SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED
PLEASE SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
INSTALLER:
Leave this manual with the wood stove.
CONSUMER:
Retain this manual for future reference.
PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS WOOD
BURNING ROOM HEATER. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD RESULT
IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH.
Tested &
Listed By
OMNI-Test Laboratories, Inc,
T L
O-
C
Report # 268-S-04b-2
US
Portland
Oregon USA
This heater meets the U. S. Environmental Protection Agencies emission limits
for wood heaters sold after July 1st, 1990. Under specic conditions this heater
has been shown to deliver heat at rates ranging from 11,479 to 34,196 BTU per
hour for the 1200 and from 9,425 to 31,780 BTU per hour for the 1700.
Installation Data Sheet.....................................................................................36
2
Page 3
Safety Precautions
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” WOOD
STOVE, PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
● Please read this entire manual before you install and use your new woodstove. Failure to
follow instructions may result in property damage, bodily injury or even death. Be aware
that local Codes and Regulations may override some items in this manual. Check with your
local inspector.
● If this appliance is not properly installed, operated and maintained, a serious house re could result.
Makeshift materials during installation could also result in a serious house re.
● HOT WHILE IN OPERATION. KEEP CHILDREN, CLOTHING, AND FURNITURE AWAY. CONTACT MAY
CAUSE SKIN BURNS.
● Operate only with the door and ash plug tightly closed and burn wood directly on the stove hearth. Do
not operate if the door glass is broken or a gasket is missing or damaged. Do not alter the combustion
air control valves. Dangerous overring could occur which could ignite creosote in the chimney or
cause a house re.
2
● At least 12 square inches (77.4 cm
to the stove through a 4 inch (10.16 cm) diameter pipe. For the stove to operate combustion-air must
be supplied through either the bottom or the back of the unit.
● Do not burn coal or charcoal as there is danger of carbon monoxide being produced. DO NOT USE
CHEMICAL FLUIDS TO START OR RE-FRESH THE FIRE. DO NOT BURN GARBAGE OR FLAMMABLE
FLUIDS SUCH AS GASOLINE, GREASE, NAPHTHA OR ENGINE OIL. Never let the stove become hot
enough to get any part red or glowing red.
) of fresh outside air should be admitted into the room or directly
● Burning wet, unseasoned wood could cause excessive creosote accumulation in the ue pipe. When
ignited, it could cause a chimney re that could result in a serious house re.
● Do not use grates, andirons or any other methods to support or raise the re up off the hearth of the
appliance.
● This appliance is tested to ULC-S627-00 Standard for Space Heaters for Use with Solid Fuel & UL 1482
-10 Standard for Safety for Solid-Fuel Type Room Heaters.
● In Canada the existing chimney must be lined to the termination for all masonry installs.
● A chimney connector shall not pass through an attic or roof space, closet or similar concealed space,
or a oor, or ceiling.
● Where passage through a wall, or partition of combustible construction is desired, the installation shall
conform to CAN/CSA-B365.
● DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
● In the event of component failure, only manufacturer specied replacement parts may be used.
● DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
● Ensure that the ash plug is installed over the ash dump hole.
● Do not open the ash pan compartment while the unit is burning. Allow unit to fully cool before touching
the ash pan latch.
3
Page 4
Operating Instructions
FIRST START
When rst installed, the chimney, rebricks and steel are cold and it usually takes several hours on a fairly
high burn for them to become hot and dry enough for the stove to function well. We recommend during
the unit’s rst burn that a door and window are opened to vent the smoke and fumes created from the
unit’s paint curing. The paint will smell a little for the rst burn or two as it cures.
DISPOSAL OF ASHES:
The Boston freestanding models are equipped with an ash plug in the rebox and an ash drawer. Lift
the ash plug out and push the ashes that have accumulated into the hole; the ashes will then drop into
the Ash Pan. Ensure that the ash plug is seated properly before relighting the unit. When the Ash Pan
is ready to be emptied, fully open the main door on the unit and then open the lower latch on the Cast
Ash Drawer. The Cast Ash Drawer will lower down and the Ash Pan will be accessible (see Figure 1).
Ashes should be placed in a steel container with a tight tting lid. The closed container of ashes should
be placed on a noncombustible oor or on the ground, well away from all combustible materials, pending
nal disposal. If the ashes are disposed of by burial in soil or otherwise locally disposed, they should be
retained in the closed container until all cinders have thoroughly cooled. Other waste shall not be placed
in this container. Prior to burning the unit, re-insert the Ash Pan into the unit and close the Cast Ash
Drawer, ensuring that the latch is closed securely.
FAN OPERATION:
This unit has been approved for operation with or without the optional fan supplied by the manufacturer.
On medium or high burns, using a fan will increase the heat transfer slightly. Route the power supply cord
along the oor behind the stove where it will remain cool.
1. Plug the fan assembly into a standard three prong grounded electrical receptacle.
2. Turn the rotary fan controller to the desired setting. Once operating temperature is reached, the fan
temperature sensor will turn the fan on. When the unit cools down, the fan temperature sensor will
shut the fan off automatically.
4
Figure 1: Ash Pan Removal
Page 5
Operating Instructions
REPLACING THE GLASS:
Never strike or slam the door, hit the glass or let burning wood rest against it. If the glass cracks when
the re is burning, do not open the door until the re is out and do not operate the stove again until
the glass has been replaced. If the glass is damaged in any way, a factory replacement is required (see
“
Parts List”). To replace the glass, remove the steel retaining clips and all loose glass. Replace only with
Neoceram 5 mm glass 16.61” (422 mm) x 10.63” (270 mm) and wrap the edges with 0.125” (3.2 mm) x
0.5” (13 mm) self-adhesive berglass gasket.
Wear gloves when handling damaged glass door assembly to prevent personal injury. When the glass
door assembly is being transported, it must be wrapped in newsprint and tape and/or a strong plastic bag.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
FIRE EXTINGUISHER AND SMOKE DETECTION:
All homes with a solid fuel burning stove should have at least one re extinguisher in a central location
known to all in the household and a smoke detection device in the room containing the stove. If it sounds
the alarm, correct the cause but do not deactivate. You may choose to relocate the smoke detection
device within the room; DO NOT REMOVE THE SMOKE DETECTOR FROM THE ROOM.
CREOSOTE - FORMATION AND NEED FOR REMOVAL:
When wood is burned slowly, it produces tar and other organic vapors, which combine with expelled
moisture to form creosote. The creosote vapors condense in the relatively cool chimney of a slow-burning
re. As a result, creosote residue accumulates on the ue lining. When ignited this creosote makes an
extremely hot re. The chimney connector and chimney should be inspected bi-weekly during the heating
season to determine if a creosote buildup has occurred. If creosote has accumulated (3mm or more) it
should be removed to reduce the risk of a chimney re.
MAINTENANCE:
At the end of each heating season clean the chimney and the smoke pipe. If soot has accumulated above
the top bafe bricks, remove, clean, and then replace them. If a secondary air tube is badly corroded,
replace it. Replace worn door gaskets and broken bricks as needed.
FAILURE TO INSPECT AND CLEAN YOUR CHIMNEY SYSTEM REGULARLY CAN RESULT IN A
CHIMNEY FIRE, WHICH COULD DAMAGE THE CHIMNEY OR CAUSE A HOUSE FIRE.
CHIMNEY OR RUN AWAY FIRE:
1. Call local re department (or dial 911)
2. Close the draft fully
3. Examine the ue pipes, chimney, attic, and roof of the house, to see if any part has become hot
enough to catch re. If necessary, spray with re extinguisher or water from the garden hose.
4. Do not operate the stove again until you are certain the chimney and its lining have not been damaged.
5
Page 6
Operating Instructions
Building Your Fire:
Proper operation of your stove will help to ensure safe, efcient heating. Please take a few moments to
review these simple operating procedures.
IMPORTANT: Please be aware when loading your stove that the air tubes in the rear are lower.
1. Fuel Selection:
This stove is designed to burn natural wood only. Higher efciencies and lower emissions generally result
when burning air-dried seasoned hardwoods, as compared to softwoods or too green or freshly cut
hardwoods. DO NOT BURN the following: treated wood, coal, garbage, solvents, colored papers or trash.
Burning these may result in the release of toxic fumes and may poison or render the secondary air tubes
ineffective. Burning coal, cardboard or loose paper can produce soot, or large akes of char or y ash that
can coat the combustor, causing smoke spillage into the room, and rendering the combustor ineffective.
2. Building/Maintaining a Fire:
a) Open the primary air slide by pulling it all the way to the right.
b) Place a base of crumpled uncolored newspaper in the bottom of the stove. Lay pieces of kindling on
or similar liquids to start or “freshen up” a re in this heater. Keep all such liquids well
away from heater while it is in use.
c) As the kindling begins to burn, add several larger pieces of wood until the re is burning well. At this
point, regular size logs may be added.
NOTE: Until the re is burning well, leave the air controls fully open.
d) Regulate the heat output of the stove by adjusting the air controls to allow a larger re and vice versa.
A short period of experimentation with the control settings will allow you to regulate the heat output
to keep your home comfortable.
Do not use a grate or elevate the re. Build wood re on the stove rebox hearth oor.
3. Refueling the Stove:
Use a long pair of gloves (barbecue gloves) when feeding the re because these stoves burn at the front.
They are clean and efcient but they are also very hot and gloves are useful. Keep a small steel shovel
and whisk nearby for moving a log or lifting a fallen ember and for keeping the hearth clean.
a) Before attempting to add fuel to the stove, OPEN the damper control fully by pulling it all the way out.
This allows the chimney to carry away the additional smoke, which occurs when the door is open.
b) DO NOT OVERLOAD THE STOVE. Normally, three or four logs will provide heat for several hours.
Never operate this stove where portions glow red hot.
c) DO NOT OVERFIRE. If the heater or chimney connector glows, you are overring. Overring could
ignite creosote in the chimney and cause a house re.
d) CAUTION: DO NOT PLACE FUEL OR COMBUSTIBLE MATERIAL WITHIN SPACE HEATER INSTALLATION
CLEARANCES OR WITHIN THE SPACE REQUIRED FOR CHARGING AND ASH REMOVAL. LOGS SHOULD BE
KEPT IN A BIN OR CONTAINER TO REDUCE THE RISK OF LOGS ROLLING INTO THE UNIT’S CLEARANCES.
e) KEEP THE ASH LIP CLEAR OF EMBERS AND ASH. If the door is closed with debris in the way,
the door gasket seal could be compromised.
6
Page 7
Operating Instructions
4. For Maximum Efciency:
When the stove is hot, load it fully to the top of the door opening and burn at medium low settings. When
the fuel is mostly consumed, leaving a bed of red coals, repeat the process. Maximum heat for minimum
fuel occurs when the stove top temperature is between 250°F (120°C) and 550°F (290°C). The most
likely causes of dirty glass are: not enough fuel to get the stove thoroughly hot, burning green or wet
wood, closing the draft until there is insufcient air for complete combustion, or a weak chimney draw.
Indeed, the cleanness of the glass is a good indicator of the stove operating efciently.
Helpful Hints Worth Repeating
1. Helpful advice on the correct way to start your re.
a) You will need small pieces of dry wood, called kindling, and paper. Use only newspaper or paper
that has not been coated or had other materials glued or applied to it. Never use coated (typically
advertising yers) or coloured paper.
b) Always open the door of the wood stove slowly to prevent suction and drawing smoke into the room.
c) Crumple several pieces of paper and place them in the center of the rebox and directly onto the
rebricks of the wood stove. Never use a grate to elevate the re.
d) Place small pieces of dry wood (kindling) over the paper in a “teepee” manner. This allows for good
air circulation, which is critical for good combustion.
e) Light the crumpled paper in 2 or 3 locations. Note: It is important to heat the air in the stovepipe for
draft to start.
f) Fully open the air controls of the wood stove and close the door until it is slightly open, allowing for
much needed air to be introduced into the rebox. Never leave the door fully open, as sparks from
the kindling may y out of the stove, causing damage or injury. As the re begins to burn the kindling,
some additional kindling may be needed to sustain the re. DO NOT add more paper after the re has
started.
g) Once the kindling has started to burn, add some smaller pieces of seasoned, dry rewood. Note:
Adding large pieces at the early stages will only serve to smother the re. Continue adding small pieces
of seasoned dry rewood, keeping the door slightly open until each piece starts to ignite. Remember
to always open the door slowly between placing wood into the re.
h) Once the wood has started to ignite and the smoke has reduced, close the wood stove door fully. The
reduction of smoke is a good indication that the draft in the chimney has started and good combustion
is now possible. Larger pieces of seasoned, dry rewood can now be added when there is sufcient
space in the rebox. Adjust the air control setting to desired setting. Note: The lower the air control
setting, the longer the burn time of your rewood.
2. What type of wood is best to use as rewood?
Both hardwood and softwood burn well in this stove. Both woods contain about 8,000 BTU/lb (18,570
KJ/Kg), but hardwood is generally more dense, will weigh more per cord, and burns a little slower and
longer. Cutting rewood so that it will t horizontally, front to back, makes it easier loading and less likely
for the fuel to roll on the glass. Except for a cold start, there is no need to crisis-cross the logs. Ideal
length for the logs used in the 1200-C would be about 16“ (381 mm) but it can burn pieces up to 18”
long. Ideal length for the logs used in the 1700-C would be about 18“ (381 mm) but it can burn pieces
up to 20” long logs. Burn only dry, seasoned wood. It produces more heat and less soot or creosote.
Freshly cut wood has about 50% moisture. A 10 pound (4.5 Kg) log contains 5 pounds (2.3 Kg) of water.
To season rewood, split and stack it so that air can get to all parts of the wood. Burn beach wood only
if its salt content has been washed away in a season of rain and then the wood dried. To prevent smoke
7
Page 8
Operating Instructions
spillage when refueling, open the door slowly.
3. What does dry, seasoned wood mean?
Wood that has been dried for a period of one year in a well-ventilated and sheltered area would be
considered dry, seasoned wood. Wood from slow-growing trees is generally considered better than wood
from fast-growing trees. To season rewood, split and stack it so that air can get to all parts of the wood.
4. Will following the above-listed steps for starting a re mean perfect results every time?
The quick answer is ‘most of the time’. There are many variables that may affect your success when
starting a re. Most of those variables and how to deal with them will be learned through experience.
Your ability to start a good re will signicantly increase with time and patience. Some of the reasons for
poor stove performance will be covered in the next section of these instructions.
5. Why can’t I get the re lit?
Damp or wet wood and poor drafts are the main reasons for poor results in starting a re. Always use dry,
seasoned wood for your re. Even wood dried for two years will be difcult to ignite if it has become wet.
6. Is it normal for soot to cover the glass at the beginning of a re?
Your stove has been built with an air-wash system that will help keep the glass clear when the rebox
has reached a good operating temperature and has a good draft. Normally, a hot stove will keep the glass
clean, but if you must clean the glass, use a soft cloth with no abrasive and clean only when the unit is
cold. Cold rebox temperature and poor draft cause sooting of the glass. Once the rebox temperature
and the draft increase, the soot will burn off.
7. What is draft?
Draft is the ability of the chimney to exhaust or draw smoke produced during the normal combustion
process. Too much draft may cause excessive temperatures in the appliance and may damage the
appliance. Inadequate draft may cause backpufng or “plugging” of the chimney. There is a certain
amount of draft that is required to allow for your stove to function at its’ highest efciency. A water
column gauge can be used to reference this amount.
8. What can cause a poor draft?
The most common factors for poor draft are:
a) Air supply
b) Environmental conditions
c) Cold chimney temperature
d) Poor chimney installation and maintenance
e) Atmospheric pressure
a) Air supply – Inside the home, normal household appliances such as clothes dryers and forced-air
furnaces compete for air, resulting in air starvation to the re. This creates a condition in the house
known as negative pressure. When a house experiences negative pressure, the combustion gases
can be drawn from the chimney and into the house. This condition is commonly referred to as down-
8
Page 9
Operating Instructions
drafting. Increased amounts of insulation, vinyl windows, extra caulking in various places and door
seals can all keep heat in but may also make a home too airtight. An easy way to stop negative
pressure in a home is to crack a window in the room containing the stove.
b) Environmental Conditions - High trees, low-lying house location such as in a valley, tall buildings or
structures surrounding your house and windy conditions can cause poor draft or down-drafting.
c) Cold Chimney Temperature - Avoid cold chimney temperatures by burning a hot re for the rst fteen
to forty minutes, being careful not to over-re the stove. If any part of the chimney or parts of the
stove start to glow, you are over-ring the stove. Where possible, install a temperature gauge on the
chimney so temperature drops can be seen.
d) Chimney Installation and Maintenance - Avoid using too many elbows or long horizontal runs. Too short
a chimney can cause difcult start-up, dirty glass, back smoking when door is open, and even reduced
heat output. Too tall a chimney may prompt excessive draft, which can result in very short burn times
and excessive heat output. If in doubt, contact a chimney expert and/or chimney manufacturer for
help. Clean chimney, rain caps and especially the spark arrestor regularly, to prevent creosote build-
up, which will signicantly reduce chimney draw and possibly a chimney re.
Note: These instructions are intended as an aid and do not supercede any local, provincial or state
requirements. Check with ofcials or authorities having jurisdiction in your area.
Air Control:
The air wash and pilot air (control the amount of air to the re) are controlled by the rod located on the
right side of the unit. To increase your air, pull the rod out and to decrease, push the rod in. All the units
have a secondary air that ows through the tubes at the top of the rebox, just below the bafes.
Pull this control all the way out when rst starting the stove. Once the re has been established you may
adjust this control to set the burn rate of the re. If this damper is closed at rst start-up, the re will
burn very slowly and could soot the appliance.
When shutting down the stove, fully open the air control. This allows the chimney temperatures to remain
as high as possible for as long as possible. Cold chimney temperatures create creosote.
Warning - This adjustment should not be altered for increased ring for any reason.
Increase air - pull rod out
Decrease air - push rod in
Figure 2: Air Control Rod.
9
Page 10
How it works:
Operating Instructions
10
Figure 3: 1200 Air Flow Path.
Page 11
1200 speCiFiCAtions:
Specifications
Model1200 Freestanding
Width x Depth
Height with legs
Fire box size
(depth x width x height)
Capacity
* Approximate heating area
**E.P.A. output rating
*Duration on low burn6 -10 hours
30” x 25” (762 mm
x 635 mm)
31.75”
(806mm)
16.1” x 18.25” x
11.15”
(409 mm x 464 mm
x 283 mm)
1.85 feet
(0.0526 meter3)
800 - 1,500 feet
(74.3 - 139.4
meter2)
11,479 to 34,196
BTU/hour
(3,361 to 10,013
watt)
3
2
Weight with packaging
E.P.A. Emissions
Rating Label LocationBack of Unit
335 lb
(151.95 Kg)
3.3 grams/hour
(0.116 oz/hour)
Table 1: 1200 General Information.
11
Page 12
Specifications
CleArAnCes to ComBustiBles - 1200 FreestAnding:
MAINTAIN THESE MINIMUM CLEARANCES TO UNSHIELDED COMBUSTIBLES*
Back wall
B
E
A
D
Side wall
A
B
C
D
E
F
G
H
Alcove (48” [1220 mm] Deep)
ITotal Width55” (1397 mm)
JTotal Height78” (1981 mm)
KTop of stove to ceiling49” (1245 mm)
LSide wall to stove15” (381 mm)
MSide wall to pipe24” (610 mm)
NBack wall to unit12” (305 mm)
OBack wall to pipe15” (381 mm)
Front
From side wall
to side of unit
From rear wall
to back of unit
From adjacent wall
to corner of unit
From side wall
to collar
From rear wall
to collar
From adjacent wall
to collar
† From door opening
to edge of hearth pad
† From side/back of unit
to edge of hearth pad
Adjacent wall
C
C
Adjacent wall
F
Table 2: 1200 Freestanding Clearance to Combustibles.
Front
Single Wall PipeDouble Wall Pipe**Double Wall Pipe
(330 mm)
(279 mm)
(229 mm)
(559 mm)
(356 mm)
(445 mm)
USA 16” (406 mm)
CND 18” (450 mm)
USA 6” (152 mm)
CND 8” (200 mm)
H
13”
11”
9”
22”
14”
17½”
H
H
Front
G
Hearth
13”
(330 mm)
10”
(254 mm)
8”
(203 mm)
22”
(559 mm)
13”
(330 mm)
16½”
(419 mm)
USA 16” (406 mm)
CND 18” (450 mm)
USA 6” (152 mm)
CND 8” (200 mm)
Alcove Back wall
N
L
M
Alcove Side wall
O
Front
I
with Heat Efciency
Shield 50-1088 (Flat
top model only)
13”
(330 mm)
8”
(203 mm)
6½”
(165 mm)
22”
(559 mm)
11”
(279 mm)
15”
(368 mm)
USA 16” (406 mm)
CND 18” (450 mm)
USA 6” (152 mm)
CND 8” (200 mm)
K
J
Alcove
Top vent out back
wall with min. 24”
(610 mm) vertical
rise; double wall
14”
(356 mm)
12”
(305 mm)
23”
(584 mm)
15”
(381 mm)
USA 16” (406 mm)
CND 18” (450 mm)
USA 6” (152 mm)
CND 8” (200 mm)
CAUTION: An uninsulated smoke pipe must not pass through an attic, roof space, closet or similar concealed
space, or through a oor, ceiling, wall, or partition, or any combustible construction.
12
Page 13
Specifications
† FLOOR PROTECTION: If a stove is installed on a combustible oor, it must have a leg kit with ash box attached
and be on a NON-COMBUSTIBLE hearth pad (see below).
If unit is raised:
0” - 2” (0mm - 51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent
2” - 8” (51mm - 203mm); ½” (13mm) non-combustible material with k value = 0.84 or equivalent
Greater than 8” (203 mm); Any non-combustible material
* ALL CLEARANCES CAN BE REDUCED WITH SHIELDING ACCEPTABLE TO THE LOCAL AUTHORITY.
**DOUBLE WALL:
IN CANADA: Any ULC-S629 listed chimney system with the accompanying listed double wall vent connector.
IN U.S.A.: Any UL 103 HT listed chimney system with the accompanying listed double wall vent connector.
dimensions - 1200 FreestAnding:
5.50"
(140mm)
25.00"
(635mm)
22.25"
(565mm)
17.00"
(432mm)
31.75"
(806mm)
(254mm)
30.50"
(775mm)
30.00"
(762mm)
10.00"
16.00"
(406mm)
29.125"
(740mm)
Figure 4: 1200 Freestanding Step Top Dimensions.
13
Page 14
Installation
removAl From pAllet:
• Remove the screws which are securing the shipping brackets to the unit.
• Remove the lag bolts and discard the brackets.
14
Figure 5: Bolts to remove.
Page 15
Installation
HeArtH proteCtion exAmples:
Table 3: Examples of Hearth Pad Sizing Using Clearances From Table 2 (refer to Figures 6).
CanadaUSA
1200170012001700
(A) Minimum Width40½” (1028mm)36½” (926mm)
(B) Minimum Depth
(C) Maximum Front Corners -
Adjacent
(D) Maximum Back Corners -
Adjacent
(E) Maximum Front Corners -
Diagonal
(F) Maximum Back Corners -
Diagonal
(G) Minimum Width remaining
without corners - Front
(H) Minimum Width remaining
without corners - Back
46”
(1168mm)
OPTIONAL - Corner removal
8¾” (314mm)6¾” (171mm)
6¼” (160mm)5⅛” (130mm)
12⅜” (314mm)9½” (242mm)
8⅞” (227mm)7¼” (185mm)
23” (583mm)23” (583mm)
27⅞” (707mm)26⅛” (665mm)
50½”
(1283mm)
42”
(1067mm)
46½”
(1181mm)
Table 4: Examples of Parallel Installation Using Clearances From Tables 2 (refer to Figure 6).
ModelCountry
Single Wall Pipe1200
Double Wall Pipe1200
Double Wall
Pipe with Heat
Efciency Shield
50-1088 (Flat top
model only)
Top vent out
back wall
with min. 24”
(610mm) vertical
rise; double wall
1200
1200
(I) Far Edge of Hearth Pad
to Side Wall - Minimum
Canada45½” (1156mm)49¼” (1252mm)
USA43½” (1104mm)47¼” (1201mm)
Canada45½” (1156mm)48¼” (1226mm)
USA43½” (1104mm)46¼” (1175mm)
Canada45½” (1156mm)46¼” (1175mm)
USA43½” (1104mm)44¼” (1125mm)
Canada46½” (1181mm)50¼” (1277mm)
USA44½” (1129mm)48¼” (1226mm)
(J) Front of Hearth Pad to
Back Wall - Minimum
Non combustible oor protection must be under the chimney connector and 2 inches (50.8 mm)
beyond each side.
15
Page 16
USA 6"
(152mm)
CND 8"
(203mm)
Installation
HD
USA 6" (152mm)
CND 8" (203mm)
Door Opening
USA 16" (406mm)
CND 18" (457mm)
F
E
B
J
(152mm)
(203mm)
Coverage
M
L
USA 6"
CND 8"
Optional
G
C
A
I
Figure 6: General Parallel Installation
(refer to Tables 11 & 12).
Optional
Coverage
N
USA 6" (152mm)
CND 8" (203mm)
Door Opening
USA 16" (406mm)
CND 18" (457mm)
E
O
P
Optional
Coverage
K
B
Figure 7: General Corner Installation (refer to Tables 11 & 13).
16
G
A
C
Page 17
Installation
3¼”
8⅞”
7⅛”
Diagonal
Removed -
(P) Back Corner
1¼”
(32mm)
(182mm)
(83mm)
(227mm)
4⅞”
Adjacent
Removed -
(O) Back Corner
Pad
30⅝”
(N) Width at
back of Hearth
29⅛”
(M) Edge of
Adjacent Wall
Hearth Pad to
Wall
57⅝”
(L) Adjacent
⅞”
(23mm)
(124mm)
34⅝”
(881mm)
(779mm)
29⅛”
(738mm)
(738mm)
54⅞”
(1393mm)
(1465mm)
2¼”
6¼”
(160mm)
31⅞”
27⅞”
(707mm)
28⅛”
28⅛”
(713mm)
53⅞”
56⅝”
(1439mm)
(59mm)
(809mm)
(713mm)
(1368mm)
Corner
(K) Front of
Hearth Pad to
Table 5: Examples of Corner Installation Using Clearances From Table 2 (refer to Figures 7).
1200Canada61⅜”
Single
(1507mm)
(1558mm)
USA59⅜”
Wall Pipe
1200Canada59⅞”
Double
(1471mm)
(1522mm)
USA57⅞”
Wall Pipe
17
Page 18
Installation
outside Air kit:
It is mandatory to use outside air for installations in mobile homes.
A 4” (10.2 cm) fresh air adaptor kit is available. This kit can be installed on
the back of the Ash Box. If outside air is to be used in conjunction with the
convection fan kit, there is a separate outside air adapter which connects
to the bottom of the Ash Box. Refer to the Parts List.
Place the ¼” mesh screen behind the fresh air adaptor (as shown to
right).
Fresh air connection to the unit must be a non-combustible pipe Example: 4” (10.2 cm) single wall aluminum ex pipe.
Figure 8: Fresh Air Adaptor
reCommended HeigHtsAnd diAmeters For Flue pipe:
The minimum ue pipe height at sea level is 12 feet (3.7 m) straight up from top of the unit. For every
1000 feet (305 m) above sea level, 4% could be added to the overall height. Use Tables 14, 15, and 16
to calculate the required vertical rise required.
Minimum recommended ue pipe height for # of elbows
(Note: No more than 2 offsets (4 elbows) can be used. 2x45°=1x90°
We recommend the use of a 6” (150mm) diameter ue pipe. However, the CSA-B365 and the WETT
Training Manual state that the ue pipe may be reduced in cross-sectional area provided that the installer
ensures sufcient draft is available at the appliance.
Table 7: Distance to add to
overall vertical height.
Part usedfeetmeters
45° elbow1.00.3
90° elbow2.00.6
“T”3.00.9
1 ft (0.3m) of
horizontal run
Table 8: Examples of calculating
overall vertical height required.
sea level with 2
x 30° elbows
one “T”3.0 ft (0.9 m)
1½ ft (0.6 m)
horizontal run
Total 119.3 ft (5.9 m)
4000-5000 ft
(1220-1525 m)
above sea level
one “T”3.0 ft (0.9 m)
2 ft (0.6 m)
horizontal run
Total 220.9 ft (6.3 m)
Rear of Ash Box
Distance to add
2.00.6
Height
13.3 ft (4.1 m)
3.0 ft (0.9 m)
13.9 ft (4.2 m)
4.0 ft (1.2 m)
18
Page 19
Installation
CHimneY instAllAtion tHrougH wAll:
Here are four (4) methods of combustible wall chimney connector pass-throughs. Information was provided from NFPA 211.
Minimum chimney clearance to brick
and combustibles 2 inches (50.8 mm)
Minimum clearance
12 inches (304.8 mm)
of brick
Chimney
connector
Fire clay liner
Minimum 12 inches
(304.8 mm) to combustibles
Chimney Flue
Masonry
chimney
Figure 9: Chimney Through Wall - Method A.
Minimum chimney clearance from masonry to sheet
steel supports and combustibles 2 inches (50.8 mm)
Method A. 12” (304.8 mm) Clearance to Combustible Wall Member:
Using a minimum thickness 3.5” (89 mm) brick and a ⅝” (15.9 mm)
minimum wall thickness clay liner, construct a wall pass-through. The
clay liner must conform to ASTM C315 (Standard Specication for Clay
Fire Linings) or its equivalent. Keep a minimum of 12” (305 mm) of
brick masonry between the clay liner and wall combustibles. The clay
liner shall run from the brick masonry outer surface to the inner surface
of the chimney ue liner but not past the inner surface. Firmly grout or
cement the clay liner in place to the chimney ue liner.
Method B. 9” (229 mm) Clearance to Combustible Wall Member: Using
a 6” (152 mm) inside diameter, factory-built Solid-Pak chimney section
with insulation of 1” (25.4 mm) or more, build a wall pass-through
with a minimum 9” (229 mm) air space between the outer wall of
the chimney length and wall combustibles. Use sheet metal supports,
fastened securely to wall surfaces on all sides, to maintain the 9” (229
mm) air space. When fastening supports to chimney length, do not
penetrate the chimney liner (the inside wall of the Solid-Pak chimney).
The inner end of the Solid-Pak chimney section shall be ush with the
inside of the masonry chimney ue and sealed with a non-water soluble
refractory cement. Use this cement to also seal to the brick masonry
penetration.
Minimum chimney clearance from masonry to sheet
steel supports and combustibles 2 inches (50.8 mm)
Two air channels each
1 inch (25.4 mm)
Chimney
connector
Minimum 6 inches
Two ventilated air channels
each 1 inch (25.4 mm).
Construction of sheet steel
Chimney flue
Masonry
chimney
(152.4 mm) glass
fiber insulation
Sheet steel supports
Figure 11: Chimney Through Wall - Method C.
Method C. 6” (152.4 mm) Clearance to Combustible Wall Member:
Starting with a minimum 24 gauge (.024” [0.6 mm]) 6” (152.4 mm)
metal chimney connector and a minimum 24 gauge ventilated wall
thimble which has two air channels of 1” (25.4 mm) each, construct a
wall pass-through. There shall be a minimum 6” (152.4 mm) separation
area containing berglass insulation, from the outer surface of the wall
thimble to wall combustibles. Support the wall thimble and cover its
opening with a 24 gauge minimum sheet metal support. Maintain the
6” (152.4 mm) space. There should also be a support sized to t and
hold the metal chimney connector. See that the supports are fastened
securely to wall surfaces on all sides. Make sure fasteners used to secure
the metal chimney connector do not penetrate chimney ue liner.
Method D. 2” (50.8 mm) Clearance to Combustible Wall Member:
Start with a solid-pak listed factory-built chimney section at least 12”
(304 mm) long, with insulation of 1” (25.4 mm) or more, and an inside
diameter of 8” (2” [51 mm] larger than the 6” [152.4 mm] chimney
connector). Use this as a pass-through for a minimum 24 gauge singlewall steel chimney connector. Keep solid-pak section concentric with
and spaced 1” (25.4 mm) off the chimney connector by way of sheet
metal support plates at both ends of chimney section. Cover opening,
and support chimney section on both sides, with 24 gauge minimum
sheet metal supports. See that the supports are fastened securely to
Figure 12: Chimney Through Wall - Method D.
wall surfaces on all sides.
Make sure fasteners are used to secure
chimney ue liner.
NOTES:
1. Connectors to a masonry chimney, excepting method B, shall extend in one continuous section through the wall pass-through
system and the chimney wall, to but not past the inner ue liner face.
2. A chimney connector shall not pass through an attic or roof space, closet or similar concealed space, or a oor, or ceiling.
19
Page 20
Installation
Roof
Ridge
2ft(0.6m)
Minimum
3ft(0.9m)
Minimum
Within10ft(3m)
instAllAtionoF A listed, FACtorY Built CHimneY - FreestAnding:
This is a generic set of instructions; always follow the chimney manufacturer’s instructions
explicitly. Also refer to “reCommended HeigHts For Flue pipe”.
1. Set non combustible oor protector and stove in location in accordance with the “
CombustibLes - 1200 Freestanding”.
2. Mark the position for the ceiling hole by
suspending a plumb bob from the ceiling
over the exact center of your stove ue and
mark a spot on the ceiling to indicate the
center of the chimney.
3. Move this location, if necessary, to avoid
oor joists, ceiling rafters, electrical wiring
and plumbing while still maintaining required
clearances. If oor joists or ceiling rafters
must be cut they must be made structurally
sound again. Install chimney according
to chimney manufacturers instructions. A
chimney connector cannot pass through
an attic or roof space, closet or similar
Figure 13: Roof Clearances.
Rain cap/
Spark arrestor cap
Storm Collar
Roof flashing
concealed space, or a oor, ceiling, wall
or partition of combustible construction.
In Canada, if passage through a wall or
partition of combustible construction is
Insulated chimney
Attic
radiation shield
desired, the installation shall conform to
CAN/CSA-B365 Installation Code for SolidFuel Burning Appliances and Equipment and
NFPA 211 Standard for Chimneys, Fireplaces,
Vents, and Solid Fuel-Burning Appliances.
4. Mark the hole for the outside air kit.
5. Move the stove out of the way.
6. Cut a pilot hole in the ceiling.
Ceiling
Minimum air space in
accordance with
chimney manufacturer.
Radiation shield
Ceiling support
Chimney
connector
7. Cut a hole for the ceiling penetration
components and frame in the sides of the
hole in both the ceiling and roof. Check, and
follow chimney manufacturer’s instructions
for all of these steps.
8. Install the support box and chimney through
the roof. Install the slip section for the
chimney connector.
9. Slip the roof ashing over the chimney and
secure to the roof, being careful to keep the
pipe centered in the opening. To meet the
code, the chimney must extend above the
roof penetration at least 3 feet (91.4 cm), and
in any area within 10 feet (304.8 cm) of the
Outside air connection
through wall or floor
Figure 14: Standard Vertical Installation.
CLearanCes to
Roof
Woodstove
Hearthpad
Floor
20
Page 21
Installation
roof ridge, the chimney must
be 2 feet (60.9 cm) above the
ridge. Refer to Figure 13.
Note: Increasing the chimney
height above the roof may
Roof radiation
shield (if required)
help your unit to draft better.
This greater draft can decrease
Insulated chimney
problems such as difcult
start-ups, smoke coming out
when door is open, and dirty
glass. You may initially try
Ceiling
Minimum
18" (475 mm)
the minimum required height
and if problems do arise, add
additional height later.
10. Slide the roof ashing over
your chimney and seal the
ashing to the roof with a
Chimney
connector
roong compound. Secure the
roof ashing to your roof with
nails or screws.
Woodstove
11. Place the storm collar over the
ashing and seal the joints
with silicone caulking.
Hearthpad
12. Fasten the rain cap / spark
arrestor cap to the top of your
chimney.
13. Place the stove back into
position.
Floor
Figure 15: Standard Horizontal Installation.
Outside air connection
through wall or floor
14. Install the chimney connector
pipe with the lower (crimped) edge of the pipe inside the ue collar. Any creosote formed will then run
back down into the stove. All connections must be tight and secured with three sheet metal screws
equally spaced. Double wall pipe is recommended over single wall.
15. Also install an outside air ex pipe to the stove.
Rain cap/
Spark arrestor cap
Storm Collar
Roof flashing
Roof
Minimum air space
in accordance with
chimney manufacturer.
Insulated corner
Wall support
Chase
(optional)
IMPORTANT: When a metal prefabricated chimney is used, the manufacturer’s installation instructions
must be followed. You must also purchase and install the ceiling support package or wall pass-through
and “T” section package, restops (where needed), insulation shield, roof ashing, chimney cap, etc.
Maintain proper clearance to the structure as recommended by the manufacturer. The chimney must be
the required height above the roof or other obstructions for safety and proper draft operation.
Note: If you are using a horizontal connector (refer to Figure 15), the chimney connector
should be as high as possible while still maintaining the 18” (475 mm) minimum
distance from the horizontal connector to the ceiling.
21
Page 22
Installation
mAsonrY CHimneY instAllAtion - FreestAnding:
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
A non-combustible oor protector is required under all freestanding units; refer to “CLearanCes to
CombustibLes - 1200 Freestanding”. When venting into a masonry chimney, the oor protector must be
installed directly below the chimney vent and 2” (50.8 mm) on either side of the chimney vent.
Vent the stove into a clean, lined, approved masonry chimney in good condition, conforming to local
building codes and meeting the minimum standards of the National Fire Protection Association (NFPA).
Make sure there are no cracks, loose mortar or other signs of deterioration and blockage. Have the
chimney cleaned before the stove is installed and operated, or vent with a listed 6” (150 mm) factorybuilt chimney suitable for use with solid fuels and conforming to ULC-S629 Standard for 650°C factoryBuilt Chimneys in CANADA or UL 103 HT Factory-Built Chimneys for Residential Type and Building Heating
Appliances in the U.S.A. Connect the stove to this chimney with a short and straight 6” (150 mm), 24
gauge or heavier, single-wall black or blued steel smoke pipe. Connection to all masonry chimneys must
be a metal or masonry thimble cemented in place. All smoke pipes must slope upwards, all connections
must be tight and secured with three sheet metal screws equally spaced. The smoke pipe length should
not exceed 40% of the chimney height above the stove.
When connecting the stove through a combustible wall to a masonry chimney, additional steps are
required. Consult the chimney connector manufacturer and refer to Figure 17.
All chimneys in Canada must be fully
lined with a 6" (150 mm) stainless
steel liner from the chimney connector
to the top of the chimney.
Chimney thimble; non-combustible (cement
or metal) and must be cemented in place.
Single or listed double
wall chimney connector.
Woodstove
Hearth pad.
Outside air connection
through wall or floor.
Figure 16: Installation into a masonry chimney.
22
Floor.
Figure 17: Installation into chimney through a
combustible wall.
Page 23
Installation
mAsonrY FireplACe instAllAtion - FreestAnding:
Rain Cap
Chimney
Support and Clamp
Rigid Stainless
Steel Liner
Listed Liner
Stove pipe must
end higher than liner
Flexible Stainless
Steel Section
Steel Plate or Flashing
Damper Removed
or Fastened Open
Unless you are experienced, we recommend
installation by your dealer or a professional
installer.
Many venting manufacturers have listed kits
available to connect a stove to a masonry replace.
Always follow the vent manufacturer’s installation
instructions.
The existing damper may have to be
removed to allow installation.
Stainless Steel
Connector Pipe
Clean-out tee
Clean-out
cover
Figure 18: Freestanding Installation into existing replace.
Masonry Fireplace
Floor Protection
Combustible Floor
moBile Home instAllAtion:
SPECIAL REQUIREMENTS: All freestanding installation requirements in “
Factory Built Chimne
y”, must comply with all local codes that may apply, and the following must be met:
VENTING:
In Canada: Any ULC-S629 listed chimney system with the accompanying double-wall vent connector.
In U.S.A. Any UL-103-HT listed chimney system with the accompanying double-wall vent connector.
Do not connect a listed chimney of one manufacturer with a listed double wall connector from another
manufacturer.
These connectors must be installed in accordance with the manufacturer’s instructions. Use only specied
components. The chimney and pipe must extend at least 10 feet (2.4 m) above the stove and 3 feet (0.9
m) above the highest point of the roof. Install a rain cap with spark arrestor at the top that will not impede
the smoke exhaust. The chimney must be supported at the ceiling or roof so that its weight will not sit
on the stove. Seal with silicone to maintain vapor barrier at the chimney and outside air penetrations.
Installation Of A Listed,
23
Page 24
Installation
Chimney must be removable to allow for
transportation of the mobile home.
CAUTION: THE STRUCTURAL INTEGRITY
OF THE MOBILE HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
OUTSIDE AIR :
Connection from the stoves air intake to the outside
is mandatory, (MOBILE HOMES ONLY) either
through a hole in the wall not higher than the stoves
bottom or through a hole in the oor, using the
fresh air adaptor. Avoid cutting any oor joists, wall
studs, electrical wiring or plumbing. Seal around the
outside air pipe with insulation to prevent drafts.
Also install a ¼” mesh rodent or pest screen in the
end of fresh-air pipe. Fresh-air connection must be
of a non-combustible material, example: 4” (10.16
cm) exible aluminum single wall pipe.
Fresh air could also be supplied from a vented
crawlspace.
The legs must be rmly bolted to the oor using
four ¼” bolts. Be sure to replace any insulation or
panels removed when fastening the bottom nuts.
If room air starvation occurs because the air intake
is blocked with ice, leaves etc., or because the stove
door was left open, or due to a strong exhaust fan
operating, dangerous fumes could be sucked into
the room.
IN SOME AREAS IT MAY BE REQUIRED TO
ELECTRICALLY GROUND THE STOVE TO THE STEEL
CHASSIS OF THE MOBILE HOME.
When this unit is installed in a Mobile Home it must
be grounded to the steel chassis or connected to a
grounding rod.
Spark arrestor cap
At least
3 feet (914 mm)
Insulated
chimney
Ceiling
Outside air connection
through wall or floor
Figure 19: Freestanding installation into mobile home.
Roof flashing
Roof
Radiation Shield
Ceiling support
Double wall pipe
Woodstove
Hearthpad
Floor
Bolt stove to floor
Manufactured (Mobile) home installation must be in accordance with the Manufactured Home Construction
and Safety Standard, UL 307B, Title 24 CFR, Part 3280 and/or The Standard for Manufactured Home
Installations, ANSI A225.1/NFPA 501A.
WARNING: DO NOT INSTALL IN SLEEPING ROOM.
24
Page 25
Installation
model 1200 BriCk plACement & tuBe loCAtions:
COMPLETE THE STOVE AND SMOKE PIPE INSTALLATION BEFORE PLACING THESE BRICKS.
Tube E
Tube D
Tube A
1. Place the three (3) full size
bricks along each side of the
rebox and one (1) full size
brick on either side of the back
of the rebox.
2. To place the oor bricks, lay
the two (2) partial bricks along
the back of the oor. Then on
the left, lay two (2) full size
k
c
i
r
B
l
a
ti
r
a
P
F
e
z
i
S
ll
k
u
c
i
r
B
f
l
a
k
H
c
i
r
B
bricks and on the right, lay a
full size brick in the center and
the half brick in the front (for
the ash dump). The spaces
between the bricks will soon
ll with ashes.
Figure 20: Brick Placement for 1200 shown with Secondary Air Channel
and Tubes.
When replacing bricks, use only pumas type re bricks.
TOTAL BRICKS:
11 - Full size bricks 9” long x 4.5” wide x 1.25” thick
(22.9 cm long x 11.4 cm wide x 3.2 cm thick)
2 - Partial bricks 9” long x 3” wide x 1.25” thick
(22.9 cm long x 7.6 cm wide 3.2 cm thick)
1 - Half brick 4.5 “ long x 4.5” wide x 1.25” thick
(11.43 cm long x 11.43 cm wide x 3.175 cm thick)
Removing Air Tube: If a secondary air tube needs to be removed, place a screwdriver (any style except
at head) into one of the air holes and tap it with a hammer/mallet to the left until the right end of the
tube is freed. To install a secondary air tube, reverse the above instructions.
IMPORTANT: All secondary air tubes must be in place for proper operation.
25
Page 26
Installation
C-CAst CerAmiC BAFFle instAllAtion:
1. Slide the right C-Cast Ceramic Bafe in
over the secondary air tubes at the top
of the rebox. The tab must be on the
top and pointing towards the center
and the smooth side is to face down.
2. Hook the outside edge of the bafe
over the top of the secondary air
chamber. This will make room to for the
installation of the left C-Cast Ceramic
Bafe.
3. Slide the left C-Cast Ceramic Bafe in
over the secondary air tubes. The tab
must be on the bottom and pointing
towards the center and the smooth side
is to face down.
4. Pull the bafes together in the middle
so the right tab rests on top of the left
tab. Ensure the bafes are ush with
the back and both sides of the rebox.
Right Ceramic Baffle
Left Ceramic Baffle
Figure 21: Installation of C-Cast Ceramic Bafe.
FAn wiring diAgrAms:
This appliance, when installed, must be electrically connected and grounded in accordance with local
codes or in the absence of local codes, with the current CSA C22.1 CANADIAN ELECTRICAL CODE. Part
1, SAFETY STANDARDS FOR ELECTRICAL INSTALLATIONS, or THE NATIONAL ELECTRICAL CODE ANSI
/ NFPA 70 in the USA.
CAUTION Label all wires prior to disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation. Verify proper operation after servicing.
DO NOT oil the fan bearings.
DO NOT cut or remove the grounding prong from the plug.
DO NOT route the power cord beneath the heater.
WARNING: This appliance is equipped with a three-prong (grounding) plug for your protection against
shock hazard and should be plugged into a properly grounded three-prong receptacle.
26
Page 27
White
Black
White
Installation
Fan
Black
Black
Fan
temperature
sensor
Power Supply
Figure 22: Freestanding Fan Kit Wiring Diagram.
optionAl FAn instAllAtion - FreestAnding:
Refer to Fan Wiring diagram before installing your
optional fan kit.
1. Remove the fan assembly from the box and
inspect for any damage to the assembly. If
damage is noticed call your dealer, distributor
or courier company and have components
replaced before installing kit.
2. Install the four #10 screws loosely into the
bottom of the air cabinet.
3. Align the keyslots of the fan assembly with
four screws. Fully bottom the keyslots before
tightening the screws
Fan
controller
4. Plug the fan assembly in and check for proper
operation.
Figure 23: Back View of Freestanding Unit
with Fan Kit.
27
Page 28
DISASSEMBLY
removAloF CAst sidesAnd door:
To remove the cast sides, lift off the Cast Top and then
unscrew the slider knob and then remove the two top bolts
using a 3/8” socket. The Cast Side may then be lifted up.
The door may be taken off by rst lifting off the Cast Top
and then removing the two bolts from the top door hinge,
using a 3/8” socket.
door lAtCH Adjustment:
Over time as the door gasket fully compresses to the face of the rebox, it may be necessary
to adjust the door latch position to maintain a tight seal. Signs that the door latch may need
adjusting are if the door handle feels overly loose when closed, or if you notice air leaks
occurring during low burns.
1. Remove the right Cast Side (shown above)
2. Use a 3/8” socket to loosen the two 1/4” bolts and slide the latch slightly back. Retighten
the bolts and latch the handle. The handle should provide a bit of resistance and close rmly.
Certifié pour installation au Canada et aux Etats-Unis.
Models 1200 and 1700 Freestanding units: SUITABLE FOR MOBILE HOME INSTALLATION
Tested to ULC-S627-00, ULC-S628-93 (FPI only), & UL-1482-10.
US Environmental Protection Agency, certified to comply July 1, 1990, particulate emission standards.
Install and use only in accordance with the manufacturers installation and operating instructions. Contact
local building or fire officials about restrictions and installation inspection in your area. Use 6” (150 mm)
diameter minimum 24 MSG black or 25 MSG blued steel connector listed factory-built chimney suitable for
use with solid fuels or masonry chimney. See local building code and manufacturer’s instructions for
precautions required for passing a chimney through a combustible wall or ceiling. Do not pass chimney
connector through a combustible wall or ceiling. Minimum clearances from horizontal connector and ceiling
18” (455 mm). Do not connect this unit to a chimney flue servicing another appliance.
Minimum Clearances to Combustible Materials /
Espaces Libres Aux Materiax Combustibles.
Model / Modèle
Sidewall to unit / De la paroi latérale au dispositif
A
Backwall to unit / De la paroi arrière au dispositif
B
Adjacent wall to corner of unit /
C9” (229 mm)6½" (165 mm)
De la paroi adjacent au coin de dispositif
Sidewall to connector / De la paroi latérale au connecteur
D
Backwall to connector / De la paroi arrière au connecteur
E
Adjacent wall to connector/
F
De la paroi adjacent au connecteur
† Front of door opening to edge of hearth /
G
Le devant d'ouverture de porte au bord de coussin de coeur
† Side/back of unit to edge of hearth /
H
Le latérale/arrière de dispositif au bord de coussin de coeur
CAUTION: An uninsulated smoke pipe must not pass through an attic, roof space, closet or similar concealed
space, or through a floor, ceiling, wall, or partition, or any combustible construction.
† FLOOR PROTECTION: If a stove is installed on a combustible floor, it must have the legs or pedestal
attached and be on a NON COMBUSTIBLE hearth pad
* ALL CLEARANCES CAN BE REDUCED WITH SHIELDING ACCEPTABLE TO THE LOCAL AUTHORITY.
SINGLE WALL:
IN CANADA: Any ULC-S629 listed chimney system with the accompanying listed single wall vent connector.
IN U.S.A.: Any UL 103 HT listed chimney system with the accompanying listed single wall vent connector.
**DOUBLE WALL :
IN CANADA: Any ULC-S629 listed chimney system with the accompanying listed double wall vent connector.
IN U.S.A.: Any UL 103 HT listed chimney system with the accompanying listed double wall vent connector.
DOUBLEWALL IS REQUIRED FOR MOBILE HOME INSTALLATIONS.
**Alcove (Use double wall pipe) / Alcôve (Utilisant le double connecteur de mur)
ITotal width / Largeur totale55” (1397 mm)
JTotal height / Hauteur totale78” (1981 mm)
K Top of stove to ceiling / Le sommet de poêle au plafond49” (1245 mm)
LSidewall to unit / De la paroi latérale au dispositif
Sidewall to connector / De la paroi latérale au connecteur
M24” (610 mm)
Backwall to unit / De la paroi arrière au dispositif
N12” (305 mm)
Backwall to connector / De la paroi arrière au connecteur
O15” (381 mm)
Maximum Depth / Profondeur maximumP48” (1220 mm)48” (1220 mm)
Models 1200 and 1700 inserts may be installed as an insert in a masonry fireplace. / On peut encastrer le modèles 1200 et 1700 dans un foyer de maçonnerie.
Model / Modèle 1200 FPI 1700 FPI
A To unshielded side wall / aux mur non protegé 10” (254 mm) 10” (254 mm)
B To an unshielded 8” (203 mm) mantle / aux manteau 8“ non protegé 21” (533 mm) 24” (610 mm)
C To top facing (protruding ¾” [19 mm]) clearance / aux revêtement supérieur 17½” (445 mm) 19½” (495 mm)
D To side facing (protruding ¾” [19 mm]) clearance / aux revêtement a côté 1” (25 mm) 1” (25 mm)
E † From door opening of unit to edge of floor protection /
De ouverture de la porte de l'unité à bord de la protection de plancher USA 16” (406mm) / CND 18” (450mm)
F † From side of unit to edge of floor protection /
Du côté de l'unité au bord de la protection de plancher USA 6” (152 mm) / CND 8” (200 mm)
OPERATE ONLY WITH DOORS CLOSED. Only open door to feed fire. For use with solid wood
fuels only. Do not use any other type of fuel. Do not use grate or elevate-fire build wood fire directly
on hearth. Do not overfire. Do not obstruct beneath the heater. If heater or chimney connector
glows, you are overfiring. Inspect and clean chimney frequently-under certain conditions of use,
creosote buildup may occur rapidly. The provided insulation materials are required for operation.
Keep furnishing and other combustibles well away from heater. Replace glass only with 5 mm thick
ceramic glass. Optional component for FS: fan, electrical rating 115V, 60 Hz 1 Amp (Part #
EFW-261). Combustion air openings are not to be obstructed.
Danger: Risk of electrical shock. Disconnect power before servicing unit. Route cord away from
heater.
CAUTION:
DO NOT TOUCH. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT MAY CAUSE
SKIN BURN. READ NAMEPLATE AND INSTRUCTIONS.
MADE IN CANADA /
FABRIQUE AU CANADA
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
LISTED SOLID FUEL SPACE HEATER / IDENTIFIE COMME UN FOYER A COMBUSTIBLE SOLIDE
Boston 1200 FS
268-S-04b-2
HOT WHILE IN OPERATION.
Venice 1200 FPI Boston 1200 FPI Venice 1700 FPI Boston 1700 FPI
268-S-05b-2 268-S-05b-2 268-S-06b-2 268-S-06b-2
Modèles 1200 et 1700 items indépendants: UTILISABLES DANS LES MAISONS MOBILES.
Testé selon ULC-S627-00, ULC-S628-93 (FPI seulement), & UL-1482-10.
États-Unis Environnemental Protection Agence, a certifié pour conformer au Juillet 1, 1990, les normes de particules d'émission.
Ce dispositif doit entre installé et opéré conformément aux instructions d'installation et d'opération du manufacturier contactez le
service local de l'inspection des bâtiments ou l'officier pompier concernant les restrictions et l'inspection d'installation dans votre
localité. Utiliser des connecteurs répertoriés 24 MSG noir ou 25 MSG en acier bronzée de 6" (150 mm) minimum, et une
cheminée de fabrication industrielle, appropriée pour utilisation avec des combustibles solides ou avec une cheminée de
maçonnerie. Vérifiez les précautions a prendre exigées parle code local et les instructions du manufacturier concernant les
conditions pour passer la cheminée a travers un mur ou un plafond combustible. Net pas installer le connecteur de la cheminée
a travers un mur ou un plafond combustible. Espaces libres minimum d'un connecteur horizontal et plafond sont 18" (455 mm)
ne pas connecter ce dispositif a un conduit de cheminée qui sert déjà un autre dispositif.
L’OPERATION DU POELE DOIT SE FAIRE AVEC LA PORTE FERME. N'ouvrir la porte que pour alimenter le feu. N'utilisez que
des combustibles solides. Ne pas utiliser un autre type de carburant. N'employez pas de grille de foyer ou ne surélevez pas le feu.
Mettez le bois à brûler directement sur l'âtre. Pour éviter la surchauffeur, ne mettez pas trop de bois. N'obstruez pas les ouvertures
d'air comburant. Si le poêle ou le connecteur commencent à luire, vous surchauffez le poêle. Inspectez et nettoyez la cheminée
souvent. Dans certaines conditions, le créosoté peut s'accumuler rapidement. Les matériaux d'isolation fournis sont requis pour
l'opération.Tenez loin les meubles et d'autres produits combustibles. Ne remplacez le verre qu'avec du verre céramique, 5mm
10” (254 mm)
8½" (216 mm)
22” (559 mm)
13” (330 mm)13” (330 mm)
17” (432 mm)15” (381 mm)
MISE EN GARDE: Un uninsulated tuyau de fumée ne doit pas passer par un grenier, un espace de toit, le placard ou
l'espace dissimulé similaire, ou par un plancher, un plafond, un mur, ou une cloison, ou une construction combustible.
† PROTÉGER LE PLANCHER: Si une cuisinière est installée sur un sol combustible, il doit avoir un piédestal attache et
être sur un coussinet non- combustible.
TOUS “ESPACES LIBRES AUX MATERIAX COMBUSTIBLES” PEUVENT ÊTRE RÉDUITS AVEC PROTÉGEANT
ACCEPTABLE À L’AUTORITÉ LOCALE.
Seul Connecteur de Mur:
Au Canada: Certifiée seul connecteur de mur avec toute systèmes de cheminée listée sous ULC-S629.
Aux États-Unis: Certifiée seul connecteur de mur avec toute systèmes de cheminée listée sous UL 103 HT.
**Double Connecteur de Mur:
Au Canada: Certifiée double connecteur de mur avec toute systèmes de cheminée listée sous ULC-S629.
Aux États-Unis: Certifiée double connecteur de mur avec toute systèmes de cheminée listée sous UL 103 HT.
Sid¸e wall / Mur a côté
B
C
D
E
épais. Équipement en option pour un FS: ventilateur caractéristiques assignées 115V, 60 Hz, 1 Amp (pièce
# EFW-261) tenez le câble électrique loin du poêle. Danger: Le risque de choc électrique. Débrancher le
dispositif avant d'entretenir. Ouvertures d'air de combustion ne doivent pas être obstrués.
TRÈS CHAUD QUAND ALLUMÉ.
MISE EN GARDE:
NE TOUCHEZ PAS. TENIR LOIS
Double wall pipe with efficiency
shield (Flat top model only) / Double
connecteur de mur avec la protection
d'efficacité (Le modèle plat seulement
7” (178 mm)
6” (152 mm)
22” (559 mm)
10” (254 mm)
14½” (368 mm)
USA 16” (406 mm) CND 18” (450 mm)
USA 6” (152 mm) CND 8” (200 mm)
DOUBLE CONNECTEUR DE MUR NÉCESSAIRES POUR INSTALLATION DANS LES MAISONS
MOBILE.
Back wall/
Mur arrière
B
A
D
Front /
Mur avant
† FLOOR PROTECTION / PROTÉGER LE PLANCHER:
If unit is raised / Si l'appareil est soulevé:
0” - 2” (0mm - 51mm); 1” (25mm) non-combustible material with k value = 0.84 or equivalent /
1” (25mm) le matériel incombustible avec la valeur de k = 0.84 ou équivalent.
2” - 8” (51mm - 203mm); ½” (13mm) non-combustible material with k value = 0.84 or equivalent /
Greater than/Plus grand que 8” (203 mm) any non-combustible material /
n'importe quel type de matériel incombustible.
Adjacent wall /
Mur adjacent
E
C
F
Adjacent wall / Mur adjacent
C
H
Floor Protection /
Front /
Mur avant
Protection du sol
½” (13mm) le matériel incombustible avec la valeur de k = 0,84 ou équivalent.
LES ENFANTS, LES VÊTEMENTS ET LES MEUBLES. LE CONTACT
PEUT CAUSER DES BRÛLURES. LISEZ ATTENTIVEMENT
L’ÉTIQUETTE ET LES INSTRUCTIONS.
MANUFACTURED BY /
FABRIQUE PAR
: SHERWOOD INDUSTRIES LTD. 6782 OLDFIELD ROAD, SAANICHTON, BC CANADA
DATE OF MANUFACTURE /
DATE DE FABRICATION:
J F M A M J J A S O N D 2011 2012 2013 2014 2015
Serial No. / No. De Serié:
XXXXXXXXXXX
Top vent out back wall with min. 24” (610mm)
vertical rise; double wall pipe / Donné vent hors
de la paroi arrière avec le min. 24” (610 mm)
l'ascension verticale; double connecteur de mur
11” (279 mm)
13” (330 mm)
16” (381 mm)
15” (406 mm)
Alcove Back wall /
Mur d’alcôve a l’arrière
Front /
Mur avant
H
H
G
N
L
M
Front /
Alcove Side wall /
Mur d’alcôve a côté
Mur avant
I
O
Alcove /
Alcôve
C-12430
K
J
29
Page 30
Parts List
Reference #DescriptionPart #
1120°F (49°C) Ceramic Fan Temperature SensorEC-001
2Convection Blower50-512
3FPI Fan Controller - 115VEC-039
3Fan Controller KnobEC-040
4Domestic power cord - 115VEC-042
5Boston FS Fan Kit50-2417
6Fresh Air Kit (for fan)50-2440
7Fresh Air KitEF-186
8Boston 1200 FS Cast Top50-2441
9Boston 1200 Cast Side Right50-2443
10Cast Leg Lip Right50-2114
11Boston 1200 FS Cast Side Left50-2442
12Side Shelves (Set of 2)50-1991
13Cast Leg Lip Left50-2113
14Cast Leg50-2106
15Boston 1200 Ash Pan50-2446
16Boston 1200 Cast Ash Drawer Cover50-2444
171200 C-Cast Ceramic Bafe (1 Piece)50-1146
181200 Secondary Air Tube Rear E50-1102
191200 Secondary Air Tube Middle D50-1103
201200 & 1700 Front Secondary Air Tube A50-1099
21Pumice Brick 4.5” x 9”50-1105
22Pumice Brick 3” x 9”50-1104
23Pumice Bricks - 4½” X 4½”50-1106
241200 & 1700 Right Shield Assembly50-1145
251200 & 1700 Left Shield Assembly50-1144
261200 & 1700 Cast Ash Plug50-1120
27Door Gasket - 7 feet (2.13m)EF-168
28Wood Door Glass Retainer Kit (With Screws)50-1122
29Glass with Tape10-000
30Boston 1200 Cast Front50-2445
31Boston Door Handle Complete50-2393
32Woodstove Poker50-1816
Owner’s Manual50-2439
Gloves50-1525
30
Page 31
Parts Diagram - Freestanding
13
4
6
16
14
21
24
15
3
1
2
11
5
7
8
17
9
31
26
2829
30
27
23
25
22
18
19
20
10
12
32
31
Page 32
Warranty
Sherwood Industries Ltd. is the manufacturer of the Enviro line of heating products. At Sherwood
Industries, our commitment to the highest level of quality and customer service is the most important
thing we do. Each Enviro stove is built on a tradition of using only the nest materials and is backed by
our Exclusive Lifetime Limited Warranty to the original purchaser. With Enviro, you’re not just buying a
stove, you’re buying a company with years of unequalled performance and quality.
Limited Lifetime Warranty:
Under this warranty, Sherwood Industries Ltd. covers the stove body and accessories against defects
in materials and workmanship, for part repair or replacement for the rst seven (7) years and limited
labour for the rst two (2) years to the original purchaser. This Warranty covers: Firebox, Stainless Steel
Secondary Air Tubes, Cabinet Sides, C-Cast Ceramic Bafe Bafe, Surround Panels, Pedestals, Legs,
Ceramic Glass, Slider Control and Cast Iron Door Assembly against defects. Please see the exclusions and
limitation section below as certain restrictions and exclusions apply to this warranty.
Limited Two (2) Year Warranty:
Under this warranty, Sherwood Industries Ltd. covers all electrical components against defects in
materials and workmanship, for part repair or replacement for the rst two (2) years and limited labour
for the rst two (2) years to the original purchaser. Please see the exclusions and limitation section below
as certain restrictions and exclusions apply to this warranty.
Limited One (1) Year Warranty:
Under this warranty, Sherwood Industries Ltd. covers all exterior surface nishes against defects in
materials and workmanship, for part repair or replacement and limited labour for the rst year to the
original purchaser. Please see the exclusions and limitation section below as certain restrictions and
exclusions apply to this warranty.
How the Warranty Works
1. All warranties by the manufacturer are set herein and no claim shall be made against the manufacturer
on any oral warranty or representation. All claims under this Limited Warranty must be made in writing
by your dealer.
2. Any stove or part thereof that is repaired or replaced during the Limited Warranty period will be
warranted under the terms of the Limited Warranty for a period not exceeding the remaining term of
the original Limited Warranty or six (6) months, whichever is longer.
3. For any part or parts of this stove, which in our judgment show evidence of defects, Sherwood
Industries Ltd. reserves the option to repair or to replace the defective product through an accredited
distributor or agent, provided the defective part is returned to the distributor or agent, transportation
prepaid, if requested. Sherwood Industries Ltd. may chose to buy back the item at the cost the dealer
was invoiced.
4. If you discover a problem that you think may be covered by the Limited Warranty, you MUST REPORT
it to your Enviro dealer WITHIN 30 DAYS, giving them proof of purchase and the date of purchase.
The dealer will investigate the problem and work with Sherwood Industries Ltd. to determine whether
the problem:
a) Is covered by the Limited Warranty or
b) Can be xed in your home or does the product need to be returned to Sherwood Industries Ltd.
for repair.
5. If Sherwood Industries Ltd. determines that the stove needs to be returned to Sherwood Industries
Ltd. for repair, the customer has the responsibility and the expense of removing it from their home
and shipping it to Sherwood Industries Ltd. If the problem is covered by the Warranty, Sherwood
Industries Ltd. will replace the item at their discretion and the customer will be responsible for return
shipping and re-installation in their home.
32
Page 33
Warranty
6. If the problem is not covered by the Limited Warranty, the customer will be responsible for all repair
costs, as well as all storage, shipping and the cost of removing and re-installing the stove.
If you are not satised with the service provided by the Enviro dealer, write to Sherwood Industries Ltd.
at the address listed on the last page of the Owner’s Manual. Include the date you bought the product
and a description of the problem.
Exclusions and Limitations:
1. This Warranty does not cover tarnish, discoloration or wear on the plating or paint.
2. This Warranty does not cover gasket material.
3. A qualied installer must install this stove. This Limited Warranty covers defects in materials and
workmanship only if the product has been installed in accordance with local building and re codes;
in their absence refer to the owner’s manual. If the product is damaged or broken as a result of
any alteration, willful abuse, mishandling, accident, neglect, or misuse of the product, the Limited
Warranty does not apply.
4. The stove must be operated and maintained at all times in accordance with the instructions in the
Owner’s Manual. If the unit shows signs of neglect or misuse, it is not covered under the terms of
this Warranty policy. Performance problems due to operator error will not be covered by the Limited
Warranty policy.
5. As this is a heating appliance, some changes in colour of surface nishes may occur. This is not a aw
and as such is not covered under this warranty.
6. Some minor expansion, contraction, or movement of certain parts and resulting noise, is normal and
not a defect and, therefore, is not covered under this Limited Warranty.
7. Misuse includes over-ring. This will result if the stove is used in such a way that one or more of the
plates glows red. Over-ring can be identied later by warped plates and paint pigment being burnt
off. Over-ring this appliance can cause serious damage and will nullify the Limited Warranty.
8. The Limited Warranty will cover glass thermal breakage only and will not cover misuse of the stove
glass, including but not limited to:
a) Glass that is struck, has surface contaminates or has had harsh or abrasive cleaners used on it.
b) If the door is slammed or is closed while wood in the rebox is protruding out the stove opening thus
striking the glass.
9. This warranty does not cover products made or provided by other manufacturers and used in
conjunction with the operation of this stove without prior authorization from Sherwood Industries Ltd.
The use of such products may nullify the Limited Warranty on this stove. If unsure as to the extent of
this Limited Warranty, contact your authorized Enviro dealer before installation.
10. Sherwood Industries Ltd. will not be responsible for inadequate performance caused by environmental
conditions.
11. The Limited Warranty does not cover installation and operational related problems such as use of
downdrafts or spillage caused by environmental conditions. Environmental conditions include but
are not limited to nearby trees, buildings, roof tops, wind, hills, mountains, inadequate venting
or ventilation, excessive offsets, negative air pressures or other inuences caused by mechanical
systems such as furnaces, fans, clothes dryers etc.
33
Page 34
Warranty
12. The Limited Warranty does not cover damage caused by burning salt-saturated wood, corrosive
driftwood, chemically treated wood or any fuel not recommended in the Owner’s Manual (use cord
wood only).
The Limited Warranty is void if:
a) The stove has been operated in atmospheres contaminated by chlorine, uorine or other damaging
chemicals.
b) The stove is subject to submersion in water or prolonged periods of dampness or condensation.
c) Any damage to the unit, combustion chamber or other components due to water, or weather
damage which is the result of, but not limited to, improper chimney/venting installation.
d) Salt air in coastal areas or high humidity can be corrosive to the nish; these environments can
cause rusting. Damage caused by salt air or high humidity is not covered by the Limited Warranty.
13. Exclusions to the Limited Warranty include: injury, loss of use, damage, failure to function due to
accident, negligence, misuse, improper installation, alteration or adjustment of the manufacturer’s
settings of components, lack of proper and regular maintenance, alteration, or act of God.
14. The Limited Warranty does not cover damage caused to the stove while in transit. If this occurs, do
not operate the stove and contact your courier and/or dealer.
15. The Limited Warranty does not extend to or include paint, door or glass gaskets or rebricks damage
caused by normal wear and tear, such as paint discoloration or chipping, worn or torn gaskets,
chipped or cracked rebrick, etc.
16. The Limited Warranty does not include damage to the unit caused by abuse, improper installation,
or modication of the unit.
17. Damage to plated surfaces caused by ngerprints, scratches, melted items, or other external scores
and residues left on the plated surfaces from the use of abrasive cleaners or polishes is not covered
in this warranty.
18. The Limited Warranty does not cover tarnish, discoloration or wear on the plated surfaces.
19. Sherwood Industries Ltd. is free of liability for any damages caused by the stove, as well as
inconvenience expenses and materials. The Limited Warranty does not cover incidental or
consequential damages.
20. The Limited Warranty does not cover any loss or damage incurred by the use or removal of any
component or apparatus to or from the Enviro stove without the express written permission of
Sherwood Industries Ltd. and bearing a Sherwood Industries Ltd. label of approval.
21. Any statement or representation of Enviro products and their performance contained in Enviro
advertising, packaging literature, or printed material is not part of the Limited Warranty.
22. The Limited Warranty is automatically voided if the stove’s serial number has been removed or altered
in any way. If the stove is used for commercial purposes, it is excluded from the Limited Warranty.
23. No dealer, distributor, or similar person has the authority to represent or warrant Enviro products
beyond the terms contained within the Limited Warranty. Sherwood Industries Ltd. assumes no
liability for such warranties or representations.
24. Sherwood Industries Ltd. will not cover the cost of the removal or re-installation of the stove, hearth,
facing, mantels, venting or other components.
25. Labour to replace or repair items under this Limited Warranty will be covered per our warranty
service fee reimbursement schedule. Labour rates are set per component and as such total labour
costs may not be covered.
34
Page 35
Warranty
26. Sherwood Industries Ltd. is not liable for freight or labour on any stove replaced in-eld and is not
liable for travel costs for service work. In the event of in-home repair work, the customer will pay any
in-home travel fees or service charges required by the Authorized Dealer.
27. At no time will Sherwood Industries Ltd. be liable for any consequential damages which exceed the
purchase price of the unit. Sherwood Industries Ltd. has no obligation to enhance or modify any
stove once manufactured (example: as a stove evolves, eld modications or upgrades will not be
performed).
28. This Limited Warranty is applicable only to the original purchaser and it is non-transferable.
29. This warranty only covers Enviro products that are purchased through an authorized Enviro dealer.
30. If for any reason any section of the Limited Warranty is declared invalid, the balance of the warranty
remains in effect and all other clauses shall remain in effect.
31. The Limited Warranty is the only warranty supplied by Sherwood Industries Ltd., the manufacturer of
the stove. All other warranties, whether express or implied, are hereby expressly disclaimed and the
purchaser’s recourse is expressly limited to the Limited Warranty.
32. Sherwood Industries Ltd. and its employees or representatives will not assume any damages, either
directly or indirectly, caused by improper usage, operation, installation, servicing or maintenance of
this stove.
33. Sherwood Industries Ltd. reserves the right to make changes without notice. Please complete and
mail the warranty registration card and have the installer ll in the installation data sheet in the back
of the manual for warranty and future reference.
34. Sherwood Industries Ltd is responsible for stocking parts for a maximum of seven (7) years after
discontinuing the manufacture or incorporation of the item into its products. An exception to this
would be if an OEM supplier is not able to supply a part.
35
Page 36
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
MODEL:___________________________________
SERIAL NUMBER:___________________________
DATE OF PURCHASE: ______________(dd/mm/yyyy)
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
_________________________________________
DATE OF INSTALLATION:___________(dd/mm/yyyy)
INSTALLER’S SIGNATURE:
_________________________________________
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
www.enviro.com
May 26, 2011
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
C-12426
36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.