
C60 FIREPLACE
Installation Reference Guide
REFER TO OWNER’S MANUAL FOR SPECIFIC INSTALLATION REQUIREMENTS AND ADDITIONAL PRODUCT INSTRUCTIONS
Minimum
Framing Dimensions
1” (25mm)
Clearance from
framing studs
to venting
STEEL STUD
Depth 20” 508 mm
Width 71” 1803 mm
Header Height 38” 965 mm
Enclosure Ceiling 72” 1829 mm
Note: Vent size 5/8
20”
(508mm)
Clearance to Combustibles
A - Finishing edge to side wall 7" 229 mm
B - Minimum clearance to enclosure ceiling 72" 1829 mm
72”
(1829mm)
38”
(965mm)
71”
(1803mm)
C - Minimum clearance to mantel height See Chart See Chart
D - Front of door to edge of floor protection 0" 0 mm
E - Minimum alcove width 76" 1930 mm
A
C
E
D

Non-Combustible Board
1 2 3 4 5 6 7 8 9 10 11 12 13 14
MANTLE HEIGHT
MANTLE DEPTH
Minimum Mantle Clearances
8” MANTLE
4”MANTLE
47”
46”
45”
44”
43”
42”
41”
39”
40”
12” MANTLE
Specications
7
1
4
"
186mm
62"
1575mm
65"
1651mm
9
1
4
"
235mm
16
1
2
"
422mm
12
1
4
"
308mm
4"
103mm
9
1
4
"
232mm
7"
176mm
3
1
4
"
81mm
Gas Inlet
Bottom
(Optional)
70
3
4
"
1797mm
17
3
4
"
453mm
15"
378mm
Gas Inlet
Right Side
Specications
Dimensions:
7
1
4
"
186mm
30
3
4
"
779mm
62"
1575mm
65"
1651mm
9
1
4
"
235mm
16
1
2
"
422mm
12
1
4
"
308mm
4"
103mm
9
1
4
"
232mm
38"
965mm
3"
73mm
9
1
4
"
232mm
7"
176mm
3
1
4
"
81mm
20"
507mm
1
2
"
13mm
70
3
4
"
1797mm
17
3
4
"
453mm
9"
231mm
15"
378mm
Electrical
Inlet Left
Side
Gas Inlet
Right Side
Specications
7
1
4
"
186mm
30
3
4
"
779mm
62"
1575mm
65"
1651mm
9
1
4
"
235mm
16
1
2
"
422mm
12
1
4
"
308mm
9
1
4
"
232mm
7"
1
20"
70
3
4
"
1797mm
17
3
4
"
453mm
9"
231mm
15"
378mm
Gas Inlet
Right Side
Fireplace Dimensions
Placement
Framing
COMBUSTIBLE
56 1/2”
MetalStud
Concrete
Board
Drywall
Sidewall
7”
72
NON COMBUSTIBLE
Minimum Venting Requirements
Minimum venting is shown in figure 20. the framing height to the
center of the thimble is 62”. Minimum venting must include a 24”
vertical section and a 90 degree elbow which is then terminated
horizontally. For a vertical termination please follow the vent
pipe manufacturer’s installation instructions for vertical vent
termination framing. A minimum of 1 in. (25 mm) clearance on
all sides of the vertical vent pipe must be maintained. For every
12” of horizontal run there must be a 1/4” of rise. 1” of clearance
between framing and venting must be maintained at all times. 2”
above the venting and 3” above an elbow.
509mm
62"
[1575mm]
*Do not use two
12” vent sections
or this dimension
will not work.
Use one 24”
section.
15"
378mm
453mm
3
"
17
4
5 3/16
13 3/4”
231mm
20"
507mm
1
"
2
13mm
10”
3
"
70
4
Mantel Projections
Mantel graph dimensions are measured from the bottom of the
replace, if you wish to reference the mantel height from the
tiling edge subtract 15 inches (381mm) from the mantel height
depicted on the graph. If you plan to install a TV above your
replace refer to the appropriate section of the owner’s manual
for available options. It is acceptable to install a combustible
mantel over top of the non-combustible board. If you are
activating the Cool Surface System you are eligible to subtract
12” (305mm) from the mantel height shown in this diagram.

OPTIONAL STEP Cool Surface System Part 1
7
5
8
"
(19.4 cm)
45" (114.3 cm)
31
3
4
" (80.6 cm)
25" (63.5 cm)
5" Vent Collars
40" (101.6 cm)
9
3
8
"
(23.8 cm)
2
3
4
" (7 cm) Standoff
2
1
2
" (6.6 cm) Standoff
11
7
8
"
(30.2 cm)
7
3
8
"
(18.7 cm)
2
1
8
"
(5.4 cm)
1
2
"
(1.3 cm)
3
1
2
" (8.9 cm)
2
5
8
" (6.7 cm)
9
3
8
"
237mm
11
7
8
"
301mm
71
7
8
"
1825mm
2
3
4
"
70mm
2
1
2
"
64mm
76
7
8
"
1952mm
51
1
2
"
1308mm
5" Vent Collars
2
1
8
"
53mm
1
2
"
13mm
3
1
2
"
89mm
2
5
8
"
67mm
7
1
4
"
185mm
9
3
8
"
237mm
71
7
8
"
1825mm
2
3
4
"
70mm
2
1
2
"
64mm
8.00
6.17
8.42
14.39
0.88
2.63
7.47
11.74
6.07 4.65
10.72
7.67
0.50
12.18
14.92
1.39
12.24
13.64
36.00
4.75
4.75
9.95
26.00
36.00
9.75
2.48
.49
.49
2.48
4.75
.50
2.00
.92
.50
.50
36.00
4.75
36.00
9.75
2.48
.49
.49
2.48
4.75
.50
2.48
.49
.49
2.48
4.75
.50
2.00
.92
.50
.50
2.48
.49
.49
2.48
4.75
.50
2.00
Dimensions
CSS Front Vent - Overall Dimensions (C34/C44/C60)
CSS Side Vent - Dimensions
11
301mm
5
7
8
192mm
7
"
8
"
3
"
9
8
237mm
7
"
71
8
1825mm
"
76
8
1952mm
1
"
51
2
1308mm
5" Vent Collars
53"
1346mm
Figure 4. Cool Surface System Front Vent - Overall Dimensions (C72)
Figure 5. Cool Surface System Combustible Facing Kit Dimensions
53mm
64mm
1
"
2
13mm
1
"
2
8
3
"
2
4
70mm
1
"
2
2
185mm
89mm
7
1
"
3
2
5
"
2
8
67mm
1
"
4

OPTIONAL STEP Cool Surface System Part 2
7 1/2"
(2.5 cm)
45" (114 cm)
37 1/4"
(94.6 cm)
Min.
Height
2 x 4 (On Edge)
2 x 4 (On Edge)
7 1/2"
(2.5 cm)
C44/60 = 45" (114 cm)
2 x 4 (On Edge)
37 1/4"
(94.6 cm)
Min.
Height
C60 = 71" (180 cm)
C44 = 55" (140 cm)
Steel Stud - C60 & C72 ONLY
Steel Stud - C60 & C72 ONLY
C72 = 83" (211 cm)
46 1/2"
(118 cm)
Min.
Height
C72
C34
C60
C44
C72 = 77 1/4" (196 cm)
Min. Height
51-3/8”
( 130cm)
C34 = 45” (114cm)
C44 = 55” (140cm)
C60 = 71” (180cm)
C72 = 83” (211cm)
1 2 3 4 5 6 7 8 9 10 11 12 13 14
MANTLE HEIGHT
MANTLE DEPTH
Minimum Mantle Clearances
8” MANTLE
4”MANTLE
35”
34”
33”
32”
31”
30”
29”
27”
28”
12” MANTLE
Framing & Rough Opening – Front Vent
CSS Outlet Min. Top and Bottom stando = 25/8” (6.7 cm) *All C Series*
CSS Outlet Min. Top and Bottom stando = 25/8” (6.7 cm) *All C Series*
C34
Framing & Rough Opening – Side Vent
C44/C60/C72
Revised Mantel Requirements:
Note: Minimum height of mantle if you intend on
using a surround is 31”

OPTIONAL STEP Cool Surface System Part 3
5
5
8
" (14.3 cm)
4" (10.2 cm)
2
3
4
" (69.8 cm)
73
1
4
"
(174.9 cm)
Side Brace
Min. Height
20" (50.8 cm)
Min. Depth
15.00” (38cm)
11.50”
(29cm)
Min. Height
to Ceiling
14.50
Min. Height
66.00”
(168cm)
Min. to
Ceiling
5” (12.5cm)
Min. Height
from oor
69.5” (176.5cm)
Min. Distance to
wall from standoff
5.00” (13cm)
Min. Ceiling
Height
18.75”
(48cm)
*15.75” (40cm)
11.5” (29cm)
Min. Dist
61.75”
(157cm)
*NOTE: 15.75” from the
header is required for min.
ceiling height. Rest unit on
lower standoff. There will be
a 3/4“ (2cm) gap on from
the top standoff to the
header in this confirguration.
Min Framing is 15” x 11.5”
3/4” (2cm)
Gap Shown
Min. Distance
to Ceiling
4.5” (11.5cm)
Min. Distance
to oor
64” (162.5cm)
80” (203 cm)
C34/44/60 Min. Ceiling
91” (231 cm)
C72 Min. Ceiling
Venting Clearances - Front Vent
Shown here are the minimum framing and clearances for
the CSS when the replace is installed with the minimum
allowable vent length:
Min. Ceiling Clearance from top of CSS outlet = 4” (10.2 cm)
5
Min. Ceiling Clearance in wall from top of CSS Body = 5
/8” (14.3 cm)
CSS Body Min. Rear stando = 2¾” (69.8 cm)
C72
C34
C44
C60
39” (99 cm) Min.
Length 5” dia. ex vent
(not supplied)
Min. Vent
82 3/8”
(212 cm)
Side Brace
Min. Height
Venting Clearances – Side Vent
Length 5” dia. ex vent
Min. Vent
39” (99 cm) Min.
(not supplied)
39” (99 cm) Min.
Length 5” dia.
ex vent
(not supplied)
CSS Horizontal Vent - Min. Framing & Clearances CSS Vertical Vent - Min. Framing & Clearances

OPTIONAL STEP Cool Surface System Part 4
29°F 41”
21°F 35”
21°F 29”
24°F 23”
17°F 17”
20°F 11”
30°F 5”
0”
Above
Ambient
Height from
Opening
4” Mantle
29” from oor.
Combustible
Facing Kit
1/2” Combustible Base
Material (Drywall)
Up to 1” Combustible
Material.
NOTE: You cannot install a Surround
with the mantle at its lowest position.
Install mantle at 31” for a Surround
Min.
2-1/2”
(6.4cm)
Min. 2” (5cm)
Gap
Combustible
Facing Kit
1/2” Combustible Base
Material (Drywall)
Up to 1” Combustible
Material
29°F 41”
29°F 35”
29°F 29”
27°F 23”
35°F 17”
38°F 11”
49°F 5”
0”
Above
Ambient
Height from
Opening
1-1/2” Air Gap behind the TV.
(Typically provided by a wall
mount)
Framing Clearances - Front Vent Framing Clearances - Side Vent
Min. Height
to Ceiling
64 1/8”
(1630mm)
Min. Height
to Ceiling
55-1/16”
(1399cm)
C72
C34
C44
C60
Min. Height
to Ceiling
55-1/16”
(1399cm)
12” (305mm)
8” (203mm)
4” (102mm)
33“
(84cm)
31 “
(79cm)
Min. Height
For Surround
29 “
(74cm)
2-1/16”
(75cm)
TV Installation Considerations:
If you are planning to mount a TV above your
replace some considerations must be made to
ensure it is protected from the heat.
During testing temperatures did not exceed
121°F (49°C) midway up the front wall (Figure 12 &
13). There is no guarantee that these temperatures
will not harm the longevity of your TV. Make sure
to consult your TV manufacturer’s specications
to nd the maximum allowable operating
temperature. Since every home and installation
is unique, temperatures should be veried at the
time of install if possible. If desired, front wall
temperatures can be lowered to 104°F (40°C) with
the use of a mantle (Figure 13). Refer to page 7
for revised mantle clearances. A TV should not be
installed if temperatures exceed the manufacturers
maximum allowable temperature.
12” (305mm)
8” (203mm)
4” (102mm)
31 “
(79cm)
33“
(84cm)
2-1/16”
(75cm)
Min. Height
For Surround
29 “
(74cm)
TV must be 5” min from
discharge if no mantle
Figure CSS TV Clearances Figure CSS TV Clearances