While your alarm system or device is reliable and sophisticated, it does not offer guaranteed protection against
burglary, fire or other emergency. Any security product, whether commercial or residential, is subject to
compromise or failure-to-warn for a variety of reasons. These include:
•Individuals may gain access through unprotected openings or have the technical sophistication to
bypass an alarm sensor or disconnect an alarm warning device.
•Monitoring devices will not operate without power. Devices powered by AC will not work if their AC
power supply is off for any reason. If system has battery backup, batteries that are not maintained can
fail to provide the necessary power for devices to function properly.
•Alarm warning devices such as sirens, bells, and horns may not alert people or awaken sleepers if they
are located on the other side of closed or partly closed doors. If warning devices are on a different level
of the residence from the bedrooms, they are less likely to awaken or alert people inside the bedrooms.
•Telephone lines needed to transmit alarm signals from a premises to a central monitoring station may
be out of service, and are subject to compromise by sophisticated means of attack.
•Signals sent by wireless transmitters may be blocked or reflected by metal before they reach the alarm
receiver. Even if the signal path has been recently checked during a weekly test, blockage can occur if
a metal object is moved into the path.
•Even if the system responds to the emergency as intended and is a monitored alarm system, the
authorities may not respond appropriately.
•This equipment, like other electrical devices, is subject to component failure.
•The most common cause of an alarm system not functioning properly is due to inadequate
maintenance. Your alarm system should be tested weekly to make sure all detection devices are
operating properly. Your control panel and keypads should be tested as well.
Installing an alarm system may make you eligible for lower insurance rates, but an alarm system is not a substitute
for insurance. Homeowners, property owners, and renters should continue to insure their lives and property.
Table of Contents
General Information............................................................................................................................... 1
Appendix D: System Configuration Record ...................................................................................... 87
Warranty and Service Information ..................................................................................................... 93
iiD-011-0152
General Information
Overview
The EnviroAlert® EA800 Multi-Zone Environmental Alarm System monitors the environmental conditions detected
by the sensors connected to the base unit, and provides alarm signals when monitored conditions at any of the
sensors exceed the user-programmable HIGH LIMIT or LOW LIMIT set points. The alarm signals are provided via
relay outputs that can operate with process controls, security systems, or other similar automated equipment. The
EA800 Alarm System can be configured with wired or optional wireless sensors (sold separately). The EA800
allows connection of up to 4 wired and 4 wireless sensors.
Setup and programming is done using the front panel keys and the liquid crystal display (LCD) on the base unit.
The display assists the user during setup, and shows measured conditions for the monitored environment during
operation.
The EA800 can monitor multiple critical environments using multiple sensor inputs. Each sensor input/alarm
channel is designated a “Relay”.
Using the appropriate accessory sensors (sold separately), the EA800 Alarm System monitors and provides
alarms for the following conditions:
■ Normally open/normally closed contacts
■ Temperature: from -80° C to 150° C (-112° F to 302° F)
■ Humidity: from 5% to 95% RH (non-condensing)
■ Presence of water
■ Any sensor with a 4-20mA interface
The EA800 base unit may be mounted directly to a 3-gang electrical enclosure or to walls. The wireless sensors
are easily mounted to the wall. Figure 1 shows the base unit and a wireless sensor.
Figure 1 EnviroAlert EA800 Base Unit and Optional Wireless Sensor
-
-
How to Use This Manual
Enter:
0800
F1
Step 1: Press the
F1 soft key.
Step 2: The
UNLOCK screen
is displayed. Enter your
password using the arrow
keys.
Step 3: Press the
ENTER key
F1 can be pressed at this time
to lock the unit.
How to Use This Manual
This manual is organized into sections that guide you through the installation process, then describe how to use the
EA800 and change its programmed settings if necessary. Some troubleshooting guidelines are provided, and the
appendices contain forms for you to photocopy and use to record the programmed settings of the EA800 and the
monitoring system setup.
The manual presents EA800 programming procedures by showing you the sequence of menus and screens you
will see as you perform the procedure, and the keys to press to advance to the next screen. The example below is
the procedure for unlocking the EA800 base unit to allow programming.
The arrows on the drawing indicate the direction of procedure flow.
In all procedures, use the keys to select menu options and to increase/decrease alphanumeric values for
programming options. Use the PREV and NEXT soft keys (F2 and F3) to move the cursor to the next digit when
entering numeric data.
The functions of the soft keys change and are defined on the screen in the area above each key. If no
F1 F2 F3
text is shown above a soft key, it means the key performs no function on the current screen.
“Keys” on page 6 describes the functions of each key on the base unit.
Note: For convenient reference, “Appendix A: Screen Maps” on page 75 contains maps of all menus and
screens.
Throughout the manual, text that appears on the EA800 base unit screens is shown like this: MONITORING
Key names are shown in text like this: F1
The current menu selection is highlighted on the screen by arrows on either side of the
selection, as shown in the example at right. On this MAIN MENU screen, the current selection
is Sensors.
Use the or keys to move the highlight to the desired menu item, then press
to make the selection.
2D-011-0152
General Information
Sensor 5
Sensor 6
Sensor 7
Sensor 8
Wireless Sensors
Relay 1
Output 1
Output 2
Relay 2
Output 3
Relay 3
Output 4
Relay 4
Output 5
Relay 5
Output 6
Relay 6
Output 7
Relay 7
Output 8
Relay 8
EA800 Base Unit
Aux Output
RF Receiver
Sensor 1
Sensor 2
Sensor 3
Sensor 4
System Control
Relay 9
Relay 1 coil control logic
Relay 2 coil control logic
Relay 3 coil control logic
Relay 4 coil control logic
Relay assignment
and coil control logic
Alarm Panel
From other
EA800, EA400, and EA200
Environmental Alarm Systems
Sensor 5
Sensor 6
Sensor 7
Sensor 8
Wireless Sensors
Relay 1
Output 1
Output 2
Relay 2
Output 3
Relay 3
Output 4
Relay 4
Output 5
Relay 5
Output 6
Relay 6
Output 7
Relay 7
Output 8
Relay 8
EA800 Base Unit
Aux Output
RF Receiver
Sensor 1
Sensor 2
Sensor 3
Sensor 4
System Control
Relay 9
Relay 1 coil control logic
Relay 2 coil control logic
Relay 3 coil control logic
Relay 4 coil control logic
Relay assignment
and coil control logic
Sensor 5
Sensor 6
Sensor 7
Sensor 8
Wireless Sensors
Relay 1
Output 1
Output 2
Relay 2
Output 3
Relay 3
Output 4
Relay 4
Output 5
Relay 5
Output 6
Relay 6
Output 7
Relay 7
Output 8
Relay 8
EA800 Base Unit
Aux Output
RF Receiver
Sensor 1
Sensor 2
Sensor 3
Sensor 4
System Control
Relay 9
Relay 1 coil control logic
Relay 2 coil control logic
Relay 3 coil control logic
Relay 4 coil control logic
Relay assignment
and coil control logic
Block Diagrams
Figure 2 shows a block diagram of the base unit interfaces and functions. The EA800 provides eight relays for
indicating when a programmed alarm limit has been exceeded or a warning condition exists. An additional AUX
(Auxiliary) Output relay provides an output signal to an optional audible alarm or strobe that is activated whenever
an alarm condition exists.
Figure 2 EA800 Environmental Alarm System Block Diagram
The EA800 can be made part of a larger security system as shown in Figure 3. In a security system there may be
more than one EA800 installed along with other components such as the Winland EA200 or EA400 multi-zone
environmental alarm systems.
-
-
Figure 3 Facility Security System Block Diagram - Example
Symbols on the Product or Manual Labeling
Symbols on the Product or Manual Labeling
Symbols appearing on the product labeling, packaging, and/or in this manual are shown and described in Table 1.
Table 1Symbols on Product or Manual
SymbolDefinition
Attention, consult accompanying documents or statements.
AUXCombined single pole double throw (SPDT) NO relay output that activates upon an
Model: EA800
• FCC ID:
V5SEA800-031108
• IC: 7635A-EA800
Models: EA-WMFS,
EA-WTS, EA-WHS
• FCC ID:
V5SEA-WS-031108
• IC: 7635A-EAWS
For product disposal, ensure the following:
• Do not dispose of this product as unsorted municipal waste.
• Collect this product separately.
• Use collection and return systems available to you.
Indicates product complies with RoHS-WEEE directive.
alarm from any of the sensors.
This device complies with part 15 of the FCC Rules. Operation is subject to the follow-
ing two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause
undesired operation.
Caution Statement (per CFR 15.21):
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Class B Product Compliance Statement (per CFR 15.105(b)):
NOTE: This equipment has been tested and found to comply with the limits for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one
or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver
• Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
The TÜV certification combines electrical safety certification for Canada (SCC), United
States (NRTL), and Europe (EU Directives). This product was voluntarily tested
according to the relevant safety requirements and mentioned properties pertaining to
this certification mark.
The product is in conformity with all applicable requirements for its placing on the
European Union market.
4D-011-0152
General Information
Monitoring Screens
The EA800 user interface is menu-based. During normal system monitoring, one of the following three screens is
displayed depending on the current state of the programmed sensors:
The MONITORING (home) screen is displayed
when there are no active alarms. The screen lists
all programmed sensors connected to the base
unit and their current reading or state.
The MONITORING (home) screen displays pending
alarms in reverse video as shown in the example
at right (71° exceeds the temperature limit for
Sensor 2, so it is shown as light text on black).
Pending alarms indicate that the programmed limits for the sensor have been exceeded, but the
sensor’s programmed delay time has not elapsed
yet. If the monitored conditions continue to
exceed the programmed limits for longer than the
programmed delay period, the pending alarm will
become an active alarm.
The ACTIVE ALARMS screen is shown when one or
more sensors are in an active alarm or warning
state. If more than one alarm is active, each will
be listed on the screen. In the example shown,
Walk-in Cooler and Warehouse alarms are
occurring simultaneously.
-
-
Keys
Keys
Figure 4 shows the base unit display and entry keys. The keys are described in Table 2.
Figure 4 EA800 Base Unit Keys
Table 2Key Functions
KeyFunction
F1This key's function changes as determined by the software. Its current function is
displayed immediately above the key on the display.
F2This key's function changes as determined by the software. Its current function is
displayed immediately above the key on the display.
F3This key's function changes as determined by the software. Its current function is
displayed immediately above the key on the display.
Up Arrow: This key provides the scroll up function. It moves the selection cursor up
a list or increments the value of alphanumeric entry fields as identified by the flashing cursor. The values provided are dependent on the currently active field. For
example, the available selections may be a + or - sign, numbers, or alphanumeric
characters and special characters.
Down Arrow: This key provides the scroll down function. It moves the selection
cursor down a list or decrements the value of alphanumeric entry fields as identified
by the flashing cursor. The values provided are dependent on the currently active
field. For example, the available selections may be a + or - sign, numbers, or alphanumeric characters and special characters.
ENTER key. This key accepts the currently entered selection when pressed. If the
selection is a menu item, the selected item is accessed. If the current selection is an
entered value, pressing the ENTER key accepts the entered value.
HOME key. This key displays the home screen (MONITORING) when pressed.
MENU key: Displays the MAIN MENU screen when pressed from any menu level or
from the home screen.
SILENCE key: Alarms cannot be cleared and will continue to recur until the moni-
tored conditions detected by the sensors are within the programmed parameters.
Pressing the SILENCE key temporarily silences the local audible alarm and deactivates the auxiliary relay for 10 minutes.
If a new alarm originating from a different sensor occurs within this 10-minute
period, the audible alarm and aux relay are reactivated, and require another key
press to silence the audible alarm.
NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC NO COM NC
Base Unit Connections
Figure 5 shows the EA800 base unit's connections and Table 3 describes the functions of each connection.
Note: The base unit has four wired sensor inputs and four wireless RF sensor inputs.
Figure 5 EA800 Base Unit Connections
Table 3EA800 Base Unit Connector Functions
ConnectorDesignationFunction
J2USBUSB Type A connection used to program firmware, export logs, and export
and import configuration files. www.winland.com lists compatible USB sticks.
J5Power In11-26 VDC input power connection for EA800 base unit (from accessory
power supply or alarm panel).
CAUTION
Observe (+) and (-) polarity markings screened on circuit board. EA800
can be damaged if power polarity is reversed.
Aux Power Out11-26 VDC power out connection for EA800 accessories requiring power
(such as HA-III+ Humid Alert). This output voltage equals that of Power In and
is current-limited to a maximum of 500 mA.
CAUTION
Connect only accessories specified in this manual to the Aux Power Out
connection. Connection of unsuitable loads to this connection may
damage the power supply and EA800, or result in improper or unreliable
operation.
Note: Accuracy for the HA-III+ sensor is stated at +12VDC input.
If Aux Power Out is used to power the HA-III+ and is not
+12VDC, then the accuracy of the HA-III+ is compromised.
-
-
Access Control and Passwords
Table 3EA800 Base Unit Connector Functions — continued
AUX OUTForm C relay output that activates upon an alarm from any of the relays
(Relay 1 through Relay 8).
J13AntennaRF receive and transmit
J14AntennaRF receive and transmit
Access Control and Passwords
The EA800 base unit is normally locked to prevent unauthorized use. The currently active function of the F1 soft
key (UNLOCK or LOCK) is displayed above the key. The locked and unlocked states are described below.
Note: The base unit locks automatically after 30 minutes of inactivity if the user does not press the LOCK soft
key (F1).
■ Locked: This is the default state and limits access to the EA800 to viewing only.
UNLOCK is displayed above the F1 soft key indicates that the base unit is
currently locked. Pressing the F1 soft key prompts the user to enter a password
to unlock the base unit, permitting full access to all screens and functions. The
HOME key, MENU key, and the MAIN MENU options shown on the screen at right
are available to the user when the base unit is locked.
■ Unlocked: When the base unit is unlocked, LOCK displayed above the F1 soft key, and all information,
programming, and maintenance screens may be viewed and programming changes may be made. Pressing
the F1 soft key locks the EA800 base unit and protects it from unauthorized or unintended programming
changes, log downloads, and firmware uploads.
The base unit allows the use of two passwords for unlocking:
■ The factory default password is 0800. This password cannot be changed or deleted.
■ A second, optional password may be set by the user. To create a second user password, see “Changing the
Password” on page 63.
8D-011-0152
System Configuration Parameters
WARNING
!
The EA800 base unit requires certain system level information as outlined in Table 4.
Table 4System Configuration Parameters
ParameterSelectionsFactory DefaultDescription
General Information
Date Format• MM/DD/YYYY
• DD/MM/YYYY
Time Format• 12-hour
• 24-hour
Data Collection Frequency
Buzzer• Enable
• 30 seconds
• 1 minute
• 5 minutes
• 15 minutes
• 30 minutes
• 60 minutes
•Disable
MM/DD/YYYYSets the desired date format for all event time stamps.
24-hourSets the desired time format for all event time stamps.
5 minutesSets the interval for collecting and recording data from the
sensors. The data collection frequency applies to all sensors.The EA800 provides approximately 10,000 data
points to be collected regardless of the frequency
selected. The estimated time duration covered for each
data collection frequency is listed below.
EnabledEnables and disables the buzzer when an alarm limit has
been exceeded or a warning condition exists.
Selecting Disable for this parameter turns the audible
alarm buzzer off completely. No audible alarm tone
will sound when an alarm occurs if DISABLE is
selected.
channel 16Selects the ISM band radio frequency (RF) channel for
transmission between the wireless sensors and EA800
base unit.
-
-
Sensors
Sensors
A variety of sensors may be used with the EA800 base unit to provide environmental status and information. These
include the following:
■ Wired Sensors: Relays 1 through 4 are for use with sensors wired to the base unit. Wired sensors can be any
of the following types:
•Low temperature sensors - Blue Thermistor Probes
•High temperature sensors - Red Thermistor Probes
•Ultra Low temperature sensors - White Thermistor Probes
•HA-III+ humidity sensor
•Water Bug sensor (supervised)
•N.O. Contact
•N.C. Contact
•4-20 mA
■ Wireless Sensors: Relays 5 through 8 are for use with wireless sensors. These sensors transmit to the EA800
base unit through RF links. Each wireless sensor is hard-coded with an address the base unit uses to identify
the sensors installed in the system. When you program the system you assign each installed wireless sensor
to a relay using its hard coded address. Wireless sensors can be any of the following types:
•Wireless Humidity Sensor (EA-WHS)
•Wireless Temperature Sensor (EA-WTS)
•Wireless Multi-Function Sensor (EA-WMFS): Any of the following wired sensors can be connected to the
wireless multi-function sensor, effectively converting the wired sensor to wireless:
•Low temperature sensors - Blue Thermistor Probes
•High temperature sensors - Red Thermistor Probes
•Ultra Low temperature sensors - White Thermistor Probes
•Water Bug sensor (supervised)
•Normally Open (NO) Contact
•Normally Closed (NC) Contact
Temperature Sensors
Table 5 lists the temperature sensors available for use with the EA800 Alarm System.
HA-III+PN M-001-0091Humidity monitoring module5% to 95% rh
(non-condensing)
Wireless
Humidity
PN M-001-0126Wireless humidity monitoring
module
5% to 95% rh
(non-condensing)
4-20mA Sensors
Theory of Operation
Industry standard 4-20mA sensors can be used with the EA800. However, it is important to verify that this type of
sensor will operate properly over the entire output range.
Figure 6 shows an example of the loop circuit for a 4-20mA sensor whose minimum operating voltage is 8V or less
when connected to an EA800 base unit that is powered with 12VDC.
Figure 7 shows an example of the loop circuit for a 4-20mA sensor whose minimum operating voltage is greater
than 8V when connected to an EA800 base unit that is powered with 12VDC.
-
-
Figure 6 I4-20mA Sensor Wiring Diagram - EA800 Aux Power Supply
Figure 7 4-20mA Sensor Wiring Diagram - External Power Supply
Sensors
Power Supply / Sensor Voltage Selection
In order to determine the power supply voltage necessary to ensure correct full-scale operation, it is necessary to
identify all voltage drops within the current loop.
Figures 6 and 7 show an EA800 drop of 4.0 VDC. This value accounts for the voltage drop generated by
connecting the 4-20mA sensor to the EA800 using 1000 feet of 22 AWG wire.
Now it is only necessary to identify the operating voltage range of the 4-20mA sensor, more importantly the
minimum operating voltage. Once identified, the minimum operating voltage of the sensor can be added to the
4.0V voltage drop of the EA800 (+ wire) to determine the power supply voltage necessary to ensure correct
full-scale operation.
Example:
■ Assume that a 4-20mA sensor whose operating input voltage range is 10 – 30V has been selected for use.
Therefore the minimum operating voltage of the sensor is 10V (V
). When the 4.0V drop of the EA800
sensor
(and wire) is added, it can be determined that at least 14VDC is needed to power the loop.
■ If the EA800 is connected to a 12VDC power supply, use of the sensor in this example requires an external
power supply of at least 14V as shown in Figure 7.
It is important to not exceed the maximum operating voltage of the 4-20mA sensor, as specified within the sensor’s
product specification.
The following formula provides the basis for the selection matrix shown in Table 7. Please use Table 7 to select
either the proper sensor rating to be used with a known power supply, or select a power supply for a known sensor
rating.
R
< (Vcc – x) .023
L
where:
■ R
= Loop resistance of 200
L
■ V
= Power supplied to EA800 or Aux Power Out
cc
■ X = Sensor voltage (max)
Table 74-20mA Voltage Select Matrix
Power Supplied to EA800
or AUX. Power Out
V
(max.) [Maximum
sensor
sensor voltage rating]
Power Supplied to EA800 or
AUX. Power Out
V
sensor
sensor voltage rating]
11 VDC7 VDC19 VDC15 VDC
12 VDC8 VDC20 VDC16 VDC
13 VDC9 VDC21 VDC17 VDC
14 VDC10 VDC22 VDC18 VDC
15 VDC11 VDC23 VDC19 VDC
16 VDC12 VDC24 VDC20 VDC
17 VDC13 VDC25 VDC21 VDC
18 VDC14 VDC26 VDC22 VDC
(max.) [Maximum
12D-011-0152
General Information
Water Sensors
Table 8 lists the water sensors available for use with the EA800 Alarm System.
Use of water sensors requires that at least one supervised water sensor be used. Up to five additional
unsupervised water sensors may be added in parallel on the same input where the supervised water sensor is
configured.
Table 8EA800 Compatible Water Sensors
Operating
SensorPart NumberDescription
Water BugPN M-001-0094Supervised water sensor
1
Range/Parameters
NA
1 Water sensors are not effective nor intended for use in distilled or deionized water.
Multi-Function Sensors
Multi-function wireless sensors may be connected to a wired sensor to act as a transmitter. Table 9 lists the
multi-function sensor available for use with the EA800 Alarm System.
Table 9EA800 Compatible Multi-Function Sensors
Operating
SensorPart NumberDescription
Range/Parameters
Wireless
Multi-Function
PN M-001-0127Wireless link for sensors. See
page 16 for allowed sensors.
Dependent on sensor
connected.
Contact Closure Sensors
Table 10 lists the contact closure sensors compatible for use with the EA800 Alarm System.
Table 10EA800 Compatible Closure Sensors
SensorDescription
NO closureNormally open contact closure such as door contacts, motion detectors,
NC closureNormally closed contact closure such as door contacts, motion detectors,
and glass break sensors
and glass break sensors
-
-
Sensors
Sensor Parameter Descriptions
This section provides a description of each sensor parameter.
Table 11Sensor Parameter Descriptions
ParameterApplicable to SensorsDescription
Sensor Name AllA name used to identify the sensor in the alarm system. Select a name
readily identified by the viewer. The sensor name is displayed on the
Main screen during a no-alarm condition and on the Alarm screen during
an alarm condition. Two name choice types are available:
• Common Name: These are preprogrammed names.
• Custom Name: This selection allows you to enter any name if the
preprogrammed common names do not adequately identify the sensor
in the system (limited to 16 characters).
Note: Duplicate sensor names are not permitted.
Unit of
Measure
• Blue, Red and White
temperature sensors
• 4-20mA sensor
• Wireless
temperature sensors
This parameter allows you to choose the unit of measure used for sensor reading and display.
• Blue, Red and White temperature sensors: °C or °F
• 4-20mA sensors: the following Common Units of measure are
available: F (Fahrenheit), C (Centigrade), K (Kelvin), % rh (percent
relative humidity), psi (pounds per square inch), Pa (Pascals), kPa
(kiloPascals), lb (pound), kg (kilogram)
• 4-20mA sensors can also use custom units. Enter the appropriate units
for the connected 4-20mA sensor via the keypad.
Resolution4-20mA sensorThis determines the range that may be used for the 4-20mA sensor. The
full scale range is determined by the values entered in the Low Scaled
Value and the High Scaled Value. You must select the correct resolution
in order to set the true range limits for the 4-20mA sensor you are installing. The available values are as follows:
Maximum Allowed Maximum Allowed
ResolutionLow Scaled ValueHigh Scaled Value
1.-9999.+9999.
0.1-999.9+999.9
0.01-99.99+99.99
0.001-9.999+9.999
Low Scaled
Value
4-20mA sensorThis parameter equals the environmental reading that results in a sensor
output of 4mA or its minimum valid reading. This is dependent on the
setting of the resolution as discussed above.
High Scaled
Value
4-20mA sensorThis parameter equals the environmental reading that results in a sensor
output of 20mA or its maximum valid reading. This is dependent on the
setting of the resolution as discussed above.
Hysteresis• Blue, Red and White
temperature sensors
• HA-III+
• 4-20mA sensor
The Hysteresis setting helps prevent alarms from being set and reset
continually if the environment is at or near the alarm set point by providing an acceptable variance. For example, if Hysteresis is set at 2 and the
sensor High limit is set at 50, the sensor reading must decrease to 48
(50 minus 2) in order for the alarm condition to reset to a no-alarm condition.
Low Alarm
Limit
• Blue, Red and White
temperature sensors
The Low Alarm Limit sets the value that trips the low alarm when
exceeded.
• HA-III+
• 4-20mA sensor
• Wireless humidity
sensor
• Wireless
temperature sensor
14D-011-0152
Table 11Sensor Parameter Descriptions — continued
NC
NO
To
alarm
panel
From
EA800
logic
Idc
C
NC
NO
To
alarm
panel
From
EA800
logic
Idc
C
NC
NO
To
alarm
panel
From
EA800
logic
Idc = 0
C
ParameterApplicable to SensorsDescription
General Information
High Alarm
Limit
• Blue, Red and White
temperature sensors
The High Alarm Limit sets the value that trips the high alarm when
exceeded.
• HA-III+
• 4-20mA sensor
• Wireless humidity
sensor
•Wireless
temperature sensor
Alarm Delay
Time
AllThis sets the time period that an alarm condition can exist before the
alarm is triggered. This is useful for helping to prevent false alarms from
occurring in situations where normal activities cause conditions to temporarily exceed alarm thresholds. For example, the temperature in a
freezer may temporarily rise above the High alarm limit while frozen food
is being restocked and the freezer door is open, but the delay prevents
the alarm from going off unless the temperature fails to cool below the
alarm threshold within the alarm delay period.
Relay Operation
This section describes the operation of the base unit's relays. The relays must be programmed correctly so that
their outputs provide the desired signaling to the alarm panel.
Table 12Relay Configuration Settings
Relay SettingDescription
No Alarm
Relay State:
De-Energized (default)
No Alarm: Power is removed from the relay coil as shown below.
To
NC
NO
alarm
panel
From
EA800
logic
C
Idc = 0
No Alarm
Relay State: Energized
Active Condition:
Alarm Only
Active Condition:
Alarm or Warning (default)
-
-
Alarm: Power is applied to the relay coil as shown below.
No Alarm: Power is applied to the relay coil as shown below.
Alarm: Power is removed from the relay coil as shown below. This provides for a
default alarm if the EA800 loses power in addition to the sensors' alarms.
Sets the alarm to be active when an alarm condition exists.
Sets the alarm to be active when an alarm condition exists or a warning is active.
Relay Operation
16D-011-0152
Preparation
CAUTION
!
CAUTION
!
CAUTION
!
Before you begin installation, ensure that you properly plan the alarm system. During the planning phase you will
generate all the documentation you need to successfully install the EA800 base unit and sensors in the alarm
system. This is important because complete and accurate installation documentation aids in system maintenance
later.
If the EA800 base unit will be connected to a remote alarm panel, do not connect
the base unit to the alarm panel until after sensor connection and configuration
is complete. Connecting the remote alarm panel before configuring the EA800
sensors will result in false alarms at the remote panel.
The suggested preparation procedure is as follows:
1.Read and understand the entire manual. General Information provides important information required to
properly plan, install, and use the EA800. The preparation phase helps ensure that the EA800 system will
function as required.
2.Photocopy the pages of Appendix B: Planning Worksheet, Appendix C: EA800 Wiring Diagram (one for each
EA800 base unit in the system), and Appendix D: System Configuration Record to create a record of the
specific EA800 alarm system installation you are currently working on.
3.Draw a floor plan for the facility where you will install the EA800 alarm system. Identify important details such
as the coolers, doors, computer rooms, etc. An example is shown below.
Cooler1
Cooler 2
Storage Room 3Computer
Room
Rear
Entry
Freezer 1
4.
Locate the base unit where authorized personnel can readily access it. If required, consideration should be
Freezer 2Room 1
Figure 8 Example Floor Plan
Room 2
Women's Room
Alarm panel
installation area
Men's Room
Front
Entry
Front Desk
Conference Room
made regarding a location that discourages unauthorized access. If using wireless sensors, locate the base
unit to minimize the wireless distance. Ensure that the desired mounting locations for the EA800 base unit and
each sensor comply with the environmental specifications listed in Table 13: Specifications.
Do not install the EA800 base unit in coolers or freezers.
Use only wired sensors specified in this manual for the INPUT 1 through INPUT 4
connections. Unverified sensors may damage the EA800 or result in improper or
unreliable operation.
-
-
5.Complete the copy of Appendix B: Planning Worksheet for the facility in which the EA800 system is to be
WARNING
!
CAUTION
!
installed. This must include all monitored areas for the total security system so that you know how many EA800
base units are needed.
6.Determine the sensors required from the Planning Worksheet you completed and the information provided for
each sensor type in “System Configuration”. Enter these in the copy of the System Configuration Record you
made.
Note: When water sensors are required, you must use at least one supervised water sensor and may add up to
five additional unsupervised water sensors, all in parallel. Thus, an alarm on any sensor will result in an
alarm with no way to determine which sensor is the source.
7.Enter the sensor information in the copy of the EA800 Wiring Diagram you made. It is a good idea to name
each sensor on this diagram and use that name in both the EA800 Wiring Diagram and the System
Configuration Record. This helps ensure proper programming of the system after you have physically installed
the system.
EA800 relay outputs are intended only for use as low-voltage, low-current
alarm connections, and not for direct switching or control of AC-mains
powered loads. Additionally, local codes may further dictate or limit the types
of loads and associated wiring to be used with the low-current Form C relay
outputs used with the EA800. Connecting AC-mains type circuits to the EA800
may result in an electric shock and/or fire hazard.
Do not connect a load to the AUX OUT or OUTPUT 1 through OUTPUT 8 relay
outputs that exceeds limitations stated in the Specifications section of this
manual. Loads exceeding the specified limitations may damage the EA800, or
result in improper or unreliable operation.
8.Using the floor plan you created, identify the specific locations for each sensor and verify that their locations
meet the specifications. See Specifications for operational parameters such as cable length.
Note: For 4-20mA sensors: See 4-20mA Sensors for a discussion of determining the constraints for your
4-20mA sensor to ensure accuracy over its rated range.
9.Determine the channel to use for the wireless sensors. If more than one EA800 is being installed on-site, it is
recommended that they be configured to use different channels.
10. The wireless sensor must be located so that the wireless signal strength is adequate as outlined in Winland
Application Note AN00101. You must verify that the wireless sensors can communicate with the base unit
before you permanently mount them.
Note: Certain environments may present conditions that intermittently cause interference with wireless sensor
to base unit communications. You should understand the environment in which the EA800 is to operate
to minimize their affects on system performance.
11. Decide the loop design you will use. Figure 9 shows an alarm loop where alarm power is derived from the
alarm loop. Figure 10 shows an alarm loop where alarm power is derived from the power supply feeding the
EA800.
Note: if using a self-powered loop, ensure the power supply can provide power for all loading conditions.
12. Create an interconnect wiring diagram for the system. Identify the location of each sensor An example of a
Sensor 5
Sensor 7
Sensor 8
Relay 1
Output 1
Output 2
Relay 2
Output 3
Relay 3
Output 4
Relay 4
Output 5
Relay 5
Output 6
Relay 6
Output 7
Relay 7
Output 8
Relay 8
EA800 No. 1
Aux Output
Alarm Panel
Sensor 5
Sensor 6
Sensor 7
Sensor 8
Relay 1
Output 1
Output 2
Relay 2
Output 3
Relay 3
Output 4
Relay 4
Output 5
Relay 5
Output 6
Relay 6
Output 7
Relay 7
Output 8
Relay 8
EA800 No. 2
Aux Output
Computer
Room
Rear
Entry
Front
Entry
Front Desk
Men's Room
Women's Room
Conference Room
Alarm panel
installation area
Ch1
Ch2
Sensor 6
Ch1
Ch1
Ch1Ch1
Ch2
Ch2
Ch2Ch2
Zone 1
Output 1
Output 2
Zone 2
Output 3
Zone 3
Output 4
Zone 4
EA400
Aux Output
Internal
Sensor
Output 1
Output 2
Zone 1
EA200
Aux Output
Cooler1Cooler 2
Storage Room 3
Freezer 1Freezer 2
Room 1
Room 2
system map is shown in Figure 11. This example illustrates a system that includes multiple EA800 Multi-Zone
Environmental Alarm systems, a Winland EA400 Multi-Zone Environmental Alarm system, and a Winland
EA200 Multi-Zone Environmental Alarm system.
13.
Determine the cabling required to complete the installation as indicated by the loop design, the sensors you
have selected, and the system interconnect wiring diagram.
14. Complete the System Configuration section on the copy of the System Configuration Record you made. See
System Configuration for a description of each system level parameter.
When you have completed the previous steps you are ready to proceed to physically install the EA800 base unit
and its associated sensors using the documentation you have just created.
Figure 11 System Interconnect Wiring Diagram Example
20D-011-0152
Installation
WARNING
!
CAUTION
!
CAUTION
!
CAUTION
!
CAUTION
!
CAUTION
!
Tools and Supplies Required
Ensure that you have the following prior to starting the installation:
■ Phillips Screwdriver
■ Mounting hardware for the EA800 base unit and any optional sensor units
■ If required, a drill and the appropriate drill bits
■ Wire stripper
■ Sensors (not supplied; see “Accessories” on page 54)
■ Sensor Wiring (typically 18-22 AWG twisted-pair; not supplied)
All power terminals must be connected to a Class 2 power limited circuit complying with the National Electric Code
NFPA 70, Article 725. Where required, this equipment is to be isolated from the mains supply by a limited power
source as specified in EN60950.
EA800 relay outputs are intended only for use as low-voltage, low-current alarm
connections, and not for direct switching or control of AC-mains powered loads.
Additionally, local codes may further dictate or limit the types of loads and
associated wiring to be used with the low-current Form C relay outputs used with
the EA800. Connecting AC-mains type circuits to the EA800 may result in an
electric shock and/or fire hazard.
Connect only sensors specified in this manual to the wired and wireless input
connections. Using sensors not specified in this manual may damage the EA800 or
cause improper or unreliable operation.
Do not connect a load to the AUX OUT or OUTPUT 1 through OUTPUT 8 relay
outputs that exceeds limitations stated in the Specifications section of this manual.
Loads exceeding the specified limitations may damage the EA800, or result in
improper or unreliable operation.
The EA800 printed circuit board (PCB) contains electrostatic discharge (ESD)
sensitive devices. To help prevent damage caused by ESD, observe appropriate
ESD handling rules whenever the PCB in the EA800 is exposed.
Batteries shall not cause explosion or produce a fire HAZARD as a result of
excessive charge or discharge, or if a battery is installed with incorrect polarity.
If the equipment is used in a manner not specified by the manufacturer, the
protection provided by the equipment may be impaired.
Mounting the EA800 Rear Plate
The base unit has a removable rear plate that may be attached to a 3-gang electrical enclosure or directly to a wall.
1.Remove the rear mounting plate from the base unit as follows:
■ Pull the rear mounting plate down and away from the EA800 main chassis. The retainer tabs on the main
chassis disengage from the holes in the rear mounting plate.
■ Completely remove the mounting plate from the base unit by disengaging the mounting plate hinges from the
mating tabs on the base unit.
-
-
Install the Wired Sensors
CAUTION
!
CAUTION
!
CAUTION
!
2.Mount the mounting plate as follows:
■ Mounting to 3-gang enclosure: Use four (4) machine screws to secure the mounting plate to the mating holes in
the 3-gang enclosure.
■ Mounting to drywall surface: Place the mounting plate in mounting position. Mark the four mounting hole
locations. Install drywall anchors and secure the mounting plate to the anchors.
Note:If wall-mounted, prepare a wiring access hole at this time. All wiring must pass through the opening in the
center of mounting plate.
Install the Wired Sensors
Install the wired sensors in accordance with the instructions provided with the wired sensors.
1.Mount each wired sensor in its designated location.
2.Label each sensor's wires for easy identification.
3.Route the wires from the sensor to the base unit and dress the wires as required by local code. It is important
to ensure that the wires are protected along their entire length, are not stressed at any point, and are
adequately supported along their entire length.
4.Pass the wires through the mounted EA800 rear panel.
EA800 Base Unit Power Connections
Do not connect or disconnect power, sensor, or alarm wiring while power is applied.
Connecting and disconnecting the EA800 base unit with power connected may damage the
base unit or result in improper or unreliable operation.
Connection of unsuitable loads to this connection may damage the power supply and
EA800 base unit, or result in improper or unreliable operation.
Note:Do not apply power to the base unit until you are ready to begin sensor programming. The base unit has
a 30-minute timer that starts when the unit is first powered up. If at least one sensor is not added and programmed within the 30-minute time period, an alarm will occur.
1.Using a terminal block adapter, connect power supply + and - leads to POWER IN (+) and (-) on J5. Observe
proper polarity. If using a transformer, ensure that the transformer is an isolated power supply.
2.If Aux Power Out is to be used, connect + and - leads to AUX POWER OUT (+) and (-) on J5 using a terminal
block adapter.
Install the Wireless Sensors
If the EA800 base unit will be connected to a remote alarm panel, do not connect
the base unit to the alarm panel until after sensor connection and configuration
is complete. Connecting the remote alarm panel before configuring the EA800
sensors will result in false alarms at the remote panel.
22D-011-0152
Installation
RESET BUTTON
SENSOR MODEL NO.
(Example: EA-WTS = Wireless Temperature Sensor)
MAC Address Label
Figure 12 Wireless Sensor MAC Address Location
Enter
0800
F1
Example shown, set values as
appropriate for your system.
Note:Verify that the wireless sensors can communicate with the base unit as outlined in the following proce-
dure before permanently mounting them.
1.Remove the cover from the wireless sensors and
record the MAC addresses (see Figure 12) of
each wireless sensor on the Configuration
Worksheet you completed during the preparation
phase. The MAC address is printed on a label
affixed to each wireless sensor’s printed circuit
board (PCB) and is used to identify each sensor
during programming.
2.Temporarily mount the front panel of the base
unit to the mounted rear panel.
3.Connect power to the EA800. The EA800
completes its boot process and the MONITORING
or NO SENSORS INSTALLED (if there are currently
no wireless sensors installed) screen is
displayed.
4.With the wireless sensors located near the base
unit, connect power to each wireless sensor.
5.Unlock the keypad and allow the base unit to detect the wireless sensors using the following procedure.
Note:The keypad locks automatically after 30 minutes of inactivity (no key presses). If you have not finished
the detection and programming process for a sensor and this occurs, entered values are lost and you
must start the programming procedure for the sensor from the beginning. It is recommended that you
allow the base unit to identify the wireless sensors one at a time, with the sensors unmounted and in the
same location as the base unit.
-
-
Connecting Wired Temperature, Contact Closure, and Water Bug Sensors
RESET BUTTON
SENSOR MODEL NO.
(Example: EA-WTS = Wireless Temperature Sensor)
MAC Address Label
Figure 13 Wireless Sensor IDs and MAC Address Location
J6
Input 1 Input 2 Input 3 Input 4
+ (-) + (-) + (-)
+ (-)
Note:It may take a few minutes for the base unit to detect the wireless sensors.
At this point the NEW WIRELESS SENSOR screen is displayed and an arrow moves from left to right indicating that the
EA800 is waiting to receive sensor ID data. When the EA800 has communicated with the reachable sensors the
SELECT SENSOR screen displays a list of wireless sensors detected.
■ When a sensor is detected, confirm that the ID
number shown matches the ID number on the
sensor’s label..
■ If the sensors can communicate with the EA800,
their IDs appear in the list as shown in the
example at right. Do not permanently install the
sensors that appear in the list until you verify
their signal strength when you program the
wireless sensors in the system later in the
installation process.
■ If the list of number(s) on the screen does not
contain the number found on the sensor's PC
board, press F1 (CANCEL) to continue the
search process.
Note:Press the Reset Button on the sensor to
restart the search process if necessary.
After the base unit has identified each wireless sensor and you have programmed it, temporarily mount it in its
desired location using tape. This allows the sensor to be relocated if necessary in order to obtain good signal
strength
Connecting Wired Temperature, Contact Closure, and Water Bug Sensors
1.Make certain the sensor's wiring is passed through the opening in the mounting plate.
2.Remove the adapter from the correct input connector header by pulling the adapter up and off of the circuit
board header connector.
3.Strip the ends of each of the sensor's wires as indicated by the gauge on adapter you just removed.
4.Insert the stripped wire ends into screw terminals of the adapter as indicated by the EA800 Wiring Diagram you
completed in the preparation phase. There is no need to observe polarity when connecting sensor wires. See
Figure 14.
Figure 14 EA800 Base Unit Wired Temperature, Contact Closure, and Water Bug Sensor Connections
5.
Secure the connections using the setscrews on the adapter. Check the connection by lightly pulling on each
connection.
6.After connecting the wire ends to the adapter, align the adapter to the correct header pins as indicated by your
EA800 Wiring Diagram, and press the adapter fully onto the header connector pins.
24D-011-0152
Connecting Wired HA-III+ Humidity Sensors
J6
Input N
User
supplied
cable
HA-III+
Connector
Power Input
GND
SINK
SOURCE
NC
NC
J5
Aux Power Out
EA800 Base Unit
J6
Input N
User
supplied
cable
HA-III+
Connector
Power Input
GND
SINK
SOURCE
NC
NC
J5
Aux Power Out
External
Powe r
Adapter
EA800 Base Unit
Base Unit-Powered
External Adapter-Powered
1.Make certain the sensor's wiring is passed through the opening in the mounting plate.
2.Remove the adapter from the correct input connector headers by pulling the adapter up and off of the circuit
board header connectors.
3.Strip the ends of each of the sensor's wires as indicated by the gauge on adapter you just removed.
4.Insert the stripped wire ends into screw terminals of the adapter as indicated by your EA800 Wiring Diagram
you completed in the preparation phase. Observe proper polarity. See Figure 15.
Installation
Figure 15 EA800 Base Unit Wired HA-III+ Sensor Connections
5.Secure the connections using the setscrews on the adapter. Check the connection by lightly pulling on each
connection.
6.After connecting the wire ends to the adapter, align the adapter to the correct header pins as indicated by your
EA800 Wiring Diagram, and press the adapter fully onto the header connector pins.
-
-
Connecting Wired 4-20mA Sensors
4-20mA Sensors
(3-wire)
EA800 Base
Unit Powered
External
Adapter
Powered
J6
Input N
User
supplied
cable
4-20mA
Transmitter
Connector
NC
J5
Aux Power Out
EA800 Base Unit
J6
Input N
User
supplied
cable
NC
J5
Aux Power Out
External
Powe r
Adapter
EA800 Base Unit
4-20mA
Transmitter
Connector
4-20mA
Output
4-20mA
Output
4-20mA Sensors
(2-wire)
J6
Input N
User
supplied
cable
4-20mA
Transmitter
Connector
NC
J5
Aux Power Out
EA800 Base Unit
J6
Input N
User
supplied
cable
NC
J5
Aux Power Out
External
Powe r
Adapter
EA800 Base Unit
4-20mA
Transmitter
Connector
4-20mA
Output
4-20mA
Output
4-20mA Sensors
(4-wire)
J6
Input N
User
supplied
cable
4-20mA
Transmitter
Connector
NC
J5
Aux Power Out
EA800 Base Unit
J6
Input N
User
supplied
cable
NC
J5
Aux Power Out
External
Powe r
Adapter
EA800 Base Unit
4-20mA
Transmitter
Connector
Connecting Wired 4-20mA Sensors
1.Make certain the sensor's wiring is passed through the opening in the mounting plate.
2.Remove the adapter from the correct input connector headers by pulling the adapter up and off of the circuit
board header connectors.
3.Strip the ends of each of the sensor's wires as indicated by the gauge on adapter you just removed.
4.Insert the stripped wire ends into screw terminals of the adapter as indicated by your EA800 Wiring Diagram
you completed in the preparation phase. Observe proper polarity. See Figure 15.
5.
6.After connecting the wire ends to the adapter, align the adapter to the correct header pins as indicated by your
Figure 16 EA800 Base Unit Wired 4-20mA Sensor Connections
Secure the connections using the setscrews on the adapter. Check the connection by lightly pulling on each
connection.
EA800 Wiring Diagram, and press the adapter fully onto the header connector pins.
26D-011-0152
Loading...
+ 68 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.