Enviro 170S5FG User Manual

MQL • TABLE OF CONTENTS
2
Product Overview .....................................................................................................................................3
Features and Benefits...............................................................................................................................6
Application Considerations ......................................................................................................................5
Unit Configuration ...................................................................................................................................6
Electric Heat .............................................................................................................................................7
Coil and Filter Data ..................................................................................................................................9
Static Pressure Data ................................................................................................................................10
Fan Notes ................................................................................................................................................13
Fan Performance Data.............................................................................................................................14
Guide Specifications................................................................................................................................25
Metric Conversion Chart..........................................................................................................................28
Features and Options ..............................................................................................................................30
GENERAL NOTES
Some drawings are not shown in this catalog. Please refer to www.enviro-tec.com for complete submittal drawings for your project.
All data herein is subject to change without notice. Refer to www.enviro-tec.com for current catalog and submittal drawings.
Drawings not for installation purposes; refer to IOM manual at www.enviro-tec.com.
ETL Report Number 3017723-001.
MEA Number MEA 107-02-E applies to all units with any combination of chilled water or R-22 direct expansion coils and either hot water coils, steam coils, or electric heat.
ENVIRO-TEC
PRODUCT OVERVIEW • MQL
3
The Perfect Solution for Schools, Hospitals, and Commercial Buildings.
The flexibility of the Model MQL Blower Coil allows you to design the unit to meet the specific project needs. The MQL design allows you to configure draw thru applications in horizontal, vertical, and foot­print-saving arrangements. From basic air handling to the sophisticated isolation room systems required to meet challenging indoor air quality (IAQ), controls, and acoustic (sound sensitive) projects – the Model MQL Blower Coil is your solution!
Standard Features
Modular construction allows for footprint saving arrangements including stacking modules in two-high
configuration.
IAQ galvanized drain pans are double sloped to prevent standing water and minimize microbial growth.
Stainless steel drain pans are available.
Removable access panels for improved accessibility, cleanability, and serviceability. Hinged access doors
with quick action latches are available.
Single point power connection – even with draw thru or blow thru electric heat – simplifies installa-
tion. Fan motors are factory mounted and wired to the junction box.
Available in nine sizes, from 600 to 10,000 CFM.
Internal spring isolation standard on all unit sizes 02 - 17.
Single wall and double wall-galvanized construction are available. Double wall construction enhances
indoor air quality, protects insulation, and provides the ability to clean the inside of the unit.
Optional Features
Factory-packaged blower coils are available with starters or variable frequency drives, factory mounted
and wired. Simply connect power, piping, and ductwork, and the units are ready for operation. An excellent way to minimize installation time, coordination and costs, while increasing reliability.
Quiet, flexible, acoustical discharge plenums may be used for sound sensitive projects.
Exhaust / Return Fan with Economizer Sections for use with IAQ applications (“free” heating and cool-
ing – cost savings for space conditioning).
Customized Options including:
- Direct drive plug fans
- High efficiency filters
- Double wall perforated lining
- External face and bypass dampers
- Inspection windows
ENVIRO-TEC
MQL • FEATURES AND BENEFITS
4
Designed For Maximum Flexibility
The ENVIRO-TEC
®
Model MQL Blower Coil Unit is designed to maximize flexibility of selection and installation.
The unit is also designed to exceed the stringent quality standards of the institutional market, while remaining cost competitive in the light commercial segment of the market.
ENVIRO-TEC
®
Model MQL sets the new standard for quality, flexibil­ity, and competitive pricing.
For the Building Designer: OPTIONAL COMPONENTS MEAN FLEXIBILITY
The extensive variety of standard options available on the MQL is where you find the versatility to fit any HVAC system designer’s needs.
Options include: Mixing boxes with standard low leak dampers, High efficiency filter sections for 2" prefilter and 4" final filter, blow thru electric heat with single point power connection. All electric heat units are listed with ETL as an assembly and carry the cETL label.
High Efficiency motors, starters, disconnects and fusing mean eas­ier coordination between mechan­ical and electrical trades.
Coil options allow for 4 or 6 row cooling coils. Water coils have optional circuiting that can be used to reduce Water Pressure Drop, which may also allow for pipe size reductions and lower material cost. Hot Water or Standard Steam coils may be placed in the Preheat or Reheat position.
All Model MQL blower coils have the option of foil faced insulation.
For the Contractor: L
OWER INSTALLED COST
Model MQL blower coils are shipped completely assembled, reducing field installation time and labor. All units are thor­oughly inspected and tested prior to shipment, eliminating potential problems at startup. Motor wiring is brought to a junction box on the outside of the unit casing, reduc­ing electrical hook-up time.
A wide variety of fan discharge configurations allow for increased flexibility and easier installation on the jobsite, resulting in cost reduc­tions by eliminating expensive elbows, etc.
For the Owner: QU
ALITY PRODUCT
Model MQL blower coil units are built from G60 minimum spangled galvanized steel with a chromate coating. This metal surpasses the ASTM 125 hour salt spray test for corrosion and rust. Standard insu­lation is 1 inch fiberglass insulation which is glued and pin spotted for maximum positive adhesion. Insulation complies with UL 181 and NFPA 90A.
All units, with or without Electric Heat, are ETL listed and labeled. All wiring is in compliance with NEC, assuring safety and quality for the owner.
ENVIRO-TEC
APPLICATION CONSIDERATIONS • MQL
5
Application Considerations
Model MQL blower coil units offer a wide range of application flex­ibility, while maintaining a simple, easy to install unit design. These units are intended to provide comfort cooling and heating within a small footprint. They may be applied in many types of building structures including schools, office buildings, hospi­tals, condominiums, assisted liv­ing facilities, apartments or stores. Applications can be constant or variable volume.
There are many applications in which the MQL product can be utilized. Some examples include:
Constant volume applications
Two-pipe hydronic system for cooling and/or heating
Two-pipe hydronic cooling system with electric heat
Four-pipe system with dedi­cated heating and cooling coils
Direct Expansion (DX) split systems with hydronic heat
Direct Expansion (DX) split systems with electric heat
Variable volume applications
Two-pipe hydronic system for cooling and/or heating.
Two-pipe hydronic cooling system with electric heat.
Four-pipe system with dedi­cated heating and cooling coils.
Acoustics
Control of noise within both occu­pied and unoccupied spaces has become increasingly important to designers and building own­ers/occupants. Proper considera­tion must be given to placement of indoor air conditioning units, particularly in the occupied space.
Inherent flexibility of the fan and coil combination in the vertical configuration allows application in sound-sensitive areas. In such instances, a fan running at low speed with a high capacity coil normally yields satisfactory results. It also may be desirable to select a larger nominal capacity unit and operate it at a less than nominal airflow for further acoustic benefit.
Three phase motors are recom­mended for sound-sensitive appli­cations to avoid potential single phase motor hum. Unit operation in the stall region of the fan curve is not recommended since it may cause unsatisfactory noise levels and excessive unit vibration.
Installation
These floor mounted or ceiling hung units can be installed on a base rail or hanger rods at the cor­ner points. All units have internally isolated fan decks; therefore, flex connections are not required, which will reduce installation costs. One of the most important and basic IAQ issues is condensate management. The first step to ensure trouble-free operation is proper installation. It is very important that the unit be mounted high enough so that the condensate drain from the unit may be properly trapped. Please refer to the MQL IOM Manual at www.enviro-tec.com for specifics on this issue. As with all HVAC sys­tems, these units should be installed according to all applica­ble ASHRAE standards, SMACNA and local code requirements.
Operating Limitations
Units must not be operated above maximum fan speed or unit air­flow as listed in the Fan Performance section of this cata­log. Unit operation at greater than maximum fan speed could drastically reduce bearing life and may result in a catastrophic fail­ure. Operating at greater than the maximum allowable airflow in the cooling mode may result in unsatisfactory operation due to moisture carry over from the coil. In addition, it is often not eco­nomical to operate a unit at its maximum fan speed due to the greater motor power require­ments.
Units with electric heat should not be operated with leaving air tem­perature greater than 104°F, to prevent excessive leaving air tem­peratures and electric heat limit trips. A hydronic (or steam) coil and electric heat should not be operated simultaneously to pre­vent excessive leaving air tem­peratures and limit trips. Electric heat units are equipped with a lockout switch that disables the electric heater if the temperature of the hydronic (or steam) coil is greater than 104°F (40°C).
Water coils must not be operated above a fluid velocity of 8 ft./sec. to reduce the possibility of veloc­ity induced erosion and flow noise. Water coils must not be operated below a fluid velocity of 1 ft./sec. to prevent degraded coil performance caused by laminar flow. These high or low fluid flow rates may not be included in the ARI coil certification.
ENVIRO-TEC
MQL • UNIT CONFIGURATION
6
Position: 1 2 3 456 7 8 9 10
MQL - Module Size Dim. 02 03 04 06 08 10 12 14 17
H - in (mm) 17-3/8 (441) 17-3/8 (441) 17-3/8 (441) 26-3/8 (670) 26-3/8 (670) 26-3/8 (670) 41-3/16 (1046) 41-3/16 (1046) 41-3/16 (1046)
W - in (mm) 28 (711) 34 (864) 42 (1069) 42 (1069) 46 (1168) 56 (1422) 64 (1626) 68 (1727) 80 (2032)
L - in (mm) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133) 5-1/4 (133)
SAM Small Access H - in (mm) 22 (559) 22 (559) 22 (559) 30 (762) 34 (864) 34 (864) 44 (1118) 44 (1118) 44 (1118)
SCM Small Coil W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 82 (2083)
SFM Small Flat Filters (2" and/or 4" Cartridge) L - in (mm) 15 (381) 15 (381) 15 (381) 15 (381) 15 (381) 15 (381) 15 (381) 15 (381) 15 (381)
MAM Medium Access H - in (mm) 22 (559) 22 (559) 22 (559) 30 (762) 34 (864) 34 (864) 44 (1118) 44 (1118) 44 (1118)
MCM Medium Coil W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 82 (2083)
MFM
Med. INTELLITRAC
®
Mix. Box w/Flat Filters (2")
L - in (mm) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762)
MIM
Med. INTELLITRAC
®
Inlet Plenum w/Flat Filters (2")
MMM Medium Mixing Box with Flat Filters (2")
MRM Medium Inlet Plenum with Flat Filters (2")
MVM Medium V-Bank Filters (2")
HFM Horizontal FC Fan H - in (mm) 22 (559) 22 (559) 22 (559) 30 (762) 34 (864) 34 (864) 44 (1118) 44 (1118) 44 (1118)
HPM Horizontal Plug Fan W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 82 (2083)
RFM Return FC Fan L - in (mm) 32 (813) 32 (813) 32 (813) 36 (914) 36 (914) 36 (914) 40 (1016) 40 (1016) 40 (1016)
RPM Re turn Plug Fa n
VCM Vertical Coil
VFM Vertica l FC Fa n
MBM Medium Face & Bypas s H - in (mm) 30 (762) 30 (762) 30 (762) 40 (1016) 46 (1168) 46 (1168) 56 (1422) 58 (1473) 58 (1473)
MTM Medium Tall Coil W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 82 (2083)
STM Small Tall Coil L - in (mm) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762)
H - in (mm) 22 (559) 22 (559) 22 (559) 30 (762) 34 (864) 34 (864) 44 (1118) 44 (1118) 44 (1118)
W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 82 (2083)
L - in (mm) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762) 30 (762)
LAM Large Access H - in (mm) 22 (559) 22 (559) 22 (559) 30 (762) 34 (864) 34 (864) 44 (1118) 44 (1118) 44 (1118)
LFM
Lg. INTELLITRAC
®
Mix. Box w/V-Bank Filters (2")
W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 58 (1473)
LIM
Lg. INTELLITRAC
®
Inlet Plenum w/V-Bank Filters (2")
L - in (mm) 42 (1067) 42 (1067) 42 (1067) 42 (1067) 42 (1067) 42 (1067) 42 (1067) 42 (1067) 42 (1067)
LMM Large Mixing Box with V-Bank Filters (2")
LRM Large Inlet Plenum with V-Bank Filters (2")
LPM Large Discharge Plenum
FCM FC Fan and Coil Combination (Horizontal Only) H - in (mm) 22 (559) 22 (559) 22 (559) 30 (762) 34 (864) 34 (864) 44 (1118) 44 (1118) 44 (1118)
HEM Horizontal Economizer W - in (mm) 30 (762) 36 (914) 44 (1118) 44 (1118) 48 (1219) 58 (1473) 66 (1676) 70 (1778) 82 (2083)
H - in (mm) 13-1/2 (343) 13-1/2 (343) 13-1/2 (343) 18 (457) 18 (457) 18 (457) 21 (533) 21 (533) 21 (533)
W - in (mm) 11-1/2 (292) 11-1/2 (292) 11-1/2 (292) 17 (432) 17 (432) 17 (432) 24 (610) 24 (610) 24 (610)
L - in (mm) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559) 22 (559)
Electric Heat Draw Thru
Electric Heat Blow Thru
External Flat Filters (2")
UNIT CONFIGURATION (IN DIRECTION OF AIRFLOW)
EHD
EHB
EFM
Uppe r De ck - B
Low e r De ck - A
Notes:
1. All dimensions are +
1/4" (6mm). Metric
values are soft
conversions.
2. Section images are for
identification of unit
configuration only.
See individual section
submittal drawings at
www.enviro-tec.com
for details.
3. Certain configuration
rules apply; see cata-
log and selection
program for details.
4. All data subject to
change without
notice.
Fig. 1
Fig. 2
Fig. 2
Fig. 2
Fig. 2
Fig. 3
Fig. 4
Fig. 4
Fig. 5
ENVIRO-TEC
ELECTRIC HEAT • MQL
7
STANDARD FEATURES
• G60 galvanized steel casing
• Flanged construction for direct unit
mounting, in blow thru configuration
• Listed for zero clearance installation
• Meets National Electrical Code requirements
• Ni-Chrome wire in ceramic insulators
• Stainless steel element terminals
and hardware
• Element support brackets on maximum
3 1/2" centers
• Solid cover with continuous full height hinge
• Overtemperature protection
• All internal wiring rated for 105°C minimum
• Airflow switch
• Incoming line power distribution block
• ETL Listed in compliance with UL/ANSI Standard 1995
• Single point power connection
• Heater factory mounted to unit with ETL listing as an
assembly
OPTIONAL FEATURES
• Main incoming power disconnect (non-fused) (fused)
• Fusing (main) (per stage)
• Magnetic contactors wired for disconnecting operation
• Solid state relay with 4-20 mA, thermistor 0-135 Ohm, 0-16 VDC, or 6-9 VDC control
• Fan control package with heater interlock contacts (required for single point power connection)
• De-rated elements (for longer life)
Blow Thru
(installed on unit discharge)
Side View Front View
Airflow
Draw Thru
(installed upstream of fan)
Side View
Airflow
VOLTAGE
115/1 208/1 230/1 277/1 208/3 230/3 460/3 575/3
4.81
4.35
3.61
HEATER AMP CALCULATION
AMPs per kW
8.70
1.00
2.78
2.51
1.26
1.Refer to MCA/MOP Calculator at www.enviro-tec.com for MCA and/or MOP calculations.
2. Non-Fused Door Interlock Disconnect Switch shall be sized according to MCA.
3. Fused Door Interlock Disconnect Switch and Main Fusing shall be sized according to MOP.
4. Heaters above 480v must utilize one time secondary limits only.
Plan View
ENVIRO-TEC
MQL • ELECTRIC HEAT
8
Notes:
1. Blow thru heaters can have a maximum of two stages.
2. VFD controllers cannot be supplied with blow thru heaters.
3. Specific kW ratings are available within the ranges shown. Refer to selection program.
4. Heaters above 480v must utilize one time secondary limits only.
Notes:
1. Draw thru heaters can have a maximum of four stages.
2. All heaters that have an AMP draw greater than 48 AMPs will have a minimum of two stages.
3. Specific kW ratings are available within the ranges shown. Refer to selection program.
4. Heaters above 480v must utilize one time secondary limits only.
Min Ma x Mi n Max Min Ma x Min Max Min Ma x Mi n Max Min Ma x Mi n Max Min Ma x
kW353545
AMPs 26.1 43.5 26.1 43.5 34.8 43.5
kW3103104106.016716920
AMPs 14.4 48.1 14.4 48.1 19.2 48.1 28.8 76.9 33.7 76.9 43.3 96.2
kW3113114116.018718922
AMPs 13.0 47.8 13.0 47.8 17.4 47.8 26.1 78.3 30.4 78.3 39.1 95.7
kW3133134136.022722926
AMPs 10.8 46.9 10.8 46.9 14.4 46.9 21.7 79.4 25.3 79.4 32.5 93.9
kW3133204264.026728934124614461646
AMPs 8.3 36.1 8.3 55.5 11.1 72.2 11.1 72.2 19.4 77.7 25.0 94.4 33.3 127.7 38.9 127.7 44.4 127.7
kW3133204264.026732934124914491649
AMPs 7.5 32.6 7.5 50.2 10.0 65.3 10.0 65.3 17.6 80.3 22.6 85.3 30.1 123.0 35.1 123.0 40.2 123.0
kW3133204264.026752964127614881696
AMPs 3.8 16.3 3.8 25.1 5.0 32.6 5.0 32.6 8.8 65.3 11.3 80.3 15.1 95.4 17.6 110.4 20.1 120.5
kW3133204264.026752964127614881696
AMPs 3.0 13.1 3.0 20.1 4.0 26.1 4.0 26.1 7.0 52.2 9.0 64.3 12.0 76.3 14.1 88.4 16.1 96.4
UNIT
VOLTAGE
AND PHA SE
DRAW- T HRU EL ECT RI C HEAT
Unit Size
020304060810121417
Single Phase
115
230
208
277
Three Phase
208
230
460
575
Min Ma x Mi n Max Min Ma x Min Max Min Ma x Mi n Max Min Ma x Mi n Max Min Ma x
kW353545
AMPs 26.1 43.5 26.1 43.5 34.8 43.5
kW3939496979
AMPs 14.4 43.3 14.4 43.3 19.2 43.3 28.8 43.3 33.7 43.3
kW3113114116.011711911
AMPs 13.0 47.8 13.0 47.8 17.4 47.8 26.1 47.8 30.4 47.8 39.1 47.8
kW3133134136.013713913
AMPs 10.8 46.9 10.8 46.9 14.4 46.9 21.7 46.9 25.3 46.9 32.5 46.9
kW3133164164.01671691612161416
AMPs 8.3 36.1 8.3 44.4 11.1 44.4 11.1 44.4 19.4 44.4 25.0 44.4 33.3 44.4 38.9 44.4
kW3133184184.018718918121814181618
AMPs 7.5 32.6 7.5 45.2 10.0 45.2 10.0 45.2 17.6 45.2 22.6 45.2 30.1 45.2 35.1 45.2 40.2 45.2
kW3133204264.026738938123814381638
AMPs 3.8 16.3 3.8 25.1 5.0 32.6 5.0 32.6 8.8 47.7 11.3 47.7 15.1 47.7 17.6 47.7 20.1 47.7
kW3133204264.026746946124614461646
AMPs 3.0 13.1 3.0 20.1 4.0 26.1 4.0 26.1 7.0 46.2 9.0 46.2 12.0 46.2 14.1 46.2 16.1 46.2
06
08
UNIT
VOLTAGE
AND PHA SE
Three Phase
208
230
460
575
BLOW - THRU ELECTRI C HEAT
Unit Size
1417101204
Single Phase
02
03
208
230
277
115
ENVIRO-TEC
COIL AND FILTER DATA • MQL
9
ENVIRO-TEC®offers hot water, chilled water, direct expansion (DX), and standard steam coils for specific application with all Model MQL blower coils. Coils tested in accordance with ARI 410, and strict on-site inspection before, during, and after installation guarantees the highest quality and performance available.
Standard Features
• ENVIRO-TEC® coils are designed, manufactured and tested by Johnson Controls
• 1/2" O.D. seamless copper tubes
• Aluminum fin construction with die-formed spacer collars for uniform spacing
• Mechanically expanded copper tubes leak tested to a minimum 450 PSIG air pressure under water
• Manual air vent plug on all water coils
• Copper ODM sweat connections
• 300 PSIG working pressure at 200°F
• Evaporator coils are factory sealed and charged with a minimum of 5 PSIG nitrogen or refrigerated dry air
• Refrigerant coils are provided with a fixed orifice dis­tributor. Thermal expansion valves are not included.
• Steam coils rated at maximum for 15 PSIG
• 0.016" tube wall thickness (0.025" on steam)
Optional Features
• Stainless steel coil casings
• Automatic air vents on water coils
• Elevated working pressure ratings
• Heat pump compatible cooling coils
• Double circuit DX coils (50-50 split)
• 0.025" tube wall thickness
Coil
Face Area Qty. Dimensions Face Area Qty. Dimensions Face Area
02 2.1 [0.20] 1 16x20x2 [406x508x51] 2.2 [0. 20] 2 16x20x2 [406x508x51] 4.4 [0.41]
03 2.9 [0.27] 1 16x25x2 [406x635x51] 2.8 [0. 26] 2 16x25x2 [406x635x51] 5.6 [0.52]
04 3.8 [0.35] 2 16x20x2 [406x508x51] 4.4 [0. 41] 2 20x25x2 [508x635x51] 6.9 [0.64]
06 5.6 [0.52] 2 20x25x2 [508x635x51] 6.9 [0. 64] 4 20x20x2 [508x508x51] 11.1 [1.03]
08 7.4 [0.69] 2 20x25x2 [508x635x51] 6.9 [0. 64]
2 2
16x20x2 [406x508x51] 20x25x2 [508x635x51]
11.4 [1. 06]
10 9.7 [0.90]
1 2
16x25x2 [406x635x51] 20x25x2 [508x635x51]
9.7 [0. 90]
2 4
16x20x2 [406x508x51] 20x20x2 [508x508x51]
15.6 [1. 45]
12 12.6 [1.17] 4 20x25x2 [508x635x51] 13.9 [1. 29] 6 20x25x2 [508x635x51] 20.8 [1.93]
14 14.3 [1.33] 8 16x20x2 [406x508x51] 17.8 [1. 65]
3 6
20x25x2 [508x635x51] 20x20x2 [508x508x51]
27.1 [2. 52]
17 17.0 [1.58] 6 20x25x2 [508x635x51] 20.8 [1. 93] 12 20x20x2 [508x508x51] 33.3 [3.09]
COIL AND FILTER DATA
Unit Sizes
V-Bank Filters
Flat Filters
NOTES:
1. Standard filters are 2" throwaway; optional filters are 2" pleated.
2. Filter sizes are nominal and standard size, measured in inches [millimeters].
3. Coil and filter face areas are measured in square feet [square meters].
4. Cooling and heating coils have same face area.
5. For coil connection sizes, refer to the ENVIRO-TEC
®
Coil Selection Program.
ENVIRO-TEC
MQL • STATIC PRESSURE DATA
10
Mixing
Box
Econo-
mizer
Filter
Modules
Access
Modules
Plenum Module
Econo-
mizer
Blow
Thru
Draw
Thru
600 0. 01 0.02 0. 01 0.01 0.02 0.02 0.02 0.02 0.02 0.04 0.02 0. 04 0.02 0.01
850 0. 02 0.04 0. 02 0.02 0.03 0.03 0.04 0.03 0.04 0.06 0.04 0. 07 0.04 0.01
975 0. 02 0.04 0. 02 0.02 0.04 0.04 0.04 0.04 0.04 0.07 0.05 0. 09 0.06 0.01
1100 0.03 0. 05 0.03 0.03 0.05 0. 05 0.05 0.05 0.05 0.08 0. 06 0.11 0.08 0.01
900 0. 01 0.02 0. 01 0.01 0.02 0.02 0.02 0.02 0.02 0.06 0.02 0. 06 0.05 0.01
1250 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.09 0. 03 0.10 0.10 0.01
1425 0.03 0. 05 0.02 0.02 0.04 0. 04 0.05 0.04 0.05 0.11 0. 04 0.13 0.13 0.01
1600 0.03 0. 06 0.03 0.03 0.05 0. 05 0.06 0.05 0.06 0.13 0. 05 0.16 0.17 0.01
1200 0.01 0. 02 0.01 0.01 0.02 0. 02 0.02 0.02 0.02 0.04 0. 02 0.07 0.09 0.01
1600 0.02 0. 03 0.02 0.02 0.03 0. 03 0.03 0.03 0.03 0.06 0. 03 0.12 0.17 0.01
1800 0.02 0. 04 0.02 0.02 0.04 0. 04 0.04 0.04 0.04 0.07 0. 04 0.15 0.21 0.01
2000 0.03 0. 05 0.02 0.02 0.04 0. 04 0.05 0.04 0.05 0.09 0. 05 0.19 0.27 0.01
1800 0.01 0. 02 0.01 0.01 0.02 0. 02 0.02 0.02 0.02 0.04 0. 02 0.07 0.04 0.01
2500 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.06 0. 03 0.13 0.09 0.01
2850 0.03 0. 05 0.02 0.02 0.04 0. 04 0.05 0.04 0.05 0.08 0. 04 0.17 0.12 0.01
3200 0.03 0. 06 0.03 0.03 0.05 0. 05 0.06 0.05 0.06 0.09 0. 05 0.21 0.15 0.01
2300 0.01 0. 02 0.01 0.01 0.02 0. 02 0.02 0.02 0.02 0.03 0. 02 0.06 0.07 0.01
3250 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.05 0. 03 0.12 0.15 0.01
3725 0.03 0. 05 0.02 0.02 0.04 0. 04 0.05 0.04 0.05 0.06 0. 04 0.16 0.20 0.01
4200 0.03 0. 06 0.03 0.03 0.05 0. 05 0.06 0.05 0.06 0.07 0. 05 0.20 0.26 0.01
2900 0.01 0. 02 0.01 0.01 0.02 0. 02 0.02 0.02 0.02 0.02 0. 02 0.09 0.12 0.01
4100 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.04 0. 03 0.17 0.25 0.01
4700 0.03 0. 05 0.02 0.02 0.04 0. 04 0.05 0.04 0.05 0.06 0. 04 0.22 0.33 0.01
5300 0.03 0. 06 0.03 0.03 0.05 0. 05 0.06 0.05 0.06 0.07 0. 05 0.27 0.42 0.01
3800 0.01 0. 01 0.01 0.01 0.01 0. 01 0.01 0.01 0.01 0.04 0. 02 0.08 0.07 0.01
5325 0.02 0. 03 0.01 0.01 0.02 0. 02 0.03 0.02 0.03 0.07 0. 04 0.16 0.14 0.01
6090 0.02 0. 03 0.02 0.02 0.03 0. 03 0.03 0.03 0.03 0.09 0. 05 0.21 0.18 0.01
6850 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.11 0. 06 0.26 0.23 0.01
4400 0.01 0. 02 0.01 0.01 0.01 0. 01 0.02 0.01 0.02 0.02 0. 02 0.08 0.09 0.01
6200 0.02 0. 03 0.02 0.02 0.03 0. 03 0.03 0.03 0.03 0.04 0. 03 0.15 0.19 0.01
7100 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.05 0. 04 0.20 0.25 0.01
8000 0.03 0. 05 0.02 0.02 0.04 0. 04 0.05 0.04 0.05 0.07 0. 05 0.25 0.32 0.01
5100 0.01 0. 02 0.01 0.01 0.01 0. 01 0.02 0.01 0.02 0.02 0. 02 0.10 0.13 0.01
7225 0.02 0. 03 0.02 0.02 0.03 0. 03 0.03 0.03 0.03 0.04 0. 04 0.20 0.26 0.01
8290 0.02 0. 04 0.02 0.02 0.03 0. 03 0.04 0.03 0.04 0.05 0. 05 0.26 0.35 0.01
9350 0.02 0. 04 0.02 0.02 0.04 0. 04 0.04 0.04 0.04 0.06 0. 06 0.33 0.45 0.01
17
06
08
10
12
14
02
03
04
MFM
LFM
LPM
SFM
MVM
EHD
SCM
MCM
VCM
HEM
FCM
RFM VFM
SAM
MAM
LAM
EHB
MMM
LMM
HEM
COMPONEN T AIR PRESSUR E DROP (IN. W.G.)
Unit
Size
CFM
Cabinet Losse s
Da m p e r Losse s
Electric Heater
L osse s
Fan Modules
Coil Modules
Mixing Box
MFM LFM
MMM
LMM
Notes:
1. Figures do not include pressure drop of internal filter media. Refer to Air Pressure Drop Through Filter Section table for filter air pressure drop adders.
2. Figures do not include pressure drop of internal heating and/or cooling coils. Refer to Air Pressure Drop Through Dry Coil Section table for coil air pressure drop adders.
3. Mixing box with single damper in fully opened position operating at 100% air volume.
4. Economizer with outside air and exhaust dampers in fully opened position operating at 100% air volume.
Section Pressure Drops
ENVIRO-TEC
STATIC PRESSURE DATA • MQL
11
Filter Size &
Type Efficie ncy 200 250 300 350 400 450 500 550 600 650 700 750 800
2" @ 30% 0.12 0.15 0. 18 0.21 0.24 0.27 0.30 0.33 0.36 0.39 0.42 0. 45 0.48
4" @ 65% 0.18 0.23 0. 27 0.32 0.36 0.41 0.45 0.50 0.54 0.59 0.63 0. 68 0.72
4" @ 85% 0.26 0.33 0. 39 0.46 0.52 0.59 0.65 0.72 0.78 0.85 0.91 0. 98 1.04
4" @ 95% 0.30 0.38 0. 45 0.53 0.60 0.68 0.75 0.83 0.90 0.98 1.05 1. 13 1.20
AIR PRESSURE DR OP THROUGH FILTER SECTION (IN. W.G.)
Air V e locity
(FPM)
High
Efficie ncy
Pleated
Notes:
1. Figures listed represent air pressure drop of clean filters.
2. Usable pressure drop across pleated media not recommended to exceed 1.0 inch w.g.
3. Air velocities associated with pressure drops in the shaded region not recommended.
Note: Dehumidifying cooling coils with face velocities exceeding 525 fpm not recommended.
200 250 300 350 400 450 500 550 600 650 700 750 800
8 0.01 0.02 0.03 0.04 0.05 0.05 0.06 0.08 0.09 0.10 0.11 0.13 0.14
10 0.02 0.03 0. 03 0.04 0.05 0.06 0.07 0.09 0.10 0.11 0.13 0. 15 0.16
12 0.02 0.03 0. 04 0.05 0.06 0.07 0.09 0.10 0.11 0.13 0.15 0. 16 0.18
14 0.02 0.03 0. 04 0.05 0.07 0.08 0.10 0.11 0.13 0.14 0.16 0. 18 0.20
8 0.03 0.04 0.06 0.07 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.25 0.28
10 0.04 0.05 0. 07 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0. 29 0.32
12 0.04 0.06 0. 08 0.10 0.12 0.14 0.17 0.20 0.23 0.26 0.29 0. 33 0.36
14 0.05 0.07 0. 09 0.11 0.13 0.16 0.19 0.22 0.25 0.29 0.33 0. 36 0.40
8 0.04 0.06 0.09 0.11 0.14 0.16 0.19 0.23 0.26 0.30 0.34 0.38 0.42
10 0.05 0.08 0. 10 0.13 0.16 0.19 0.22 0.26 0.30 0.34 0.39 0. 44 0.48
12 0.06 0.09 0. 12 0.15 0.18 0.22 0.26 0.30 0.34 0.39 0.44 0. 49 0.55
14 0.07 0.10 0. 13 0.16 0.20 0.24 0.29 0.33 0.38 0.43 0.49 0. 55 0.61
8 0.06 0.09 0.11 0.15 0.18 0.22 0.26 0.30 0.35 0.40 0.45 0.51 0.57
10 0.07 0.10 0. 13 0.17 0.21 0.25 0.30 0.35 0.40 0.46 0.52 0. 58 0.65
12 0.08 0.12 0. 15 0.19 0.24 0.29 0.34 0.40 0.46 0.52 0.58 0. 65 0.73
14 0.09 0.13 0. 17 0.22 0.27 0.32 0.38 0.44 0.51 0.58 0.65 0. 73 0.81
8 0.09 0.13 0.17 0.22 0.27 0.33 0.39 0.45 0.52 0.60 0.68 0.76 0.85
10 0.11 0.15 0. 20 0.26 0.32 0.38 0.45 0.52 0.60 0.69 0.78 0. 87 0.97
12 0.12 0.17 0. 23 0.29 0.36 0.43 0.51 0.59 0.68 0.78 0.88 0. 98 1.09
14 0.14 0.20 0. 26 0.33 0.40 0.48 0.57 0.66 0.76 0.87 0.98 1. 09 1.21
8 0.12 0.17 0.23 0.29 0.36 0.44 0.52 0.61 0.70 0.80 0.90 1.01 1.13
10 0.14 0.20 0. 27 0.34 0.42 0.51 0.60 0.70 0.80 0.92 1.04 1. 16 1.29
12 0.16 0.23 0. 31 0.39 0.48 0.58 0.68 0.79 0.91 1.04 1.17 1. 31 1.45
14 0.19 0.26 0. 35 0.44 0.54 0.65 0.76 0.89 1.02 1.15 1.30 1. 46 1.62
8
6
AIR PRESSURE DR OP THROUGH DRY COIL SECTION (IN. W.G.)
1
2
3
4
Fins per Inch
Air V e locity (FPM)
Row s
Filter Pressure Drops
Coil Pressure Drops
ENVIRO-TEC
Coil Weight Data
8 FPI 10 FPI 12 FPI 14 FPI 8 FPI 10 FPI 12 FPI 14 FP I 8 FPI 10 FPI 12 FPI 14 FPI 1 10 [5] 11 [5] 11 [5] 11 [5] 12 [5] 12 [5] 13 [6] 13 [6] 12 [5] 12 [5] 13 [6] 13 [6] 2 16 [7] 16 [7] 17 [8] 18 [8] 19 [9] 20 [9] 21 [10] 21 [10] 20 [9] 20 [9] 21 [10] 22 [10] 3 21 [10] 22 [10] 23 [11] 24 [11] 27 [12] 28 [13] 29 [13] 30 [14] 27 [12] 28 [13] 29 [13] 30 [14] 4 28 [13] 29 [13] 30 [14] 32 [14] 35 [16] 36 [16] 37 [17] 39 [18] 35 [16] 36 [16] 38 [17] 39 [18] 6 40 [18] 42 [19] 44 [20] 46 [21] 51 [23] 53 [24] 55 [25] 57 [26] 51 [23] 53 [24] 55 [25] 58 [26] 8 57 [26] 61 [28] 65 [30] 69 [31] 71 [32] 75 [34] 79 [36] 83 [38] 72 [33] 76 [34] 80 [36] 84 [38] 1 13 [6] 13 [6] 13 [6] 14 [6] 15 [7] 16 [7] 16 [7] 17 [8] 15 [7] 16 [7] 16 [7] 17 [8] 2 19 [9] 20 [9] 21 [10] 22 [10] 24 [11] 25 [12] 26 [12] 27 [12] 25 [11] 26 [12] 27 [12] 28 [13] 3 26 [12] 28 [13] 29 [13] 31 [14] 34 [15] 35 [16] 37 [17] 38 [17] 34 [15] 36 [16] 37 [17] 39 [17] 4 34 [15] 36 [16] 38 [17] 40 [18] 44 [20] 46 [21] 48 [22] 50 [23] 44 [20] 46 [21] 48 [22] 50 [23] 6 50 [23] 53 [24] 56 [25] 59 [27] 64 [29] 67 [31] 70 [32] 73 [33] 65 [20] 68 [31] 71 [32] 74 [34] 8 71 [32] 76 [34] 81 [37] 86 [39] 89 [41] 95 [43] 100 [45] 105 [47] 91 [41] 96 [43] 101 [46] 106 [48] 1 15 [7] 15 [7] 16 [7] 17 [8] 18 [8] 18 [8] 19 [9] 20 [9] 18 [8] 19 [9] 19 [9] 20 [9] 2 23 [11] 24 [11] 26 [12] 27 [12] 29 [13] 30 [14] 32 [15] 33 [15] 30 [13] 31 [14] 32 [15] 33 [15] 3 32 [14] 33 [15] 35 [16] 37 [17] 40 [18] 42 [19] 44 [20] 46 [21] 41 [19] 43 [19] 45 [20] 47 [21] 4 41 [19] 44 [20] 46 [21] 49 [22] 53 [24] 55 [25] 58 [26] 60 [27] 54 [24] 56 [25] 59 [27] 61 [28] 6 60 [27] 64 [29] 68 [31] 72 [33] 78 [35] 82 [37] 86 [39] 89 [41] 79 [36] 83 [38] 87 [39] 90 [41] 8 80 [36] 85 [38] 90 [41] 95 [43] 103 [47] 108 [49] 113 [51] 118 [54] 105 [47] 110 [50] 115 [52] 120 [54] 1 19 [9] 20 [9] 21 [10] 22 [10] 24 [11] 25 [11] 26 [12] 27 [12] 24 [11] 25 [11] 26 [12] 27 [12] 2 32 [14] 34 [15] 36 [16] 38 [17] 41 [19] 43 [20] 45 [20] 47 [21] 42 [19] 43 [20] 45 [20] 47 [21] 3 45 [20] 48 [22] 50 [23] 53 [24] 58 [26] 61 [28] 64 [29] 67 [30] 59 [27] 62 [28] 65 [29] 67 [30] 4 59 [27] 62 [28] 66 [30] 70 [32] 76 [35] 80 [36] 84 [38] 88 [40] 77 [35] 81 [37] 85 [39] 89 [40] 6 87 [39] 92 [42] 98 [44] 104 [47] 113 [51] 119 [54] 124 [56] 130 [59] 115 [52] 120 [55] 126 [57] 132 [60] 8 117 [53] 125 [57] 133 [61] 142 [64] 152 [69] 160 [73] 169 [77] 177 [80] 155 [70] 163 [74] 171 [78] 179 [81] 1 23 [11] 25 [11] 26 [12] 27 [12] 30 [14] 31 [14] 32 [15] 33 [15] 30 [14] 31 [14] 32 [15] 34 [15] 2 40 [18] 43 [19] 45 [20] 48 [22] 52 [24] 54 [25] 57 [26] 59 [27] 53 [24] 55 [25] 58 [26] 60 [27] 3 57 [26] 61 [27] 64 [29] 68 [31] 75 [34] 78 [36] 82 [37] 86 [39] 76 [34] 79 [36] 83 [38] 87 [39] 4 75 [34] 80 [36] 85 [38] 90 [41] 98 [45] 103 [47] 108 [49] 113 [51] 100 [45] 105 [47] 110 [50] 115 [52] 6 111 [50] 118 [54] 126 [57] 133 [60] 146 [66] 153 [69] 161 [73] 168 [76] 148 [67] 155 [70] 163 [74] 170 [77] 8 157 [71] 169 [77] 182 [83] 195 [88] 204 [92] 216 [98] 229 [104] 241 [110] 207 [94] 219 [99] 232 [105] 245 [111] 1 28 [13] 30 [13] 31 [14] 33 [15] 36 [16] 37 [17] 39 [18] 40 [18] 36 [16] 38 [17] 39 [18] 41 [18] 2 48 [22] 51 [23] 54 [25] 57 [26] 63 [28] 66 [30] 69 [31] 72 [33] 64 [29] 67 [30] 70 [32] 73 [33] 3 68 [31] 73 [33] 77 [35] 82 [37] 90 [41] 95 [43] 99 [45] 104 [47] 91 [41] 96 [44] 101 [46] 106 [48] 4 89 [41] 96 [43] 102 [46] 108 [49] 119 [54] 125 [57] 131 [60] 138 [62] 120 [55] 127 [58] 133 [60] 139 [63] 6 133 [60] 142 [64] 152 [69] 161 [73] 176 [80] 186 [84] 195 [88] 204 [93] 179 [81] 188 [85] 198 [90] 207 [94] 8 183 [83] 197 [90] 212 [96] 226 [103] 241 [109] 255 [116] 270 [122] 284 [129] 244 [111] 259 [117] 273 [124] 288 [131] 1 35 [16] 37 [17] 39 [18] 42 [19] 45 [21] 48 [22] 50 [23] 52 [24] 46 [21] 48 [22] 50 [23] 52 [24] 2 62 [28] 66 [30] 70 [32] 74 [34] 81 [37] 86 [39] 90 [41] 94 [43] 83 [38] 87 [39] 91 [41] 95 [43] 3 88 [40] 94 [43] 101 [46] 107 [49] 118 [53] 124 [56] 130 [59] 137 [62] 119 [54] 126 [57] 132 [60] 139 [63] 4 116 [53] 125 [57] 133 [60] 142 [64] 155 [70] 164 [74] 172 [78] 181 [82] 158 [72] 166 [75] 175 [79] 184 [83] 6 173 [78] 186 [84] 199 [90] 211 [96] 231 [105] 244 [111] 257 [117] 270 [122] 235 [107] 248 [112] 261 [118] 274 [124] 8 233 [106] 251 [114] 269 [122] 287 [130] 311 [141] 329 [149] 347 [157] 365 [165] 316 [143] 334 [151] 352 [160] 370 [168] 1 39 [18] 41 [19] 44 [20] 46 [21] 50 [23] 53 [24] 55 [25] 58 [26] 51 [23] 54 [24] 56 [25] 58 [26] 2 69 [31] 74 [33] 78 [36] 83 [38] 91 [41] 96 [43] 101 [46] 106 [48] 92 [42] 97 [44] 102 [46] 107 [49] 3 98 [45] 106 [48] 113 [51] 120 [55] 132 [60] 139 [63] 146 [66] 154 [70] 134 [61] 141 [64] 149 [67] 156 [71] 4 130 [59] 140 [63] 149 [68] 159 [72] 174 [79] 184 [83] 194 [88] 203 [92] 177 [80] 187 [85] 197 [89] 206 [94] 6 194 [88] 208 [94] 223 [101] 237 [108] 260 [118] 274 [124] 289 [131] 303 [138] 264 [120] 279 [126] 293 [133] 308 [140] 8 272 [123] 295 [134] 318 [144] 341 [155] 359 [163] 382 [173] 405 [184] 428 [194] 365 [166] 388 [176] 411 [186] 434 [197] 1 45 [20] 48 [22] 51 [23] 53 [24] 58 [26] 61 [28] 64 [29] 67 [30] 59 [27] 62 [28] 65 [29] 68 [31] 2 79 [36] 85 [39] 91 [41] 97 [44] 106 [48] 112 [51] 117 [53] 123 [56] 108 [49] 113 [51] 119 [54] 125 [57] 3 114 [52] 122 [56] 131 [59] 140 [63] 153 [69] 162 [73] 170 [77] 179 [81] 155 [71] 164 [74] 173 [78] 181 [82] 4 150 [68] 162 [73] 173 [79] 185 [84] 203 [92] 214 [97] 226 [102] 237 [108] 206 [93] 217 [99] 229 [104] 240 [109] 6 224 [102] 241 [109] 259 [117] 276 [125] 302 [137] 319 [145] 336 [153] 354 [160] 307 [139] 324 [147] 341 [155] 359 [163] 8 206 [93] 206 [93] 206 [93] 206 [93] 309 [140] 309 [140] 309 [140] 309 [140] 315 [143] 315 [143] 315 [143] 315 [143]
06
COIL WEIGHTS
40% GLYCOL
100% WATER
DRY COIL
17
UNIT
SIZE
COIL
ROWS
08
10
12
14
02
03
04
NOTE: Unit weight data is shipping weight in pounds [kilograms].
MQL • WEIGHT DATA
12
ENVIRO-TEC
WEIGHT AND ELECTRICAL DATA • MQL
13
Motor Electrical Data
NOTES:
1. Actual motor nameplate AMPs may vary, but will not exceed values shown.
2. Consult factory for applications requiring special motors.
115/1 208/1 230/1 277/1 208/3 230/3 460/3 575/3
1/3 6.3 3.5 3.2 2.6 1.7 1.5 0.8 ­1/2 7.8 4.3 3.9 3.6 2.2 2.1 1.1 0.9 3/4 10.6 5.4 5.3 5.0 3.2 3.0 1.5 1.2
1 15.0 8.3 7.5 5.5 4.0 3.6 1.8 1.4
1 1/2 ----5.35.02.51.9
2 ----7.06.43.22.5 3 ----9.19.04.53.2 5 ----14.212.86.45.2
7 1/2 ----22.221.610.88.2
10 ----28.628.414.211.4 15 ----44.940.620.316.2
MAXIMUM MOTOR AMPERAGE
HORSEPOWER
VOLTAGE
Motor/Drive Weight Data
1/3 1/2 3/4 1 1 1/2 2 3 5 7 1/2 10 15
ODP 25 [11] 28 [13] 30 [762]
35 [16] 45 [20] 35 [16] 75 [34] 100 [45] 125 [57] 125 [57] 220 [100]
TEFC 28 [13] 35 [16] 33 [338]
45 [20] 65 [29] 70 [32] 85 [39] 105 [48] 145 [66] 160 [73] 295 [134]
E+ N/A N/A N/A
40 [18] 55 [25] 55 [25] 90 [41] 100 [45] 145 [66] 130 [59] 300 [136]
2 SPEED 45 [20] 35 [16] 33 [338]
45 [20] 40 [18] 70 [32] 75 [34] N/ A N/A N/A N/A
MOTOR WEIGHTS
MOTOR HORSEPOWER
MOTOR TYPE
NOTES:
1. Includes motor, pulleys, belts, and motor base.
2. Motor/drive weight data is shipping weight in pounds [kilograms].
General Fan Notes
Forward Curved Fans (Belt Drive)
1. Consult factory for applications at operating conditions not in the following table and curves.
2. Fan motor voltage, fan rotation, and fan RPM may require field setting/adjustment.
3. Drive losses not included in fan performance table and curves.
4. In direction of airflow, after fan discharge – only LPM (Large Plenum) and EHB (Electric Heat Blow Thru) are available.
5. Section will have internal isolation.
Plug Fans (Direct Drive)
1. Consult factory for applications at operating conditions not in the following table and curves.
2. VFD's are recommended for operation and field balancing of units whether factory supplied and factory mounted, field supplied and factory mounted, or field supplied and field mounted.
3. In direction of airflow, there must be space prior to the plug fan inlet. For sizes 02 through 06, the minimum requirement is either an SAM (Small Access) or an MCM (Medium Coil). For sizes 08 through 17, the minimum requirement is an MAM (Medium Access).
4. Section will have internal isolation.
ENVIRO-TEC
MQL • FAN PERFORMANCE DATA
14
Forward Curved Fan Performance Data
TSP UNIT SIZE
(in-wg) Actual CFM 650 750 850 950 1050 950 1100 1250 1400 1550 1200 1400 1600 1800 2000
RPM ––––––––––––––1793
BHP ––––––––––––––1.99
RPM –––––––––1913 ––––1663
BHP –––––––––1.41––––1.75
RPM ––––1782 1747 1753 1517 1526
BHP ––––0.76–––1.061.21–––1.301.51
RPM 1594 1605 1562 1567 1580 1357 1366 1383
BHP 0.55 0.63 0. 75 0.87 1. 01 0.92 1.09 1.29
RPM 1382 1395 1415 1353 1360 1375 1395 1175 1186 1204 1231
BHP 0.37 0.43 0.50 0.50 0.59 0.70 0.82 0.61 0.74 0.89 1.08
RPM 1126 1136 1154 1181 1215 1107 1117 1136 1161 1195 962 976 1000 1035 *
BHP 0.18 0.22 0.27 0. 32 0.39 0. 29 0.36 0. 43 0.52 0. 63 0.35 0. 44 0.56 0. 71 *
RPM 829863904**814846***718****
BHP 0.100.140.18**0.170.22***0.22****
TSP UNIT SIZE
(in-wg) Actual CFM 1900 2200 2500 2800 3100 2400 2800 3200 3600 4000 3100 3600 4100 4600 5100
RPM ––––1482 ––––1490 1234 1239 1245
BHP ––––2.80––––3.70––3.504.074.70
RPM 1371 1376 1379 1384 1141 1145 1151 1160
BHP 2.14 2.48 2.83 3.27 2.60 3.07 3.59 4.18
RPM 1251 1256 1264 1263 1273 1044 1049 1057 1070
BHP 1.58 1.85 2.16 2.44 2. 85 2. 22 2.64 3.12 3.68
RPM 1123 1132 1143 1129 1139 1155 933 938 945 958 975
BHP 1.32 1.57 1.85 1.73 2.06 2.44 1.51 1.84 2.22 2.67 3.19
RPM 973 983 995 1010 978 990 1007 1028 812 820 833 852 875
BHP 0. 88 1.07 1.29 1.53 1.14 1.39 1.69 2.04 1.18 1.47 1.82 2.23 2.71
RPM 798 809 823 842 * 801 816 835 858 * 673 689 711 * *
BHP 0.52 0.65 0.81 1. 00 * 0. 66 0.85 1.07 1.33 * 0.87 1.12 1.43 * *
RPM 590****598*********
BHP 0.32****0.42*********
TSP UNIT SIZE
(in-wg) Actual CFM 3900 4600 5300 6000 6700 4600 5400 6200 7000 7800 5200 6200 7200 8200 9200
RPM 1065 1068 1077 1081 1078 1084 1094
BHP 5.13 5.94 6.59 7.55 6. 82 8.06 9.49
RPM 987 994 1000 1005 1001 1009 1021
BHP 4.50 5.28 5.75 6.64 5. 96 7.12 8.46
RPM 901 906 915 911 917 925 911 919 930 944
BHP 3.28 3.90 4.63 4.21 4.93 5.75 4.21 5.13 6.20 7.44
RPM 805 809 819 832 814 819 827 838 814 819 830 844 862
BHP 2. 25 2.74 3.32 3.99 2.92 3.48 4.13 4.88 2.79 3.48 4.31 5.29 6.44
RPM 697 701 711 724 741 705 710 718 729 743 708 718 733 751 773
BHP 1.42 1.78 2.22 2. 7500 3.35 1.86 2.28 2.78 3.36 4.03 2.17 2.78 3.52 4.40 5.45
RPM 574 585 600 619 * 581 591 604 620 638 588 604 624 * *
BHP 1.02 1.34 1.72 2. 18 * 1. 31 1.67 2.09 2.60 3.19 1.57 2.09 2.74 * *
RPM 428****431448***444****
BHP 0.65****0.801.08***1.00****
17
3.5
1.0
0.5
3.0
2.5
2.0
1.5
1.0
0.5 12
14
2.5 06
2.0
1.5 03
04
3.5
3.0 08
10
2.0
1.5
1.0
0.5
3.5
3.0
2.5 02
* Contact factory.
ENVIRO-TEC
FAN PERFORMANCE DATA • MQL
15
Plug Fan Performance Data
TSP UNIT SIZE
(in-wg) Actual CFM
450 650 850 1050 1250 650 900 1150 1400 1650 800 1150 1500 1850 2200
RPM 2870 2881 2950 3068 3246 2869 2877 2931 3017 3170 2868 2890 2974 3122 3318
BHP
0.92 1.08 1.24 1.42 1.65 1.32 1.52 1.71 1.92 2.20 1.58 1.85 2.13 2.48 2.91
RPM 2704 2725 2805 2946 3135 2703 2721 2786 2891 3048 2701 2734 2829 3000 3218
BHP
0.79 0.93 1.07 1.25 1.47 1.13 1.31 1.48 1.68 1.94 1.36 1.59 1.85 2.19 2.63
RPM 2527 2559 2651 2816 3028 2526 2555 2632 2761 2927 2524 2572 2683 2870 3111
BHP
0.67 0.79 0.91 1.08 1.31 0.96 1.10 1.26 1.46 1.70 1.15 1.35 1.59 1.89 2.34
RPM 2336 2387 2499 2677 2913 2336 2380 2466 2622 2812 2340 2406 2543 2748 2996
BHP
0.55 0.65 0.77 0.92 1.15 0.79 0.91 1.05 1.24 1.49 0.94 1.12 1.34 1.65 2.04
RPM 2139 2207 2347 2552 2788 2141 2199 2313 2479 2687 2146 2226 2391 2622 2871
BHP
0.44 0.52 0.63 0.79 0.98 0.62 0.73 0.86 1.03 1.27 0.75 0.90 1.10 1.40 1.74
RPM 1924 2007 2179 2413 2660 1926 2000 2145 2340 2549 1931 2037 2236 2484 2759
BHP
0.33 0.40 0.50 0.65 0.83 0.47 0.56 0.68 0.85 1.04 0.56 0.69 0.89 1.15 1.54
RPM 1683 1810 2020 2257 2542 1687 1797 1975 2183 2420 1698 1846 2079 2343 2641
BHP
0.23 0.29 0.39 0.50 0.71 0.32 0.40 0.52 0.66 0.88 0.39 0.51 0.69 0.94 1.31
RPM 1415 1597 1833 2117 2401 1419 1580 1788 2029 2280 1433 1644 1904 2202 2500
BHP
0.14 0.19 0.27 0.41 0.55 0.20 0.27 0.36 0.52 0.69 0.24 0.35 0.51 0.75 0.99
RPM 1118 1366 1650 1940 2239 1128 1345 1595 1848 2112 1153 1422 1721 2030 2344
BHP 0.07 0.11 0.18 0.28 0.40 0.10 0.15 0.24 0.34 0.50 0.12 0.21 0.33 0.52 0.75
TSP UNIT SIZE
(in-wg) Actual CFM 1200 1700 2200 2700 3200 1600 2300 3000 3700 4400 1900 2800 3700 4600 5500
RPM 2074 2056 2081 1605 1728 1755 1812 1727 1754 1812
BHP 3.25 3.55 3.89 2.65 3.99 4.47 5.10 4.95 5.57 6.38
RPM 1946 1944 1979 1520 1646 1633 1670 1733 1650 1632 1669 1733
BHP 2.79 3.06 3.40 2.29 3.06 3.44 3.91 4.49 3.79 4.27 4.87 5.61
RPM 1810 1823 1871 1429 1532 1532 1581 1649 1535 1531 1579 1649
BHP 2.35 2.59 2.93 1.95 2.57 2.90 3.37 3.89 3.18 3.61 4.19 4.86
RPM 1700 1679 1707 1763 1332 1410 1432 1490 1572 1413 1429 1488 1572
BHP 1.73 1.93 2.17 2.47 1.61 2.11 2.42 2.85 3.37 2.61 3.00 3.54 4.21
RPM 1541 1539 1581 1645 1226 1289 1326 1391 1488 1288 1323 1389 1488
BHP 1.37 1.54 1.76 2.03 1.29 1.67 1.97 2.34 2.83 2.07 2.44 2.91 3.54
RPM 1368 1394 1451 1531 1166 1159 1214 1299 1407 1158 1211 1296 1407
BHP 1.03 1.18 1.38 1.63 1.07 1.26 1.54 1.89 2.39 1.56 1.90 2.35 2.99
RPM 1202 1192 1238 1313 1411 998 1025 1096 1200 1320 1002 1021 1091 1197 1320
BHP 0.61 0.71 0.85 1.03 1.27 0.74 0.91 1.14 1.48 1.93 0.91 1.11 1.41 1.84 2.42
RPM 967 999 1071 1172 1288 817 876 976 1098 1229 817 870 970 1094 1229
BHP 0.36 0.44 0.56 0.73 0.94 0.44 0.58 0.80 1.11 1.49 0.54 0.71 0.98 1.37 1.87
RPM 706 784 895 1021 1159 617 720 848 992 1140 609 710 841 987 1140
BHP 0.16 0.22 0.32 0.45 0.67 0.20 0.32 0.50 0.80 1.14 0.24 0.38 0.61 0.98 1.43
TSP UNIT SIZE
(in-wg) Actual CFM 2600 3800 5000 6200 7400 2900 4300 5700 7100 8500 3400 4800 6200 7600 9000
RPM 1576 1604 1592 1584 1645 1584 1613 1563 1625 1722 1413 1436 1426 1413 1460
BHP 3.98 5.04 5.93 6.72 7.79 4.25 5.47 6.32 7.47 8.95 5.11 6.34 7.38 8.28 9.47
RPM 1490 1516 1484 1508 1581 1498 1524 1488 1560 1661 1336 1357 1330 1345 1402
BHP 3.46 4.39 5.09 5.88 6.92 3.69 4.77 5.53 6.64 8.02 4.44 5.53 6.34 7.25 8.42
RPM 1398 1422 1378 1429 1512 1406 1411 1407 1491 1604 1254 1273 1231 1273 1341
BHP 2.94 3.76 4.32 5.07 6.06 3.15 4.02 4.75 5.81 7.16 3.78 4.73 5.36 6.24 7.37
RPM 1300 1316 1291 1355 1442 1307 1287 1320 1417 1541 1166 1176 1154 1205 1275
BHP 2.45 3.13 3.62 4.35 5.24 2.63 3.30 4.00 4.98 6.26 3.15 3.93 4.50 5.33 6.32
RPM 1192 1182 1197 1274 1375 1197 1167 1239 1348 1477 1068 1056 1069 1133 1215
BHP 1.98 2.47 2.95 3.63 4.49 2.12 2.64 3.33 4.26 5.42 2.54 3.11 3.67 4.44 5.42
RPM 1071 1042 1102 1192 1300 1076 1063 1150 1273 1424 960 934 984 1057 1148
BHP 1.52 1.87 2.34 2.95 3.70 1.63 2.05 2.67 3.51 4.88 1.96 2.36 2.90 3.60 4.46
RPM 933 924 1001 1107 1238 918 952 1062 1203 1364 831 828 893 981 1088
BHP 1.09 1.35 1.75 2.3000 3.20 1.14 1.51 2.07 2.95 4.12 1.39 1.70 2.18 2.81 3.79
RPM 736 797 898 1029 1167 746 835 971 1132 1175 661 716 801 909 1024
BHP 0.65 0.89 1.23 1.83 2.50 0.70 1.02 1.55 2.33 2.82 0.83 1.12 1.53 2.21 2.99
RPM 558 660 798 857 1023 579 718 788 982 1175 507 595 711 753 891
BHP 0.30 0.48 0.82 1.00 1.00 0.34 0.62 1.00 1.00 1.00 0.40 0.62 1.01 1.25 1.25
2.0
1.5
1.0
0.5
4.0
3.5
3.0
2.5 17
2.0
1.5
1.0
0.5
3.0
2.5 12
14
10
2.0
1.5
1.0
0.5 04
4.5
4.0
3.5
4.5
4.5 02
03
3.0
2.5 06
08
4.0
3.5
ENVIRO-TEC
MQL • FAN PERFORMANCE CURVES
16
MQL02 (Fan 09-04 Class I)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
1/3 HP
1/2 HP
1 HP
600
800
1000
1200
1400
1600
1800
2000
2200 RPM
3/4 HP
1.5 HP
2 HP
MQL03 (Fan 09-06 Class I)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800
2000 RPM
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
2 HP
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
FAN PERFORMANCE CURVES • MQL
17
MQL06 (Fan 12-09 Class I)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400 RPM
1/2 HP 3/4 HP
1 HP
1.5 HP
3 HP 400
2 HP
MQL04 (Fan 10-07 Class I)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800 RPM
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
2 HP
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
MQL • FAN PERFORMANCE CURVES
18
MQL08 (Fan 12-12 Class I)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 5200
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400 RPM
3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
5 HP
2 HP
MQL10 (Fan 15-11 Class I and II)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
2400 2600 2800 3000 3200 3400 3600 3800 4000 4200 4400 4600 4800 5000 5200 5400 5600 5800
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200 RPM
1.5 HP
1 HP
3/4 HP
5 HP
3 HP
2 HP
400
CLASS I
CLASS II
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
FAN PERFORMANCE CURVES • MQL
19
MQL12 (Fan 18-13 Class I and II)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
1000 RPM
1 HP
1.5 HP
2 HP
3 HP
5 HP
7.5 HP
400
800
CLASS I
CLASS II
SE = CFM x SP
6362 x BHP
MQL14 (Fan 18-18 Class I and II)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
800
7.5 HP
1 HP
1.5 HP
2 HP
1000 RPM
5 HP
3 HP
600
400
CLASS I
CLASS II
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
MQL • FAN PERFORMANCE CURVES
20
MQL17 (Fan 18-18 Class I and II)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 10000 10500 11000 11500 12000 12500 13000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000 RPM
10 HP
1.5 HP
15 HP
7.5 HP
5 HP
3 HP
2 HP
400
CLASS I
CLASS II
SE = CFM x SP
6362 x BHP
MQL02 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 200 400 600 800 1000 1200 1400
CFM
STATIC PRESSURE - INCHES WATER GAUGE
1/3 HP
1/2 HP
1 HP
600
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3/4 HP
3000 RPM
1.5 HP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
FAN PERFORMANCE CURVES • MQL
21
MQL03 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 200 400 600 800 1000 1200 1400 1600 1800
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
1/3 HP
1/2 HP
3/4 HP
1 HP
3000 RPM
1.5 HP
2 HP
MQL04 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800
2000
2200
2400 2600
2800
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
2 HP
3000 RPM
3 HP
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
MQL • FAN PERFORMANCE CURVES
22
MQL06 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800
2000
2200 RPM
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
3 HP
400 2 HP
MQL08 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 500 1000 1500 2000 2500 3000 3500 4000 4500
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800 RPM
3 HP
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
5 HP
2 HP
400
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
FAN PERFORMANCE CURVES • MQL
23
MQL10 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600
1800 RPM
1.5 HP
1 HP
3/4 HP
1/2 HP
1/3 HP
7.5 HP
5 HP
3 HP
2 HP
400
MQL12 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600 RPM
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
2 HP
3 HP
5 HP
7.5 HP
400
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
MQL • FAN PERFORMANCE CURVES
24
MQL14 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400
1600 RPM
7.5 HP
1/3 HP
1/2 HP
3/4 HP
1 HP
1.5 HP
2 HP
400
10 HP
1800 RPM
5 HP
3 HP
MQL17 Plug Fan
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500
CFM
STATIC PRESSURE - INCHES WATER GAUGE
600
800
1000
1200
1400 RPM
10 HP
1.5 HP
1 HP
3/4 HP
1/2 HP
1/3 HP
400
7.5 HP
5 HP
3 HP
2 HP
SE = CFM x SP
6362 x BHP
SE = CFM x SP
6362 x BHP
ENVIRO-TEC
GUIDE SPECIFICATIONS • MQL
25
Guide Specifications Blower Coil Unit
HVAC Guide Specifications - Section 15XXX Size Range: 600 – 10,000 CFM
ENVIRO-TEC®Model Number: MQL
Part 1 — General
1.01 SYSTEM DESCRIPTION A. Indoor mounted blower coil unit designed to provide air to a conditioned space as required to meet specified
performance requirements for ventilation, heating, cooling, filtration and air distribution. Unit shall be assem­bled for draw thru application and shall be arranged to discharge conditioned air horizontally or vertically as shown on the contract drawings.
B. Unit with a direct-expansion cooling coil shall have the capability to be used in a refrigerant circuit in conjunc-
tion with a field supplied and matched air-cooled condensing unit.
1.02 QUALITY ASSURANCE A. Coils shall be tested in accordance with ARI 410 “Standard for Forced-Circulation Air-Cooling and Air-Heating
Coils”.
B. Direct expansion coils shall be designed and tested in accordance with ANSI/ASHRAE 15 “Safety Code for
Refrigeration Systems”.
C. Insulation and insulation adhesive shall comply with NFPA 90A and 90B requirements for flame spread and
smoke generation.
D. Unit shall be constructed in accordance with UL 1995 standards, comply with NEMA standards and shall
carry the cETL label, display certification symbol on units of certified models. Installation of ancillary electrical components shall comply with NEC.
1.03 DELIVERY, STORAGE AND HANDLING
Unit shall be stored and handled in accordance with the unit manufacturer’s instructions.
Part 2 — Products
2.01 EQUIPMENT A. General:
Factory assembled blower coil that is modular in design and construction. Unit may consist of a fan and coil section with factory-installed chilled water or direct expansion coil, preheat or reheat coil, heating coil section, filter section, combination filter/mixing box (flat or V-bank arrangement), economizer, or access section(s) as indicated on the equipment schedules.
B. Unit Cabinet:
1.0 Unit panels shall be constructed of G60 galvanized steel and shall be capable of withstanding 125-hour salt spray test per ASTM Standard 117. All casing panels shall be removable for easy access to the unit. All panels shall be gasketed to ensure a tight seal.
2.0 Double wall unit panels (includes corner posts, mullions and access doors) shall be 1-in. nominal thickness using 1.5-lbs/ft3fiberglass insulation between galvanized steel panels.
3.0 Single wall unit panels shall be 1-in. nominal thickness using matt-faced fiberglass insulation with a nom­inal density of not less than 1.5-lbs/ft3.
4.0 Insulation shall be secured to casing with water based adhesive corresponding to 25/50-flame spread/smoke developed. Testing criteria and weld pins where necessary.
5.0 Condensate drain pans shall be sloped to prevent standing water and shall be constructed of 18 gauge G90 galvanized steel or stainless steel; they shall have a galvanized steel or stainless steel male pipe threaded drain connection.
C. Fan Section:
1.0 Fan sections shall be constructed of G60 steel and shall have a formed channel base for integral mount­ing of fan, motor, and casing panels. Fan housing, wheel, shaft, and bearings shall be rigidly secured to the base unit.
ENVIRO-TEC
MQL • GUIDE SPECIFICATIONS
26
2.0 Fan decks shall be internally spring isolated (one-inch deflection) with the fan outlet connection to be made using canvas duct.
3.0 Each unit shall have one fan wheel and housing only.
4.0 Fan wheels shall be designed for continuous operation at the maximum rated fan speed and motor horsepower. Fan wheels and shafts shall be selected to operate at least 25% below the first critical speed, and shall be statically and dynamically balanced as an assembly.
5.0 Fan shafts shall be solid steel, turned, ground and polished.
6.0 Fan bearings shall be self-aligning, non-regreasable (permanent) ball bearing type selected for an aver­age life (L50) of 100,000 hours at design operation conditions, per ANSI Code B3.15.
7.0 Fan motor shall be mounted within the fan section casing. Motor shall be NEMA Design B with sizes and electrical characteristics as shown on the equipment schedule.
8.0 Fan drive shall be designed for a minimum of 1.15 service factor and shall be factory mounted and aligned. Belt drive package shall be variable-pitch type (constant volume) or fixed-pitch type (variable volume).
D. Coil Sections:
1.0 All coils shall have aluminum plate fins mechanically bonded to 1/2-in. OD seamless copper tubes by mechanical expansion. Coils shall be factory leak tested at 450-psig air pressure under water in an illu­minated test tank. Copper tubes shall be either 0.016” or 0.025” copper tube wall thickness. Coils shall have G90 galvanized steel or stainless steel casings with copper headers and sweat connections.
2.0 Chilled water coils shall have a working pressure of 300-psig at 200° F. No turbulence-promoting devices will be permitted inside the tubes. Headers shall have vent connections.
3.0 Direct-expansion coils shall be provided with pressure-type brass distributors with solder-type connec­tions. Coils shall be designed and tested in accordance with ANSI/ASHRAE 15.
4.0 Hot water coils shall have a working pressure of 300-psig at 200° F. No turbulence-promoting devices will be permitted inside the tubes. Headers shall have vent connections.
5.0 Steam distributing coils (standard single tube type) shall have a maximum working pressure of 15-psig at ambient temperatures above 35° F. Tube wall thickness shall be 0.025” as standard.
6.0 Electric heat coils for use in blower coil units shall be open coil type, nichrome wire resistance elements, insulated by floating ceramic bushings. Thermal cutouts for primary and secondary over-temperature protection shall be provided to meet UL and NEC requirements. Maximum element watt density shall be 55-watts/sq inch. The manufacturer shall furnish an integral control box. It shall contain primary and sec­ondary control thermal cutouts, relays, airflow switch, and fused control transformer.
E. Filter Sections:
1.0 Each filter section shall be designed and constructed to house the specific type of filter specified on the equipment schedule.
2.0 Flat filter sections shall accept 2-in. 30% (MERV-6) pleated filters of standard sizes. Sections shall include side access slide rails. Flat filter section shall be arranged with minimum depth in direction of airflow.
3.0 Angle filter section shall accept 2-in. 30% (MERV-6) pleated filters of standard sizes arranged in horizon­tal V formation. Sections shall include side access slide rails. Angle filter section shall be arranged with minimum depth in direction of airflow.
F. Damper Sections:
1.0 Mixing boxes, filter mixing boxes and economizers shall have parallel blade, interconnecting dampers. Damper blades shall have parallel bends for stiffness and shall be mechanically fastened to steel rods rotating in brass bushings and mounted in rigid galvanized steel frames. Dampers shall be sectionalized to limit blade width, minimize blade warpage, and ensure tight closure.
2.0 All dampers for mixing boxes and filter mixing boxes shall be rated with a leakage rate not to exceed 5% of air quantity calculated at 2000 fpm velocity though damper and 4.0-in.wg. pressure difference. Damper blades shall be gasketed and stainless steel perimeter-sealing strips shall be provided. Damper linkage shall be provided and installed with all mixing boxes.
G. Access Sections:
1.0 Access sections shall be installed where indicated on the drawings and shall be as specified on the equipment schedule.
2.0 Access sections shall have removable access panels.
ENVIRO-TEC
GUIDE SPECIFICATIONS • MQL
27
H. Special Features:
The following unit options shall be available.
1.0 Fan Section:
a. Variable frequency drives. b. Motor starters – contactor with overload for three phase and contactor for single phase. c. High-efficiency motors (inverter-duty). d. Totally enclosed fan cooled (TEFC) motors (inverter-duty). e. Two-speed motors. f. Direct drive plug fans with internal isolation. g. Class II forward curved fans with regreasable pillow block bearings. h. Exhaust or return fans for use with economizer sections.
2.0 Coil Section:
a. Chilled water coil with copper plate fins and/or stainless steel casing. b. Direct-expansion coil with copper plate fins and/or stainless steel casing. c. Hot water coil with copper plate fins and/or stainless steel casing. d. Steam distributing coil with copper plate fins and/or stainless steel casing.
3.0 Filtration:
a. 4” pleated filter type (standard size), 60-65% efficiency (MERV-11) b. 4” pleated filter type (standard size), 80-85% efficiency (MERV-13) c. 4” pleated filter type (standard size), 90-95% efficiency (MERV-14)
4.0 Access Doors: Hinged (lift-off type) doors with quick-action latches (handles) on both sides of the section
for access to both the fan and filter from either side of the unit.
5.0 Base Rail: Unit mounted base rail shall be a minimum of 4” in height and constructed of galvanized
steel, structurally capable of supporting unit on floor or by ceiling suspension.
I. End Devices:
The following guide specifications should be used as a basis for design when using optional factory/field­mounted direct digital controls. These specifications should be reviewed to match the specific system control requirements and available control packages.
1.0 The electrical components shall be recognized by UL. The unit shall be in compliance with the UL 1995
standards. Fan motors are wired and terminated in the control enclosure.
2.0 All application software performing the required control functions shall be field-supplied with the DDC
controller factory or field mounted and wired (tested and configured).
3.0 Available End Devices and Controls:
a. Variable Frequency Drives
• Factory supplied and mounted
• Field supplied and factory mounted
b. Motor Starters
• Factory supplied and mounted
• Field supplied and factory mounted
c. End Devices (factory supplied and mounted)
• Disconnect switch (fused or non-fused)
• Damper actuator (modulating from 100% OA to 100% RA)
• Fuses, relays, transformers, etc.
• Electric heat interlock relay
• Hand off auto switch
ENVIRO-TEC
MQL • METRIC CONVERSION
28
SI UNIT
CONVERSION
FACTOR
= ENGLISH UNIT
CONVERSION
FACTOR
= SI
UNIT
SI UNIT
CONVERSION
FACTOR
= ENGLISH
UNIT
CONVERSION
FACTOR
= SI
UNIT
cm
2
100
mm
2
°C 1.8 °F 0.5556 °C
cm
2
0.1550
in
2
645.2
mm
2
m
2
10.76
ft
2
0.09290
m
2
m/s 3.281 ft/s 0.3048 m/s
m/s 196.9 ft/min 0.00508 m/s mm 0.03937 in. 25. 4 mm mm 0.003281 ft. 304.8 mm
mm
3
1.0x10
-6
L
m 3.281 ft. 0.3048 m
mm
3
6.102x10
-5
in.
3
0.01639 L
m 1.094 yd. 0.9144 m L 0.03531
ft
3
28.32 L
m
3
1.308
yd
3
0.7646
m
3
g 0.03527 oz. 28.35 g L 0.2642 U.S . gal 3.785 L
kg 2.205 lb. 0.4536 kg L 2.113 U.S . pint 0.4732 L
tonne, Mg 1.102 U.S. ton (2000 lb.) 0.9072 tonne, Mg
mL, cm
3
0.03381 U.S. oz 29. 57 mL
kcal/h 1.163 W
m3/h
0.2778 L/s
kcal/h 3.968 Btu/h 0.2931 W
m3/h
0.5886
ft3/min
0.4719 L/s
HP metric 0.7355 kW
m3/h
4.403 U.S . gal/min 0. 06309 L/s
HP metric 0.9863 HP (550 ) 0.7457 kW L/h
2.778x10
-4
L/s
Mcal/h 1.163 kW L/h
4.403x10
-3
U.S. gal/min 0.06309 L/s
Mcal/h 0.3307 Ton refr. 3.517 kW
(m3/h)/
(1000 kcal/h)
mm w.g. 4°C 9.806 Pa
mm w.g. 4°C 0.03937
in H2O 39.2°F 249.1 Pa
mm Hg 0°C 0.1333 kPa mm Hg 0°C 0.03937 in Hg 32°F 3.386 kPa
kgf/cm
2
98.07 k Pa
kgf/cm
2
14.22 ps i 6.895 kPa °C °C + 273.15 °K
mH2O 3.281 ft H2O 2.989 kPa °C (°C x 1.8) + 32 °F (°F - 32) ÷ 1. 8 °C
CONVERSION
FACTOR
= SI
UNIT
Area
Length
Mass
P re ssu re
Power
Temperature Interval
Volume
Temperature
Volume / Time
Velocity
SI UNIT
CONVERSION
FACTOR
1.780
cfm/ton
0.1342
L/s - kW
= ENGLISH
UNIT
ft. lb.
S
Metric Conversion Chart
PREFIXES
M MEGA- 10
6
k KILO- 10
3
d DECI 10
-1
c CENTI 10
-2
m MILLI 10
-3
LEGEND
m METER cal CALORIE kg KILOGRAM (mass) kgf KILOGRAM — FORCE kp KILOGRAM — FORCE L LITER °C DEGREES CELSIUS K KELVIN WWATT Pa PASCAL J JOULE N NEWTON h HOUR m MINUTE s SECOND g GRAM
UNITS
HP metric = METRIC
HORSEPOWER
mm w.g. MILLIMETERS
WATER GAUGE
mmCE MILLIMETERS
WATER GAUGE
mmHg MILLIMETERS
MERCURY tonne = 1000 kg kcal = KILOCALORIES bar = 100 kPa
ENVIRO-TEC
NOTES
29
ENVIRO-TEC
STANDARD FEATURES
Construction
• Modular design facilitates retrofit
• Galvanized steel cabinet construction
• 1" thick fiberglass insulation, glued and pinned in place
• Gasketed, removable access panels sized for easy handling
• Left and right hand arrangement
• Access panels on all sections
Fan Assembly
• Single forward-curved fan sec­tions
• Statically and dynamically balanced
• Solid steel shafting
• Ball bearings with a minimum design average life (L50) of 100,000 hours
• Fan decks with internal vibration isolation
Fan Motor and Drive
• Single speed ODP motors
• 1750 RPM single speed, 60 Hertz
• Single phase motors with inherent thermal protection
• Three phase motors
• Standard cross section "V-belt" drive with 1.2 service factor
• Adjustable pitch motor pulley and fixed pitch blower pulley
Coils
• 1/2" O.D. seamless copper tubes
• G90 steel coil casings
• Collared aluminum fins
• Manual air vent plug on all water coils
• 300 PSIG Working Pressure at 200°F
• Copper ODM sweat connections
• 0.016" tube wall on water and evaporator coils
• 0.025" tube wall on steam coils
Filters and Filter Rack
• Hinged side access flat filter rack
• 2" pleated filters (30%)
Electrical
• Fan motor wired and terminated to junction box
• All units cETL listed in compliance with UL/ANSI 1995
Electric Heat Section
• Draw Thru or Blow Thru configurations
• Factory mounted electric heater with single point power connec­tion, ETL listed as an assembly
OPTIONAL FEATURES
Construction
• Double wall (solid or perforated) cabinets
• Stainless steel IAQ drain pan with stainless steel male pipe threaded connection
• Fan discharge arrangements
• Scrim reinforced foil faced insulation
• Hinged access panels with lift and turn fasteners
• 4" Base rails with rigging slots factory assembled and installed
Fan Motor and Drive
• Direct drive plug fans with inter­nal rubber-in-shear (RIS) isolation
• TEFC motors
• High efficiency motors
• Two-speed motors with contactors
• Variable frequency drives, factory installed (mounted and wired)
• Motor starter (contactor with overload for three phase; contac­tor for single phase), factory installed (mounted and wired)
• Return FC and plug fan sections
Coils
• 3, 4, 6 and 8 row chilled water or R22 DX coils
• Up to 4 rows hot water or up to 2 rows standard steam
• Heating coil in preheat or reheat position
• Coil connections opposite handing
• Stainless steel coil casings
• 0.025" tube wall thickness
• Auto air vents
Filters and Filter Rack
• 4" high efficiency pleated filters (65, 85, and 95%)
• Mixing box with filter sections (flat or v-bank filter arrangements)
Inlet Damper Section
• Factory assembled and installed
• Heavy gauge galvanized steel formed blade dampers
• Low leak dampers with extruded vinyl blade seals and flexible metal jamb seals
• Medium and large inlet plenums with v-bank or flat filters
• Parallel blade operation
• Interconnecting damper linkage
• Damper actuator (modulating from 100% OA to 100% RA)
Additional Modules
• Face and bypass with medium and small coils
• Economizer sections
• Discharge plenums
• Access sections
• High efficiency filter sections
Electrical
• Motor wiring in conduit
• Single phase fan control package
• Three phase fan control package
• Door interlocking disconnect switch (non-fused or fused)
• Fusing (main or per stage)
• Hand off auto switch (HOA)
• Frequency inverters
• Electric heat interlock relay
• Relays, transformers, etc.
MQL • STANDARD & OPTIONAL FEATURES
Printed on recycled paper
Catalog: ET102.19-EG1 (810) Supersedes Catalog: ET102.19-EG1 (410) © 2010 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA www.johnsoncontrols.com