SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED
PAPER.
PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
E44IGas Insert -
Log Set & Proame IPI Valve
OWNER’S MANUAL
INSTALLER:
Leave this manual
with the appliance.
CONSUMER:
Retain this manual for
future reference.
enviro.com/warranty
FOR YOUR SAFETY
Do not store or use
gasoline or other
ammable vapours
and liquids in the
vicinity of this or any
other appliance.
WARNING: If the information in this manual
is not followed exactly, a re or explosion may
result causing property damage, personal injury
or loss of life. Installation and service must be
performed by a qualied installer, service agency
or the gas supplier.
This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases, unless a certied kit is used.
WHAT TO DO IF YOU SMELL GAS
• Open windows/extinguish any open
ame.
• Do not try to light any appliance.
• Do not touch any electrical switch
or use any phone in your building.
• Immediately call your gas supplier
from a neighbour’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas
supplier, call the re department.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or gas tter
when installed within the Commonwealth of Massachusetts. Other Massachusetts code requirements:
Flexible connector must not be longer than 36in., a shut off valve must be installed; only direct vent
sealed combustion products are approved for bedrooms/bathrooms. A carbon monoxide detector is
required in all rooms containing gas red direct vent appliances. The replace damper must be removed
or welded in the open position prior to installation of a replace insert.
4001609
50-2628
Page 2
Safety Precautions
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER,
PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas-red appliances must be installed in
accordance with their instructions. Carefully read all the
instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for a
permit prior to commencing the installation.
• NOTE: Failure to follow these instructions could cause
a malfunction of the replace, which could result in death,
serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your
re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a qualied
service person. The appliance should be inspected before
the rst use and, at least, annually by a qualied service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative the control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• Due to high temperatures, the appliance should be
located out of high trafc areas and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when
in the same room as the appliance. Toddlers, young
children and others may be susceptible to accidental
contact burns. A physical barrier is recommended if there
are at risk individuals in the house. To restrict access to a
replace or stove install an adjustable safety gate to keep
toddlers, young children and other at risk individuals
out of the room and away from hot surfaces. Any safety
screen or guard removed for servicing an appliance must
be replaced prior to operating the appliance.
• Clothing or other ammable materials should not be
placed on or near the appliance.
WARNING
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH
GLASS UNTIL COOLED.
NEVER ALLOW
CHILDREN TO TOUCH
GLASS.
2
FOR YOUR SAFETY
• Installation and service must be performed by a qualied
installer, service agency or gas supplier.
• This installation must conform to local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1.
• To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
• To prevent injury, if the pilot or pilot and burners
have gone out on their own, open the glass door and
wait 5 minutes to air out before attempting to relight the stove.
• Always keep the area around these appliances clear of
combustible material, gasoline and other ammable liquids
and vapours.
• These appliances should not be used as a drying rack for
clothing or for hanging Christmas stockings/decorations.
• Due to the paint curing on the stove, a faint odor and slight
smoking will likely be noticed when the stove is rst used.
Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another
room or inside the building. Make sure the specied vent
pipe is used, properly sized and of adequate height to
provide sufcient draft. Inspect the venting system annually
for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts specically approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or qualied service person.
• Never use solid fuels such as wood, paper, cardboard, coal,
or any ammable liquids, etc., in this appliance.
• Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system or
any gas control which has been under water.
• Do not abuse the glass by striking it or slamming the door
shut.
• If the E44 unit is pulled out of its installation, and the ventair intake system is disconnected for any reason, ensure that
the vent-air intake pipes are reconnected and re-sealed in
accordance to the instructions noted in
Installation Data Sheet...................................................................................................45
3
Page 4
Codes And Approvals
DIRECT VENT: This type is identied by the sufx DV. This appliance draws all of its air for combustion from
outside the dwelling, through a specially designed vent pipe system.
This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas Association
guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000
(610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level. Refer also to local authorities or
codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high altitude
rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
• This appliance has been tested by Intertek and found to comply with the established
VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
DIRECT VENTED GAS FIREPLACE INSERT HEATER
TESTED TO: ANSI Z21.88-2009/CSA 2.33-2009 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 (R2009) GAS FIRED APPLIANCES FOR HIGH ALTITUDES
CSA P.4.1-09 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This ENVIRO E44 Fireplace Insert:
• Has been certied for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a permanent wall thermostat
for bedroom installations. Consult the authority having local jurisdiction in your area. IN USA: see current ANSI
Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current installation code CAN/CGA B149 in
Canada or ANSI Z223.1/NFPA 54 in the USA.
• Must be properly connected to an approved venting system and not connected to a chimney ue serving a
separate solid-fuel burning appliance.
• Is not approved for closet or recessed installations.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned on
for the rst time, it should be turned onto high without the fan on for the rst 4
hours. This will cure the paint, logs, gasket material and other products used in the
manufacturing process. It is advisable to open a window or door, as the unit will start
to smoke and can irritate some people. After the unit has gone through the rst burn,
turn the unit off, let the unit get cold then remove the glass door and clean it with a
good gas replace glass cleaner, available at your local ENVIRO dealer. See “
remoVal” and “cleanIng the glass” sections.
Door
4
Page 5
Specifications
Rating LabeL Location:
The rating label is located on the left side of the unit, next to the receiver box.
Dimensions:
12.08
34.15
24.17
10.0910.08
18.57
10.56
20.85
23.82
14.79
24.77
24.77
22.76
23.82
20.85
21.06
18.57
45.00
31.03
29.33
2.17
4.4218.60
30.13
32.33
2.17
4.42
18.60
8.40
46.33
Figure 1: E44 Exterior Dimensions.
5
Page 6
32 ⁄”
Specifications
45”
30 ⁄”
46 ⁄”
Figure 2: E44 Contemporary Surround with Base Shelf and Riser.
For Your Safety, Read Safety Precautions And Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION
MAY RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
LightinganD tuRning off instRuctions:
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING:IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION
MAY RESULT CAUSING PROPERTY DAMAGE, PERSONAL INJURY OR LOSS OF LIFE.
A. This appliance is equipped with an ignition device
which automatically lights the pilot. Do not try to
light the pilot by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the
floor because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any
phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
If you cannot reach your gas supplier, call the
fire department.
OPERATING INSTRUCTIONS
C. Use only your hand to push in or
turn the gas control knob. Never
use tools. If the knob will not push
in or turn by hand, don’t try to
repair it, call a qualified service
technician. Force or attempted
repair may result in a fire or
explosion.
D. Do not use this appliance if any
part has been under water.
Immediately call a qualified service
technician to inspect the appliance
and to replace any part of the
control system and any gas control
which has been under water.
1. STOP! Read the safety information above on this label.
2. Read the owner's manual including the section on
"Remote Control" operation.
3. Set the thermostat to the lowest setting.
4. Turn off all electric power to the appliance.
5. Do not attempt to light the pilot by hand.
6. Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas, STOP!
Follow "B" in the safety information above on this label.
If you don't smell gas, go to the next step.
7. Turn on all electric power to the appliance.
8. Using the remote control, set
thermostat to desired setting, or
press the ON/OFF key on the
remote. "ON" will be indicated on the
display of the remote and an audible
"beep" will be heard at the unit to
indicate the command has been
received.
9. This appliance is equipped with a
completely automatic ignition and
lighting control. The control will
attempt to light the pilot several
times if necessary. If it is
unsuccessful, it will discontinue
operations. If the appliance will
not operate, follow the
instructions "To Turn Off Gas To
Appliance" and call your service
technician or gas supplier.
Blue LCD Display
ON/OFF Key
THERMOSTAT Key
UP/DOWN Arrow Key
MODE Key
TO TURN OFF GAS TO APPLIANCE
1. Set thermostat to lowest setting, or press the ON/OFF Key. "OFF" will be indicated on the display
and an audible "Beep" will be heard at the unit to indicate the command has been received.
2. Turn off all electric power to the appliance if service is to be performed.
C-12455
Figure 3: Lighting instruction label.
7
Page 8
Operating Instructions
VentuRi aDjustment:
The venturi adjustment lever is located on the right side of the unit, behind the surround panel (see
Figure 4). To avoid touching hot surfaces under the unit, use the Door Tool to adjust the venturi.
The venturi allows the amount of air coming into the replace to be adjusted in order to accommodate
different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot
ame is burning normally and none of the burner ports are plugged. Let the replace burn for roughly
fteen (15) minutes and then examine the ames. The
ideal ame will be blue at the base and light orange
above. The ames should be of medium height. If the
ames look like this, no venturi adjustment is needed. If
the ames are fairly short and mostly blue, the replace
is getting too much air. Therefore, the air shutter should
be closed (push in) slightly until the correct ames are
achieved. Flames that are very orange, with tall dark
stringy tips are not getting enough air. Open (pull out)
the venturi until the ames clean up. If the venturi is
opened, then closed all the way, and the correct ames
Figure 4: Adjusting the venturi air setting.
Warning: Incorrect venturi adjustment may lead to improper combustion, which is a safety hazard.
Contact the dealer if there is any concern about the venturi adjustment.
cannot be attained, turn off the gas and contact the
dealer.
noRmaL sounDs DuRing opeRation:
ComponentSound & Reason
Fire BoxCreaking when heating up or cooling down.
BurnerLight pop or poof when turned off; this is more common with LP units.
Temperature SensorClinking when it senses to turn the blower on or off.
Pilot FlameQuiet whisper while the pilot ame in on.
Blower / FanAir movement that increases and decreases with the speed of the blower.
Gas Control ValveDull click when turning on or off, this is the valve opening and closing.
ReceiverBeeps when remote control buttons are pressed.
Table 2: Normal Sound
8
Page 9
Operating InstructionsOperating Instructions
Remote contRoL opeRations:
The Proame GTMF is a modular remote control system that directs the functions of the E44. The Proame
GTMF is congured to control the on/off main burner operation, its ame levels and provides on/off and
Smart thermostatic control of the appliance. The system controls a remotely actuated 120V/60Hz power
outlet, fan speed through six (6) levels and has a constantly powered 120V/60Hz power outlet.
ATTENTION!
- TURN “OFF” THE MAIN GAS SUPPLY OF THE APPLIANCE DURING INSTALLATION OR
MAINTENANCE OF THE RECEIVER.
- PLACE THE RECEIVER’S 3 POSITION SLIDER SWITCH IN THE “OFF” POSITION DURING
INSTALLATION OR MAINTENANCE.
- TURN “OFF” MAIN GAS SUPPLY TO THE APPLIANCE PRIOR TO REMOVING OR REINSERTING
THE BATTERIES IN THE RECEIVER.
- DURING APPLIANCE INSTALLATION/MAINTENANCE OR IN CASE OF REMOTE CONTROL
MALFUNCTION TURN OFF THE FAN CONTROL MODULE USING THE “ON/OFF” MAIN POWER
SWITCH ON THE FRONT PANEL OF THE FCM.
technicaL Data
Transmitter (Remote Control):
Supply voltage: 4.5 V (three 1.5 V AAA batteries)
Radio frequency: 315 MHz
Receiver:
Supply voltage: 6.0 V (four 1.5 V AA batteries)
Radio frequency: 315 MHz
Fan Control Module:
Supply voltage / frequency: 120 V / 60 Hz
Aux switched output: 120 V / 60 Hz / 2 A
Fan speed output: 120 V / 60 Hz / 1 A
Digital Fireplace Controller:
Supply voltage: DC IN - 7 Vdc - 200mA (Class 2 power supply)
BB IN - 6 Vdc - 200mA (four 1.5 V AA batteries)
Spark voltage / frequency: >15kV / 1Hz
system DescRiption:
The Proame Remote Control System consists of three (3) elements:
1. Proame Transmitter.
2. Proame Receiver and a wiring harness to connect the Receiver to the gas valve, stepper motor and
Fan Control Module.
3. Proame Fan Control Module (FCM)
4. Digital Fireplace Controller (DFC)
9
Page 10
SplitFlow
Operating Instructions
TRANSMITTER (Remote Control with LCD
Display)
The Proame Transmitter uses a streamline
design with a simple button layout and
informative LCD display (Figure 5). The
Transmitter is powered by three (3) AAA type
batteries. A Mode Key is provided to Index
between the features and a Thermostat
Key is used to turn on/off or index through
Thermostat functions (Figure 5 & 6).
Figure 5: Proame Transmitter.
Figure 6: Proame Transmitter LCD Screen.
RECEIVER
The Proame Receiver (Figure 7) connects directly to
the gas valve, stepper motor, DFC, and Fan Control
Module with a wiring harness. The Receiver is
powered by four (4) AA type batteries. The Receiver
accepts commands via radio frequency from the
Transmitter to operate the appliance in accordance
with the particular Proame system conguration.
The Receiver three (3) position slider switch can be
set to one of three positions: ON (Manual Override),
Remote (Remote control), or Off.
Figure 7: Proame Receiver.
FAN CONTROL MODULE
Fan Control Module (FCM) offers the added
ability to control the fan speed through six (6)
speeds, a remotely actuated 120V outlet and
a constantly powered 120V outlet. The FCM
provides DC power to the Receiver allowing the
batteries to be used only when line power is
interrupted or lost (see Figure 8).
Figure 8: Proame Fan Control Module.
10
Page 11
Operating Instructions
WallPlate
Slider
Switch
Receiver
J-Box
Remote mounting the ReceiVeR (optionaL):
The receiver can be removed from the unit and placed inside a standard Junction type wall box or another
convenient location. This installation can take place up to 6’ft (1.8 m) from the appliance control valve.
1. Connect the wiring harness to the back of the
Receiver.
2. Install the Receiver in the Junction box using the
existing J box screws (Figure 9).
3. Insert the four (4) AA type batteries in the battery
compartment with the correct polarity.
4. Place the slider into the cover plate.
5. Put the Receiver switch in the “OFF” position.
6. Make sure the Receiver and cover plate words “ON”
and “UP” are on the same side.
7. Align the slider with the switch on the Receiver and
couple the switch into the slider.
8. Align the screw holes.
9. Using the two (2) screws provided secure the cover
Figure 9: Wall Mounting the Receiver.
plate to the Receiver.
opeRating pRoceDuRe:
Initializing The System For The First Time
Install the four (4) AA batteries into the receiver battery bay. Note the polarity of the battery and insert into
the battery bay as indicated on the Battery cover (+/-). Place the 3-position slider switch in the “Remote”
position (see Figure 7). Using the end of a paper clip, or other similar object, insert the end of the paper clip
into the hole marked “PRG” on the Receiver front cover (see Figure 7).
The Receiver will “beep” three (3) times to indicate that it is ready to synchronize with a Transmitter. Install
the three (3) AAA type batteries in the Transmitter battery bay, located on the base of the Transmitter. With
the batteries already installed in the Transmitter, push the ‘ON’ button. The Receiver will “beep” four (4)
times to indicate the Transmitter’s command is
accepted and sets to the particular code of that
Transmitter. The system is now initialized.
Temperature Indication Display
With the system in the “OFF” position, press the
Thermostat Key and the Mode Key at the same
time. Look at the LCD screen on the transmitter
to verify that a °C or °F is visible to the right of
the Room Temperature display (see Figure 10).
Turn on the Appliance
Press the ON/OFF Key on the Transmitter. The Transmitter display will show all active Icons on the screen. A
single “beep” from the Receiver will conrm reception of the command and will commence to rst ignite the
pilot light, followed by the main burner. This should take about 10 seconds to complete.
Figure 10: Remote Control Display in Farenheit and Celcius.
11
Page 12
RoomTemperature
SetTemperature
ThermostatON
FlameOff
FlameLevel1
FlameLevel5
MaximumFlameLevel
Operating Instructions
Turn off the Appliance
Press the ON/OFF Key on the Transmitter. The Transmitter LCD display
will only show the room temperature and Icon (see Figure 11). A single
“beep” from the Receiver conrms reception of the command and both
the pilot light (if the unit is not set to continuous pilot) and main burner
will turn off.
Room Thermostat (Transmitter Operation)
The Remote Control can operate as a room thermostat. The thermostat
can be set to a desired temperature to control the comfort level in a
room. To activate this function, press the Thermostat Key (see Figure
5). The LCD display on the Transmitter will change to show that the
room thermostat is “ON” and the set temperature is now displayed (see
Figure 11). To adjust the set temperature, press the Up or Down Arrow
Keys until the desired set temperature is displayed on the LCD screen of the Transmitter.
Smart Thermostat (Transmitter Operation)
The Smart Thermostat function adjusts the ame height in accordance to the difference between the set
point temperature and the actual room temperatures. As the room temperature gets closer to the set point
the Smart Function will modulate the ame down. To activate this function, press the Thermostat Key (Figure
6) until the word “SMART” appears to the right of the temperature bulb graphic (Figure 12). To adjust the
set temperature, press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD
screen of the Transmitter.
Figure 11: Remote Control Displays
Set Temperature.
Figure 12: Remote Control’s Smart Flame Function.
Remote Flame Control
The Proame GTMF has six (6) ame levels. With
the system on, and the ame level at the maximum
in the appliance, pressing the Down Arrow Key once
will reduce the ame height by one step until the
ame is turned off. The Up Arrow Key will increase
the ame height each time it is pressed. If the Up
Arrow Key is pressed while the system is on but
the ame is off, the ame will come on in the high
position (refer to Figure 13). A single “beep” will
conrm reception of the command.
12
Figure 13: Remote Control’s Flame Levels.
Page 13
Operating Instructions
Key lock
This function will lock the keys to avoid
unsupervised operation. To activate this function,
press the MODE and UP keys at the same time
and the a lock will appear (see Figure 15). To
de-activate this function, press the MODE and
UP Keys at the same time.
Low Battery Power Detection
Transmitter: The life span of the remote control
batteries depends on various factors: quality of
the batteries used, the number of ignitions of
the appliance, the number of changes to the
room thermostat set point, etc. When the
Transmitter batteries are low, a Battery Icon will
appear on the LCD display of the Transmitter
(see Figure 16) before all battery power is lost.
When the batteries are replaced this Icon will
disappear.
Figure 14: Remote Control with Aux for Accent Lights.
Receiver: The life span of the Receiver batteries
depends on various factors: quality of the
batteries used, the number of ignitions of the
appliance, the number of changes to the room
thermostat set point, etc. When the Receiver batteries are low, No “beep” will be emitted from the Receiver
when it receives an On/Off command from the Transmitter. This is an alert for a low battery condition for the
Receiver. When the batteries are replaced the “beep” will be emitted from the Receiver when the ON/OFF Key
is pressed (See
Manual Bypass Of The Remote System
If the batteries of the Receiver or Transmitter are low or depleted, the appliance can be turned on manually by
sliding the three position slider switch on the Receiver to the ON position. This will bypass the remote control
feature of the system and the appliance main burner will come on.
WARNING: Fire Hazard. Can cause severe injury or death The Receiver causes ignition of the
appliance. The appliance can turn on suddenly. Keep away from the appliance burner when
operating the remote system or activating manual by pass of the remote system.
WARNING: Shock Hazard. Can cause severe injury or death. This device is powered by line
voltage. Do not try to repair this device. In no way is the enclosure to be tampered with or
opened. Disconnect from line voltage before performing any maintenance.
WARNING: Devices rated more than 5A shall not be connected to the OUT receptacle. Devices
rated more than 1A shall not be connected to the FAN receptacle. Devices rated more than 2A
shall not be connected to the AUX receptacle.
Initializing The System For The First Time
Figure 15: Remote Control
Locked.
).
Figure 16: Low Battery
Indicator.
CAUTION: Property Damage Hazard. Excessive heat can cause property damage. The appliance
can stay lit for many hours. Turn off the appliance if it is not going to be attended for any length
of time. Always place the Transmitter where children cannot reach it.
13
Page 14
Maintenance And Service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specically approved with this appliance, may result in property damage or personal injury.
The appliance area should be kept clear and free from combustible materials, gasoline, and other
ammable vapors and liquids.
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not
blocked by anything. The pilot ame should be blue with little or no yellow on the tips.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied person.
Always ensure that the ow of combustion and ventilation air is not obstructed is any way.
cLeaning the gLass:
When the replace is cool, remove the glass door. See maIntenanceanD serVIce - glass Door remoVal.
Check the gasket material on the back of the glass, making sure that it is attached and intact.
During a cold start up, condensation will form on the glass. This is a normal condition with all replaces.
However, this condensation can allow dust and lint to cling to the glass surface. Initial paint curing of the
appliance can leave a slight lm on the glass. The glass will need cleaning after the replace has cooled
off from the rst burn and about two weeks after rst burn. Use a mild glass cleaner and a soft cloth. Abrasive cleaners will damage the glass and painted surfaces. Depending on the amount
of use, the glass should require cleaning no more than two or three times a season. Do not clean the
glass when it is hot.
cLeaning the fiRebox:
Remove the logs carefully, as they are very fragile. Gently remove all the embers and rock wool and
place on a paper towel. Vacuum the bottom of the rebox thoroughly. Carefully clean any dust off the
logs and remove any lint from the burner and pilot. At this time, inspect the burner tube for cracking or
severe warping. If a problem is suspected, contact the dealer. Check the logs for deterioration or large
amounts of soot; a small amount on the logs is normal. Replace the logs and embers as in the seconDary
InstallatIon - log setanD ember InstallatIon section. If new/more embers and rock wool are required,
contact your nearest ENVIRO dealer.
RepLacing the gLass:
The glass in the replace is a high temperature ceramic. If the glass is damaged in any way, a factory
replacement is required (see
to prevent personal injury. Do not operate with the glass front removed, cracked or broken. Removal
and replacement of the glass from the door must be done by a licensed or qualied service person.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
Remove the door (see page 15). The replacement glass will come with a new gasket installed. Remove
any silicone remnants from the door. Apply high temperature silicone to the two vertical faces of the
door and install the new piece of glass with gasket (be sure to maintain edge clearances). Apply even
pressure to the glass to allow the silicone to adhere to the gasket material.
parts lIst). Wear gloves when handling damaged glass door assembly
14
Page 15
Maintenance And Service
check piLotanD buRneR fLames:
Periodically do a visual check of the pilot ames. One ame should encompass
the thermocouple and the other should burn over the burner ports (see
Figure 17). Also check that the burner is operating correctly, refer to Venturi
Adjustment section.
gLass DooR RemoVaL:
Figure 18: Door Release.
Figure 17: Pilot Flame
Figure 19: Door Removal.
Remove the glass door by placing the hooked end of the door release tool in the hole on the
door latch mechanism (see Figure 18) and pulling the latch out then up. When the two (2)
latches have been released, tilt the bottom of the door forward and then lift up to unhook
the top door tabs (see Figure 19).
Re-assemble in the reverse order.
Warning: Do not touch or attempt to remove the glass if the replace is not completely cool.
Never operate the replace with the glass removed.
cLeaning the painteD suRfaces:
Painted surfaces should be periodically wiped with a damp cloth when the unit is cool.
CAUTION GLASS MAY SEPARATE FROM DOOR.
15
Page 16
Maintenance And Service
RemoVing VaLVe coVeR:
The valve cover can be removed to access the gas valve.
1. Use a T-20 screwdriver to remove the four screws that hold down the valve cover shown in Fig. 20.
Figure 20: Valve Cover.
VALVE
COVER
16
Page 17
Maintenance And Service
RemoVing/RepLacing conVection fan:
The fan assembly can be removed to access the convection blower.
1. Use a T-20 screwdriver to remove the screws that hold the Fan Mounting Plate in place See Figure 21.
2. Tilt the assembly back and pull it away from the unit.
3. The Fan is removed from the Mounting Plate by removing the six (6) screws that hold it in place
using a T-20 screwdriver.
4. The fan can then be disconnected from the wiring harness (See Figure 22 for fan wiring).
5. To replace fan, follow steps 1-4 in reverse order.
Temperature Sensor
Black
White
Convection Blower
Figure 22: Fan Wiring.
Figure 21: Fan Mount Removal.
Black
FCM
Green
Ground
17
Page 18
Fuel Conversion
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
WARNING: This conversion kit shall be installed by a qualied service agency in accordance
with the manufacturer’s instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed
exactly, a re, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualied service agency is responsible for
the proper installation of this kit. The installation is not proper or complete until the
operation of the converted appliance is checked as specied in the manufacturer’s
instructions supplied with the kit.
Carefully inspect the orice supplied with this conversion kit. If it has been damaged or is missing,
contact your dealer, distributor or courier company to have it replaced before starting this installation.
NOTE: The unit is shipped from the factory adjusted for use with NATURAL gas.
1. Ensure all the components of the conversion kit are accounted for.
2. If the unit has already been connected to a gas supply, shut off the gas supply to the unit.
CAUTION: The gas supply must be shut off prior to disconnecting the electrical power and before
proceeding with the conversion.
3. If the unit has been run, shut off and allow cooling to room temperature.
4. Remove the glass as shown in the Maintenance and Service - Glass Door Removal.
5. Carefully remove the log set and ember material if they are installed.
6. Remove the burner as shown in the Maintenance and Service - Burner Removal.
7. Convert the pilot injector:
a) Using a
b) Push the slider, with your nger or at head screwdriver.
-Natural gas is marked NAT.
-Propane gas is marked LP with an indicating hole between L and P. It is also marked red.
c) Turn the pilot head a ¼ turn clockwise; back to its original position.
8. Convert the burner orice(s):
a) Remove the main burner orice with a 1/2” deep socket.
b) Put a bead of pipe-thread sealant on the orice threads before installing.
c) Install the new orice from the kit into the orice mount. DO NOT OVER-TIGHTEN.
9. Convert the SIT gas valve:
a) Remove Valve Cover.
b) Use a T-20 driver to remove the two screws that hold the servo regulator to the gas valve.
c) Remove the rubber regulator diaphragm that is situated between the servo regulator and the
valve body and replace it with the one provided in the kit.
d) Install the LP servo regulator, with the new longer T-20 screws included in the kit.
e) Reinstall the Valve Cover plate.
7
/16” wrench, turn the pilot head a ¼ turn counter-clockwise.
18
Page 19
Fuel Conversion
10. Reinstall the burner, brick panels, log set, embers, and glass door. Also refer to seconDary InstallatIon
- InstallIng log setanD embers in your Owner’s Manual. When re-installing the burner, ensure that
the burner to pilot hood relationship is similar to what is shown in Figure 23.
11. Reconnect the electrical power to the unit.
12. Refer to the Operating Instructions to light the unit and verify proper burner ignition and operation
and proper ame appearance.
13. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the
unit has been converted to a different fuel type.
Figure 23. Ignitor assembly
beside the burner.
19
Page 20
Initial Installation
40"
(1016 mm)
minimum
from bottom
of unit
8" (203mm) Mantel
40"
(1016 mm)
minimum
from bottom
of unit
Combustible
Facing
non-combustible
hearth
16"
(406 mm)
minimum
from wall
If hearth is raised
a minimum of 1/2”
18"
(457 mm)
minimum
from wall
If hearth is
flush with flooring
WARNING: Operation of this heater when not connected to a properly installed and maintained
venting system can result in carbon monoxide (CO) poisoning and possible death.
cLeaRancesto combustibLes:
Maintain sufcient clearances for operation, service and
maintenance.
• A minimum distance of 23 1/2” (597 mm) is required
from the centerline of the unit to the sidewalls.
• Minimum clearance for any combustible facing is 40”
(1016 mm) from the bottom of the unit.
• A 8” (203 mm) wide mantel can be mounted at a
minimum height of 40” (1016 mm) from the bottom of
unit.
• If installed with a minimum of 1/2” (13 mm) raised
hearth, there must be a minimum of 16” (406 mm) of
non-combustible material in front of the unit.
• If installed where the hearth is ush with the
combustible ooring, there must be a minimum of 18”
(457 mm) of non-combustible material in front of the
unit.
• Minimum ceiling clearance is 60” (1524 mm) from
bottom of unit.
Figure 24: Mantle width and height.
minimum fiRepLace size:
Table 3: Minimum dimensions of replace for E44 to be installed into.
NOTE: Space must be provided for gas line on right side of unit for servicing purposes.
DiRect Vent:
WARNING: This appliance has been designed to draw room air for proper heat circulation
from the sides of the unit, and out the top front. Blocking or modifying these openings in
any way can create hazardous situations.
The vent length for the E44 must be between 15ft (4.5 m) and 40ft (12 m).
This model is vented with a 3” intake and a 3” exhaust aluminum or stainless steel approved ex vent
leading into a vertical termination cap. The ue collars of this model will t inside of a standard 3” vent
and must be fastened directly to the vent with three screws. The exhaust vent and air intake are both
located on the top of the unit.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been
properly sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must
be installed in the correct locations on the top of the E44.
20
Page 21
Initial Installation
QUALIFIED INSTALLERS ONLY
Venting fiRepLace inseRts:
The ENVIRO E44 may be installed and vented into any solid fuel replace that has been installed in
accordance with the National, Provincial/State and local building codes and has been constructed of noncombustible materials. Before starting, refer to InItIal InstallatIon - preparIng your e44 For InstallatIon.
Please reference the information in Table 4 and Figures 25, and 27.
An approved chimney liner and rain cap must be used. A throat connector or ashing must be installed to
ensure a tight seal, top performance, safety and efciency. Carefully follow the manufacturer’s instructions
that accompany the chimney liner kit. Use double walled aluminum ex vent (3” ex conversion piece and
4”x 6 5/8” cap) from any of the following approved products; Simpson Dura-Vent (Direct Vent GS) or (ICC
Excel Direct). If necessary, remove the vent collar plate from the top of the insert and connect it securely
to the liner with sheet metal screws.
Check for any tears in the liner at this point. IMPORTANT: The screws that hold the vent collar plate in its
approved position must be installed.
NOTE: If the E44 unit is pulled out of its installation, and the vent-air intake system is disconnected
for any reason, ensure that the vent-air intake pipes are re-sealed with high-temperature sealant and
reconnected with three (3) sheet metal screws evenly spaced.
Table 4: Vent termination clearances
Minimum Clearance Description
3 ft (0.9 m)
24 in (0.6 m)
5 ft (1.5 m)
6 ft (1.83 m)Clearance to mechanical air supply inlet.
3ft (0.9m) Clearance to each side of center line extended above meter/regulator assembly.
6 ft (1.83 m)Radial clearance around service regulator vent outlet.
12 in (30 cm)Clearance above grade, verandah, porch, deck, or balcony.
3 ft (0.9 m)
9 in (0.23 m)Exception for inputs up to and including 50,000 Btu/h (15kW)
12 in (0.3 m)
Clearance above the highest point where it passes through a roof surface, refer to
Figure 25.
Clearance above a roof ridge, any other portion of a building, or any other obstruction within a horizontal distance of 10 feet (3 m), refer to Figure 25.
Clearance for a vent or chimney above either the highest connected appliance
drafthood outlet, or ue collar.
Clearance to a building opening or combustion air inlet of another appliance, except with the approval of the authority having jurisdiction for the following reduced
clearances.
Exception for inputs exceeding 50,000 Btu/h (15kW) but not exceeding 100,000
Btu/h (30kW)
3ft (0.9m)
Minimum
2ft (0.6m)
Minimum
Within
10ft (3m)
Figure 25: Roof Clearances.
Roof ridge or
any other portion
of a building
21
Page 22
Initial Installation
QUALIFIED INSTALLERS ONLY
3" (76mm) Exhaust
3" (76mm) Intake
Figure 26: Generic Vent Cap Underside.
The height for the vent must be between 15 ft (4.5 m) and 40 ft (12 m).
Install a sealed vent cap to prevent leakage of room air up through
chimney.
The intake and the exhaust are 3" (76mm).
Measure the height of the chimney beforehand and purchase the
appropriate venting. Never attempt to over-stretch a flexible liner to
accommodate the height of the chimney. Every joint in the venting must
be secured with three (3) #8 x 3/8” HWH sheet metal screws and an
appropriate sealant (either silicone or stove cement).
The flue damper can be fully blocked open or removed for installation of
the E44; the smoke shelves, shields and baffles may be removed if
attached by mechanical fasteners.
The fireplace and fireplace chimney must be clean, in good working order
and constructed of non-combustible materials.
Make sure that all chimney cleanouts are tight fitting and will not permit
air to leak into the chimney.
Refractory, glass doors, screen rails, screen mesh and log grates can be
removed from the fireplace before installing the E44.
Figure 27: Installation of E44 DV .
22
Page 23
Initial Installation
QUALIFIED INSTALLERS ONLY
DiRect Vent VeRticaL Vent teRmination:
instaLLation instRuctions:
1. Plan your installation and clearances to combustibles. The E44 may be installed and vented into
any solid fuel replace that has been installed in accordance with the National, Provincial/State and
local building codes and has been constructed of non-combustible materials. Also refer to the
InstallatIon - preparIng your e44 For InstallatIon and clearancesto combustIbles sections. Refer to
Figure 24 throughout installation.
2. Stretch the Ø3” (76mm) ex vent liners to the length needed to ensure they can be easily connected
to the vent terminals.
3. Install the ex pipe assembly up through the chimney, ensure that the pipe slides through far enough
to connect onto the vent cap.
4. Most vent caps can be installed onto chimneys with ue openings up to 16” (406mm) x 16” (406mm)
and the actual ashing is 18”x18” (refer to Figure 28). If the chimney is smaller the cap should be
trimmed down and folded over.
5. Apply a bead of stove cement sealant to the top section of the Ø3” (76mm) exhaust vent collar plate.
Slide the Ø3” (76mm) ex vent over the ue collar and secure with three (3) sheet metal screws
evenly spaced.
InItIal
6. Place a bead of high temperature silicone on the intake collar of the replace, slide the Ø3” (76mm)
ex intake liner over the collar, secure the ex liner with three (3) sheet metal screws evenly spaced.
7. At the top of the chimney, apply a bead of stove cement sealant to the Ø3” (76mm) pipe of the
exhaust vent terminal (refer to Figure 26). Slide the ex liner onto the vent terminal and secure with
three (3) sheet metal screws evenly spaced.
8. Place a bead of high temperature silicone on the intake collar of the vent terminal (refer to Figure 26).
Slide the Ø3” (76mm) ex intake liner over the collar, secure the ex liner with three (3) sheet metal
screws evenly spaced.
9. Make a tight connection between the gas replace insert ue collar and the replace chimney at the
top of the chimney. Secure the vent terminal to the chimney using adequate sealant, and according
to local building codes.
APPROVED TERMINATIONS:
-Simpson Dura-Vent
46DVA-VCH cap with 46DVA-GK
termination adapter
or 46DVA-CL33 termination kit
-
ICC TM-4SVT cap with TM-CTA
termination adapter
Trim flashing
as required.
18"
(457mm)
18"
(457mm)
Figure 28: Generic Vent Cap Dimensions.
23
Page 24
Initial Installation
QUALIFIED INSTALLERS ONLY
instaLLingtheunit:
• Remove the packaging from the appliance and surround panels; check to make sure there is no
damage. Carefully check the glass door. Do not use the unit if it is damaged. In the event damage is
found, please report it to your dealer as soon as possible.
• Carefully clean the replace and ue before installing the stove. Failure to do so may result in fumes
or soot being blown into the room and may cause a re leading to death or serious injury.
1. Remove the unit from the crating and remove all packaging material from the appliance.
2. Remove door. See
3. Remove log and ember set and all wrapping material from the stove. Remove wrapping material from
log and embers and check for any damage. If damage is observed, do not use unit and contact your
local dealer.
4. Check that the chimney clean outs t properly. The ue damper must be fully blocked open or removed
for installation of the E44; the smoke shelves, shields and bafes may be removed if attached by
mechanical fasteners.
5. If the replace opening is lower than 25” (635 mm), remove the vent collar plate from the top of the
insert by unscrewing the single T-20 Torx screw located on the center top of the stove above the door
opening (see Figure 29). Slide the collar plate backwards. Properly secure the vent collar plate to the
exible vent pipe liner(s) previously installed in the chimney. Be careful not to over-stretch the liner(s).
6. Place the unit part way into the replace. Connect the gas line to the ⅜” NPT pipe nipple at the lower
left rear of the unit using locally approved methods (see
Place the electric cable so it can be connected to the power supply.
7. As you push the unit into its nal position in the replace, if the vent collar plate was removed, reinstall
it to the stove by sliding it along the top of the unit and secure with the screw previously removed.
8. Adjust the levelling legs to ensure the unit is level and high enough if a base shelf and/or riser is to be
installed. There are four levelling legs on the bottom of the unit (shown in Figure 30).
maIntenanceanD serVIce - glass Door remoVal.
InItIal InstallatIon - gas lIne connectIon).
Vent Collar Screw
Figure 29: Vent Collar Plate Screw Location.
24
Figure 30: Levelling Legs Position.
Page 25
Initial Installation
QUALIFIED INSTALLERS ONLY
zeRo cLeaRance (zc) fiRepLace instaLLation:
The base, sidewalls and top structure of the solid fuel rebox cannot be altered with the exception of:
removal of dampers, removal of smoke shelf or bafe, removal of ember catches, removal of log grate,
removal of viewing screen/curtain, and removal of doors. THE ORIGINAL FIREPLACE MAY NEVER BE
RETURNED TO SOLID FUEL USE IN THIS CONDITION.
IMPORTANT: If the factory-built replace has no gas access hole(s) provided, an access hole of 1.5 inch
(37.5 mm) or less may be drilled through the lower sides or bottom of the rebox in a proper workmanship
like manner. This access hole must be plugged with non-combustible insulation after the gas supply line
has been installed. Cutting any sheet-metal parts of the replace, in which the gas replace insert is to
be installed is prohibited.
The included label plate shown below must be permanently attached inside the cavity of the replace
in a visible location.
WARNING: This fireplace has been converted
for the use with a gas fireplace insert only and
cannot be used for burning wood or solid
fuels unless all original parts have been
replaced, and the fireplace re-approved by the
authority having jurisdiction.
Figure 31: Fireplace Altered Plate.
eLectRicaL RequiRements:
The replace must be electrically connected and grounded in accordance with local codes or, in the
absence of local codes, with the current CSA C22.1 Canadian Electrical Code Part 1, Safety Standards For
Electrical Installations, or The National Electrical Code ANSI / NFPA 70 in the US.
WARNING: The electrical grounding instructions must be followed. The fan kit is equipped with a threeprong (grounding) plug for your protection against shock hazard, and should be plugged directly into a
properly grounded three-prong outlet. DO NOT cut or remove the grounding prong from this plug.
C-11168
CAUTION: When servicing controls, label all wires prior to disconnection. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 18
AWG wire with a temperature rating of 105°C
25
Page 26
Initial Installation
5 of 10
QUALIFIED INSTALLERS ONLY
26
Figure 32: Wiring Schematic.
Page 27
Initial Installation
QUALIFIED INSTALLERS ONLY
gas Line connection:
WARNING: Only persons licensed to work with gas piping
may make the necessary gas connections to this appliance.
Gas Line Connection:
• A ⅜” 45° ared tting and ex connector are supplied with
the unit (see Figures 33 and 34). Consult the local authorities
for local codes or use the CAN/CGA B149 (1 or 2) installation
code in Canada. In the US, gas installations follow either local
codes or the current edition of the National Fuel Gas Code
ANSI Z223.1.
• If the factory-built replace has no gas access hole(s)
provided, an access hole of 1.5 in (37.5mm) or less may be
drilled through the lower sides or bottom of the rebox in a
proper workmanship like manner. This access hole must be
plugged with non-combustible insulation after the gas supply
line has been installed.
Figure 33: Gas Connection Location.
• A shut-off valve is supplied with this unit.
• The appliance and its main gas valve must be disconnected
from the gas supply piping system during any pressure
testing of that system at test pressures in excess ½ psi (3.5
kPa). The appliance must be isolated from the gas supply
piping system by closing its equipment shutoff valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than ½ psi (3.5 kPa).
The pressure taps are located on the front side of the valve (see Figure 35).
1. Using a long at bladed screwdriver, turn set screw counter-clockwise to loosen.
5
2. Place
3. Check pressures using a manometer.
4. When nished, remove hose and tighten set screw.
Always check for gas leaks with a soap and water solution after completing the required
pressure test.
/16 in (8 mm) I.D. hose over the pressure taps.
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
Item numberDescrIptIon
1Pilot Adjustment
Screw
2Inlet Pressure Test
2
3
Point
3Outlet Pressure Test
Point
Table 6: Valve Details.
1
Figure 35: Valve Details.
28
Page 29
3
/8”-1/2”
(10-13mm)
Thermocouple
ProperFlame
Adjustment
Initial Installation
QUALIFIED INSTALLERS ONLY
aDjusting the piLot fLame:
The pilot ow adjustment is set to maximum at the factory and should not need to be adjusted. The pilot
ame should envelope ⅜” to ½” (10 to 13mm) of the thermocouple (see Figure 36). However, should
the need arise, follow Steps 1- 2 below.
1. The adjustment screw can be reached through the front of the
unit using a 10 inch long blade head screw driver (see Figure 35
for location on valve).
2. Turn the adjustment screw clockwise to decrease or
counterclockwise to increase pilot ame.
Figure 36: Proper Pilot Flame.
switchingto continuous piLot moDe:
In cold climates, it may be required to run the pilot continuously to keep the vent termination from
freezing up. Flip the toggle switch on the bottom right of the unit to switch between intermittent and
continuous pilot.
Figure 37: Pilot Mode Toggle Switch.
29
Page 30
Secondary Installation
optionaL base sheLf & RiseR:
The E44 Base Shelf (1⅝” (41 mm) high) and Base Shelf Riser (2⅛” (54 mm) high) are components that
can be combined to create a riser with an overall height of 23/16” (55 mm). This shelf can be installed
with or without the riser and can be used when the hearth in front of the unit is lower than the replace
opening. Additional Base Shelf Risers can be fastened together to increase the height in increments
of 2⅛” (54 mm). This Base Shelf may be used in conjunction with the any of the E44 surround panel
options, and it may also be used with the E44 Trimmable Surround. The Base Shelf and Riser are sold
separately.
Installation:
1. If unit is running, turn it off and allow it to cool completely.
2. When using more than one riser each level must be attached using nine (9) #8 T-20 screws provided
(see Figure 38).
3. If installing with riser(s) the Base Shelf is to be fastened to the riser(s) with one T-20 screw at each
end of the back (see Figure 39).
4. The leveling legs on the E44 may need to be adjusted to match the height of the riser and shelf.
5. Center the Base Shelf assembly in front of the unit ush with the bottom of the unit.
6. Install surround if required.
Figure 38: Combining 2 Base Shelf Riser.
30
Figure 39: Installing Base Shelf onto Riser.
Page 31
Secondary Installation
optionaL tRimmabLe paneLs:
Modifying the Surround Panel:
The E44 Trimmable Surround Panels are large rectangular panels that may be cut for use in cases that a nonstandard replace opening (e.g. an arched opening) is to be lled. Optionally this surround can be left uncut
and placed in front of the replace opening.
1. Measure the replace opening and/or make a template of the replace opening.
2. Transfer the measurement to the Trimmable Surround.
3. If desired, offset the measurements by approximately
to be placed just inside the replace opening for a cleaner appearance.
4. Cut along the preferred line (from direct measurements of offset) and remove any sharp edges.
5. The panel can be touched up with a high temperature metallic black paint available from your dealer.
INSTALLATION:
1. Using the supplied hardware install the appropriate mounting brackets onto the trimmable panel using a
T-20 Torx screwdriver. Ensure that the hooks are facing the middle of the panel.
1
/8” (3mm) to the inside; this will allow for the panel
2. Install the Trimmable Panel by securing the four hooks onto the corresponding slots that are on the front of
the E44 unit (See Figures 40 and 41)
3. Ensure that the trimmable panel is centered on the unit in order for the standard panels to t easily.
Figure 40: Panel Slot and
Hook Locations
Figure 41: Trimmable
Panel Installed
31
Page 32
Secondary Installation
suRRounD paneL instaLLation:
WARNING: The surround becomes hot when the unit is operating; ensure that the unit is turned off, and that
it has cooled to room temperature before beginning this installation.
HeightWidth
1
3-Sided Surround30
4-Sided Surround37
Table 7: Surround Dimensions.
Please check components supplied with this kit. If components are missing or have been damaged, contact your
dealer, distributor or courier company before starting this installation.
IMPORTANT: The panel must not seal ventilation openings in the replace.
INSTALLATION:
Lift the panel upright in front of the replace with the top mounting ange pointing towards the replace. Slide
the panel up untill the surround panel hooks engage the mounting slots on the unit (see Figure 42). Firmly press
the surround panel down in order to install it tightly. Ensure the panel is secure before releasing it.
REMOVAL:
/8” (765 mm)45” (1143 mm)
1
/16” (941 mm)45” (1143 mm)
Lift the surround straight up in order to unhook it from the slots. Pull the surround away from the replace.
Figure 42: Surround Mounting Slot Locations.
CLEANING:
Painted surfaces should be periodically wiped with a damp cloth. Never clean the face when it is hot.
32
Page 33
Secondary Installation
fiRebox LineRanD buRneR tube RemoVaL:
NOTE: The rebox liners are fragile and should be handled gently.
1. Ensure the E44 is turned off and allow the unit to cool.
2. Remove the glass door as shown in the
maIntenanceanD serVIce - glass Door remoVal.
WARNING: Do not touch or attempt to remove
the glass if the replace is not completely cool.
Never operate the replace with the
glass removed.
3. Remove the log set and all ember material (if
installed).
4. Use the following steps to remove the liners
and the burner tube.
NOTE: Follow the steps in the reverse order for
reassembly.
Figure 43: Carefully remove the front brick panel
on the bottom of the rebox by lifting it up.
Figure 44: To remove the burner tube, gently pull
it out of the venturi box.
Figure 46: Remove the rear brick panel by pulling
it forward off of the ledge.
Figure 45: The side brick panels can be removed
by pulling them towards the center of the rebox.
Figure 47: Firebox with all brick panels and burner
tube removed.
33
Page 34
Secondary Installation
Log setanD embeR instaLLation:
NOTE: The logs are fragile and should be handled gently.
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
The underside of the logs are contoured to make alignment easier. Using the pictures provided, carefully
set the logs in place (see Figures 48 through 56).
Figure 48: The rebox showing the brick panels
and burner tube already installed.
Figure 48. Empty rebox.
Figure 49: The back log rests on top of the
pilot shield and against the back of the air
diverter at the rear of the rebox.
Figure 50: Place the ember bed in the center of
the burner tube and pull it forward as far as it will
go and lightly press down on the front edge to
ensure that it is placed properly. Make sure it does
not obstruct any part of the burner.
Figure 49. First Stage Log Set Installation.
34
Figure 50. Second Stage Log Set Installation.
Page 35
Secondary Installation
WARNINGS: DO NOT pack this ember material as this could create an unsafe condition. The pieces
should be lightly placed so they don’t block any of the burner ports.
CAUTION: Use only the type of ember material supplied with this replace. Due to the irregular size
of the ember material, there is more than required. Use of other foreign materials on the burners may
create dangerous conditions.
Figure 51: Place the log grate in front of the
burner tube using the two slotted mounts
underneath.
Figure 51. Third Stage Log Set Installation.
Figure 52. Fourth Stage Log Set Installation.
Figure 52: The ember wool comes in chunks
that can be ripped into smaller pieces.
Place quarter-sized pieces of the ember wool
irregularly onto and around the front of the
burner to create a realistic look.
Figure 53: The left and right logs t as shown.
The bottom of the left log is contoured to t
the log grate.
Figure 53. Fifth Stage Log Set Installation.
35
Page 36
Secondary Installation
NOTE: While the glass is still removed, it is recommended that the gas line be purged by lighting the
pilot. Never operate the replace with the glass door removed.
When lighting the replace for the rst time since the log set and embers have been installed/replaced,
watch for ignition at ALL the burner ports. If a long delay is noticed, turn the appliance off and wait for it
to cool down. Remove the glass and rearrange the ember material, making sure none of the burner port
holes are blocked.
Figure 54: Place the small left and right logs
as shown. The bottoms of both pieces have
contours to t on the log grate.
Figure 54. Sixth Stage Log Set Installation.
Figure 55: Place the two center logs as shown.
The log on the left has a hole on the underside
that ts over a pin on the log below it.
Figure 56: Place the two large outer logs as
shown. The bottom ends of the logs will t the
shape of the log grate.
Figure 55. Seventh Stage Log Set Installation.
36
Figure 56. Eighth Stage Log Set Installation.
Page 37
Trouble Shooting
Diagnostic fLash coDes:
1. Fail to ignite: If there is no positive ignition, the board will go into lock out and the LED will blink 3 times
in intervals until the system is reset.
2. Low battery condition (<4V): the LED indicator will blink one (1) time in intervals.
3. Parasitic Pilot Flame: the LED indicator will blink two (2) times in intervals.
4. System Lock out: the LED indicator will blink three (3) times in intervals.
Additional Ignition Information
1. The Proame DFC Board will try two (2) times for ignition.
2. Each try for ignition will last approximately 60 seconds.
3. The wait time between the two tries is approximately 35 seconds.
Figure 57: Proame DFC Board with LED Indicator attached.
37
Page 38
Trouble Shooting
ProblemPossible CauseSolution
Thermostat
does not
work
No spark
generation
No pilot
ame ignition
The pilot ame has gone out
The On/Off switch is turn to OFF
The thermostat is set too high
Spark develops near the pilot
assembly or could occur onboard
No spark from the igniter
Air in the gas line
Pilot gas pressure dropout upon
main burner gas valve opening
No gas ow out of the pilot burner
· Turn it ON
· Set the thermostat to a lower temperature
· Check pilot assembly wiring
· Check for broken or poor connection from the sparker to the
electrode
· Check for the spark shorting or arcing at other locations
· Check for defective sparker and spark electrode
· See “no spark generation”
· It takes a while for all the air to purge out of the pilot before gas
can reach the pilot and ignite
· Check gas mains supply and pressure
· Check gas valve wirings and connections to the board
· Check the pilot burner for obstruction
· Check the wirings and connections between the pilot assembly and
the board
· Check the correct gas type settings on the valve and pilot burner
assembly orice
Pilot will not
remain lit
Remote
control does
not work
No reaction
to command
Problem with Flame Sensor circuit
Restrictor setting
The pilot light has gone out
The remote is too far away from
the heater
The remote control receiver is
turned “OFF”
One of the two remote control or
receiver batteries are dead
Receiver or transmitter batteries
are low
A maximum number of failed
ignitions or ame restorations have
been reached.
· Check for proper connection of the Flame Sensor to the DFC board
· Check pilot for full ame impingement around Flame Sensor
· If ame is too small, check gas pressure, adjust pilot rate screw,
check pilot head for damage
· Ensure the ground wire is properly attached to the pilot mounting
bracket and that it is makes a good electrical connection.
· Use the correct restrictor setting for the venting conguration
· See “Pilot will not remain lit”
· Use the remote closer to the heater
· Check the remote control instructions
· Replace the batteries
· Replace the batteries
· Remove any possible blocking conditions. See “locking conditions”
· See how to reset the board from Lockout
No communication between the
remote control and the receiver
38
· Reprogram the transmitter to the receiver.
· Follow the initializing system for the rst time
Page 39
TroubleShooting
ProblemPossible CauseSolution
· Turn the system off by pressing the ON/OFF button on
the transmitter
· After approximately 2 seconds press the ON/OFF button
on the transmitter again.
· In the manual ame control mode, use the down arrow
button to reduce the ame to off, indicated by the word
Locking
conditions
Main burners
will not start
Reset the Proame DFC board
The pilot ame has gone out· See “Pilot will not remain lit”
The remote control is not working
correctly
The thermostat is disconnected or
set too high
Problem with thermopile circuit
OFF displayed on the transmitter LCD screen.
· Wait approximately 2 seconds and press the up arrow
button, the ignition sequence will start.
· With the transmitter off, move the slider switch on the
receiver to the OFF position.
· Wait approximately 2 seconds and move the receiver
slider switch to the ON position.
· Replace the batteries
· Set the thermostat to a lower temperature
· Check gas line pressure
· Check wiring to thermostat for breaks
· Check for ame impingement on thermopile
Flame lifting
Blue Flames
Glass fogs up
Flames are
burning
“dirty” or
sooting
Leak in vent pipe· Check for leaks in vent connections
Improper vent conguration· Check vent conguration with manual
· Check to see if terminal is on correctly
Terminal may be re-circulating ue
gases
The heater has just been started
Improper air shutter adjustment· Adjust air shutter – contact your dealer
Normal condition: after the
appliance warms up the glass will
be clear.
The logs or glasses are placed
incorrectly
Improper air shutter adjustment
Incorrect rating input
· May need to install high wind termination cap.
· Contact dealer
· Normal during start up: ame will yellow as the replace
heats up
**Due to additives in gas, glass may get hazy during
operation** Clean as needed.
· Check log positioning
· Check level of glasses layout
· Increase primary air by opening the air shutter and/or by
opening the vent restrictor
· Check for proper venting and blockage of the vent
termination
· See also “Burners will not remain lit”
· Check manifold pressure and clock input rating for overring
39
Page 40
Parts List
Reference
Number
1DV Flue Adaptor Bottom Gasket50-2516
2DV Flue Adapter C/W Gasket50-2684
3Door Latch Mechanism (Set of 2)50-2687
4Door Release Tool50-2510
5Digital Fireplace Controller50-2781
6 SIT 885 Valve w/ NG Stepper Motor50-2682
7E44 Door Assembly - Complete50-2685
8Glass C/W Gasket (30.625” x 22.25”)50-2686
9Dual Bulb Door Gasket (10ft)50-634
10E44 Log Grate50-2688
11120 Ceramic Fan Temp SensorEC-001
12Remote Receiver50-2007
13Fan Control Module50-2031
14E44 Pilot Shield50-2691
15IPI Pilot Assembly50-2547
16Convection Fan50-2493
17Burner Tube50-2504
-Ceramic Wool Embers Only50-893
-Wire Harness - Receiver50-2008
-Wire Harness - DFC50-2009
- Proame GTMF Remote Transmitter50-2692
- Valve Pressure Check Extension Tube50-2548
- E44 Owners Manual50-2628
- Domestic Power Cord (115 V)EC-042
-Heyco Strain ReliefEC-044
- 12 oz. Can of Metallic Black Touch Up PaintPAINT-12-MB
-E44 Log Set (10 Pcs)50-2679
- E44 Conversion Kit - NG to LP50-2680
- E44 Conversion Kit - LP to NG50-2681
- E44 Valve Assembly50-2683
- E44 Burner Support Brackets (Set of 2)50-2689
- E44 Burner Air Diverters (Set of 2)50-2690
Part DescriptionPart Number
40
Page 41
OPTIONS List
Reference
Number
1E44 Contemporary Surround Panel (45” x 30
2E44 Extruded Surround Panel (45” x 30
3E44 Keystone Surround Panel (45” x 30
4E44 Cape Cod Steel Doors (45” x 30
Sher wood Industries Ltd. (“Sherwood”) hereby warrants, subject to the terms and
conditions herein set forth, this product against defects in material and workmanship
during the specified warranty period starting from the date of original purchase at retail.
In the event of a defect of material or workmanship during the specified warranty period,
Sherwood reserves the right to make repairs or to assess the replacement of a defective
product at Sherwood’s factory. The shipping costs are to be paid by the consumer.
All warranties by Sherwood are set forth herein and no claim shall be made against
Sherwood on any oral warranty or representation.
Conditions
A completed warranty registration must be submitted to Sherwood within 90 days
of original purchase via the online warranty registration page or via the mail-in
warranty registration card provided. Have the installer fill in the installation data
sheet in the back of the manual for warranty and future reference.
This warranty applies only to the original owner in the original location from date of
install.
The unit must have been properly installed by a qualified technician or installer, and
must meet all local and national building code requirements.
The warranty does not cover removal and re-installation costs.
Sherwood Industries Ltd. reserves the right to make changes without notice.
Sherwood Industries Ltd. and its employees or representatives will not assume
any damages, either directly or indirectly caused by improper usage, operation,
installation, servicing or maintenance of this appliance.
A proof of original purchase must be provided by you or the dealer including serial
number.
Exclusions
An expanded list of exclusions is available at www.enviro.com/help/warranty.html
This warranty does not cover:
Damage as a result of improper usage or abuse.
Damage caused from over-firing due to incorrect setup or tampering.
Damage caused by incorrect installation.
To the Dealer
Provide name, address and telephone number of purchaser and date of purchase.
Provide date of purchase. Name of installer and dealer. Serial number of the
appliance. Nature of complaint, defects or malfunction, description and part # of any
parts replaced.
Pictures or return of damaged or defective product may be required.
To the Distributor
Sign and verify that work and information are correct.