Enviro CFR0404, CFR0506, CFR0504, CFR0604, CFR0606 User Manual

...
December, 2005 • Part No. PX-00-0005
Features and Benefits............................................................................................................................2
Construction Features ...........................................................................................................................4
Application and Selection .....................................................................................................................6
Primary Airflow Calibration ...................................................................................................................9
Dimensional Data.................................................................................................................................10
General Selection Data (Standard PSC Motor) .....................................................................................12
Sound Power Data ...............................................................................................................................14
ECM™ Fan Motor Option .....................................................................................................................18
General Selection Data ...................................................................................................................19
Fan Performance Data ....................................................................................................................20
ARI Ratings...........................................................................................................................................21
Electric Heat .........................................................................................................................................22
Hot Water Coil Data.............................................................................................................................23
Guide Specifications.............................................................................................................................30
Standard and Optional Features ..........................................................................................................32
CFR • TABLE OF CONTENTS
2
CFR Catalog • ©December, 2005 Environmental Technologies, Inc.
©December, 2005 Environmental Technologies, Inc. 6750 Bryan Dairy Rd. • Largo, FL 33777 Stock ID: CAT-CFR • Part No. PX-00-0005
Model CFR is Designed for QUIET
, EFFICIENT COMFORT
Model CFR fan terminals are specif­ically designed for quiet operation. They also offer improved space com­fort and flexibility for a wide variety of HVAC systems. This is critical in today’s buildings, where occupants are placing more empha­sis on indoor acoustics.
Occupant-Sensitive Design
Due to heightened interest in Indoor Air Quality, many HVAC system designers are focusing on the effects of particulate contam­ination within a building’s occupied space. Often, HVAC system noise is overlooked as a source of occu­pied space contamination. The CFR terminal is specifically designed to eliminate obtrusive fan noise from reaching the occupants, while pro­viding constant air motion in the space.
Occupants will benefit from the CFR design that minimizes low fre­quency (125Hz-250Hz) sound levels that typically dominate the space sound level. The CFR also minimizes the fluctuation in sound levels that occur during VAV damper modu­lation.
For the Building Designer: FLEXIBILITY
Selection and Layout. The CFR pro-
vides flexibility in system design. Reduced noise at the fan terminal allows the system designer to place properly sized units directly above occupied spaces. It is not neces­sary to use the crowded space above a hall or corridor to locate the equipment. This will reduce lengthy and expensive discharge duct runs. The standard shallow cas­ing height (14" up to 1000 CFM) minimizes conflict with other sys­tems competing for ceiling space.
The FlowStar
TM
sensor ensures accu­rate control, even when space constraints do not permit long straight inlet duct runs to the ter­minal.
Sizes. Model CFR terminals are
available in nine fan sizes to han­dle airflow capacities between 100 and 4800 CFM. Most fan sizes are available with three primary air valve sizes to optimize the unit fan and primary air valve combinations required by current industry needs.
An ENVIRO-TEC
®
Windows®based Computer Selection Program is available on CD-ROM to facilitate the selection process. Contact your ENVIRO-TEC
®
representative to obtain a copy of this powerful and time-saving program.
F
EATURES AND BENEFITS
GENERAL NOTES
All data herein is subject to change without notice. Some drawings are not shown in this catalog. Refer to www.enviro-tec.com for current catalog and submittal drawings.
Drawings not for installation purposes; refer to IOM manual at www.enviro-tec.com.
Construction drawings and performance data contained herein should not be used for submittal purposes.
ETL Listing Number 476203.
FEATURES AND BENEFITS • CFR
©May, 2006 Environmental Technologies, Inc. • CFR Catalog
3
For the Contractor: CONVENIENCE
Quality. All CFR terminals are thor-
oughly inspected during each step of the manufacturing process, including a comprehensive “pre-ship” inspection, to assure the highest qual­ity product available. Each unit is also “run tested” before leaving the factory to ensure trouble free field “start-up.”
Quick Installation. A standard
single point electrical main power connection is provided. Electron­ic controls and electrical components are located on the same side of the casing for quick access, adjustment, and trou­bleshooting. Installation time is minimized with the availability of factory calibrated ENVIRO-TEC
®
controls.
Finite fan speed adjustment is accomplished with an electronic SCR controller. The SCR fan speed con­troller is manufactured by ENVIRO-TEC
®
and is compatible with the fan motor. This minimizes electronic interference and har­monic distortion that occurs from non-compatible motor and SCR components. Increased motor life and efficiency result from the compatible design.
CFR terminals utilize three tap motors that accommodate a broad range of flow and static pressure field conditions while dramatical­ly increasing efficiency.
The FlowStar
TM
sensor ensures accu­rate airflow measurement, regardless of the field installation conditions. A calibration label and wiring dia­gram is located on the terminal for quick reference during start-up.
The terminal is constructed to allow installation with standard metal hanging straps. Optional hanger brackets for use with all­thread support rods or wire hangers are also available.
For the Owner: V
ALUE AND SECURITY
Quality. All metal components are
fabricated from galvanized steel. Unlike most manufacturers’ ter­minals, the steel used in the CFR is capable of withstanding a 125 hour salt spray test without show­ing any evidence of red rust.
Energy Efficiency. In addition to
quiet and accurate temperature con­trol, the building owner will benefit from lower operating costs. The highly amplified velocity pressure signal from the FlowStar
TM
inlet sen­sor allows precise airflow control at low air velocities.
The FlowStar
TM
sensor’s airfoil shape provides minimal pressure drop across the terminal. This allows the central fan to run at a lower pres­sure and with less brake horsepower. Energy efficient three tap, three winding, permanent split capaci­tor fan motors are manufactured to ensure efficient, quiet, reliable, and low maintenance operation.
Three tap motors provide superi­or energy efficiency over single speed motors by delivering three separate horsepower outputs. For example, a nominal 1/2 HP motor delivers 1/3 HP on medium tap and 1/4 HP on low tap. This allows the motor to operate at a higher efficiency when at a reduced fan capacity.
Fan terminals that utilize a single speed motor must rely solely on an SCR controller to obtain the reduc­tion in fan capacity. At minimum turndown, they suffer from exces­sive power consumption and high motor winding temperatures, sig­nificantly reducing the motor life.
As an option, Model CFR is avail­able with an ECM™ fan motor, providing efficiency ratings between 70% and 80% for most applications.
Agency Certification. Model CFR
terminals, including those with electric heat, are listed with ETL as an assembly, and bear the ETL label.
CFR terminals comply with applic­able NEC requirements, are tested in accordance with ARI Standard 880, and are certified by ARI.
Maintenance and Service. CFR fan
terminals require no periodic main­tenance other than optional filter replacement. If component replace­ment becomes necessary, the unit is designed to minimize field labor. The bottom casing panels can be removed to provide easy access to the fan assembly, and the motor electrical leads are easily unplugged.
Controls. Model CFR terminals are
available with analog electronic, con­signment DDC, and pneumatic controls. ENVIRO-TEC
®
manufac­tures a complete line of analog electronic controls specifically designed for use with CFR termi­nals. These controls are designed to accommodate a multitude of control schemes.
From the most basic to the most sophisticated sequence of opera­tion, the controls are designed by experts in VAV terminal operation. Refer to the Electronic Controls Selection Guide, and the Pneu­matic Controls Selection Guide for a complete description of the sequences and schematic drawings that are available.
Standard features include the patented FlowStar
TM
airflow sensor, ETL Listing, NEMA 1 enclosure, 24 volt control transformer, floating modulating actuator, brass bal­ancing tees and plenum rated tubing.
CFR • CONSTRUCTION FEATURES
4
CFR Catalog • ©May, 2006 Environmental Technologies, Inc.
Model CFR
The CFR terminal incorporates many unique features. Most of these standard
features are expensive options for other manufacturers.
Integral discharge collar simplifies field installation
All unit configurations listed with ETL for safety compliance
Product label includes tagging, airflow, and electrical information
Mechanical lock construction ensures lowest possible casing leakage
Full bottom removable access panels
Low leakage damper incorporates closed cell foam gasket
Roll formed inlet collar with integral
stiffening ribs adds strength and rigidity
Patented FlowStar
TM
airflow sensor
(Patent #5,481,925)
Galvanized steel casing withstands 125 hour salt spray test per ASTM B-117
Mechanically fastened insulation for added security
3/4" thick, 4lb/ft
3
skin, dual density insulation complying with UL 181 and NFPA 90A
Fan assembly utilizes a forward curved, dynamically balanced, galvanized wheel with a direct drive motor
Electrical devices installed within a NEMA 1enclosure, with single point power connection
Optional Construction Features
• ECM™ fan motor
• Mounting brackets to accept all-thread hanging rods or wire hangers
• Double wall construction
• Scrim reinforced foil faced insulation meeting ASTM C1136 for mold, mildew, and humidity resistance
• Filter located at induction inlet
• Hot water (CFR-WC), steam, or electric heating coils (CFR-EH) mounted at unit discharge. Access plate upstream of hydronic coil is standard.
• Low temperature construction for use in thermal storage applications. Includes thermally isolated primary air inlet and composite damper shaft.
• Factory control options: analog electronic, DDC electronic, pneumatic
• Factory piping packages (refer to Piping Packages catalog, Stock ID CAT-PIPING)
• Induction inlet gravity damper reduces radiated NC level by up to 2 NC at full cooling condition.
CONSTRUCTION FEATURES • CFR
©December, 2005 Environmental Technologies, Inc. • CFR Catalog
5
Each pressure input signal is routed to the center averaging chamber
Equal concentric circular areas
Sizes 6 & 8: 3 Circles Sizes 10 & 12: 4 Circles Sizes 14 & 16: 5 Circles (shown)
Total pressure measured at the center of each concentric circle for maximum accuracy, as outlined in ASHRAE Fundamentals Handbook.
Sizes 6 & 8: 12 Sensing Points Sizes 10 & 12: 16 Sensing Points Sizes 14 & 16: 20 Sensing Points
Brass field pressure measuring tap
Airfoil shaped averaging chamber for low pressure loss and noise
Pressure output is routed behind probe to minimize pressure loss and noise
Accurate and Energy-Saving Airflow Control
With The Patented FlowStar™ Sensor
Many VAV terminals waste ener­gy due to an inferior airflow sensor design that requires the minimum CFM setpoint to be much higher than the IAQ cal­culation requirement. This is common with interior spaces that will be effected year round. These inferior VAV terminals waste energy in several ways. First, the primary air fan (e.g. AHU) supplies more CFM than the building requires. The higher minimum CFM setpoint overcools the zone with VAV terminals without inte­gral heat. To maintain thermal comfort a building engineer would need to change the minimum set­point to zero CFM compromising indoor air quality. Inferior VAV terminals with integral heat pro­vide adequate comfort in the space but waste significant ener­gy as energy is consumed to mechanically cool the primary air only to have more energy consumed to heat the cooled primary air. Significant energy sav­ings is obtained with proper sizing and by making sure approved VAV terminals are capa­ble of controlling at low CFM setpoints, providing the mini­mum ventilation requirement.
Currently, most DDC controllers have a minimum differential pres­sure limitation between 0.015" and
0.05" w.g. The major DDC man-
ufacturers can control down to
0.015" w.g. An airflow sensor that does not amplify, e.g., a Pitot tube, requires about 490 FPM to devel­op 0.015" w.g. differential pressure. The FlowStar develops
0.015" w.g. pressure with only 290 FPM on a size 6 terminal and less than 325 FPM for a size 16. Con­sequently, VAV terminals utilizing a non-amplifying type sensor could have minimum CFM's that are well over 50% higher than an ENVIRO-TEC terminal. Many air­flow sensors provide some degree of amplification simply due to the decrease in free area of the inlet from large area of the sensor. These VAV terminals still require minimum CFM's up to 30% high­er than an ENVIRO-TEC terminal, have higher sound levels, and higher pressure drop requiring additional energy consumption at the primary air fan.
A VAV system designed with ENVIRO-TEC terminals con­sumes significantly less energy than a comparable system with competitor's terminals. The FlowStar airflow sensor reduces energy consumption by allowing lower zone minimum CFM set­points, greatly reducing or eliminating “reheat”, and by imposing less resistance on the primary air fan.
The ENVIRO-TEC®air valve features the Flow­Star™ airflow sensor which has brought new meaning to airflow control accuracy. The multi-axis design utilizes between 12 and 20 sensing points that sample total pressure at center points within equal concentric cross- sectional areas, effectively traversing the air stream in two planes. Each distinct pressure reading is averaged with­in the center chamber before exiting the sensor to the controlling device.
This sensor adds a new dimension to signal amplification. Most differential pressure sensors provide a signal between .5 and 2 times the equivalent velocity pressure signal. The FlowStar™ provides a differential pressure signal that is 2.5 to 3 times the equivalent velocity pressure signal. This amplified signal allows more accurate and stable airflow control at low airflow capacities. Low airflow control is critical for indoor air quality, reheat minimization, and preventing over cool­ing during light loads.
Unlike other sensors which use a large probe surface area to achieve signal amplification, the FlowStar™ utilizes an unprecedented streamline design which generates amplified signals unrivaled in the industry. The streamlined design also generates less pressure drop and noise.
The VAV schedule should specify the minimum and maximum airflow setpoints, maximum sound power levels, and maximum air pressure loss for each terminal. The specification for the VAV terminal must detail the required performance of the airflow sensor. For maximum building occupant satisfaction, the VAV system designer should specify the airflow sensor as suggested in the Guide Specifications of this catalog.
FlowStar™ Airflow Sensor
Patent #5,481,925
CFR • APPLICATION AND SELECTION
6
CFR Catalog • ©December, 2005 Environmental Technologies, Inc.
PURPOSE OF SERIES FLOW FAN TERMINALS
Series flow fan powered termi­nals offer improved space comfort and flexibility in a wide variety of applications. Substantial operat­ing savings can be realized through the recovery of waste heat, reduced central fan horsepower require­ments and night setback operation.
Heat Recovery. The CFR recovers
heat from lights and core areas to offset heating loads in perimeter zones. Additional heat is available at the terminal unit using electric, steam, or hot water heating coils. Controls are available to energize remote heating devices such as wall fin, fan coils, radiant panels, and roof load plenum unit heaters.
IAQ. The CFR enhances the indoor
air quality of a building by providing constant air motion, and higher air volumes in the heating mode than typically provided by straight VAV single duct terminals or parallel flow fan terminals. The higher air capacity provides continuous air motion in the space and lowers the heating discharge air temperature. This combination improves air cir­culation, preventing accumulation of CO
2
concentrations in stagnant areas. Increased air motion improves occupant comfort. The higher air capacity also improves the performance of diffusers and minimizes diffuser “dumping”.
ACOUSTICAL CONCEPTS
The focus on indoor air quality is also having an effect on proper selection of air terminal equip­ment with respect to acoustics.
Sound. At the zone level, the
terminal unit generates acoustical energy that can enter the zone along two primary paths. First, sound from the unit fan can propagate through the downstream duct and diffusers before entering the zone (referred
to as Discharge or Airborne Sound). Acoustical energy is also radiated from the terminal casing and trav­els through the ceiling cavity and ceiling system before entering the zone (referred to as Radiated Sound).
To properly quantify the amount of acoustical energy emanating from a terminal unit at a specific oper­ating condition (i.e. CFM and static pressure), manufacturers must mea­sure and publish sound power levels.
The units of measurement, decibels, actually represent units of power (watts). The terminal equipment sound power ratings provide a consistent measure of the generated sound independent of the envi­ronment in which the unit is installed. This allows a straight for­ward comparison of sound performance between equipment manufacturers and unit models.
Noise Criteria (NC). The bottom
line acoustical criteria for most projects is the NC (Noise Criteria) level. This NC level is derived from resulting sound pressure levels in the zone. These sound pressure lev- els are the effect of acoustical energy (sound power levels) entering the zone caused by the ter­minal unit and other sound generating sources (central fan sys­tem, office equipment, outdoor environment, etc.).
The units of measurement is once again decibels; however, in this case decibels represent units of pressure (Pascals), since the human ear and microphones react to pres­sure variations.
There is no direct relationship between sound power levels and sound pressure levels. Therefore, we must predict the resulting sound pressure levels (NC levels) in the zone based in part by the published
sound power levels of the terminal equipment. The NC levels are total­ly dependent on the project specific design, architecturally and mechan­ically. For a constant operating condition (fixed sound power levels), the resulting NC level in the zone will vary from one project to another.
ARI 885. A useful tool to aid in pre-
dicting space sound pressure levels is an application standard referred to as ARI Standard 885. This stan­dard provides information (tables, formulas, etc.) required to calculate the attenuation of the ductwork, ceil­ing cavity, ceiling system, and conditioned space below a termi­nal unit. These attenuation values are referred to as the “transfer function” since they are used to transfer from the manufacturer’s sound power levels to the esti­mated sound pressure levels resulting in the space below, and/or served by the terminal unit. The standard does not provide all of the neces­sary information to accommodate every conceivable design; howev­er, it does provide enough information to approximate the transfer function for most appli­cations. Furthermore, an Appendix is provided that contains typical attenuation values. Some manu­facturers utilize different assumptions with respect to a "typical" project design; therefore, cataloged NC levels should not be used to com­pare acoustical performance. Only certified sound power levels should be used for this purpose.
GENERAL DESIGN RECOMMENDATIONS FOR A QUIET SYSTEM
The AHU. Sound levels in the zone are frequently impacted by cen­tral fan discharge noise that either breaks out (radiates) from the ductwork or travels through the dis­tribution ductwork and enters the zone as airborne (discharge) sound.
APPLICATION AND SELECTION • CFR
©December, 2005 Environmental Technologies, Inc. • CFR Catalog
7
Achieving acceptable sound levels in the zone begins with a proper­ly designed central fan system which delivers relatively quiet air to each zone.
Supply Duct Pressure. One primary
factor contributing to noisy systems is high static pressure in the primary air duct. This condition causes high­er sound levels from the central fan and also higher sound levels from the terminal unit, as the primary air valve closes to reduce the pressure. This condition is compounded when flexible duct is utilized at the ter­minal inlet, which allows the central fan noise and air valve noise to break out into the ceiling cavity and then enter the zone located below the terminal. Ideally, the system static pressure should be reduced to the point where the terminal unit installed on the duct run associat­ed with the highest pressure drop has the minimum required inlet pres­sure to deliver the design airflow to the zone. Many of today’s HVAC systems experience 0.5" w.g. pressure drop or less in the main trunk. For systems that will have substantially higher pressure variances from one zone to anoth­er, special attention should be paid to the proper selection of air ter­minal equipment.
To date, the most common approach has been to select (size) all of the ter­minals based on the worst case (highest inlet static pressure) condi­tion. Typically, this results in 80% (or higher) of the terminal units being oversized for their application. This in turn results in much higher equip­ment costs, but more importantly, drastically reduced operating efficiency of each unit. This conse­quently decreases the ability to provide comfort control in the zone. In addition, the oversized terminals cannot adequately control the min­imum ventilation capacity required in the heating mode.
A more prudent approach is to uti­lize a pressure reducing device upstream of the terminal unit on those few zones closest to the central fan. This device could sim­ply be a manual quadrant type damper if located well upstream of the terminal inlet. In tight quarters, perforated metal can be utilized as a quiet means of reducing system pressure. This approach allows all of the terminal units to experience a similar (lower) inlet pressure. They can be selected in a consistent manner at lower inlet pressure conditions that will allow more optimally sized units.
Inlet duct that is the same size as the inlet collar and as straight as pos­sible will achieve the best acoustical performance. For critical applica­tions, flexible duct should not be utilized at the terminal inlet.
Zoning. On projects where inter-
nal lining of the downstream duct is not permitted, special consider­ations should be made to assure acceptable noise levels will be obtained. In these cases, a greater number of smaller zones will help in reducing sound levels. Where pos­sible, the first diffuser takeoff should be located after an elbow or tee and a greater number of small necked diffusers should be uti­lized, rather than fewer large necked diffusers.
The downstream ductwork should be carefully designed and installed to avoid noise regeneration. Bull head tee arrangements should be located sufficiently down­stream of the terminal discharge to provide an established flow pattern downstream of the fan. Place diffusers downstream of the terminal after the airflow has completely developed.
Downstream splitter dampers can cause noise problems if placed too close to the terminal, or when excessive air velocities exist. If tee arrangements are employed, volume dampers should be used in each branch of the tee, and bal­ancing dampers should be provided at each diffuser tap. This arrange­ment provides maximum flexibility in quiet balancing of the system. Casing radiated sound usually dic­tates the overall room sound levels directly below the terminal. Because of this, special consideration should be given to the location of these terminals as well as to the size of the zone. Larger zones should have the terminal located over a corri­dor or open plan office space and not over a small confined private office. Fan powered terminals should never be installed over small occupied spaces where the wall partitions extend from slab-to­slab (i.e. fire walls or privacy walls).
Fan Terminal Isolation. Model CFR fan terminals are equipped with suf­ficient internal vibration dampening means to prevent the need for addi­tional external isolation. Flexible duct connectors at the unit dis­charge typically do more harm than good. The sagging membrane causes higher air velocities and turbulence, which translates into noise. Furthermore, the discharge noise breaks out of this fitting more than with a hard sheet metal fitting.
IDEAL DUCT DESIGN
Small Necked Diffusers
High Quality
VAV Terminal
with Low
Sound Levels
Minimum
Required
Inlet Static
Pressure
Multiple Branch Take-Offs
Damper Located at Take-Off
Short Length of
Non-Metallic Flexible Duct
CFR • APPLICATION AND SELECTION
8
CFR Catalog • ©December, 2005 Environmental Technologies, Inc.
SELECTION GUIDELINES
The CFR fan terminal has been designed to provide maximum flexibility in matching primary air valve capacities (cooling loads) with unit fan capacities. The over­all unit size is dictated by the fan size. With each unit fan size, mul­tiple primary air valve sizes are available to handle a wide range of cooling capacities.
The fan should be sized first to determine the unit size. The selec­tion is made by cross plotting the specified fan capacity and external static pressure on the appropriate fan performance curves (see page
16). Terminals utilizing hot water heating coils require the summa­tion of the coil air pressure drop and the design E.S.P. to determine the total E.S.P. It is common to have more than one fan size which can meet the design requirements. Typically, the selection begins with the smallest fan that can meet the capacity. Occasionally this selec­tion may not meet the acoustical requirements and thus the next larg­er fan size should be selected. “Upsizing” may also occur when it is necessary to meet the design capacity on the medium or low motor tap.
Fan selections can be made any­where in the non-shaded areas. Each fan performance curve depicts the actual performance of the rel­ative motor tap without additional fan balance adjustment. Actual specified capacities which fall below a particular fan curve (low, medi-
um or high) is obtained by adjust­ment of the electronic (SCR) fan speed controller. After the proper fan is selected, the unit size is fixed and then the appropriate primary air valve is selected. Most of the unit fan sizes have three air valve sizes to select from. The mid­dle size will typically be utilized. It is the size that is matched with the unit fan to deliver 100% cooling capacity for the majority of fan selec­tions.
The larger primary air valve will be used in applications where the system fan is undersized, requiring a larger air valve to take advantage of lower pressure losses. While help­ing in this fashion, a penalty is paid by having a higher controllable min­imum airflow setpoint than could be achieved with a smaller inlet size.
The smaller primary air valve will most often be utilized with ther­mal storage systems where lower than normal primary air tempera­tures are utilized. In these cases, the maximum design primary air­flow is less than the fan capacity (typically 60 to 80%), and therefore a smaller air valve may be appro­priate.
SYSTEM PRESSURE CONSIDERATIONS
Since the terminal unit fan is select­ed to move 100% of the design airflow to the zone, all down­stream pressure losses are neglected when determining minimum pri­mary air inlet pressure to the unit. The central fan is only required to
overcome the minimal loss through the unit air valve, reducing the central fan total pressure and horsepower requirements. Due to extremely low pressure drop of the air valve, central fan operating inlet static pressures may be as low as 0.5" w.g.
COMMON MISAPPLICATION
It should be noted that a conven­tional Series Flow Fan Terminal cannot be applied as a booster fan. In problem areas where there is insufficient primary airflow capac­ity, this terminal will not aid in pulling more air from the primary duct. Instead the unit fan will draw air from the plenum inlet which has less resistance.
The induction opening should never be sealed, as this will cause problems should the primary air­flow increase beyond the unit fan capacity. In this condition, the fan casing becomes pressurized which will eventually stall the fan motor and cause premature failure.
An ENVIRO-TEC
®
Windows
®
based Computer Selection Program is also available for com­plete CFR automated selection.
PRIMARY AIRFLOW CALIBRATION • CFR
©May, 2006 Environmental Technologies, Inc. • CFR Catalog
9
.015 .03 .05 1.0 > 1.5
0404 43 250 35 250 30 43 55 250 250
0504, 0506 68 350 50 350 48 68 88 350 350 0604, 0606, 0611 75 490 60 550 53 75 97 435 530 0806, 0811, 0818 145 960 115 1000 105 145 190 840 1000 1011, 1018, 1021 235 1545 185 1600 165 235 305 1355 1600
1218, 1221, 1224, 1230 340 2250 285 2300 240 340 440 1975 2300
1421, 1424, 1430 475 3100 390 3100 335 475 615 2750 3100 1630, 1640, 1644 625 4100 520 4100 440 625 805 3595 4100
1844 810 4600 640 4600 580 810 1040 4470 4600
UNIT SIZE
MIN.
MAX.
MIN.
MAX.
400 SERIES (PNEUMATIC) STANDARD CONTROLLER
7000 SERIES ANALOG
ELECTRONIC
DDC CONSIGNMENT CONTROLS
(See Notes Below)
MIN.
MAX.
Min. transducer
differential pressure
(in. w.g.)
Max. transducer
differential pressure
(in. w.g.)
Airflow Ranges (CFM)
1
Minimum and maximum airflow limits are dependent on the specific DDC controller supplied. Contact the control vendor to obtain the minimum and maximum differential pressure limits (inches W.G.) of the transducer utilized with the DDC controller.
2
Maximum CFM is limited to value shown in General Selection Data.
FlowStar™ Calibration Chart
(For dead-end differential pressure transducers)
NOTE: Maximum and minimum CFM limits are dependent on the type of controls that are utilized. Refer to the table below for specific values. When DDC controls are furnished by others, the CFM limits are dependent on the specific control vendor that is employed. After obtaining the differential pressure range from the control vendor, the maximum and minimum CFM limits can be obtained from the chart above (many controllers are capable of controlling minimum setpoint down to .015" w.g.).
CFR • DIMENSIONAL DATA
10
CFR Catalog • ©December, 2005 Environmental Technologies, Inc.
MODEL CFR
Top View
(Pneumatic Controls
Not Shown in This View)
Left Side View
(Control Enclosure and Filter Rack
Not Shown in This View)
Inlet End View
(Electronic Controls and Filter Rack
Not Shown in This View)
UNIT SIZE
IABCDXYWHL
0404
3 7/8
[98]
6
[152]
5
[127]
3/4
[19]
10 1/2
[267]
8 3/8 [213]
8
[203]
18
[457]
12
[305]
28
[711]
0504
4 7/8 [124]
6
[152]
5
[127]
3/4
[19]
10 1/2
[267]
8 3/8 [213]
8
[203]
18
[457]
12
[305]
28
[711]
0604
5 7/8 [149]
6
[152]
5
[127]
3/4
[19]
6 1/2 [165]
8 3/8 [213]
8
[203]
18
[457]
12
[305]
28
[711]
0506
4 7/8 [124]
6
[152]
2 1/4
[57]
3/4
[19]
10 1/2
[267]
11
[279]
11
[279]
23 3/8
[594]
14
[356]
35
[889]
0606
5 7/8 [149]
6
[152]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
11
[279]
11
[279]
23 3/8
[594]
14
[356]
35
[889]
0806
7 7/8 [251]
6
[152]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
11
[279]
11
[279]
23 3/8
[594]
14
[356]
35
[889]
0611
5 7/8 [149]
6
[152]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
11
[279]
11
[279]
23 3/8
[594]
14
[356]
35
[889]
0811
7 7/8 [200]
6
[152]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
11
[279]
11
[279]
23 3/8
[594]
14
[356]
35
[889]
1011
9 7/8 [251]
7
[178]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
11
[279]
11
[279]
23 3/8
[594]
14
[356]
35
[889]
0818
7 7/8 [200]
8
[203]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
15
[381]
13 1/2
[343]
29 3/8
[746]
17
[432]
40
[1016]
1018
9 7/8 [251]
8
[203]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
15
[381]
13 1/2
[343]
29 3/8
[746]
17
[432]
40
[1016]
1218
11 7/8
[302]
8
[203]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
15
[381]
13 1/2
[343]
29 3/8
[746]
17
[432]
40
[1016]
1021
9 7/8 [251]
8
[203]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
15
[381]
13 1/2
[343]
29 3/8
[746]
17
[432]
40
[1016]
1221
11 7/8
[302]
8
[203]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
15
[381]
13 1/2
[343]
29 3/8
[746]
17
[432]
40
[1016]
1421
13 7/8
[352]
9
[229]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
15
[381]
13 1/2
[343]
29 3/8
[746]
17
[432]
40
[1016]
1224
11 7/8
[302]
10
[254]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
28
[711]
15
[381]
38
[965]
19
[483]
54
[1372]
1424
13 7/8
[352]
10
[254]
2 1/4
[57]
3/4
[19]
6 1/2 [165]
28
[711]
15
[381]
38
[965]
19
[483]
54
[1372]
1230
11 7/8
[302]
10
[254]
9 3/4 [248]
1 1/4
[32]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
1430
13 7/8
[352]
11 1/2
[292]
9 3/4 [248]
1 1/4
[32]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
1630
15 7/8
[403]
11 1/2
[292]
9 3/4 [248]
1 1/4
[32]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
1440
13 7/8
[352]
11 1/2
[292]
9 3/4 [248]
1 1/4
[32]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
1640
15 7/8
[403]
11 1/2
[292]
9 3/4 [248]
1 1/4
[32]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
1644
15 7/8
[403]
11 1/2
[292]
9 3/4 [248]
3 1/4
[83]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
1844
15 7/8
[403] x
15 7/8
[403]
11 1/2
[292]
9 3/4 [248]
3 1/4
[83]
6 1/2 [165]
40
[1016]
15
[381]
52
[1321]
19
[483]
62
[1575]
NOTE: All dimensions are in inches [mm].
Drawings are not to scale and not for submittal or installation purposes. Refer to www.enviro-tec.com for current submittal drawings.
Loading...
+ 22 hidden pages