69
IP1967EN - 2016-08-01
11.1 Make a jumper for safety contacts 1-6, 1-8, 1-9. Set JR1=ON, JR5=ON.
11.2 If limit switches are used, adjust them by manually moving the wings as described here:
- deceleration limit switch: activation of the limit switch must occur before the mechanical
doorstop,
- stop limit switch: activation of the stop limit switch must occur in the open/close position of
the wings,
- proximity limit switch: activation of the proximity limit switch must occur near the mechanical
doorstop.
11.3 Switch on power.
Warning: the following operations are performed with no safety devices.
11.4 If the dedicated memory module is present, press , if it is not present, load the
configuration related to the type of automation installed.
11.5 If the automation has 1 door wing, set .
11.6 Verify the setting.
11.7 With the automation idle in the intermediate position, give a closing command + , and
check the door wings move in the correct direction. In the event of an incorrect connection,
invert the polarity of the motor.
Note: the first closing operation after a power supply interruption is carried out with one
door wing at a time, at reduced speed.
11.8 Give an opening command + and verify that the automation carries out the operation
at reduced speed stopping at the mechanical doorstops during the opening phase.
11.9 Load the predefined setting most suitable for system available in the menu.
11.10 If limit switches are used, define their use by means of settings and .
11.11 In order to save the configurations in the memory module it is necessary to set
.
11.12 To modify the operation and deceleration speed settings, the automatic closing times, and
the thrust on obstacles, consult the menus.
11.13 Connect the safety devices (removing all relevant jumpers) and verify their correct operation.
Note: ensure that the forces exerted by the door wings are compliant with EN12453-EN12445
regulations.
11.14 If desired, memorize the radio commands with command (refer to chapter 12).
11.15 Connect any other accessories and check operation.
11.16 Once the start up and check procedures are completed, close the container.
11. Starting
WARNING: the system must have mechanical doorstops of appropriate strength or limit
switches must be installed.
WARNING: if this control panel is being used to replace a faulty one, it is possible to reset the
last automation configuration by inserting the storage module of the old control panel in the
housing on the new one, then loading the last configuration set with the
command.