Entron iPAK2 Technical Manual

iPAK2 Technical Manual
Welding control for MFDC spot, projection, roll-spot, seam and multi-welding applications
For firmware version 2.01
iPAK2 Technical Manual 2
Copyright © 2019 BF ENTRON Ltd. and/or its affiliates. All rights reserved.
The information in this manual is subject to change.  BF ENTRON assumes no responsibility for any errors that may appear in this manual.  BF ENTRON assumes no responsibility for any injury, loss or damage caused by improper installation,
use or application of the iPAK2 welding control
The reproduction, transmission or use of this document or contents is not permitted without express
authority from BF ENTRON
BF ENTRON's trademarks and trade dress may not be used in connection with any product or service
that is not BF ENTRON's, in any manner that is likely to cause confusion among customers or in any manner that disparages or discredits BF ENTRON. All other trademarks not owned by BF ENTRON are the property of their respective owners, who may or may not be affiliated with, connected to, or sponsored by BF ENTRON.
BF ENTRON Ltd. Building 80 Bay 1
First Avenue
The Pensnett Estate
Kingswinford
West Midlands DY6 7FQ
Phone +44 (0)1384 455401 • Fax +44 (0)1384 455551
www.entroncontrols.com
Issue Date Comment
2.00 27-02-19 Initial release
2.00.01 13-06-19 Minor errata corrected
2.00.02 19-06-19 Corrected weld program time range.
2.01 8-08-19 Added Presqueeze to all modes
England
iPAK2 Technical Manual 3
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE iPAK2
WARNING
DO NOT DISASSEMBLE, REPAIR, OR MODIFY THE iPAK2. These actions can cause electric shock and fire.
Use only as described in this manual. Use only BF ENTRON recommended accessories and
replacement parts.
Stop operation if any problems occur. If the equipment is not working as it should, has been dropped,
damaged, left outdoors, or been in contact with water, contact BF ENTRON.
Only apply the specified power. Application of a voltage or current beyond the specified range can
cause electric shock or fire.
Do not use damaged plugs or connecting cables.  Keep water and water containers away from the iPAK2. Water ingress can cause a short circuit, electric
shock, or fire.
Do not insert objects into openings. Do not use with any opening blocked; keep free of dust and debris.  Do not install the iPAK2 in any of the following environments
o damp environments where humidity is 90% or higher. o dusty environments. o environments where chemicals are handled. o environments near a high-frequency noise source. o hot or cold environments where temperatures are above 40°C or below 0°C, or environments
where water will condense.
iPAK2 Technical Manual 4
Contents
Section 1
Introduction…………………………………………………………………………………………...…5
Section 2
Getting started………...……………………………………………………………..………………13
Section 3
Inputs and outputs…………………….…....……………………………………………………19
Section 4
Discrete I/O…………… ……………..…….…………………………………………………….……21
Section 5
MODBUS I/O…………………..…….………………………………………………………….….…...24
Section 6
Weld control…………………..…….…………………………………………….…………………....30
Section 7
Electrode management…………………..…….……………………….…………….………38
Section 8
Status information…………………………………………………………….……….………….46
Section 9
History log…………………..…….…………………………………………………………………..…49
Section 10
Multiwelding…………………..…….………………………………………………….…..…………..50
Section 11
Seam welding………………..…….……………………………………………………...…………..54
Section 12
Configuration…………………..…….……………………………………………….….……………62
Section 13
Programming…………………..…….………………………………………………….……….……65
Section 14
Tutorials…………………..…….…………………………………………………………….…………...82
Section 15
Appendix…………………..…….……………………………………………………………….…….…92
Section 16
Terminology……………..…….…………………………………………………………………….…96
Section 1 Introduction 5
Introduction
The iPAK2 controller is suitable for MFDC spot, projection, roll-spot, seam and multi-welding welding applications.
The controller supports:
pre-heat, main heat and post-heat intervals force profiles multi-gun, multi-air valve applications multiple electrodes
The iPAK2 has multiple communication and control options and can be configured by a number of programming options. The Ethernet port supports simultaneous programming and control via a single physical cable.
Short-circuit proof outputs and a guided-contact pilot relay provides enhanced safety. Connection to the power system is via a single ribbon cable. Analog inputs and outputs can be used to drive a proportional air regulator valve for force control.
Operation in Standard mode provides a basic set of features for simple applications. Extended mode adds advanced features for more demanding applications. Choose between Standard or Extended features (Section 12 Configuration). The iPAK2 must be restarted after changing this setting.
Section 1 Introduction 6
Features
NetFlash programming WSP3 programming Ethernet 1 RS232 RS485 MODBUS TCP/IP MODBUS RTU
      
Analogue inputs 2 2 Analogue outputs 2 1 Discrete inputs 16 Discrete outputs 3 16 Weld programmes 256 Pre-heat Main heat Post-heat 5 Slope Constant current Cascade/Mux 5 8 Multi air valve
4, 5
8
    
Aux valves 7 Force profile 5
Electrodes 8 Real-time clock
Data log (spot welds) 6000 Expansion Analog control mode 5
1
Two ports
2
0 to 10 V
3
24 V dc, short-circuit proof, monitored
4
Guided contact safety relay, monitored
5
Extended feature
 
The extended features can be enabled for greater flexibility or more demanding applications.
Section 1 Introduction 7
Weld parameters
Prequeeze Squeeze Pre-heat Cool1 Upslope Main heat Cool2 Downslope Pulses Post-heat 1 Hold Off WAV selection 1 Motor control Aux valve control Retract/Hi-lift Electrode selection 1 Force profile 1 Current monitor Force monitor Spot weld Roll-spot weld 1 Seam weld 1
1
Extended feature
                      
Part number
Model Part number iPAK2 01-70-27
Section 1 Introduction 8
Programming options
1.NetFlash
This PC-compatible program displays and allows editing of all welding parameters and status information.
In addition to programming, NetFlash provides backup/restore functions for control data, live data logging to a file and a utility for updating the firmware in the iPAK2.
2. WSP3 Pendant
iPAK2 series controls work with the same WSP3 pendant that is used with EN7000, WS2003 and iPAK (v1). Access to all parameters is provided, plus diagnostic indication.
3. MODBUS
A PLC or HMI MODBUS master can be used to program, control and monitor an iPAK2. All parameters are directly mapped to MODBUS registers for easy access. Both MODBUS-TCP/IP (Ethernet) and MODBUS-RTU (RS485) protocols are supported.
4. Ethernet/IP
An optional adapter card can be fitted to the expansion port, providing full data access via the EtherNet/IP protocol.
Section 1 Introduction 9
Communications
Ethernet
RS485 RS232
Section 1 Introduction 10
Applications
Standard machines, portable/manual guns, robot guns, multi-welders and seam welders.
Standard machine
Multi-head machine. Up to eight cylinders, cascade or independent firing.
Section 1 Introduction 11
Multi-welder. Up to 8 transformers and cylinders, cascade or independent firing.
Section 1 Introduction 12
Seam welder with one transformer
Seam welder with a multi-tap transformer
Section 2 Getting started 13
Getting started
iPAK2 mounts directly onto an iPAK inverter. The inverters have maximum primary current ratings as follows:
150 A 360 A 600 A 1000 A 1500 A (LMI)
For higher currents, multiple LMI modules can be connected together. The standard iPAK family operates with a supply voltage in the range 380-480V AC but lower and higher voltage inverters are available.
Section 2 Getting started 14
Control connectors
Connectors P1, P2, P3, P4 and P5 are two-part terminals, for use with wires up to 1mm2.
The RS232 port is used to connect a WSP3 programming pendant or a PC. A ribbon cable assembly is available for converting to the standard 9-way D-sub style of connector.
Connector P6 is used internally to connect to the inverter power pack, and is not used for users connections.
Connector P7 is used for MUX driver cards on systems with more than one transformer.
Section 2 Getting started 15
Power connectors
A 3-phase supply via a suitable protective device (such as a circuit breaker) should be connected to the inverter as shown (Terminals L1, L2, L3, PE). A suitable MF welding transformer/rectifier should be connected to the inverter at terminals H1 and H2. The transformer must also be connected to the protective earth (PE).
Additional earthing and/or a protective device is required for the secondary circuit depending on the application.
These tasks must only be carried out by qualified personnel.
Section 2 Getting started 16
User’s connections (discrete)
Section 2 Getting started 17
Initialisation
Make the basic connections as shown below. Additional connections may be required
depending on the application.
Make sure there is sufficient air pressure and cooling water where necessary. Section 13 Programming: switch on then use the ‘Initialise all data’ function to clear the
iPAK2’s memory.
Section 12 Configuration: set the Configuration parameters appropriately for the application.
Section 2 Getting started 18
Section 13 Programming: edit program 0 to set up a basic weld sequence e.g. Squeeze =
200, Main heat = 100, Hold = 200, Pulses=1, and Main mode = P/W. A welding operation should be possible at this stage. Begin by using the gun short-circuit. The iPAK2 should report the measured current on the diagnostic display.
Section 7 Electrode management: perform the current and CCC calibration procedures. Make any other adjustments which may be required and set up other programmes for welding.
Section 3 Inputs and outputs 19
Inputs and outputs
iPAK2 uses a number of inputs and outputs to control and monitor the weld sequence.
Inputs
Input AWS
Start FS1 When this input is activated a weld sequence begins. If the input is removed
Weld on NW1 This input enables the weld current. If this input is inactive a weld sequence will
Stop ES1 Sequencing is inhibited or aborted if this input is not active. Thermal TT1 This input is usually connected to a normally closed thermal contact attached to
2nd stage PS1 If enabled, iPAK2 checks that the 2nd Stage signal is present before
Retract RT1 This input is used to control the Retract function. Reset fault FR1 This input resets the Fault output and clears the status messages. Only
Reset counter/tip dress acknowledge Reset
2
stepper P1 BP1 Program select inputs. Weld program selection is made by applying the binary P2 BP2 P4 BP4 P8 BP8 P16 BP16 P32 BP32 P64 BP64 Toroid Input for the toroid. Resistance must be in the range 10 to 300 Ohms. Analog 0 to 10 V analog input. Can be used to monitor a proportional air regulator valve
designation
Used to reset the counter(s) or acknowledge a tip dress request.
1
SR1 Used to reset the stepper(s).
Description
during the Squeeze interval the sequence is aborted. If the input is maintained through the Squeeze interval but switched off subsequently, the sequence terminates normally.
not produce any current.
the weld transformer. Sequencing is inhibited if this input is not active.
proceeding to weld. The checking is programmable to take place either before or after the Squeeze interval. If the signal is not present iPAK2 waits for the signal before it proceeds. If the Start signal is removed while waiting, the sequence is aborted.
momentary application is required (minimum time 40ms).
code for the required program. Programs 0 to 127 can be selected (programs 128 to 255 can still be selected internally or via the fieldbus).
If the ‘key-switch’ security option is selected, then input P64 (on the discrete interface only) is not available. In this case, programs 0 to 63 can be selected (programs 64 to 255 can still be selected internally or via the fieldbus).
output or other sensor for force control and monitoring. input in ANALOG mode.
Also used as the control
Section 3 Inputs and outputs 20
Outputs
Output AWS
Description
designation EOS EH1 This output switches on to indicate the end of the weld sequence. HAV RV1 Used in conjunction with the Retract input to control the welding head. Fault FT1 This output indicates a fault condition. Ready3 This output is active if iPAK2 is ready to weld. The output switches off under
some fault conditions. Contactor MC1 This output can be used to control an isolation contactor. Counter/tip dress request
This output indicates that the counter has reached its limit or that a tip dressing
operation is required. Stepper This output indicates that the stepper has reached its limit. Pre-warn This output indicates that the stepper is close to its limit. AV1 Additional outputs that can be used during the weld sequence. AV2 AV3 AV4 AV5 AV6 AV7 AV8 Analog 0 to 10 V analog output. Can be used to drive a proportional air regulator valve
for force control
1
Momentary operation will reset all expired counters. If maintained for more than 5 seconds all counters will be
reset, regardless of status.
2
Momentary operation will reset all expired steppers. If maintained for more than 5 seconds all steppers will be
reset, regardless of status.
3
If iPAK (v1) mode is selected (Section 12 Configuration)
the sense of the READY output is reversed and it signifies NOT READY outputs AV4, 5, and 6 are used for MUX selection and are not available
Section 4 Discrete I/O 21
Discrete I/O
The inputs and outputs are accessible via connectors P1, P2, P3, P4 and P5. The connectors are two­part terminals for use with wires up to 1 mm
If the iPAK2 is supplied fitted into a case some connections will have been pre-wired by BF ENTRON. See the case wiring diagram for details.
2
Section 4 Discrete I/O 22
Outputs are rated 500 mA @24 V dc AWS designations in parenthesis
1
inputs must be linked if not required
Pin I/O bit
1. 24 V (internal)
2. 24 V for I/O
3. 2 Stop (ES1)
4. 3 Transformer thermal (TT1)
5. 1 Weld on (NW1)
1
1
6. 0 V
Pin I/O bit
1. 24 V (24 VDC)
2. 0 Start (FS1)
3.
4.
5.
6. 9 P1 (BP1)
7. 10 P2 (BP2)
8. 11 P4 (BP4)
9. 12 P8 (BP8)
10. 13 P16 (BP16)
11. 14 P32 (BP32)
12. 8 Reset stepper (SR1)
13. 7 Reset counter/tip dress ack
14. 5 Retract (RT1)
15. 6 Reset fault (FR1)
nd
16. 4 2
stage (PS1)
17. 15 P64 (BP64)/Edit enable
WSP3 Power
1
Pin I/O bit
1. 15 AV1 (SV1)
2. 14 AV2 (SV2)
3. 13 AV3 (SV3)
4. 1 HAV (RV1)
5. Do not connect
6. 5 Counter
7. 6 Stepper
8. 7 Pre-warn
9. 12 AV4 (SV4)
10. 11 AV5 (SV5)
11. 10 AV6 (SV6)
12. 9 AV7 (SV7)
13. 8 AV8 (SV8)
14. 0 EOS (EH1)
15. 2 Fault (FT1)
16. 3 Ready
17. 4 Contactor (MC1)
18. 0 V (SVC)
Section 4 Discrete I/O 23
MUX
1. Analog input #1 (0 to 10 V)
2. 0 V
3. Analog output #1 (0 to 10 V)
4. Ground
1. Analog input #2
2. Analog input #2
3. Toroid input
4. Toroid input
5. Ground
MODBUS-RTU
NetFlash MODBUS-TCP/IP
1. Heartbeat
2. Ready
3. Sequence initiated
4. Weld current
5. Data receive COM0
6. Data send COM0
7. Data receive COM1
8. Data send COM1
9. Data receive COM2
10. Data send COM2
11. Data receive COM3
12. Data send COM3
Expansion
Section 5 MODBUS I/O 24
MODBUS I/O
iPAK2 can be operated via MODBUS instead of using the discrete inputs and outputs.
Both MODBUS TCP/IP (Ethernet) and MODBUS RTU (RS485) protocols are supported.
Write the inputs using MODBUS function 16 Read the outputs using MODBUS function 3
MODBUS access types
Write inputs Type Value Description Function code UINT 16 Write multiple registers Read offset UINT 0 Read length UINT 0 Write offset UINT 16#8000 (= 32768) Write length UINT 2
Read outputs Type Value Description Function code UINT 3 Read holding registers Read offset UINT 16#9000 (= 36864) Read length UINT 24 Write offset UINT 0 Write length UINT 0
Section 5 MODBUS I/O 25
MODBUS mapping (inputs to iPAK2)
Variable Channel Address Type Description Write inputs %QW0 WORD ARRAY [0..1] Write multiple registers Write inputs [0] %QW0 WORD WRITE 16#8000 (= 32768) Start Bit 0 %QX0.0 BOOL Weld on Bit 1 %QX0.1 BOOL Stop Bit 2 %QX0.2 BOOL Transformer thermal Bit 3 %QX0.3 BOOL 2nd stage Bit 4 %QX0.4 BOOL Retract Bit 5 %QX0.5 BOOL Reset fault Bit 6 %QX0.6 BOOL Reset counter Bit 7 %QX0.7 BOOL Reset stepper Bit 8 %QX1.0 BOOL Reserved Bit 9 %QX1.1 BOOL Reserved Bit 10 %QX1.2 BOOL Reserved Bit 11 %QX1.3 BOOL Reserved Bit 12 %QX1.4 BOOL Reserved Bit 13 %QX1.5 BOOL Reserved Bit 14 %QX1.6 BOOL Reserved Bit 15 %QX1.7 BOOL Write inputs [1] %QW2 WORD WRITE 16#8001 (= 32769) P1 Bit 0 %QX2.0 BOOL P2 Bit 1 %QX2.1 BOOL P4 Bit 2 %QX2.2 BOOL P8 Bit 3 %QX2.3 BOOL P16 Bit 4 %QX2.4 BOOL P32 Bit 5 %QX2.5 BOOL P64 Bit 6 %QX2.6 BOOL P128 Bit 7 %QX2.7 BOOL Reserved Bit 8 %QX3.0 BOOL Reserved Bit 9 %QX3.1 BOOL Reserved Bit 10 %QX3.2 BOOL Reserved Bit 11 %QX3.3 BOOL Reserved Bit 12 %QX3.4 BOOL Reserved Bit 13 %QX3.5 BOOL Reserved Bit 14 %QX3.6 BOOL Reserved Bit 15 %QX3.7 BOOL
Section 5 MODBUS I/O 26
MODBUS mapping (outputs from iPAK2)
Variable Channel Address Type Description Read outputs %IW0 WORD ARRAY [0..23] Read holding registers Read outputs [0] %IW0 WORD READ 16#9000 (= 36864) EOS Bit 0 %IX0.0 BOOL HAV Bit 1 %IX0.1 BOOL Fault Bit 2 %IX0.2 BOOL Ready Bit 3 %IX0.3 BOOL Contactor Bit 4 %IX0.4 BOOL Counter Bit 5 %IX0.5 BOOL Stepper Bit 6 %IX0.6 BOOL Pre-warn Bit 7 %IX0.7 BOOL AV8 Bit 8 %IX1.0 BOOL AV7 Bit 9 %IX1.1 BOOL AV6 Bit 10 %IX1.2 BOOL AV5 Bit 11 %IX1.3 BOOL AV4 Bit 12 %IX1.4 BOOL AV3 Bit 13 %IX1.5 BOOL AV2 Bit 14 %IX1.6 BOOL AV1 Bit 15 %IX1.7 BOOL Read outputs [1] %IW2 WORD READ 16#9001 (= 36865) Start Bit 0 %IX2.0 BOOL Weld on Bit 1 %IX2.1 BOOL Stop Bit 2 %IX2.2 BOOL Transformer thermal Bit 3 %IX2.3 BOOL 2nd stage Bit 4 %IX2.4 BOOL Retract Bit 5 %IX2.5 BOOL Reset fault Bit 6 %IX2.6 BOOL Reset counter Bit 7 %IX2.7 BOOL Reset stepper Bit 8 %IX3.0 BOOL P1 Bit 9 %IX3.1 BOOL P2 Bit 10 %IX3.2 BOOL P4 Bit 11 %IX3.3 BOOL P8 Bit 12 %IX3.4 BOOL P16 Bit 13 %IX3.5 BOOL P32 Bit 14 %IX3.6 BOOL P64 Bit 15 %IX3.7 BOOL Read outputs [2] %IW4 WORD READ 16#9002 (= 36866) Start Bit 0 %IX4.0 BOOL Weld on Bit 1 %IX4.1 BOOL Stop Bit 2 %IX4.2 BOOL Thermal Bit 3 %IX4.3 BOOL 2nd stage Bit 4 %IX4.4 BOOL Retract Bit 5 %IX4.5 BOOL Reset fault Bit 6 %IX4.6 BOOL Reset counter Bit 7 %IX4.7 BOOL Reset stepper Bit 8 %IX5.0 BOOL P1 Bit 9 %IX5.1 BOOL P2 Bit 10 %IX5.2 BOOL P4 Bit 11 %IX5.3 BOOL P8 Bit 12 %IX5.4 BOOL P16 Bit 13 %IX5.5 BOOL P32 Bit 14 %IX5.6 BOOL P64 Bit 15 %IX5.7 BOOL
%QX0.0 %QX0.1 %QX0.2 %QX0.3 %QX0.4 %QX0.5 %QX0.6 %QX0.7 %QX1.0 discrete input P1 discrete input P2 discrete input P4 discrete input P8 discrete input P16 discrete input P32 discrete input P64
discrete input Start discrete input Weld on discrete input Stop discrete input Thermal discrete input 2discrete input Retract discrete input Reset fault discrete input Reset counter discrete input Reset stepper discrete input P1 discrete input P2 discrete input P4 discrete input P8 discrete input P16 discrete input P32 discrete input P64
nd
stage
Section 5 MODBUS I/O 27
Variable Channel Address Type Description Analog input (mV) Read outputs [3] %IW6 WORD READ 16#9003 (= 36867) Analog output (mV) Read outputs [4] %IW8 WORD READ 16#9004 (= 36868) % pulse width Read outputs [5] %IW10 WORD READ 16#9005 (= 36869) Reserved Read outputs [6] %IW12 WORD READ 16#9006 (= 36870) Reserved Read outputs [7] %IW14 WORD READ 16#9007 (= 36871) Status register 0 Read outputs [8] %IW16 WORD READ 16#9008 (= 36872) Stop Bit 0 %IX16.0 BOOL Bit 0 Reserved Bit 1 %IX16.1 BOOL Retract not ready Bit 2 %IX16.2 BOOL Bit 2 Inverter hot Bit 3 %IX16.3 BOOL Bit 3 Transformer hot Bit 4 %IX16.4 BOOL Bit 4 Pilot fault Bit 5 %IX16.5 BOOL Bit 5 Restart required Bit 6 %IX16.6 BOOL Bit 6 Headlock Bit 7 %IX16.7 BOOL Bit 7 Reserved Bit 8 %IX17.0 BOOL Reserved Bit 9 %IX17.1 BOOL Reserved Bit 10 %IX17.2 BOOL Reserved Bit 11 %IX17.3 BOOL Reserved Bit 12 %IX17.4 BOOL Reserved Bit 13 %IX17.5 BOOL Reserved Bit 14 %IX17.6 BOOL Test mode Bit 15 %IX17.7 BOOL Bit 15 Status register 1 Read outputs [9] %IW18 WORD READ 16#9009 (= 36873) Start on Bit 0 %IX18.0 BOOL Bit 16 Weld off Bit 1 %IX18.1 BOOL Bit 17 Program inhibited Bit 2 %IX18.2 BOOL Bit 18 Output fault Bit 3 %IX18.3 BOOL Bit 19 Reserved Bit 4 %IX18.4 BOOL Too many links Bit 5 %IX18.5 BOOL Bit 21 Bad link Bit 6 %IX18.6 BOOL Bit 22 Maximum current Bit 7 %IX18.7 BOOL Bit 23 Toroid over range Bit 8 %IX19.0 BOOL Bit 24 CT over range Bit 9 %IX19.1 BOOL Bit 25 Maximum pulse width Bit 10 %IX19.2 BOOL Bit 26 Calibration error Bit 11 %IX19.3 BOOL Bit 27 Reserved Bit 12 %IX19.4 BOOL Reserved Bit 13 %IX19.5 BOOL Reserved Bit 14 %IX19.6 BOOL Reserved Bit 15 %IX19.7 BOOL Status register 2 Read outputs [10] %IW20 WORD READ 16#900A (= 36874) Low force Bit 0 %IX20.0 BOOL Bit 32 High force Bit 1 %IX20.1 BOOL Bit 33 Low pre-current Bit 2 %IX20.2 BOOL Bit 34 High pre-current Bit 3 %IX20.3 BOOL Bit 35 Low main current Bit 4 %IX20.4 BOOL Bit 36 High main current Bit 5 %IX20.5 BOOL Bit 37 Low post-current Bit 6 %IX20.6 BOOL Bit 38 High post-current Bit 7 %IX20.7 BOOL Bit 39 No 2nd stage Bit 8 %IX21.0 BOOL Bit 40 No force Bit 9 %IX21.1 BOOL Bit 41 Reserved Bit 10 %IX21.2 BOOL Reserved Bit 11 %IX21.3 BOOL Reserved Bit 12 %IX21.4 BOOL Reserved Bit 13 %IX21.5 BOOL Reserved Bit 14 %IX21.6 BOOL Reserved Bit 15 %IX21.7 BOOL
Section 5 MODBUS I/O 28
Variable Channel Address Type Description Status register 3 Read outputs [11] %IW22 WORD READ 16#900B (= 36875) End of count 0 Bit 0 %IX22.0 BOOL Bit 48 End of count 1 Bit 1 %IX22.1 BOOL Bit 49 End of count 2 Bit 2 %IX22.2 BOOL Bit 50 End of count 3 Bit 3 %IX22.3 BOOL Bit 51 End of count 4 Bit 4 %IX22.4 BOOL Bit 52 End of count 5 Bit 5 %IX22.5 BOOL Bit 53 End of count 6 Bit 6 %IX22.6 BOOL Bit 54 End of count 7 Bit 7 %IX22.7 BOOL Bit 55 Reserved Bit 8 %IX23.0 BOOL Reserved Bit 9 %IX23.1 BOOL Reserved Bit 10 %IX23.2 BOOL Reserved Bit 11 %IX23.3 BOOL Reserved Bit 12 %IX23.4 BOOL Reserved Bit 13 %IX23.5 BOOL Reserved Bit 14 %IX23.6 BOOL Reserved Bit 15 %IX23.7 BOOL Status register 4 Read outputs [12] %IW24 WORD READ 16#900C (= 36876) End of electrode 0 Bit 0 %IX24.0 BOOL Bit 64 End of electrode 1 Bit 1 %IX24.1 BOOL Bit 65 End of electrode 2 Bit 2 %IX24.2 BOOL Bit 66 End of electrode 3 Bit 3 %IX24.3 BOOL Bit 67 End of electrode 4 Bit 4 %IX24.4 BOOL Bit 68 End of electrode 5 Bit 5 %IX24.5 BOOL Bit 69 End of electrode 6 Bit 6 %IX24.6 BOOL Bit 70 End of electrode 7 Bit 7 %IX24.7 BOOL Bit 71 Reserved Bit 8 %IX25.0 BOOL Reserved Bit 9 %IX25.1 BOOL Reserved Bit 10 %IX25.2 BOOL Reserved Bit 11 %IX25.3 BOOL Reserved Bit 12 %IX25.4 BOOL Reserved Bit 13 %IX25.5 BOOL Reserved Bit 14 %IX25.6 BOOL Reserved Bit 15 %IX25.7 BOOL Status register 5 Read outputs [13] %IW26 WORD READ 16#900D (= 36877) Tip dress 0 Bit 0 %IX26.0 BOOL Bit 80 Tip dress 1 Bit 1 %IX26.1 BOOL Bit 81 Tip dress 2 Bit 2 %IX26.2 BOOL Bit 82 Tip dress 3 Bit 3 %IX26.3 BOOL Bit 83 Tip dress 4 Bit 4 %IX26.4 BOOL Bit 84 Tip dress 5 Bit 5 %IX26.5 BOOL Bit 85 Tip dress 6 Bit 6 %IX26.6 BOOL Bit 86 Tip dress 7 Bit 7 %IX26.7 BOOL Bit 87 Reserved Bit 8 %IX27.0 BOOL Reserved Bit 9 %IX27.1 BOOL Reserved Bit 10 %IX27.2 BOOL Reserved Bit 11 %IX27.3 BOOL Reserved Bit 12 %IX27.4 BOOL Reserved Bit 13 %IX27.5 BOOL Reserved Bit 14 %IX27.6 BOOL Reserved Bit 15 %IX27.7 BOOL
Section 5 MODBUS I/O 29
Variable Channel Address Type Description Status register 6 Read outputs [14] %IW28 WORD READ 16#900E (= 36878) Prewarn 0 Bit 0 %IX28.0 BOOL Bit 96 Prewarn 1 Bit 1 %IX28.1 BOOL Bit 97 Prewarn 2 Bit 2 %IX28.2 BOOL Bit 98 Prewarn 3 Bit 3 %IX28.3 BOOL Bit 99 Prewarn 4 Bit 4 %IX28.4 BOOL Bit 100 Prewarn 5 Bit 5 %IX28.5 BOOL Bit 101 Prewarn 6 Bit 6 %IX28.6 BOOL Bit 102 Prewarn 7 Bit 7 %IX28.7 BOOL Bit 103 Reserved Bit 8 %IX29.0 BOOL Reserved Bit 9 %IX29.1 BOOL Reserved Bit 10 %IX29.2 BOOL Reserved Bit 11 %IX29.3 BOOL Reserved Bit 12 %IX29.4 BOOL Reserved Bit 13 %IX29.5 BOOL Reserved Bit 14 %IX29.6 BOOL Reserved Bit 15 %IX29.7 BOOL Status register 7 Read outputs [15] %IW30 WORD READ 16#900F (= 36879) Bus fail Bit 0 %IX30.0 BOOL Bit 112 Short circuit Bit 1 %IX30.1 BOOL Bit 113 Fan failure Bit 2 %IX30.2 BOOL Bit 114 Inverter not ready Bit 3 %IX30.3 BOOL Bit 115 LMI config. error Bit 4 %IX30.4 BOOL Bit 116 LMI error Bit 5 %IX30.5 BOOL Bit 117 Duty cycle limit Bit 6 %IX30.6 BOOL Bit 118 Reserved Bit 7 %IX30.7 BOOL Reserved Bit 8 %IX31.0 BOOL Reserved Bit 9 %IX31.1 BOOL Reserved Bit 10 %IX31.2 BOOL Reserved Bit 11 %IX31.3 BOOL Reserved Bit 12 %IX31.4 BOOL Reserved Bit 13 %IX31.5 BOOL Reserved Bit 14 %IX31.6 BOOL Reserved Bit 15 %IX31.7 BOOL Pre-heat current (A) Read outputs [16] %IW32 DWORD READ 16#9010 (= 36880) Main current (A) Read outputs [18] %IW36 DWORD READ 16#9012 (= 36882) Post-heat current (A) Read outputs [20] %IW40 DWORD READ 16#9014 (= 36884) Program number Read outputs [22] %IW44 WORD READ 16#9016 (= 36886) Force1 Read outputs [23] %IW46 WORD READ 16#9017 (= 36887)
1
value is multiplied by the scale factor (898.88 for kN or 4 for lbf
Section 6 Weld control 30
Weld control
iPAK2 controls the weld sequence by using the I/O in conjunction with the welding parameters. The parameters are stored in programs so that different materials and machine sequences can be used. There are 256 weld programs.
Loading...
+ 67 hidden pages