Entrematic Ditec E1A Technical Manual

Page 1
Ditec E1A
Control panel installation manual for one motor automation with built-in radio.
IP2045EN
Technical manual
www.ditecentrematic.com
POWER
SA
IN
J12
com
Limit switch
Limit switch
Accessories output
M1
1~
R1
AUX
A N T
C O
M
F1
TC TM
JR6
12
12 011
11 0 1568941
NCUWVLN
SO 6>4
NIO
PRG
JR4
JR10
JR3
1ON234
F
U
S
E
E1A
SIG
LN
Power supply
Step by step
Stop safety device
Safety reopening
Stop
Safety test
Flashing light
Lamp
PT3
GOL4
RF
CT
1 2 3 4 5
F2
F
U
S
E
Page 2
24
IP2045EN - 2014-09-22
Page 3
25
IP2045EN - 2014-09-22
Index
Subject Page
1. General safety precautions 26
2. EC declaration of conformity 27
3. Technical data 27
3.1 Applications 27
4. Commands 28
4.1 Self-controlled safety edge 29
5. Outputs and accessories 30
6. Adjustments 31
6.1 Trimm er 31
6.2 Dip-switch 32
6.3 Jumper 32
6.4 Signals 33
7. Radio 34
8. Start-up 35
9. Troubleshooting 36
10. Application example for sliding doors and gates 37
11. Application example for in-parallel automations 38
12. Application example for barriers 39
13. Application example for rolling shutters 39
14. Application example for sectional overhead doors 40
Caption
i
This symbol indicates informations which are useful for correct product function.
This symbol indicates instructions or notes regarding safety issues which require particular attention.
Page 4
26
IP2045EN - 2014-09-22
1. General safety precautions
This installation manual is intended for qualified personnel only. Installation, electrical connections and adjustments must be performed in accordance with Good Working Methods and in compliance with applicable regulations. Before installing the product, carefully read the instructions. Bad installation could be hazard­ous.
The packaging materials (plastic, polystyrene, etc.) should not be discarded in the environ-
ment or left within reach of children, as these are a potential source of hazard. Before installing the product, make sure it is in perfect condition. Do not install the product in an explosive environment and atmosphere: gas or inflammable fumes are a serious hazard risk. Before installing the motors, make all structural changes relating to safety clearances and protection or segregation of all areas where there is risk of being crushed, cut or dragged, and danger areas in general. Make sure the existing structure is up to standard in terms of strength and stability. The motor manufacturer is not responsible for failure to use Good Working Methods in building the frames to be motorized or for any deformation occurring during use.
The safety devices (photocells, safety edges, emergency stops, etc.) must be installed
taking into account: applicable laws and directives, Good Working Methods, installation premises, system operating logic and the forces developed by the motorized door. The safety devices must protect any areas where the risk exists of being crushed, cut or gragged, or where there are any other risks generated by the motorized door. Apply hazard area notices required by applicable regulations. Each installation must clearly show the identification details of the motorized door. When necessary, connect the motorized door to a reliable earth system made in accordance with applicable safety regulations. During installation, maintenance and repair, interrupt the power supply before opening the lid to access the electrical parts. The protective casing of the automation must be removed by qualified personnel only.
To handle electronic parts, wear earthed antistatic conductive bracelets. The motor
manufacturer declines all responsibility in the event of component parts being fitted that are not compatible with the safe an correct operation. For repairs or replacements of products only original spare parts must be used. The installer shall provide all information relating to automatic, manual and emergency operation of the motorized door, and provide the user with operating instructions.
1.1 Installation warning
Secure the control panel permanently. Drill a hole into the lower side of the container so as to run the cables through it. Secure the cables, if they are accessible, by means of appropriate gland plates (not provided by us). Keep the line and motor conductors separate (at least 8 mm) from the control conductors at the terminal board connection points (for example, by means of clamps). Connect the line and motor protection conductors (yellow-green) by means of the transformer and control panel using the clamp provided. At the end of the installation to close again the container.
Failure to observe the information in this manual may result
in minor personal injury or damage to equipment.
Save these instructions for future reference.
Page 5
27
IP2045EN - 2014-09-22
The manufacturer Entrematic Group AB with headquarters in Lodjursgatan 10, SE-261 44 Landskrona, Sweden
declares that the control panel Ditec E1A is in conformity with the provisions of the following EC directives:
EMC Directive 2004/108/CE; Low energy Directive 2006/95/CE. R&T TE Directive 1999/5/CE
Landskrona, 29-01-2013 Marco Pietro Zini (President)
2. EC Declaration of conformity
3. Technical data
Ditec E1A Ditec E1AJ
Power supply 230 V~ 50 Hz 120 V~ 60 Hz
Fuse F1
F6,3A F8A with NIO=OFF
F6,3A
Fuse F2 / F6,3A Motor output 230 V~ 5A max 120 V~ 6,3A max Accessories power supply 24 V 0,5 A 24 V 0,5 A Temperature -20 °C - +55 °C -20 °C - +55 °C Degree of protection IP55 IP55
Radio frequency 433,92 MHz 433,92 MHz
Memorizable radio codes 200 200
i
3.1 Applications
NOTE: the given operating and performance features can only be guaranteed with the use of Entrematic accessories and safety devices.
Page 6
28
IP2045EN - 2014-09-22
4. Commands
Command Function Description
1 5 N.O. STEP-BY-STEP
WITH AUTOMATIC CLOSING
With DIP1=OFF and TC<MAX, the closure of the contact activates an opening or closing operation in the following sequence: open­stop-close-open. NOTE: the stop is not permanent, but has the
duration set by TC. STEP-BY-STEP WITHOUT AUTOMATIC CLOSING
With DIP1=OFF and TC=MAX, the closure of the contact activa-
tes an opening or closing operation in the following sequence:
open-stop-close-open.
OPENING WITH AUTOMATIC CLOSING
With DIP1=ON and TC<MAX, the closure of the contact activates
an opening operation.
OPENING WITHOUT AUTOMATIC CLOSING
With DIP1=ON and TC=MAX, the closure of the contact activates
an opening operation.
If 6→4=ON, with the automation idle, contact 1-5 performs the
closure operation as well.
If 6→4=OFF, the closure operation is performed by contact 1-6.
1 6
N.O. CLOSING With 6→4=OFF, the closure of the contact activates a closing operation.
41 6 N.C. SAFETY STOP The opening of the safety contact stops and prevents any movement. 41 8 N.C. REVERSAL SAFETY
DEVICE
Opening the safety contact triggers a reversal of the movement
(reopening) during a closing operation.
1 9 N.C. STOP Opening the safety contact stops the current operation.
EMERGENCY STOP To enable the emergency stop function (e.g. with a specific red
button), connect the opening and closing controls to terminal 9
instead of 1 (9-5, 9-6).
1 9
N.O. HOLD-TO-RUN
FUNCTION
Permanently opening the safety contact enables the operator
presence dependent function. In this state, the opening (1-5) and
closing (1-6) controls function only if held in the pressed position,
and the automation stops when the controls are released. Any
safety devices, plus the automatic closing, are disactivated.
0 11 N.C. CLOSING
LIMIT SWITCH
With DIP2=OFF, the opening of the contact blocks the movement
of the automation during the closing phase.
With DIP2=ON, the opening of the contact blocks the movement
of the automation during the opening phase.
Alternatively, you can connect the limit switch to the fastons 0-11
(in this case, the terminals 0-11 must not be jumped).
0 11 N.O. CLOSING
PROXIMITY SWITCH
In the event of obstacle detection during closing and before the
activation of the proximity limit switch, the door wing reopens;
after the activation of the proximity limit switch, the door wing
blocks against the mechanical closing stop.
0 12
N.C. OPENING
LIMIT SWITCH
With DIP2=OFF, the opening of the contact blocks the movement
of the automation during the opening phase.
With DIP2=ON, the opening of the contact blocks the movement
of the automation during the closing phase. Alternatively, you
can connect the limit switch to the fastons 0-12 (in this case,
the terminals 0-12 must not be jumped).
0 12 N.O. OPENING
PROXIMITY SWITCH
In the event of obstacle detection before the activation of the
proximity limit switch while opening, the door wing stops,
performing a disengagement operation; after the activation
of the proximity limit switch, the door wing blocks against the
mechanical opening stop.
WARNING: Make a jumper on all N.C. contacts if not in use. The terminals with the same number are equal.
Page 7
29
IP2045EN - 2014-09-22
4.1 Self-controlled safety edge SOFA1-SOFA2 or GOPAVRS
Command Function Description
GOPAV
SOFA1-SOFA2
SAFETY TEST Place the SOFA1-SOFA2 or GOPAVRS device into its hou-
sing for plug-in cards AUX. Connecting terminal 41 enables a safety edge test cycle before every operation. If the test fails the SA led flashes and the test is repeated.
1 6
N.C. STOP SAFET Y
DEVICE
Connect the output contact of device SOFA1-SOFA2 to terminals 1-6 on the control panel (in series with the photocell output contact, if installed).
1 8
N.C. REVERSAL
SAFETY DEVICE
Connect the output contact of device SOFA1-SOFA2 to terminals 1-8 on the control panel (in series with the photocell output contact, if installed). ATTENTION: for quick operation on the safety edge, con­nect it to contact 1-6.
Page 8
30
IP2045EN - 2014-09-22
Output Value - Accessories Description
4901 23
24 V 0,5 A
Accessories power supply. Power supply output for external accessories, including automa­tion status lamps.
AUX
SOFA1-SOFA2
GOPAV
The control panel has one space for coupling board, type radio receivers, magnetic loops etc. The coupling board working mode is selected by DIP1. WARNING: the plug-in cards must be inserted and removed with the power supply disconnected.
11 ...
1
24 V 3 W
Automation open lamp. Only with the limit switch 0-11 (N.C.) connected and DIP2=OFF will the light switch off when the automation is closed. Automation closed lamp. With DIP2=ON, the light switches off when the automation is open.
QIKLUX
24 V 120 mA max
Light kit for QIK barrier. With DIP2=ON, the light switches off when the automation is open.
12 ...
1
24 V 3 W
Automation closed lamp. Only with the limit switch 0-12 (N.C.) connected and DIP2=OFF will the light switch off when the automation is open. Automation open lamp. With DIP2=ON, the light switches off when the automation is closed.
QIKLUX
24 V 120 mA max
Light kit for QIK barrier. With DIP2=OFF, the light switches off when the automation is open.
M1
UVW
230 V~ 5 A
120 V (E1AJ)
Motor 1 (M1). Terminal W must be connected to the common motor phase connec­tion. The condenser must be connected between the U and V phases.
N
W ...
LAMP
230 V~ 25 W
120 V~ (E1AJ)
Flashing light. Activated during opening and closing operations.
CN ...
LUXK7
230 V~ 60 W
120 V~ (E1AJ)
Courtesy light in CROSS sliding automation. Comes on for 180 seconds after receiving any opening (total or partial) or closing command.
230 V~ 100 W
120 V~ (E1AJ)
Drive unit external courtesy light. Comes on for 180 seconds after receiving any opening (total or partial) or closing command.
J12
Membrane push-button panel (PT3). Starts the opening operation. NOTE: to activate the closing operation, connect the connector of the push-button panel to J12 (rotated by 180°). Membrane push-button panel (PT3). Causes the blocking of the movement.
Membrane push-button panel (PT3). Starts the closing operation. NOTE: to activate the opening operation, connect the connector of the push-button panel to J12 (rotated by 180°).
WARNING: use a double insulated cable
WARNING: use a double insulated cable
5. Output and accessories
Page 9
31
IP2045EN - 2014-09-22
Trimmer Description
R1
MAX=disabled
MIN
Setting obstacle thrust. The control panel is equipped with a safety system that stops motion if an obstacle is encountered during an opening operation and either stops or reverses motion during a closing operation. R1=MIN gives maximum obstacle sensitivity (minimum thrust). R1=MAX disables detection (maximum thrust).
TC
MIN=0 s MAX=disabled
120 s
Setting automatic closing time. From 0 to 120 s. With TC=MAX, the automatic closing is disactivated. The count begins from the blocking of the automation, for the time set by the TC. With DIP3=OFF, once a safety switch has been activated, the counter starts as soon as the safety switch is released (for example, after passing through the photocells), and lasts for a period of time set with TC (50%). Note: with DIP3=OFF and 6→4=OFF, the automatic closing is immediate. With DIP3=ON, the counter starts when automation is opened and lasts for the entire duration set with TC (100%). NOTE: after the activation of the stop command, once contact 1-9 has clo­sed again, the automatic closing is only activated after a total or step-by­step opening command.
TM
MIN=10 s MAX=120 s
60 s
Setting the operating time. From 10 to 120 s. NOTE: with NC limit switch, set TM=MAX.
RF
CT 1 23
45
Power setting. Sets voltage supplied to motor (CT-1=MIN / CT-5=MAX).
ATTENTION: disconnect the power supply before adjusting.
6.1 Trimmer
6. Adjustments
Page 10
32
IP2045EN - 2014-09-22
Jumper Description
OFF
ON
JR3 Incorporated radio receiver. Disabled. Enabled. JR4 Overtravel reduction.
Reduces the overtravel distance for the door wing.
Disabled. Enabled.
NOTE: preferably set JR4=ON if the door wing performs an excessive overtravel.
JR6 Application type. Sliding gate. Other applications. JR10 Maximum power start. Disabled.
The motor starts with the voltage set with RF.
Enabled. The motor starts at maximum power for 1 s.
NIO Electronic antifreeze system.
Maintains motor function even at low ambient temperatures. NOTE: for correct operation, the control panel must be exposed to the same ambient tempera­ture as the motors.
Enabled. ATTENTION: do not use with E1AJ.
Disabled.
SO Reversal safety switch function. With the automation blocked,
if the contacts 1-8 or 41-8 are open, it is possible to activate the opening operation. NOTE: after the activation of the proximity limit switch closes the opening of the safety contact 1-8, 41-8 provokes the STOP during the closing phase.
With the automation blocked, if the contacts 1-8 or 41-8 are open, any operation is impossible.
6→4 Control 1-6 function. Closing. Stop.
6.2 Dip-switch
DIP Description
OFF
ON
DIP1 Control 1-5 function. Step-by-Step. Opening. DIP2 Direction selection. Opens towards right. Opens towards left. DIP3 Restore automatic closing time. 50% 100%
NOTE: the setting of DIP3=ON is recommended for overhead and sectional doors, and condomi­nial entrances.
Immediate if 6→4=OFF. NOTE: the setting of DIP3=OFF and 6→4=OFF is recommended for the immediate reclosing of the barriers.
DIP4 Automation status at power on.
Indicates how the control panel considers automation when po­wered up.
Open. If DIP1=OFF, the first command 1-5 activates the closing. If DIP1=ON, the first command 1-5 activates the opening. NOTE: with a limit switch instal­led, preferably set DIP4=OFF.
Closed. The first command 1-5 activates the opening. NOTE: the automatic closing will not be the first command, even if enabled. If the automatic closing function is not used, preferably set DIP4=ON.
6.3 Jumper
Page 11
33
IP2045EN - 2014-09-22
6.4 Signals
LED On Flashing
POWER 24 V power supply / SA Indicates that at least one of the safety con-
tacts is open.
Safety test failure (terminal 41).
Operations count performed (only when control panel is switched on):
= 1000 operations
= 10000 operations
IN
Activated at every command and adjustment to the dip-switch and jumper.
/
11 Indicates that the 0-11 limit switch contact
is open.
/
12
Indicates that the 0-12 limit switch contact is open.
/
SIG Activated during the radio reception phase or
transmitter memorisation.
Indicates the absence of the memory module.
Page 12
34
IP2045EN - 2014-09-22
The control panel is equipped with a radio receiver with a frequency of 433.92 MHz. The antenna consists of a rigid wire, 173 mm long, connected to the ANT clamp. It is possible to increase the range of the radio by connecting the antenna
of the flashing lights, or by installing the tuned BIXAL antenna. NOTE: to connect the external antenna to the control panel, use a coaxial cable type RG58 (max 10 m). Check that the storage module is inserted on COM connector of the control panel. Up to 200 remote controls can be stored in the storage module. WARNING: if the radio receiver on the control panel is not used, set JR3=OFF and remove the storage module.
Transmitter storage:
- press the PRG button on the radio receiver or on the control panel; the SIG LED lights up;
- make a transmission by pressing one of the desired CH buttons of the transmitter (within the
range of the radio receiver). The transmitter is now stored. During this phase, the SIG LED flashes. When the SIG LED is again lit up, it is possible to validate another transmitter. Validate all the new transmitters by making a transmission as indicated;
- you automatically exit the procedure 10 seconds after the last transmission, or you can press
the PRG button again (the SIG LED goes off).
Up to four CH keys of a single remote control can be stored:
- if only one (any) CH key of the remote control is stored, command 1-5 (step-by-step/opening) is
carried out;
- from two to four CH keys of a single remote control are stored, the functions matched with the
CH keys are as follows:
• CH1=command1-5step-by-step/opening;  • CH2=partialopeningcommand,itcausestheautomationtoopenforabout1m;  • CH3=commandtoswitchon/offthecourtesylight;  • CH4=stopcommand,equivalenttoimpulsivecommand1-9.
Transmitter cancellation:
- keep pressed for 3 s the PRG button on the radio receiver or on the control panel, the SIG LED
begins to flash;
- to erase all the transmitters from the memory of the radio receiver keep pressed for 3 s again
the PRG button;
- to erase a single transmitter, press one of the previously stored CH keys of the transmitter to
be erased;
- the cancellation is confirmed by the quick flashing of the SIG LED. If the control panel is replaced, the storage module being used can be inserted in the new control panel.
10 s
CH1 CH2
CH3 CH4
1 2 3
PRG
Receiver
7. Radio
ATTENTION: the insertion and extraction of the BIXMR2 memory must be carried out in the absence of a power supply.
For further information see the user manual for GOL series transmitters.
i
Page 13
35
IP2045EN - 2014-09-22
• Bridge the NC safety contacts with a jumper.
• Before starting up, check the application type selected (see JR6 jumper).
• Any limit switches installed must be adjusted so that they are triggered near the mechanical
opening and closing end stops. Set TM=MAX.
NOTE: limit switches must be kept pressed until the operation has been completed.
• If no limit switches are installed, bridge terminals 0-11 and 0-12 with jumpers and set TM to
half.
• Set TC=MAX. Set RF=CT-3 and R1 to half.
• Using DIP2, set the direction.
• Switch on power.
• Perform opening and closing commands and check that the automation functions correctly
and that the limit switches (if installed) are correctly set.
NOTE: if mechanical stops are used to block the stroke of the automation, or a proximity limit switch
with N.O. contact, adjust the TM trimmer in order to obtain an operation time 2-3 s greater than the time effectively taken by the automation.
• Connect the safety devices (removing the relative jumpers) and check that they function correctly.
• If required, regulate the automatic closing by means of the TC trimmer.
• Set RF to a position that allows the automation to function correctly while ensuring the safety
of the user in the event of collision.
• Set obstacle thrust with R1.
• NOTE: ensure that the forces exerted by the door wings are compliant with EN12453-EN12445
regulations.
• Connect any other accessories and check operation.
• Once the start up and check procedures are completed, close the container.
WARNING: The following operations are performed with no safety devices.
8. Starting
Page 14
36
IP2045EN - 2014-09-22
Problem Possible causes Remedy
Automation does not open or close. No power.
(POWER led off).
Check that the control panel is powered correctly.
Short circuited accessories. (POWER led off).
Disconnect all accessories from terminals 0-1 (voltage must be 24
V=) and reconnect one at a time. Blown line fuse. (POWER led off). Replace fuse. Safety contacts are open.
(SA led on).
Check that the safety contacts are
closed correctly (N.C.). Safety contacts not correctly con-
nected or self-controlled safety edge SOFA1-SOFA2 not functioning correctly. (SA led flashing).
Check connections to terminals 6-8
on control panel and connections
to the self-controlled safety edge
SOFA1-SOFA2. Release microswitch open.
(11 and 12 led on).
Check that the hatch is closed cor-
rectly and the microswitch makes
contact. The motor thermal overload switch
is open.
Check for continuity between the
phases U-V-W of the motor discon-
nected from the control panel. The remote control does not work. Check the correct memorisation
of the transmitters on the incorpo-
rated radio. The remote control does not work.
(SIG led flashing).
Memory module BIXMR2 absent.
Automation opens but does not close.
Safety contacts are open. (SA led on).
Check that the safety contacts are
closed correctly (N.C.). Safety contacts not correctly con-
nected or self-controlled safety edge SOFA1-SOFA2 not functioning correctly. (SA led flashing).
Check connections to terminals 6-8
on control panel and connections
to the self-controlled safety edge
SOFA1-SOFA2.
Photocells activated. (SA led on).
Check that the photocells are
clean and operating correctly. The automatic closing does not
work.
Check that the TC trimmer is not
set at the maximum.
The automation is very weak and does not invert the movement.
The motor’s condenser has an in­correct capacity value.
Replace the motor’s condenser.
External safety devices not activat­ing.
Incorrect connections between the photocells and the control panel.
Connect NC safety devices together
in series and remove any bridges on
the control panel terminal board.
The remote control has limited range and does not work with the automation moving.
The radio transmission is impeded by metal structures and reinforced concrete walls.
Install the antenna outside. Substi-
tute the transmitter batteries.
9. Troubleshooting
Page 15
37
IP2045EN - 2014-09-22
(Example 1). Connect opening and closing limit switches N.C. contacts to plug 12-0-11;
or
(Example 2). Connect opening and closing limit switches N.C. contacts to terminals 0-11-12.
With the above connections, when limit switches operate the wing stops. In the event of obstacle detection, the wing stops and releases during opening operation and reo­pens during closing operation.
NOTE: if the self-controlled safety edge SOFA1-SOFA2 is used, make the con­nections indicated in par. 4.1.
R1
<MAXMAX
TC TM
JR6
12
12 011
11 01568941
1ON234
Limit switch
Limit switch
DIP2=OFF
DIP2=ON
1ON234
1ON234
R1
<MAXMAX
TC TM
JR6
12
12 011
11 01568941
1ON234
Limit switch
Limit switch
DIP2=OFF
DIP2=ON
1ON234
1ON234
10. Example applications for sliding door and gates
When control panel is used for sliding automations ope­rations:
- set JR6=OFF;
- set TM=MAX;
- select the proper opening direction by means of DIP2.
i
Page 16
38
IP2045EN - 2014-09-22
It is possible to command two automations [A] and [B] side by side, making the connections indicated in figure. Commands 1-5 and the remote control (with DIP1=ON) are equivalent to a total opening command. To manage both automations with a single remote control, do not use
the radio receivers on the control panels, but insert a BIXLR22 receiver. The automatic closing is obtained by regulating the TC trimmer not at the maximum, and in the same position in both control panels.
11. Example of automation in parallel
R1
<MAX
TMTC
JR3
12 11 01568941
1
ON
234
R1
<MAX
TM TC
121101568941
1
ON
234
0
6841
6
8
SWT
OUT2
0
6841
6
8
SWT
BIXLR22
JR1 JR2
E1A
A
E1A
B
A B
i
NOTE: the opening and closing movements are not synchronised.
ATTENTION: in the absence of safety edges SOFA1-SOFA2, connect commands 1-6 and 1-8 to the SWT card.
Page 17
39
IP2045EN - 2014-09-22
When the control panel is used in applications for rolling shutters:
- set JR6=ON
- connect the N.C. limit switches in succession to the motor phases
- make a jumper with the terminals 0-11-12.
13. Application example for rolling shutters
(Example 1). Connect opening and closing limit switches N.C. contacts to plug 12-0-11.
(Example 2). Control N.C. 1-6 (safety stop) can be changed into control N.O. 1-4 (closing) setting 6→4=OFF. To have the barrier close again soon after transit between the photocells (or other safeties con­nected to 1-8), set DIP3=OFF.
i
NOTE: if the control panel is used in the hold to run mode, disconnect terminal 9 (see example 1 in Section 14).
12. Application example for barriers
R1
<MAX <MAX
TC TM
JR6
12
12 011
11 01568941
1ON234
Limit switch
NCUWV
com
M1
1~
When control panel is used for barriers operations:
- set RF=CT-5 (MAX);
- set TM=MAX;
- set JR6=ON;
- select the proper opening direction by means of DIP2.
R1
RF=CT-5
MAX
TC TM
12
12 011
11 01568941
1ON234
Limit switch
Limit switch
DIP2=OFF
DIP2=ON
1ON234
1ON234
JR6
CT
1 2 3 4 5
R1
DIP3=OFF
TC TM
12
12 011
11 01568941
1ON234
6>4
Closing
Opening
JR6
Page 18
40
IP2045EN - 2014-09-22
R1
MAX
TC TM
12
12 011
11 01568941
1ON234
6>4
Closing
Opening
Limit switch
Limit switch
A
C
J12
PT3
JR6
R1
MAX
TC TM
12
12 011
11 01568941
1ON234
6>4
Closing
Opening
Limit switch
Limit switch
A
C
J12
PT3
AUX
SOFA1
OUT1
141IN1
JR6
14. Application example for sectional
overhead doors
(Example 1) When the control panel is used in applications for sectional automations:
- set TM=MAX;
- connect opening and closing limit switches N.C.
contacts to terminals 0-11-12:
- select the opening control by means of DIP1=ON;
- select the direction of the movement by means of
DIP2=OFF;
- select the closing control by setting 6→4=OFF.
- set JR6=ON;
NOTE: to use electronic control panel in hold to run mode, disconnect terminal 9.
In this case, the opening (1-5) and the closing (1-6) controls operate only if kept pressed, if released the automation will stop. Automatic closing and radio remote controls are disabled.
(Example 2) If you have connected the self-controlled safety edge SOFA1 in closing, it is possible to make the following connections:
- set TM=MAX;
- connect opening and closing limit switches N.C.
contacts to terminals 0-11-12:
- select the opening control by means of DIP1=ON;
- select the direction of the movement by means of
DIP2=OFF;
- select the closing control by setting 6→4=OFF;
- set SO=OFF.
Page 19
41
IP2045EN - 2014-09-22
All rights related to this material are the exclusive property of Entrematic Group AB. Although the contents of this publication have been compiled with the greatest possible care, Entrematic Group AB cannot accept liability for any damage that might arise from errors or omissions in this publication. We reserve the right to make modifications without prior notice. No part of this publication may be copied, scanned, adapted or modified without prior permission in writing from Entrematic Group AB.
Page 20
IP2045EN - 2014-09-22
Entrematic Group AB
Lodjursgatan 10 SE-261 44, Landskrona Sweden www.ditecentrematic.com
Loading...