure 22: Burner Removal.
top Light - buLb RepLacement:
The top light assembly is screwed into the top of rebox, behind the bafe, and consists of a
single halogen bulb behind a glass lens. Over time, dependant on the amount of use, the bulb
may require replacement. Should this occur contact your local dealer for service.
Halogen Bulb
19
Page 20
Maintenance And Service
fueL conVeRsion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualied service agency in accordance
with the manufacturer’s instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed
exactly, a re, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualied service agency is responsible for
the proper installation of this kit. The installation is not proper or complete until the
operation of the converted appliance is checked as specied in the manufacturer’s
instructions supplied with the kit.
Kit Parts List for all EX32 models:
1 - Orice (NG: #37) or (LP: #52) 1 - Servo Regulator with diaphragm
Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are
missing, contact your dealer, distributor or courier company to have them replaced before starting this
installation.
Conversion Kit Installation:
1. Turn the unit off by pressing the ON/OFF Key on the remote and shut off gas supply at the shut-off
valve upstream of the unit. CAUTION: The gas supply must be shut off prior to disconnecting the
electrical power and before proceeding with the conversion. Allow the valve and unit to cool down
to room temperature.
2. Remove the glass door as shown in the maIntenanCeanD serVICe - glass Door remoVal.
3. Carefully remove the log set.
4. Remove the burner as shown in
maIntenanCeanD serVICe - burner remoVal.
5. Convert the pilot injector (see Figure 23):
a) Using a
1/4 turn counter-clockwise
b) Push the slider with your nger or at head screwdriver
- Natural Gas is marked NAT.
- Propane gas is marked LP with an indicating hole
between L and P. It is also marked red.
c) Turn the pilot head a 1/4 turn clockwise
back to its original position.
7
/16” wrench, turn the pilot head a
Figure 23. Pilot Slider set to LP
6. Convert the burner orice:
a) Remove the main burner orice with a 1/2” deep socket
b) Put a bead of pipe-thread sealant into the orice mount. DO NOT OVER-TIGHTEN
20
c) Install new orice.
Page 21
Maintenance And Service
7. Convert the SIT gas valve:
a) Use a T-20 driver to remove the two screws that hold the servo regulator to the gas valve and
disconnect the wire harness from the IFC.
b) Remove the rubber regulator diaphragm that is situated between the servo regulator and the valve
body. The new servo regulator already has this diaphragm installed.
c) Install the LP servo regulator, with the new longer T-20 screws included in the kit and connect the
harness to the IFC.
8. Reinstall the burner, log set, and glass door. Also refer to seConDary InstallatIon - log set InstallatIon
in your Owner’s Manual. When re-installing the burner, ensure that the burner to pilot hood and
shield relationship is similar to what is shown in Figure 24.
9. Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the
unit.
10. Reconnect the electrical power to the unit.
11. Use a small brush to apply a warm soapy water
solution to all gas connections (use a half dish soap
and half warm water). If a gas leak is present,
bubbling will occur. Gas leaks can be repaired by
using an approved pipe thread sealant or approved
Teon tape. NEVER USE AN OPEN FLAME WHEN
TESTING FOR LEAKS.
12. Relight the pilot and conrm the ame properly
covers the ame sensor (see Figure 24). Should
the pilot require adjustment, turn the adjustment
screw (gure 34, page 29) clockwise to decrease
or counterclockwise to increase until the correct
ame is achieved.
13. Relight the main burner in both the “MAX” and low positions to verify proper burner ignition, operation
and proper ame appearance (gure 51, page 36). Conrm the inlet and manifold pressures are
within the acceptable ranges as directed in section
testIng. If the EX32 has been installed at an altitude higher than 2000ft (610m) it is required to
de-rate the unit accordingly:
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
14. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the unit
has been converted to a different fuel type.
IntIal IntallatIon - gas lIne ConneCtIonanD
Figure 24. Correct Pilot
21
Page 22
Initial Installation
42”
41”
40”
39”
38”
37”
36”
35”
34”
33”
1 2 3 4 5 6 7 8 9 10 11 12
M A N T L E H E I G H T
( F R O M U N I T B O T T O M )
M A N T L E D E P T H
Minimum Mantle Clearances
12” MANTLE
INSTALLATION
NOT PERMITTED
WARNING: Operation of this heater when not connected to a properly installed and maintained
venting system can result in carbon monoxide (CO) poisoning and possible death.
cLeaRancesto combustibLes:
Maintain sufcient clearances for operation, service
and maintenance.
• A minimum distance of 21” (533 mm) is required
from the centerline of the unit to the sidewalls.
• Minimum clearance for any combustible facing is
33” (762 mm) from the bottom of the unit.
• A 12” (305 mm) wide mantel can be mounted
at a minimum height of 42” (107 cm) from the
bottom of unit.
• If installed at oor level there must be a minimum
of 9” (229 mm) of non-combustible material in
front of the unit. Once unit is rasied 2” (51 mm)
or more no oor protection is required.
• Unit may be installed with combustible material
underneath as long as it is raised 1/2” (13 mm)
off the oor.
• Minimum ceiling clearance is 54” (137 cm) from
bottom of unit.
Figure 25: Mantle width and height.
minimum fiRepLace size:
Table 5: Minimum dimensions of replace for EX32 to be installed into.
Width At FrontWidth At BackHeightDepth
1
Fireplace Dimensions28” (711 mm)18
/2” (470 mm)20” (508 mm)
16” (406 mm)
NOTE: Space must be provided for gas line on right side of unit for servicing purposes.
Venting:
WARNING: This appliance has been designed to draw room air for proper heat circulation
from the sides and bottom of the unit, and out the top front. Blocking or modifying these
openings in any way can create hazardous situations.
The vent length for the EX32 must be between 10ft (3.05 m) and 40ft (12.2 m).
The EX32 intake and exhaust must be connected to 3” dia. exible venting, made of either aluminum
or stainless steel, leading into a vertical termination cap. The ue collars of this model will t inside of a
standard 3” vent and must be fastened directly to the vent with three screws.. The exhaust vent and air
intake are both located on the top of the unit.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been
properly sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must
be installed in the correct locations on the top of the EX32.
22
Page 23
Initial Installation
QUALIFIED INSTALLERS ONLY
The height for the vent must be between 10 ft (3.05 m) and 40 ft (12.19 m).
Measured from the fireplace vent collars.
Install a sealed vent cap to prevent leakage of room air up through
chimney.
The intake and the exhaust are 3" (76mm).
Measure the height of the chimney beforehand and purchase the
appropriate venting. Never attempt to over-stretch a flexible liner to
accommodate the height of the chimney. Every joint in the venting must be
secured with three (3) #8 x 3/8” HWH sheet metal screws and an
appropriate sealant (either silicone or stove cement).
The flue damper can be fully blocked open or removed for installation of
the fireplace; the smoke shelves, shields and baffles may be removed if
attached by mechanical fasteners.
The fireplace and fireplace chimney must be clean, in good working order
and constructed of non-combustible materials.
Make sure that all chimney cleanouts are tight fitting and will not permit air
to leak into the chimney.
Refractory, glass door, safety screen, and log set can be removed from the
fireplace prior to installation.
Figure 26: Installation of EX32
The ENVIRO EX32 may be installed and vented into any solid fuel replace that has been installed
in accordance with the National, Provincial/State and local building codes and has been constructed of
non-combustible materials. Please reference the information in Table 7 and Figure 28.
An approved chimney liner and rain cap must be used. A throat connector or ashing must be installed to
ensure a tight seal, top performance, safety and efciency. Carefully follow the manufacturer’s instructions
that accompany the chimney liner kit. Use double walled aluminum or stainless steel ex vent from any of
the approved brands listed in table 7. If necessary, remove the vent collar plate from the top of the insert
and connect it securely to the liner with sheet metal screws.
Check for any tears in the liner at this point. IMPORTANT: The screws that hold the vent collar plate in its
approved position must be installed.
NOTE: If the EX32 unit is pulled out of its installation, and the vent air intake system is disconnected
for any reason, ensure that the vent-air intake pipes are re-sealed with high-temperature sealant and
reconnected with three (3) sheet metal screws evenly spaced.
23
Page 24
Initial Installation
QUALIFIED INSTALLERS ONLY
exhaust RestRictoR:
Figure 27: Exhaust Restrictor
This replace has an internal exhaust restrictor that can adjusted
externally while the replace is in operation. Depending on the length
of venting required for installation this may need to be adjusted.
The restrictor is accessed from the front of the replace through the
discharge opening as shown above. Using a 3/8” socket on a 10”
long extension, rotate the restrictor COUNTER-CLOCKWISE until the
required setting is inline with the nger catch. Refer to Table 5 for the
required restrictor setting.
Note: The restrictor is set to setting #1 from the factory.
1
FINGER CATCH
2
3
4
Table 6: Restrictor Settings
Vent Length
10’-20’
(3.05-6.1m)
20’-30’
(6.1-9.1m)
30’-40’
(9.1-12.2m)
Restrictor
Setting
1
2
3
instaLLingthe ex32:
• Remove the crate and packaging from the appliance and check to make sure there is no damage.
Carefully check the glass door. Do not use the unit if it is damaged. In the event damage is found,
please report it to your dealer as soon as possible.
• Carefully clean the replace and ue before installing the stove. Failure to do so may result in fumes
or soot being blown into the room and may cause a re leading to death or serious injury.
instaLLation instRuctions:
1. Plan your installation and clearances
to combustibles. The EX32 may be
installed and vented into any solid
fuel replace that has been installed
in accordance with the National,
3ft (0.9m)
Minimum
Provincial/State and local building
codes and has been constructed of
non-combustible materials. Also refer
ClearanCesto CombustIbles section.
2. Remove door. See maIntenanCeanD
serVICe - glass Door remoVal.
3. Remove packaged log set and all wrapping material from the stove. Remove wrapping material from
the log set and check for any damage. If damage is observed, do not use unit and contact your local
dealer.
2ft (0.6m)
Minimum
Within
10ft (3m)
Figure 28: Roof Clearances.
Roof ridge or
any other portion
of a building
24
Page 25
Initial Installation
QUALIFIED INSTALLERS ONLY
Table 7: Vent termination clearances
Minimum Clearance* Description
3 ft (0.9 m)
24 in (0.6 m)
6 ft (1.83 m)Clearance to mechanical air supply inlet.
3ft (0.9m) Clearance to each side of center line extended above meter/regulator assembly.
6 ft (1.83 m)Radial clearance around service regulator vent outlet.
12 in (30 cm)Clearance above grade, verandah, porch, deck, or balcony.
3 ft (0.9 m)
9 in (0.23 m)Exception for inputs up to and including 50,000 Btu/h (15kW)
12 in (0.3 m)
*Clearances are in accordance with local installation codes and the requiremenets of the gas supplier
Clearance above the highest point where it passes through a roof surface, refer to
Figure 23.
Clearance above a roof ridge, any other portion of a building, or any other obstruc-
tion within a horizontal distance of 10 feet (3 m), refer to Figure 23.
Clearance to a building opening or combustion air inlet of another appliance, ex-
cept with the approval of the authority having jurisdiction for the following reduced
clearances.
Exception for inputs exceeding 50,000 Btu/h (15kW) but not exceeding 100,000
Btu/h (30kW)
4. Check that the chimney clean outs t properly. The ue damper must be fully blocked open or removed
for installation of the EX32; the smoke shelves, shields and bafes may be removed if attached by
mechanical fasteners.
5. Stretch the Ø3” (76mm) ex vent liners to the
Table 8: Approved Terminations & other parts
length needed to ensure they can be easily
connected to the vent terminals.
6. Install the ex pipe assembly up through the
chimney, ensure that the pipe slides through far
enough to connect onto the vent cap. Refer to
table 8 to conrm the vent cap is approved for
use.
7. Most vent caps can be installed onto chimneys
with ue openings up to 16” (406mm) x 16”
(406mm) when the actual ashing is 16” x 16”
EXCELDirect
Vertical
Termination
High-Wind
Shield†
FlashingTF-MFR
Co-Linear
Adapter
TM-SVT*
TM-IVT
TM-SVTS46DVA-VWG
TM-CTA
ICC
M&G
DirectVent
Pro
46DVA-VCH*
46DVA-GK
Z-Flex
See Liner
Kit
See Liner
Kit
or larger. If the chimney is smaller, the ashing
should be trimmed down and folded over.
8. Apply a bead of stove cement sealant to the Ø3”
(76mm) pipe of the exhaust vent terminal. Slide
the ex liner onto the vent terminal and secure
with three (3) sheet metal screws evenly spaced.
35’ Liner KitTM-ALK46DVA-CL332DVI335X
35’ Flex Pipe
(1 pce.)
*Requires co-linear adapter
†Required when installed with minimum vent length
TC-øAL353DFA-35
9. Place a bead of high temperature silicone on the
intake collar of the vent terminal. Slide the Ø3” (76mm) ex intake liner over the collar, secure the ex
liner with three (3) sheet metal screws evenly spaced. Secure the vent terminal to the chimney using
adequate sealant, and according to local building codes.
25
Page 26
Initial Installation
QUALIFIED INSTALLERS ONLY
10. If the replace opening is lower than 24” (610 mm), remove the vent collar plate from the top of
the insert by unlatching the hook located on the center top of the stove above the door opening (see
Figure 29). Slide the collar plate backwards. Properly secure the vent collar plate to the exible vent
pipe liner(s) previously installed in the chimney. Be careful not to over-stretch the liner(s).
11. Apply a bead of stove cement sealant to the top section of the Ø3” (76mm) exhaust vent collar plate.
Slide the Ø3” (76mm) ex vent over the ue collar and secure with three (3) sheet metal screws
evenly spaced.
12. Place a bead of high temperature silicone on the intake collar
of the replace, slide the Ø3” (76mm) ex intake liner over the
collar, secure the ex liner with three (3) sheet metal screws
evenly spaced.
13. Place the unit part way into the replace. Connect the gas
line to the ⅜” NPT tting on the right side of the unit using
locally approved methods (see
InItIal InstallatIon - gas lIne
ConneCtIon). Route the power cord so it can be connected to
the power supply.
Unlatch
Latch
14. As you push the unit into its nal position in the replace, if
the vent collar plate was removed, reinstall it on the stove by
pulling it into the brackets on top using the supplied tool and
latch it back in place (shown in Figure 30).
15. Adjust the levelling legs to ensure the unit is level
and high enough if a base shelf and/or riser is to be
installed. There are four levelling legs on the bottom of
the unit (shown in Figure 31).
Pull
Figure 29: Vent Collar Plate Latch.
Brackets
Figure 30: Vent Collar Plate Tool.
Figure 31: Levelling Legs Position.
26
Page 27
Initial Installation
QUALIFIED INSTALLERS ONLY
zeRo cLeaRance (zc) fiRepLace instaLLation:
The metal oor of the ZC solid fuel rebox can be removed to allow the installation of the insert. THE
CLEARANCE TO COMBUSTIBLE MATERIAL UNDER THE INSERT IS 1/2” (13 mm). YOU MUST RAISE THE
INSERT A MINIMUM OF 1/2” (13 mm) IF THE UNIT IS TO BE INSTALLED ON COMBUSTIBLE MATERIAL.
The optional Base Shelf and Riser are recommended to ll the space under the unit once raised. The
sidewalls and top structure of the solid fuel rebox cannot be altered with the exception of: removal of
dampers, removal of smoke shelf or bafe, removal of ember catches, removal of log grate, removal of
viewing screen/curtain, and removal of doors. THE ORIGINAL FIREPLACE MAY NEVER BE RETURNED TO
SOLID FUEL USE IN THIS CONDITION.
IMPORTANT: If the factory-built replace has no gas access hole(s) provided, an access hole of 1.5 inch
(37.5 mm) or less may be drilled through the lower sides or bottom of the rebox in a proper workmanship
like manner. This access hole must be plugged with non-combustible insulation after the gas supply line
has been installed. Cutting any sheet-metal parts of the replace, in which the gas replace insert is to
be installed, except as tested for the oor is prohibited.
The included label plate shown below must be permanently attached inside the cavity of the replace
in a visible location.
WARNING: This fireplace has been converted
for the use with a gas fireplace insert only and
cannot be used for burning wood or solid
fuels unless all original parts have been
replaced, and the fireplace re-approved by the
authority having jurisdiction.
Figure 32: Fireplace Altered Plate.
eLectRicaL RequiRements:
The replace must be electrically connected and grounded in accordance with local codes or, in the
absence of local codes, with the current CSA C22.1 Canadian Electrical Code Part 1, Safety Standards For
Electrical Installations, or The National Electrical Code ANSI / NFPA 70 in the US.
WARNING: The electrical grounding instructions must be followed. The fan kit is equipped with a three-
prong (grounding) plug for your protection against shock hazard, and should be plugged directly into a
properly grounded three-prong outlet. DO NOT cut or remove the grounding prong from this plug.
C-11168
CAUTION: When servicing controls, label all wires prior to disconnection. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 18
AWG wire with a temperature rating of 105°C
27
Page 28
IFC
Main
Harness
Transmitter - TMFLSA
885 Gas Valve
IPI Pilot
Convection Fan
Proflame 2 System - Wiring Diagram
Main
On/Off
Power Cord
To
Battery
Holder
Flame Sensor
Spark Electrode
Ember
Lights
Top
Light
Initial Installation
QUALIFIED INSTALLERS ONLY
Figure 33: Wiring Schematic.
28
Page 29
Initial Installation
Pilot
Adjustment
Screw
Manifold Pressure
Tap
Inlet
Pressure
Tap
Servo
Regulator
Pilot
Solenoid
Burner
Solenoid
Gas IN
QUALIFIED INSTALLERS ONLY
gas Line connection:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance.
Gas Line Connection:
• Prior to installation consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation
code in Canada, or in the USA gas installations follow either local codes or the current edition of the
National Fuel Gas Code ANSI Z223.1.
Figure 34: Fully Labeled Gas Valve.
The appliance must be disconnected from the gas supply piping system during any pressure testing
where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve. The appliance must
be isolated from the gas supply piping system by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.45
KPa).
Always check for gas leaks with a soap and water solution after completing the
required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the valve shown in Figure 34.
• Turn set screw 1 turn counter clockwise to loosen,
5
• Place
• Check pressures using a manometer.
• When nished, release pressure, remove hose & tighten set screw.
Min. Input:21,000 BTU/hr (6.15 KW)24,500 BTU/hr (7.18 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
aDjusting the piLot fLame:
The pilot ow adjustment is set to maximum at the factory and should not need to be adjusted. The pilot
ame should envelope ⅜” to ½” (10 to 13mm) of the Flame sensor (see Figure 35). However, should the
need arise, follow Steps 1- 2 below.
1. The adjustment screw can be reached through the front of the unit using a 10 inch long blade head
screw driver (see Figure 34 for location on valve).
2. Turn the adjustment screw clockwise to decrease or counterclockwise to increase pilot ame.
Flame Sensor
.375
-.500
(10-13mm)
30
Figure 35: Proper Pilot Flame.
Page 31
Secondary Installation
optionaL base sheLf & RiseR:
The optional Base Shelf (1⅝” (41 mm) high) and Base Shelf Riser (2⅛” (54 mm) high) are components
that can be combined to create a riser with an overall height of 23/16” (55 mm). This shelf can be installed
with or without the riser and can be used when the hearth in front of the unit is lower than the replace
opening. Additional Base Shelf Risers can be fastened together to increase the height in increments
of 2⅛” (54 mm). This Base Shelf may be used in conjunction with the any surround panel options
(excluding 4-sided), and it may also be used with the trimmable Surround. The Base Shelf and Riser are
sold separately.
Installation:
1. If unit is running, turn it off and
allow it to cool completely.
2. When using more than one riser
each level must be attached
using nine (9) #8 T-20 screws
provided (see Figure 36).
3. If installing with riser(s) the
Base Shelf is to be fastened
Figure 37: Installing Base Shelf
onto Riser.
4. The leveling legs may need to be adjusted to match the height of
the riser and shelf.
5. Center the Base Shelf assembly in front of the unit ush with the
bottom of the unit.
6. Install surround if required.
to the riser(s) with one T-20
screw at each end of the back
(see Figure 37).
Figure 36: Combining 2 Base Shelf
Riser.
31
Page 32
Secondary Installation
suRRounD paneL instaLLation:
WARNING: The surround becomes hot when the unit is operating; ensure that the unit is turned off, and that
it has cooled to room temperature before beginning this installation.
HeightWidth
7
3-Sided Surround25” (635 mm)39
1
4-Sided Surround31
Table 10: Surround Dimensions.
Please check components supplied with this kit. If components are missing or have been damaged, contact your
dealer, distributor or courier company before starting this installation.
IMPORTANT: The panel must not seal ventilation openings in the replace.
INSTALLATION (3 and 4 sided Surrounds):
Lift the face upright in front of the replace with the four hooks pointing towards the replace. Slide the hooks
over their corresponding screws (see Figures 38 & 39). Ensure the hooks are secure before releasing the
surround. The surround should be wiped with a damp cloth periodically. Screws can be tightened for a more
permanent install.
/2” (800 mm)39 7/8” (1013 mm)
/8” (1013 mm)
REMOVAL:
Lift the surround straight up in order to unhook the notch on the hooks from the screws. Pull the surround away
from the replace. Place the surround where it will not be damaged.
Access Panel
removed for
clarity.
Figure 39: Screw and Hook Close-Up.
Figure 38: Screw Locations.
Burner Switch Blank INSTALLATION:
The burner switch supplied with the surround comes pre-installed and wired. This replace doesn’t require a
burner switch and it can be removed from the surround. Use the black switch blank supplied with the replace
manual to ll the hole in the surround panel where burner switch was for a cleaner appearance.
CLEANING:
NEVER CLEAN FACES WHEN THEY ARE HOT. Turn off replace and allow to fully cool.
Painted surfaces should be periodically wiped with a damp cloth. Plated surfaces mut be free of ngerprints and
smudges prior to installation and should be cleaned with a clean soft rag and a small amount of Isopropyl
alcohol.
32
Page 33
Secondary Installation
optionaL 3 anD 4 siDeD tRimmabLe paneLs:
Modifying the Surround Panel:
Trimmable Surround Panels are large rectangular panels that may be cut for use in cases that a non-standard
replace opening (e.g. an arched opening) is to be lled. Optionally this surround can be left uncut and placed
in front of the replace opening.
1. Measure the replace opening and/or make a template of the replace opening.
2. Transfer the measurement to the Trimmable Surround.
3. If desired, offset the measurements by approximately
to be placed just inside the replace opening for a cleaner appearance.
4. Cut along the preferred line (from direct measurements of offset) and remove any sharp edges.
5. The panel can be touched up with a high temperature metallic black paint available from your dealer.
INSTALLATION:
1. Install the two Trimmable Panel brackets onto the unit using a T-20 Torx screwdriver. See Figures 40-44.
for the screw installation locations. There are three sets of hole patterns on cabinet side depending on which
Surround Panel is being installed. See Figures 42 and 43.
1
/8” (3mm) to the inside; this will allow for the panel
NOTE: The Extruded and Contemporary Surround Panels use the same holes for mounting the Side Cabinet
Extensions. The Regular Surround Panel uses its own set of holes.
Installed Brackets
Figure 40: Screw
Installation Locations.
Figure 41: Screw
Installation Locations.
Figure 42: Installation for Contemporary
and Extruded Surround.
Figure 44: Screw
Installation Locations.
Figure 43: Installation
for Regular Surround.
33
Page 34
Secondary Installation
Log set instaLLation:
The placement of the logs is not arbitrary. If they are positioned incorrectly, the ames can be “pinched”
and will not burn correctly. All of the logs come with either a drilled hole or notch to make alignment
easier. Using the pictures provided, carefully set the logs in place (see Figures 45 through 51).
NOTE: The logs are fragile and should be handled gently.
Please ensure that there is no damage
to the log set and all 9 pieces are
included prior to installation.
To Install Log Set:
1. Remove the safety screen from the
unit. Then remove the glass door
by releasing the top spring latches
using the provided door tool.
2. Next, install the back log, as shown
in Figure 45, and position it all the
Figure 45. Back Log and Ember Glass.
way to the right. The right front
corner will rest on the triangle
support when installed correctly.
Then ll the front ember tray with
the supplied glass media. Save a
few pieces for the end of the setup.
Figure 46. Rear Ember Logs.
that sits on a corresponding pin on the
burner. The opposite ends of the logs
will rest on metal supports. Push the
ends towards the back of the rebox
until they contact the back log
4. Next, Install the front two at
bottommed logs on the burner, as
shown in Figure 47. Both logs have
two drilled holes on the bottom that
sit on the matching burner pins.
3. Install the two large at bottommed
logs in the middle of the ember bed
as shown in Figure 46. Both logs
have a hole drilled in the bottom
34
Figure 47. Front Ember Logs.
Page 35
Secondary Installation
Figure 48. Final Ember Log & First Right Top Log.
6. Next, Install the left and second
right top log, as shown in Figure
49. Note the locating notches
on the bottom side of both
logs (areas highlighted). The
opposite ends will rest on the
ember tray as shown.
5. Install the nal ember log, as shown
in Figure 48, by locating the drilled
holes on the burner pins. Then install
the rst right top log by sitting the
depression on the bottom side onto
the half-round on top of the back log.
The opposite end of the log sits into
the notch on top of the right ember
log.
Figure 50. Nuggets and Ember Wool.
Figure 49. Left and Second Right Top Logs.
7. Finally, use the supplied ember
nuggets, wool, and remaining
glass media to decorate the burner
and ember tray as shown. Avoid
covering the burner ports and rear
air supply (highlighted) as this will
greatly affect the appearance of
the ame.
TIP: While the glass is still removed,
it is recommended that the gas line
be purged by lighting the pilot.
35
Page 36
Secondary Installation
Figure 51. Proper Installation & Flame Appearance
8. Re-install the rebox door, then the safety screen.
9. Run the unit for 15 minutes then adjust the venturi as neededusing the door tool. Figure 51 above
depicts what the burn and ame appearance shoud look like when the log set is properly installed
and venturi adjusted.
When re-lighting the replace for the rst time since the log set has been installed/replaced, watch
for ignition at ALL the burner ports. If a long delay is noticed, turn the appliance off and wait for it to
cool down. Then remove the glass and make sure none of the burner ports are blocked.
Maintenance: Once a year, the logs should be removed and checked for deterioration or large amounts
of soot. A small amount on the bottom side of the logs is normal. Remove and replace the logs in the
same manner described above.
If new logs are required, contact your nearest ENVIRO dealer.
Never operate the replace with the glass door removed.
36
Page 37
TroubleShooting
Diagnostic fLash coDes:
1. Fail to ignite: If there is no positive ignition, the board will go into lock out and the LED will blink 3 times
in intervals until the system is reset.
2. Low battery condition (<4V): the LED indicator will blink one (1) time in intervals.
3. Parasitic Pilot Flame: the LED indicator will blink two (2) times in intervals.
4. System Lock out: the LED indicator will blink three (3) times in intervals.
Additional Ignition Information
1. The Proame2 IFC will try two (2) times for ignition.
2. Each try for ignition will last approximately 60 seconds.
3. The wait time between the two tries is approximately 35 seconds.
LED Location
Figure 52: IFC LED Location
37
Page 38
TroubleShooting
ProblemPossible CauseSolution
Thermostat
does not
work
No spark
generation
No pilot
ame ignition
The pilot ame has gone out
The On/Off switch is turn to OFF
The thermostat is set too high
Spark developes near the pilot
assembly or could occur onboard
No spark from the igniter
Air in the gas line
Pilot gas pressure dropout upon
main burner gas valve opening
No gas ow out of the pilot burner
· Turn it ON
· Set the thermostat to a lower temperature
· Check pilot assembly wiring
· Check for broken or poor connection from the sparker to the
electrode
· Check for the spark shorting or arcing at other locations
· Check for defective sparker and spark electrode
· See “no spark generation”
· It takes a while for all the air to purge out of the pilot before gas
can reach the pilot and ignite
· Check gas mains supply and pressure
· Check gas valve wirings and connections to the board
· Check the pilot burner for obstruction
· Check the wirings and connections between the pilot assembly and
the board
· Check the correct gas type settings on the valve and pilot burner
assembly orice
Pilot will not
remain lit
Remote
control
(transmitter)
does not
work
No reaction
to command
Problem with Flame Sensor circuit
Restrictor setting
The pilot light has gone out
The transmitter is too far away
from the heater
The transmitter batteries are dead
Transmitter batteries are low
A maximum number of failed
ignitions or ame restorations have
been reached.
No communication between the
remote control and the receiver
· Check for proper connection of the Flame Sensor to the IFC board
· Check pilot for full ame impingement around Flame Sensor
· If ame is too small, check gas pressure, adjust pilot rate screw,
check pilot head for damage
· Ensure the ground wire is properly attached to the pilot mounting
bracket and that it is makes a good electrical connection.
· Use the correct restrictor setting for the venting conguration
· See “Pilot will not remain lit”
· Use the transmitter to the heater
· Replace the batteries
· Replace the batteries
· Remove any possible blocking conditions. See “locking conditions”
· See how to reset the board from Lockout
· Reprogram the transmitter to the receiver.
· Follow the initializing system for the rst time
38
Page 39
TroubleShooting
ProblemPossible CauseSolution
· Turn the system off by pressing the ON/OFF button on
the transmitter
· After approximately 2 seconds press the ON/OFF button
on the transmitter again.
· In the manual ame control mode, use the down arrow
button to reduce the ame to off, indicated by the word
Locking
conditions
Main burners
will not start
Reset the Proame IFC board
The pilot ame has gone out· See “Pilot will not remain lit”
The remote control is not working
correctly
The thermostat is set too high· Set the thermostat to a lower temperature
OFF displayed on the transmitter LCD screen.
· Wait approximately 2 seconds and press the up arrow
button, the ignition sequence will start.
· With the transmitter off, disconnect main power from
stove for a few seconds then re-connect power.
· Wait approximately 2 seconds and press the Reset
button on the IFC
· Replace the batteries
Flame lifting
Blue Flames
Glass fogs up
Flames are
burning
“dirty” or
sooting
Leak in vent pipe· Check for leaks in vent connections
Improper vent conguration
Terminal may be re-circulating ue
gases
The heater has just been started
Improper air shutter adjustment· Adjust air shutter – contact your dealer
Normal condition: after the
appliance warms up the glass will
be clear.
The logs or glasses are placed
incorrectly
Improper air shutter adjustment
Incorrect rating input
· Check vent conguration with manual
· Check to see if terminal is on correctly
· May need to install high wind termination cap.
· Contact dealer
· Normal during start up: ame will yellow as the replace
heats up
**Due to additives in gas, glass may get hazy during
operation** Clean as needed.
· Check log positioning
· Check level of glasses layout
· Increase primary air by opening the air shutter and/or
by opening the vent restrictor
· Check for proper venting and blockage of the vent
termination
· See also “Burners will not remain lit”
· Check manifold pressure and clock input rating for over-
- 12 oz. Can of Metallic Black Touch Up PaintPAINT-12-MB
Page 41
Parts Diagram - Components
16
12
11
10
9
8
7
15
6
23
14
17
3
4
5
18
22
19
20
21
2
1
13
24
25
26
27
41
Page 42
Notes
42
Page 43
Jan 2018
Sher wood Industries Ltd. (“Sherwood”) hereby warrants, subject to the terms and
conditions herein set forth, this product against defects in material and workmanship
during the specified warranty period starting from the date of original purchase at retail.
In the event of a defect of material or workmanship during the specified warranty period,
Sherwood reserves the right to make repairs or to assess the replacement of a defective
product at Sher wood’s factory. The shipping costs are to be paid by the consumer.
All warranties by Sherwood are set forth herein and no claim shall be made against
Sherwood on any oral warranty or representation.
Conditions
A completed warranty registration must be submitted to Sherwood within 90 days
of original purchase via the online warranty registration page or via the mail-in
warranty registration card provided. Have the installer fill in the installation data
sheet in the back of the manual for warranty and future reference.
This warranty applies only to the original owner in the original location from date of
install.
The unit must have been properly installed by a qualified technician or installer, and
must meet all local and national building code requirements.
The warranty does not cover removal and re-installation costs.
Sherwood Industries Ltd. reserves the right to make changes without notice.
Sherwood Industries Ltd. and its employees or representatives will not assume
any damages, either directly or indirectly caused by improper usage, operation,
installation, servicing or maintenance of this appliance.
A proof of original purchase must be provided by you or the dealer including serial
number.
This warranty does not cover any discoloration of the safety screen mesh.
Exclusions
An expanded list of exclusions is available at www.enviro.com/help/warranty.html
This warranty does not cover:
Damage as a result of improper usage or abuse.
Damage caused from over-firing due to incorrect setup or tampering.
Damage caused by incorrect installation.
To the Dealer
Provide name, address and telephone number of purchaser and date of purchase.
Provide date of purchase. Name of installer and dealer. Serial number of the
appliance. Nature of complaint, defects or malfunction, description and part # of any
parts replaced.
Pictures or return of damaged or defective product may be required.
To the Distributor
Sign and verify that work and information are correct.