Ethernet Gateway Set-Up
Please refer to the following pages for detailed instructions on the correct procedures for setting up the Ethernet
gateway.
Please note the following settings should be used:
Module IP The IP address being allocated to the gateway
Default Gat eway IP The default gateway IP address being allocated.
If this is not available (enter zeroes in these fields)
Subnet Mask The desired subnet mask
Socket Timeout 90
Converter Mode 0
Char Timeout 0
Port Number N/A
Server IP N/A
Watchdog Interval 15 Minutes
Baud Rate 4800
Data Bits 8
Sto p Bits 1
Parity None
RS232/RS485 RS485
Seri al Reply Timeout 25
RS485 On Delay 5
RS485 Off Delay 0

Building a beer fu ture together
Enviro UK Ltd., Commerce Court, Cutler Heights Lane, Bradford, BD4 8NW.
01274 662226 | sales@envirouk.com | www.envirouk.com & www.becsuk.com TEC-ENV908-EG
Equipment to be
monitored
Use either
Ring CTs ENV941 or
Split CTs ENV940
1 x RDMData Manager
Enviro Range of Kwh
Meters
Enviro ENV908-EG
Ethernet Gateway
Via Cat 5 or 6
Typical Site set-up for energy Meters