Entre Matic Ditec DAB105 Technical Manual

Page 1
Ditec DAB105
Swing doors
(translation of the original instructions)
www.entrematic.com
IP2159EN
Technical Manual
Page 2
IP2159EN - 2017-06-12
Contents
Key
Subject Page
1. General safety precautions 3
2. General safety precautions for the user 4 Declaration of incorporation of partly completed machinery 5
6
3. Technical specifications 7
4. Standard installation 8
5. Dimensions 9
6. Main components 10
7. Installation 11
7.1 Preliminary checks 11
7.2 General information 11
7.3 Installation examples 12
7.4 Removing the cover 12
8. Automation with articulated arm DAB805PSA 13
8.1 Automation preparation and fastening 13
8.2 Fixing the arm 16
8.3 Assembling the left-hand articulated arm 16
9. Automation with articulated arm DAB805PSAF 17
9.1 Automation preparation and fastening 17
9.2 Fixing the arm 20
10. Automation with sliding arm DAB805PLA 21
10.1 Automation preparation and fastening 21
10.2 Fixing the sliding arm 25
10.3 Fixing the door stop 26
11. Connecting to the electricity supply 27
12. Starting up the door 28
13. DAB105CU Electrical connections 29
13.1 Commands 29
13.2 Outputs and accessories 30
13.3 Adjustments 31
14. Pre-configured parameters 33
15. Door requisites for Low Energy use 34
16. Example of an application with a standard automation 35
17. ESE extension unit DAB905ESE (optional) 36
17.1 Commands 36
17.2 Outputs and accessories 38
17.3 Adjustments 38
17.4 Advanced settings available on the control panel version indicated, or subsequent versions 39
18. DAB905ESA extension unit 40
18.1 Commands 40
18.2 Outputs and accessories 41
18.3 Adjustments 42
19. Example of an application with optional extension units 43
20. Parallel and interlocked automations 43
21. Electrical start-up 47
22. Routine maintenance plan 47
23. Troubleshooting 48
24. Signs 49
i
This symbol indicates instructions or notes regarding safety, to which special attention must be paid.
This symbol indicates useful information for the correct functioning of the product.
This symbol advises you to contact the Technical Service.
Page 3
IP2159EN - 2017-06-12
1. General safety precautions
This installation manual is intended for qualified personnel only.
Installation, electrical connections and adjustments must be performed in accordance with Good Working Methods and in compliance with the present standards. Read the instructions carefully before installing the product. Incorrect installation could be dangerous.
The packaging materials (plastic, polystyrene, etc.) should not be discarded in the envi-
ronment or left within reach of children, as they are a potential source of danger. Before installing the product, make sure it is in perfect condition. Do not install the product in explosive areas and atmospheres: the presence of inflammable gas or fumes represents a serious safety hazard. Before installing the motorisation device, make all the necessary structural modifications to create safety clearance and to guard or isolate all the crushing, shearing, trapping and general hazardous areas. Make sure the existing structure is up to standard in terms of strength and stability. The mo­torisation device manufacturer is not responsible for failure to observe Good Working Methods when building the frames to be motorised, or for any deformations during use. The safety devices (photocells, safety edges, emergency stops, etc.) must be installed taking into account the applicable laws and directives, Good Working Methods, installation premises, system operating logic and the forces developed by the motorised door.
The safety devices must protect the crushing, shearing, trapping and general hazardous
areas of the motorised door. Display the signs required by law to identify hazardous areas. Each installation must bear a visible indication of the data identifying the motorised door. When requested, connect the motorised door to an effective earthing system that complies with current safety standards. During installation, maintenance and repair operations, cut off the power supply before opening the cover to access the electrical parts. The automation protection casing must be removed by qualified personnel only.
The electronic parts must be handled using earthed antistatic conductive arms. The manu-
facturer of the motorisation declines all responsibility if component parts not compatible with safe and correct operation are fitted. Only use original spare parts when repairing or replacing products. The installer must supply all information on the automatic, manual and emergency operation of the motorised door, and must provide the user with the operating instructions.
All the rights concerning this material are the exclusive property of Entrematic Group AB. Although the contents of this publication have been draw n up with the greatest care, Entrematic Group AB cannot be held responsible in any w ay for any dam­age caused by mistakes or omissions in this publication. We reserve the right to make changes without prior notice. Copying, scanning or changing in any way is expressly forbidden unless authorised in writing by Entrematic Group AB.
Page 4
IP2159EN - 2017-06-12
These precautions are an integral and essential part of the product and must be supplied
to the user. Read them carefully since they contain important information on safe installation, use and maintenance. These instructions must be kept and forwarded to all possible future users of the system. This product must only be used for the specific purpose for which it was designed. Any other use is to be considered improper and therefore dangerous. The manufacturer cannot be held responsible for any damage caused by improper, incorrect or unreasonable use. Avoid operating in the proximity of the hinges or moving mechanical parts. Do not enter within the operating range of the motorised door or gate while it is moving. Do not obstruct the motion of the motorised door or gate, as this may cause a dangerous situation. The motorised door or gate may be used by children over the age of 8 and by people with reduced physical, sensorial or mental abilities, or lack of experience or knowledge, as long as they are properly supervised or have been instructed in the safe use of the device and the relative hazards. Children must be supervised to make sure they do not play with the device, nor play/remain in the sphere of action of the motorised door or gate. Keep remote controls and/or any other command devices out of the reach of children, to avoid any accidental activation of the motorised door or gate. In the event of a product fault or malfunction, turn off the power supply switch. Do not attempt to repair or intervene directly, and contact only qualified personnel. Failure to comply with the above may cause a dangerous situation. Any repairs or technical interventions must be carried out by qualified personnel. Cleaning and maintenance work must not be carried out by children unless they are supervised. To ensure that the system works efficiently and correctly, the manufacturer’s indications must be complied with and only qualified personnel must perform routine maintenance on the mo­torised door or gate. In particular, regular checks are recommended in order to verify that the safety devices are operating correctly. All installation, maintenance and repair work must be documented and made available to the user. Only lock and release the door wings when the motor is switched off. Do not enter within the operating range of the wing.
To dispose of electrical and electronic equipment correctly, users must take the product to special “recycling centres” provided by the municipal authorities.
2. General safety precautions for the user
Page 5
IP2159EN - 2017-06-12
Declaration of incorporation of partly completed machinery
We: Entrematic Group AB Lodjursgatan 10 SE-261 44 Landskrona Sweden
declare under our responsibility that the following types of equipment:
Ditec DAB105
comply with the following directives:
2014/30/EU Electromagnetic Compatibility Directive (EMCD) 2006/42/EC Machinery Directive (MD) for the following essential health and safety requirements: 1.1.2, 1.1.3, 1.2.1,
1.2.3, 1.2.4, 1.2.6, 1.3.2, 1.3.4, 1.5.1, 1.5.2, 1.5.3, 1.5.8, 1.5.9, 1.5.10, 1.5.11, 1.6.3, 1.7.3, 1.7.4
Technical documentation for safe integration supplied.
Harmonised European standards which have been applied:
EN 60335 -1:2012 EN 61000 -6-2:2005 EN 61000 -6-3:2007+A1:2011 EN ISO 13849 -1:2008 EN 16005:2012 EN 60335-2-103:2003+A11:2009
Other standards or technical specifications, which have been applied:
BBR BVL IEC 60335-1: 2010 ed.5 IEC60335-2-103:2002 ed.1+2011 ed.2.1 EN1634-1:2008
CE type examination or certificate issued by a notified or competent body (for the full address, contact Entrematic Group AB) for the equipment:
SC0250-14
The production process aims to guarantee that the equipment complies with the technical documentation. The production process is regularly assessed by an independent body.
The equipment must not be put into service until the final door system installed has been declared compliant with the Machinery Directive 2006/42/EC by the installer.
Person in charge of technical data sheet:
Matteo Fino E-mail: matteo.fino@entrematic.com
Entrematic Group AB Lodjursgatan 10 SE-261 44 Landskrona Sweden
Place Date Signature Position Landskrona 2017-05-02 Matteo Fino Entrance Automation President
g
ttttttteo
F
inoo
o
Page 6
IP2159EN - 2017-06-12
Revisions
Page Revision 2016-05-05 → 2017-06-12
7 DAB805PLA arm inertia data item
11 "Fixing requisites" paragraph added
17 Modified dimensions for Y arm extension distance
25 Slide guide dimension
29 GND-OPD description
32 DIP1 description
32 Description of alarm 1
38 Description of the battery functions
38 Trimmer description
39 Paragraph for advanced settings (increased thrust force on closure / management of electric lock power supply)
The following pages have been revised:
Page 7
IP2159EN - 2017-06-12
3. Technical specifications
DAB105
Power 100-240V~ +10/-15% 50/60 Hz
Consumption max. 75W
Power supply for accessories 24V
400 mA max.
Power supply fuse F1-F2 2xT6.3A 250 V
Opening time min. 3s / 0°-80°
max. 6s / 0°-80°
Closing time min. 3s / 90°-10°
max. 6s / 90°-10°
Max. inertia (J / kg2)
Inertia J = door weight x (door width)
2
3
DAB805PSA/PSAF: 45kg m2 DAB805PLA: 33 kg m
2
-
50
100
150
200
250
0,7 0,8 0,9 1,0 1,1 1,2
DOOR WEIGHT [kg]
DOOR WIDTH [m]
DAB805PSA/PSAF
DAB805PLA
-
1
30 50 70 90 110 130 150 170 190 200
2
3
4
5
6
7
OPSP/CLSP TRIMMER POSITION
DOOR WEIGHT [kg]
OPSP/CLSP TRIMMER
7
4
5
62
3
1
Type of operation Motor opening
Spring-plus-motor closure
Fire barriers Applied using the arm DAB805PSAF
Maximum wing weight (see inertia graph)
150 kg DAB805PLA 200 kg DAB805PSA
Door wing width 700 ÷ 1200 mm
Minimum number of manoeuvres in AVERAGE conditions of use
1,000,000 cycles
Temperature min. -20°C max. +45°C
Degree of protection IP20 (FOR INTERNAL USE ONLY)
DOOR WEIGHT [kg]
DOOR WIDTH [m]
DOOR WEIGHT [kg]
OPSP/CLSP TRIMMER POSITION
OPSP/CLSP TRIMMER
Page 8
IP2159EN - 2017-06-12
4. Standard installation
Ref. Code Description
1 DAB105 Electro-mechanical actuator
2 Control panel
3 DAB805PSA-PSAF
DAB805PLA DAB805PLAT DAB805PLAB
Articulated movement arm (DAB805PSAF for applications on fire barriers) Sliding movement arm Movement arm with three levers Sliding movement arm (break-out/anti-panic)
4 Opening sensor
5 COM400MHB
COM400MKB
Function selector switch
6 Command button
A Connect the power supply to a type-approved omnipolar switch, with a contact opening distance of at
least 3 mm (not supplied). Connection to the mains must be via an independent channel, separate from the connections to the control and safety devices.
5
6
1
2
3
A
4
Page 9
IP2159EN - 2017-06-12
5. Dimensions
75
Ø7 (6x)
50
23 (2x)
Ø18 (6x)
57 633
712
133
22
238
34
Ø7 (6x)
63
131
34 3838
7518 18
720
8
1
/
4"
1
11
/
16"
30 mm
210 mm
Page 10
10
IP2159EN - 2017-06-12
6. Main components
Ref. Code Description
1 Base plate
2 Gearmotor
3 DAB105CU Control panel
4 Power
5 End stop
6 Upper head
7 Lower head
8 Casing
9 DAB905ESE
DAB905ESA
Safety and pulse extension card (optional) Extension card for safety functions (optional)
10 Cable fastener
11 Cable transit slits
12 DAB905BAT Battery kit
13 Encoder
14 ON/OFF/HOLD OPEN switch
15
DAB805SE2 DAB805SE5 DAB805SE7
DAB805SE5F
Shaft extension kit 20mm 50mm 70mm 50mm
DAB805SE2 DAB805SE5 DAB808SE7 DAB805SE5F
1
11
3
6
6
8
10
1211
7
9
4
2
13
5
14
15
Page 11
11
IP2159EN - 2017-06-12
7. Installation
7.1 Preliminary checks
7.2 General information
The given operating and performance features can only be guaranteed with the use of DITEC Entrematic accessories and safety devices. Unless otherwise specified, all measurements are expressed in mm.
Check the stability and weight of the door wing. Make sure it moves smoothly, without any friction (reinforce the frame if necessary). Any “door closers” must be removed or completely annulled.
Once you have made the slits for the cables to pass through, check the edges and smooth them if they are sharp, as they could damage the cables.
To improve the degree of safety and the protection against vandalism, install the automation access inside the building if possible.
• Make sure the ambient temperature falls within the parameters indicated in the “Technical specifications” paragraph.
• Before you begin the installation, make sure the mains power supply is not connected.
• Check that the door wings and wall are adequately reinforced in the fixing points.
• Unpack the automation and make sure both it and its components are in good condition.
• Check the door wings have been built with suitable materials, and that there are no sharp corners. Any protruding parts must not create potential hazards. Sharp glass edges must not come into contact with other glass parts. You are advised to use tempered or stratified glass.
• Make sure there is no risk of getting trapped between the moving parts and the adjacent fixed ones when the door is opening. The following distances are considered sufficiently safe to avoid trapping the body parts indicated:
- for the fingers: more than 25mm or less than 8mm
- for the head: more than 200mm
- for the feet: more than 50mm
- for the whole body: more than 500mm
The DAB105 automation for swing doors can use articulated or sliding arms to open the doors. The door is closed by a spring system, combined with the force of the motor. The spring is pre-tensioned at 210°.
Do not alter the pre-tensioning of the spring unless it is strictly necessary.
i
Fixing requisites
Material Minimum requisites for the wall profile
Steel 5mm (reinforce with threaded rivets if the thickness is less than this)
Aluminium 6mm (reinforce with threaded rivets if the thickness is less than this)
Reinforced concrete min. 50mm from the lower side
Wood 50mm
Brick Anchor plug min. M6X85 UPAT PSEA B10/25 - min. 50mm from the lower side
Page 12
12
IP2159EN - 2017-06-12
7.4 Removing the casing
Remove the casing [8] by loosening the screw [Z]. NB: the product label is in the position shown in the figure below.
Z
7.3 Installation examples
The DAB105 automation for swing doors can be installed on one swing door, on two swing doors, or on two swing doors with a double exit.
DAB805CMP
DAB805CMP
DAB805SE2
Page 13
13
IP2159EN - 2017-06-12
Apertura a sinistra
• Prepare the set-up for fixing the automation to the wall, respecting the measurements shown in the figures above (with reference to the hinge axis).
• Drill a hole in the door wing, in line with the fixing for the articulated arm.
• If necessary, use the DAB805SE2/SE5/SE7 extensions to increase the X measurement between the automation and the arm fixing points.
8. Automation with articulated arm DAB805PSA
8.1 Automation preparation and fastening
Before fixing the base plate [1], make holes for the cables to pass through.
i
11
==
Ø 16
Use the articulated arm for doors that open outwards (as seen from the automation side).
300
max
~400
107X
OPENING
Left-hand opening
X+16 75
34
31
264 248 35
633
Shaft extension X
/ 30
DAB805SE2 50
DAB805SE5 80
DAB805SE7 100
Page 14
14
IP2159EN - 2017-06-12
• Fix the automation in place using the screws [A]; tighten them firmly and evenly.
• Move the gearmotor sideways by loosening the 4 screws [B], so the base plate can be fixed in place.
• Fix the base plate with the screws [A].
• Return the motor to its original position.
• Fix the motor by tightening the 4 screws [B] supplied, in the sequence shown in the figure.
Respect the measurement between the hinge and the gearmotor shaft output [C], as shown in the figure.
i
210
2
4
1
3
B
x4
C
6 mm
A
A
A
A
1
6 mm
2
A
A
B
Page 15
15
IP2159EN - 2017-06-12
Apertura a destra
• Fix the automation in place using the screws [A]; tighten them firmly and evenly.
• Move the gearmotor sideways by loosening the 4 screws [B], so the base plate can be fixed in place.
• Fix the base plate with the screws [A].
• Return the motor to its original posi­tion.
• Fix the motor by tightening the 4 screws [B] supplied, in the sequence shown in the figure.
Respect the measurement be­tween the hinge and the gearmo­tor shaft output [C], as shown in the figure.
i
Right-hand opening
A
A
A
A
B
A
A
1
2
6 mm
210
1
3
2
4
C
B x4
6 mm
X+16
75
34
31
26 424835
633
• Prepare the set-up for fixing the automation to the wall, respecting the measurements shown in the figures above (with reference to the hinge axis).
• Drill a hole in the door wing, in line with the fixing for the articulated arm.
• If necessary, use the DAB805SE2/SE5/SE7 extensions to increase the X measurement between the automation and the arm fixing points.
Page 16
16
IP2159EN - 2017-06-12
• Move the door manually to check it opens and closes correctly, without any friction.
• With the door closed, fix the arm to the arm support [A] on the automation.
• Fix the bracket [B] to the door wing, forming an angle of 90°. Lengthen or shorten the arm [C] if necessary.
• In the case of automations with left-hand opening, you must invert the assembly of the articulated arm as shown in the figure.
8.3 Assembling the left-hand articulated arm.
8.
2 Fixing the arm
A
C
B
90°
16 Nm
+/-
210
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
A
B
210264
NB: open the door slightly and tighten the screw of the arm support seat [A] at 16 Nm (as shown in the figure). If a torque wrench is not available, use a hexagon wrench of the type shown in the figure, gripping it on the long side and tightening very firmly.
Page 17
17
IP2159EN - 2017-06-12
Apertura a sinistra
Before fixing the base plate [1], make holes for the cables to pass through.
i
11
==
Ø 16
Y 335
107X
OPENING
Y Arm expansion
0-100 /
100-215 DAB805TFL
215-305 DAB805TFS
DAB805TKJ
• Prepare the set-up for fixing the automation to the wall, respecting the measurements shown in the figures above (with reference
to the hinge axis).
• Drill a hole in the door wing, in line with the fixing for the articulated arm.
• If necessary, use the DAB805SE5F extension to increase the X measurement between the automation and the arm fixing points.
Shaft extension X
/ 48
DAB805SE5F 98
9. Automation with articulated arm DAB805PSAF
(for applications on fire barriers)
9.1 Automation preparation and fastening
X+16 75
34
31
264 248 45
633
Left-hand opening
Page 18
18
IP2159EN - 2017-06-12
• Fix the automation in place using the screws [A]; tighten them firmly and evenly.
• Move the gearmotor sideways by loosening the 4 screws [B], so the base plate can be fixed in place.
• Fix the base plate with the screws [A].
• Return the motor to its original position.
• Fix the motor by tightening the 4 screws [B] supplied, in the sequence shown in the figure.
Respect the measurement between the hinge and the gearmotor shaft output [C], as shown in the figure.
i
210
2
4
1
3
B
x4
C
6 mm
A
A
A
A
1
6 mm
2
A
A
B
Page 19
19
IP2159EN - 2017-06-12
Apertura a destra
• Fix the automation in place using the screws [A]; tighten them firmly and evenly.
• Move the gearmotor sideways by loosening the 4 screws [B], so the base plate can be fixed in place.
• Fix the base plate with the screws [A].
• Return the motor to its original posi­tion.
• Fix the motor by tightening the 4 screws [B] supplied, in the sequence shown in the figure.
Respect the measurement be­tween the hinge and the gearmo­tor shaft output [C], as shown in the figure.
i
Right-hand opening
A
A
A
A
B
A
A
1
2
6 mm
210
1
3
2
4
C
B x4
6 mm
X+16 75
34
31
26 4
24845
633
• Prepare the set-up for fixing the automation to the wall, respecting the measurements shown in the figures above (with reference to the hinge axis).
• Drill a hole in the door wing, in line with the fixing for the articulated arm.
• If necessary, use the DAB805SE5F extension to increase the X measurement between the automation and the arm fixing points.
Page 20
20
IP2159EN - 2017-06-12
9.2 Fixing the arm
A
C
B
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
25 Nm
A
210
90°
+/-
DAB805TFL
Kit prolungamento braccio
DAB805TFS
DAB805TKJ
• Move the door manually to check it opens and closes correctly, without any friction.
• With the door closed, fix the arm to the arm support [A] on the automation.
• Fix the bracket [B] to the door wing, forming an angle of 90°. If necessary, lengthen (using the arm lengthening kit) or shorten the arm [C].
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
25Nm
A
A
NB: open the door slightly and tighten the screw of the arm support seat [A] at 25 Nm (as shown in the figure). If a torque wrench is not available, use a hexagon wrench of the type shown in the figure, gripping it on the long side and tightening very firmly.
A
B
21026 44
Arm extension kit
Page 21
21
IP2159EN - 2017-06-12
Apertura a sinistra
10. Automation with sliding arm DAB805PLA
Before fixing the base plate [1], make holes for the cables to pass through.
i
11
==
Ø 16
Use the sliding arm for doors that open inwards (as seen from the automation side).
• Prepare the set-up for fixing the automation to the wall, respecting the measurements shown in the figures above (with reference to the hinge axis).
• Drill a hole in the door wing, in line with the fixing for the sliding arm.
• If necessary, use the DAB805SE2/SE5/SE7 extensions to increase the X measurement between the automation and the arm fixing points.
OPENING
30 107X
10.1 Automation preparation and fastening
Shaft extension X
/ 50
DAB805SE2 70
DAB805SE5 100
DAB805SE7 120
X+16 7530
31 633
264
34
Left-hand opening
Page 22
22
IP2159EN - 2017-06-12
• Fix the automation using the screws [A], tightening them firmly.
• Loosen the screws [B] that hold the motor in place. Remove the motor. Fix the base plate with the 2 screws [A].
• Rotate the motor 180°, as shown in the figure.
A
A
A
A
A
B
A
B
180°
a
210
6 mm
C
1
3
4
2
Bx4
• Fix the motor by tightening the screws [B] supplied, in the sequence shown in the figure.
Respect the measurement between the hinge and the gearmotor shaft output [C], as shown in the figure.
i
Page 23
23
IP2159EN - 2017-06-12
Apertura a destra
X+16 7530
31633
26 4
34
• Fix the motor by tightening the screws [B] supplied, in the sequence shown in the figure.
A
A
A
A
• Prepare the set-up for fixing the automation to the wall, respecting the measurements shown in the figures above (with reference to the hinge axis).
• Drill a hole in the door wing, in line with the fixing for the sliding arm.
• If necessary, use the DAB805SE2/SE5/SE7 extensions to increase the X measurement between the automation and the arm fixing points.
Right-hand opening
Page 24
24
IP2159EN - 2017-06-12
• Loosen the screws [B] that hold the motor in place. Remove the motor. Fix the base plate with the 2 screws [A].
• Rotate the motor 180°, as shown in the figure.
• Fix the motor by tightening the screws [B] supplied, in the sequence shown in the figure.
Respect the measurement between the hinge and the gearmotor shaft output [C], as shown in the figure.
i
A
A
B
B
180°
210
C
1
3
4
2
Bx4
6 mm
Page 25
25
IP2159EN - 2017-06-12
• Move the door manually to check it opens and closes correctly, without any friction.
• With the door closed, fix the arm to the arm support [A] on the automation.
• Fix the guide [B] to the door wing, cutting off the excess part if necessary.
210
920
A
B
10.2 Fixing the sliding arm
min 700
max
120
210
4 mm
A
B
F
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
16 Nm
NB: open the door slightly and tighten the screw of the arm support seat [A] at 16 Nm (as shown in the figure). If a torque wrench is not available, use a hexagon wrench of the type shown in the figure, gripping it on the long side and tightening very firmly.
Page 26
26
IP2159EN - 2017-06-12
Apertura a sinistra Apertura a destra
A
A
B
B
C
B
B
180°
10.3 Fixing the door stop
In the case of installations with a sliding arm, proceed as follows:
• Remove the limit switches [B]. Loosen the door stop [A] and move it to the unknurled part of the drive arm.
• Rotate the limit switches by 180°. Reposition them on the gearmotor as shown in the figure.
• Reposition the door stop [A] as shown in the figure.
• Move the door manually to check it opens and closes correctly, without any friction.
• Adjust the internal open door stop [F], as indicated in paragraph 10.3.
The door stop [A] must be fitted as close to the closure limit switch [B] as possible.
i
The following operations must be carried out with the arm installed and the door closed.
A
B
B
C
B
B
180°
i
Left-hand opening Right-hand opening
Page 27
27
IP2159EN - 2017-06-12
11. Connecting to the electricity supply
Before connecting the power supply, make sure the plate data correspond to that of the mains power supply. An omnipolar disconnection switch with a contact opening distance of at least 3 mm must be fitted on the mains supply. Check there is an adequate residual current circuit breaker and overcurrent cut-out upstream of the electrical system. Use a H05RN-F 3G1,5 or H05RR-F 3G1,5 type electric cable. In the section outside the automation, the connection to the mains power supply must be via an independent channel separate from the connections to the control and safety devices. Make sure there are no sharp edges that may damage the power supply cable.
0
1
= Yellow/Green
10AT
L = Brown
N = Blue
Yellow/Green
Brown
Blue
Page 28
28
IP2159EN - 2017-06-12
12. Starting up the door
Close the door by rotating the SPTE trimmer to 0°.
Place the door in the closed position.
Rotate the SPTE trimmer on the control panel to 0° (if it is not already in this position).
Turn on the power supply. Gradually rotating the SPTE trimmer clockwise, the door opens electrically. Slowly bring it to the required open position, plus about 15 mm.
SPTE
SPTE
Loosen the door stop [A]. Move it to the unknurled part of the arm. Insert the door stop [A] in the groove, as close as possible to the opening limit switch [B]. If necessary, make a fine adjustment with the screw [C] on the opening limit switch.
A
A
A
C
B
SPTE
A
C
B
Page 29
29
IP2159EN - 2017-06-12
13. Electrical connections DAB105CU
13.1 Commands
Contact Function / Accessory Description
1-2 GND-IIMP
NO OPENING - INNER SIDE Contact closure activates the opening operation.
The contact is always active if the ON-OFF-HOLD OPEN switch is present. The contact is controlled by the COM400MHB/MKB function selector switch (if present).
1-3 GND-XIMP
NO OPENING - OUTER SIDE,
MANAGED BY THE ON­OFF-HOLD SWITCH
Contact closure activates the opening operation. The contact is only active if the ON-OFF-HOLD OPEN switch is present. DO NOT USE contact 1-3 or the ON-OFF-HOLD OPEN switch if the COM400MHB/MKB func­tion selector switch is installed.
1-4 GND-OPD
NO Overhead presence detector
(OPD), frame mounted
Overhead presence detector (OPD), frame mounted When an OPD sensor is mounted on the frame or operator cover just above the swing side of the door, it will–when activated–either keep the door open or closed. The sensor is not active during opening and closing.
• a closed door will not open, if the OPD detects activity in the field.
• an open door will not close, if the OPD detects activity in the field.
• during opening, the door will continue to open, even if the OPD detects activity in the field.
• during closing, the door will continue to close, even if the OPD detects activity in the field.
• the OPD is not active in program mode OFF, manually opened door or during battery operation (Power Save Mode).
1-5 GND-LOUT
DO NOT USE
Fix the label to the terminal board, taking care to apply it in the correct direction (see the figure above).
612345
678
12345
12 345678910111213
612345
ON
SPTE OPSP CLSP POAS CLTQ
LRN
HOT
PAG
MAT
SOS
ARM1
ARM2
LED
12345
ON/OFF/HOLD OPEN
ENCODER
NON USAR
E
SINCRONIZZAZIONE ANTE DOPPIE
NON USARE
GND
IIMP
XIMP
OPD
LOUT NON USARE
Apertura (controllata da ON/OFF HOLD OPEN)
Rilevamento di presenza / pedana a pavimento
Apertura
24 V
+
-
MOTORE
i
Optional extension units can be connected to the DAB105CU control panel: the DAB905ESE extension unit, or the DAB905ESA one, or both, depending on the required functions.
SYNCHRONISATION OF DOUBLE DOOR WINGS
ON/OFF/HOLD OPEN
DO NOT USE
Motion sensor / mat safety
DO NOT USE
Opening (controlled from ON/OFF HOLD OPEN)
Opening
DO NOT USE
MOTOR
Page 30
30
IP2159EN - 2017-06-12
Contact Function / Accessory Description
LRN
Automatic self-learning. When the door is started up, and on every spring tensioning variation, CLTQ trimmer variation, replacement of the extension units (DAB905ESE-DAB905ESA) or replacement of the electric lock / electic strike, it is necessary to perform an automatic self-learning operation.
By pressing the LRN button, the door launches an opening/closing operation for the automatic self-learning of the positions and of the opening/closing stops.
During the closure phase, the spring pushes the door to acquire the door wing weight.
By pressing the LRN button once, the door will open after 2 seconds. Press the LRN button twice to open the door immediately.
In the case of double doors, the automatic self-learning operation must be carried out first on the MASTER door and then on the SLAVE door. The doo rs can be configured separately before connec ting them with the synchronis ation cable. In the case of door wing overl ap and separate configurations, the MA STER door must be kept open until the SLAVE door has completed its own self-learning procedure.
Make sure the door is fully closed. Move away from the door as soon as you have pressed the LRN button. The door has no safety settings during the automatic self-learning procedure. The door could suddenly slam shut.
DO NOT intervene during the self-learning procedure.
i
i
13.2 Outputs and accessories
Output Description
+24V DC
GND
1 ... 6
Output for the power supply to the accessories 24V 400 mA max. NB: the maximum absorption of 400 mA corresponds to the sum of all the accessories installed.
MOTOR
Motor connection
ENCODER
Encoder connection
ON/OFF
DO NOT USE
SYNC
Connection for cable for synchronisation between two swing doors. For details about the operation, refer to the “SYNCHRONISED DOORS” chapter.
ON/OFF/HOLD
Connection of the ON/OFF/HOLD switch
ON The IIMP and XIMP opening contacts are enabled. OFF The XIMP opening contact is excluded. HOLD OPEN Door open.
MOTION SENSOR
DO NOT USE
Page 31
31
IP2159EN - 2017-06-12
13.3. Adjustments
Trimmer
Trimmer Description SPTE
210°
Door start-up
The SPTE trimmer is used to make adjustments for the acquisition of the opening/closing stops when the door starts up.
Spring tension adjustment
The spring pre-tensioning is factory-set at 210°.
To reduce/increase the pre-tensioning:
Loosen and remove the door stop (see chapter 10)
Rotate the trimmer clockwise until the door opens at 45°
Loose the fixing screw of the actuation arm
Move the door towards the open position to reduce the spring tension
Move the door towards the closed position to increase the spring tension (this operation is only possible if the
spring has a pre-load less than the factory setting (210°) and no more than 210°).
Tighten the fixing screw of the actuation arm
Rotate the trimmer to minimum
Open the door to the required open position plus about 15 mm, by rotating the trimmer clockwise
Fix the door stop. For the fine adjustment, refer to chapter 10.
Rotate the trimmer to minimum
Press the LRN button to begin the door self-learning procedure
OPSP Adjustment of the opening speed time (from 3 to 6 s).
Rotate the trimmer clockwise to increase the opening speed. ATTENTION. The opening and closing speeds are regulated according to the weight of the wing, as shown in the following diagram.
-
1
30 50 70 90 110 130 150 170 190 200
2
3
4
5
6
7
OPSP/CLSP TRIMMER POSITION
DOOR WEIGHT [kg]
OPSP/CLSP TRIMMER
7
4
5623
1
CLSP Adjustment of the closing speed time (from 3 to 6 s).
Rotate the trimmer anticlockwise to reduce the closing speed. ATTENTION. The opening and closing speeds are regulated according to the weight of the wing, as shown in the following diagram.
-
1
30 50 70 90 110 130 150 170 190 200
2
3
4
5
6
7
OPSP/CLSP TRIMMER POSITION
DOOR WEIGHT [kg]
OPSP/CLSP TRIMMER
7
4
5623
1
POAS Adjustment of the servo-assisted movement during the manual opening of the door.
With the trimmer at its minimum, the door is not servo-assisted. By rotating the trimmer clockwise, the motor increases the servo-assistance when the door is opened manually. The range of the POAS is depending on the spring pre-tension.
CLTQ Closing force adjustment
With the trimmer at its minimum, the door closes with the force of the spring. By rotating the trimmer clockwise, the motor increases the closing force. Increase the closing force on doors installed in environments with different pressure levels or subject to strong gusts of wind.
HOT Adjustment of the automatic closing time (from 1.5 to 30 s)
Adjust the time that passes between the end of the opening operation and the start of the closing operation. The count begins with the door fully open.
The maximum pre-tensioning of the spring is 210°. A greater tension could damage the spring or overheat the motor.
i
Page 32
32
IP2159EN - 2017-06-12
Dip-switches
DIP Description OFF
ON
DIP1 - PAG Push & Go
The manual pushing of the door activates an automatic opening operation. When the door is closed, a closure thrust is main­tained by the motor or the spring. Push and Go is not active in program se­lector setting DOOR CLOSED.
Disabled Enabled
DIP2 - MAT DO NOT USE DIP3 - SOS Obstacle during opening Stall
If an obstacle is detected during the open­ing operation, the door continues to push and then closes after the time lapse set with the HOT trimmer.
Stop If an obstacle is detected during the open­ing operation, the door stops its move­ment and closes after 2 s.
DIP4 - ARM1
Selection of the arm type. See the following table.
DIP5 - ARM2
Articulated arm DAB805PSA-PSAF
(FACTORY SETTING)
DIP4 OFF
DIP5 OFF
Sliding arm DAB805PLA-PLAB 3-lever arm DAB805PLAT
DIP4 ON DIP5 OFF
The factor y configuration is set for an articulated arm. To alter DIP4 and DIP5, disconnect the mains power supply. Select the arm type. Restore the power supply.
Signals
Alarms
ON OFF
FLASHING
LED
Normal operation No mains power supply Alarm (see the alarms table)
LED
CAUSE SOLUTION
(1) External short circuit on 24V .
Incorrect sensor detection
Check for short-circuiting or a damaged sen­sor
(2)
Faulty battery Replace the battery
(3)
Faulty control panel Replace the control panel
(4)
Encoder error Check the encoder cable.
Manually open and close the door, then check the automatic function. If the problem persists, replace the control panel.
(5)
Faulty blocking device Check for short-circuiting in the blocking
device Replace the blocking device
Faulty DAB905ESE unit Replace the DAB905ESE unit
(6)
Synchronisation cable not connected, or faulty
(parallel doors only)
Connect the cable
Replace the cable
(7)
SLAVE control panel faulty (parallel doors only) Check the frequency of the flashes on the
SLAVE LED, and adopt the necessary meas­ures on the basis of this table
(8)
Overheated motor Wait for the motor to cool down
(9)
Door blocked and repetitive command Activate and deactivate the command
i
Page 33
33
IP2159EN - 2017-06-12
14. Pre-configured parameters
The DAB105 automation has 10 groups of pre-configured system-loaded parameters. The group of parameters set in the factory corresponds to number 1. To modify the group of parameters:
1. Disconnect the batteries (if installed).
2. Disconnect the mains power supply.
3. Press the LRN self-learning button, and keep it pressed.
4. Enable the power supply - the LED will light up
3s 3s
Release the LRN self-learning button - the LED will switch off.
5. The LED flashes for a number of times corresponding to the number of the group of parameters (see the table).
6. Press the LRN button to pass to the next group of parameters after the set one. When you have reached the maximum limit of
the parameters, you will restart from number 1.
7. Press the LRN button until you reach the required group of parameters.
8. Disconnect the mains power supply.
9. When the mains power supply is reconnected, the automation will use the new group of parameters.
Parameter group
1 (default) 2 3 4 5 6 7 8 9 10
Time of door open contact 3-5 ESE card (a)
15 min endless 15 min 15 min 15 min 15 min 15 min 15 min 15 min 15 min
Battery use Energy
savings
Energy savings
Continuity
Energy savings
Energy savings
Energy savings
Energy savings
Energy savings
Energy savings
Continuity
Block mode with KILL command active
Blocked Blocked Blocked
Block managed by selector
Blocked Blocked Blocked Blocked
Block managed by selector
Blocked
Obstacle during closure (b)
Closure Closure Closure Closure Reversal Closure Closure Closure Closure Reversal
Motion sensor in­stalled on synchro­nised doors. (c)
Separate detection
Separate detection
Separate detection
Separate detection
Separate detection
Common Limit
Separate detection
Separate detection
Separate detection
Separate detection
Block attempt on closure (d)
Enabled Enabled Enabled Enabled Enabled Enabled Disabled Enabled Enabled Enabled
O/C command opening/closing (e)
TWO-WAY mode
TWO-WAY mode
TWO-WAY mode
TWO-WAY mode
TWO-WAY mode
TWO-WAY mode
TWO-WAY mode
TWO-WAY / DOOR CLOSED / ONE-WAY mode
TWO-WAY mode
TWO-WAY mode
Configuration of emergency closure contact (KILL)
NO NO NO NO NO NO NO NO NC NO
NOTES: (a) If the door stays open following an O/C open command, the control panel will launch a closure command after 15 minutes of inactivity. (b) If set in “CLOSURE” mode, the automation will stop if an obstacle is detected. If set in “REVERSAL” mode, the automation will re-open. It continues to attempt the closure operation until the obstacle is removed. With parameters set on 1 (factory setting), if there is a problem with block coupling during the closure phase, the door will attempt to enable the coupling twice in
automatic mode, then once more in manual mode. This function can be disabled (see Parameter 7). (c) In the case of synchronised doors, the motion sensor can intervene independently on each door, or simultaneously. (d) If there is a problem with block coupling during the closure phase, the door will again close and attempt to enable the coupling. (e) With the ON/OFF/HOLD switch, the O/C command is always active except in the "HOLD - Door open" position. With the program selector, the O/C command usually functions in TWO-WAY mode. With Parameter 8 selected, the O/C command functions in TWO-WAY / ONE-WAY / DOOR CLOSED mode.
Page 34
34
IP2159EN - 2017-06-12
Door wing weight [kg]
50 60 70 80 90
Door wing length [mm]
750
3,0 s (3,0 s) 3,0 s (3,2 s) 3,0 s (3,2 s) 3,0 s (3,3 s) 3,5 s (3,5 s)
850
3,0 s (3,1 s) 3,0 s (3,1 s) 3,5 s (3,2 s) 3,5 s (3,4 s) 4,0 s (3,6 s)
1000
3,5 s (3,2 s) 3,5 s (3,4 s) 4,0 s (3,7 s) 4,0 s (4,0 s) 4,5 s (4,2 s)
120 0
4,0 s (3,8 s) 4,5 s (4,2 s) 4,5 s (4,5 s) 5,0 s (4,8 s) 5,5 s (5,1 s)
The DAB105 automation is factory supplied with the Low Energy setting enabled. If necessar y, adjust the OPSP and CLSP trimmers so that the opening and closing times are the same or longer than those indicated in the table in accordance with EN16005:2012 and ANSI 156.19 (the information in brackets refers to DIN 18650-2). The table shows the minimum opening times for opening of up to 80° and the minimum closing times for openings from 90° to 10°.
15. Door requisites for Low Energy use
Or modify the classifications as shown in the table.
1. Disconnect the batteries (if installed).
2. Disconnect the mains power supply.
3. Press the LRN self-learning button, and keep it pressed. Enable the power supply.
4. The LED will light up
3s 3s 3s
.
5. Release the LRN self-learning button - the LED will switch off.
6. The LED flashes as many times as the classification number (see table).
7. Press the LRN button to pass to the next classification number after the set one.
8. Press the LRN button until you reach the required classification.
9. Disconnect the mains power supply.
10. When the mains power supply is reconnected, the automation will use the new setting.
CLASSIFICATION 1 - Maximum performance (Default) 2 - Low energy
Standard / In accordance with DIN18650-2 (EN16005:2012)
Opening speed 3-6 s Automatic limit 1,69J
Closing speed 3-6 s Automatic limit 1,69J
Launch the automatic self-learning procedure (LRN button) after every parameter setting modification.
i
The maximum setting for the opening speed and closing speed is automatically limited to the value indicated in the table; conse­quently, the speed may only be reduced.
Page 35
35
IP2159EN - 2017-06-12
16. Example of an application with a standard control panel
PASS24 (XIMP)
ON/OFF/HOLD OPEN
PASS24
(XIMP)
DAB105
Double wings connection
Open command (IIMP)
ON/OFF/HOLD OPEN
Open command (IMP)
Page 36
36
IP2159EN - 2017-06-12
17. Extension unit DAB905ESE (optional)
There is a command extension card for managing the electric lock / electric strike, function selector, batteries, key selector switch and night-time closure.
17.1 Commands
Contact Function - Accessory Description
3
4
GND-OIMP
NO OUTER SIDE OPENING Contact for connection of external detection radar.
The closure of the contact activates an opening operation. NB: this command is only active with the COM400MKB-MHB function selector switch.
3
5
GND-O/C
NO STEP-BY-STEP The closure of the contact activates an opening operation. The door stays open until a new
command is given. If the door does not receive any command, it closes automatically after 15 minutes of inactivity. Automatic closing cannot be adjusted using the HOT trimmer; it is factory-set. The automatic closing time can be modified from 15 min to endless (∞), by altering the pre­configured parameters as explained in chapter 14. The opening/closing command only works in TWO-WAY mode. Modify the operating mode to CLOSED door or ONE-WAY opening, altering the pre-config­ured parameters as explained in chapter 14.
3
6
GND-KEY
NO KEY OPENING The closure of the contact activates an opening operation.
This command is always active, even when the COM400MHB/MKB function selector switch or ON-OFF-HOLD OPEN switch is installed. The automatic closure time is set to 5 s when the door is open regardless of HOT trimmer adjustment. Can be used for opening from night/CLOSED mode.
DAB905ESA
(optional)
DAB905ESE
(optional)
Torx T10
Long pin used for 2 Extension Unit
Short pin used for 1 Extension Unit only
5 mm nut driver
612345
678
12345
1 2 3 4 5 6 7 8 9 10 11 12 13
Fix the label to the terminal board, taking care to apply it in the correct direction (see the figure above).
-
+
12345
ON
+24 V DC
KILL
KEY
O/C
OIMP
GND
BATTERIE
12 345678910111213
OPEN
EXIT
OFF
UNL
KRST
Serratura elettrica / Incontro elettrico 12 V max 1,2 A 24 V max 600 mA
Apertura lato esterno
Passo passo
Apertura a chiave
Chiusura di emergenza
Reset chiusura di emer
genza
Porta sbloccata
Temporizzatore porta chiusa
J
i
(optional)
Torx T10
5 mm nut driver
(optional)
Long pin used for 2 Extension Unit
Short pin used for 1 Extension Unit only
BATTERIES
Closed door timer
Emergency closure reset
Key opening
Door released
Emergency closure
Step-by-step
Outer side opening
Electric lock / Electric strike
Page 37
37
IP2159EN - 2017-06-12
Contact Function - Accessory Description
3
7
GND-KILL
NO EMERGENCY CLOSURE
(FIRE BARRIERS)
The closure of the contact activates an emergency closure operation. This command is ac­tive in every situation, and has priority over every other command. When the contact has reopened (with JUMPER J=ON), the door resumes operating as set by the selector.
WARNING: if an EMERGENCY CLOSURE is activated, all the safety functions are ignored and the door closes. People or objects in the path of the door during the closing operation could suffer serious injury or damage.
This function is generally used to cut off a specific area in the case of a fire. NB: this command can be combined with an emergency button. The output contact can be changed from NO to NC by altering the pre-configured param­eters, as explained in chapter 13. The operation of the block during the emergency closure can be selected from the pre-set parameters explained in chapter 13. A panic bar can be installed in combination with a magnetic block on the fire barrier. In the event of a fire alarm or a power supply failure, the panic bar keeps the closed door blocked. In the case of escape routes, the panic bar can be manually released. Configure the relay contact of the DAB905ESA card, choosing parameter 11, 12 or 13 as explained in chapter 13.
3 7 GND-KILL
NO “NURSE & BED” FUNC-
TION
In installations with parallel doors, the “NURSE & BED” function can be enabled by con­necting a switch to contacts 3-7 on the SLAVE door control panel.
With 3-7 closed, opening of the MASTER door is enabled (NURSE function). With 3-7 open, opening of both doors is enabled (BED function).
3
7
GND-KILL
NO INTERLOCKED DOORS Applications with interlocked doors are possible. For the connections, see paragraph 21.1.
3 8 GND-JRST
NO EMERGENCY
OPENING
If JUMPER=ON, the panel makes an automatic reset after an emergency closure.
3
9
GND-UNL
NO DOOR RELEASED
SIGNAL
Contact for door released signal. The closure of the contact brings forward the opening operation when the electric lock / electric strike is fully released, within the time set by the delay time adjustment trimmer (max. 3 s).
3
10
GND-OFF
NO DOOR CLOSED Contact for connecting a closed door timer.
Page 38
38
IP2159EN - 2017-06-12
Output Description
+24V DC
GND
3 ... 13
Output for the power supply to the accessories 24V 400 mA max. NB: the maximum absorption of 400 mA corresponds to the sum of all the accessories installed.
12
Output for connecting an electric lock / electric strike. Select the type of electric lock / electric strike using DIP1. NOTE1: do not use electric locks / electric strikes with a reset feature. NOTE2: with DIP2 in OFF and no COM400 function selector switch (or the latter in two-way mode), output 1-2 is perma­nently powered so that the electric lock / electric strike can always open the door. If, on the other hand, you want to lock the door wing with the door closed, set the selector to one-way mode or make a jumper GND-EXIT (3-11). In this condi­tion, output 1-2 is powered throughout the operation (from opening until complete closure); for this reason, locks with mechanical reset cannot be used. With DIP2 in ON, the behaviour will be the same except for the fact that output 1-2 will always be unpowered in two-way mode and throughout the open/close operation in one-way mode”.
OPEN
EXIT
OFF
GND
3 ... 10 11 12
Output for connecting the function selector switch. If the function selector switch is on OFF, the Push and Go function is disabled. If a function selector switch is installed, disconnect the ON/OFF/HOLD switch (if present).
BATTERY
BATTERY KIT If no mains power supply is available, the batter y kit will guarantee operation in "energy-saving" mode. If no mains power supply is available, the door only operates with the key switch connected to 3 GND -6 KE Y. In “energy-saving” mode, the door can remain stationar y for up to a week while waiting for the KEY command. The following sensors are not active during “energy saving” operation:
-OPD motion sensor
-PIMP reversal safety contact
-PDET opening safety device In this mode (on automations connected in parallel), connect the batteries only to the MA STER automation fitted with DAB905ESE. By changing the pre-configured parameter group, you can set the battery kit to CONTINUITY mode. If no mains power supply is available, the door operates normally until the batteries are fully discharged. In this mode, on automations connected in parallel, connect the batteries on both automations equipped with DAB905ESE. NB: for charging purposes, the battery kit must be connected to the control panel at all times. A new kit with fully-charged batteries can usually open and close a door consecutively in CONTINUITY mode. If you want to check the battery kit is working correctly, set DIP5=ON. In the event of a battery alarm, the DAB105CU control panel LED will flash twice. An acoustic/light alarm signal can be connected to terminals 6-7-8 on the DAB905ESA card.
17.3 . Ad ju st ment s
17.2 Outputs and accessories
Trimmer
Trimmer Description
Adjustment of the opening delay time, from 0 s to 3 s. With DIP3=ON, the door release is active throughout the opening delay.
Dip-switches
DIP Description OFF
ON
DIP1 Power supply to the electric lock / electric
strike.
12 V max 500 mA 24 V max 250 mA
DIP2 Type of electric lock / electric strike.
DO NOT USE ELECTRIC LOCKS / ELEC­TRIC STRIKES WITH A RESET FEATURE.
Normal When it is powered, the door can be opened.
Anti-panic When it is unpowered, the door can be opened.
DIP3 Release Disabled Enabled during the time set by the delay time
adjustment trimmer.
DIP4 Electric lock / electric strike coupling Disabled Enabled
When it approaches the closing stop, the door increases its force/speed to ensure correct closure on the electric lock / electric strike.
DIP5 Battery test Disabled Enabled
Jumper
Description OFF
ON
J
Emergency closure reset Manual Automatic
For more information, refer to the COM400MKB-MHB selector manual.
i
Page 39
39
IP2159EN - 2017-06-12
17.4 Advanced settings available on the control panel version indicated, or subse­quent versions
Increased thrust force on closure when an electric lock is fitted
Management of electric lock / electric strike power supply
1. Disconnect batteries if any.
2. Disconnect the mains.
3. Press the LEARN BUTTON (LRN) and keep it depressed.
4. Connect the mains.
5. Watch the ERROR LED.
3s1s3s1s3s1s3s1s3s
6. Release the LEARN BUTTON after 5 flashes (LED is out).
7. Identify the current lock kick status:
The ERROR LED flashes an amount of short flashes that correspond to the status number. After a short pause the LED will repeat the status number and so on.
8. Changing the status:
If you push the LEARN BUTTON once, the status number will increase. When you have reached the highest status number it will start at number one again.
• Push the button until you get the requested lock kick status, 1=Basic (default), 2=Enhanced
• Disconnect the mains
Next time the mains is connected, the operator will use the new status setting.
1. Disconnect batteries if any.
2. Disconnect the mains.
3. Press the LEARN BUTTON (LRN) and keep it depressed.
4. Connect the mains.
5. Watch the ERROR LED.
3s1s3s1s3s1s3s1s3s 3s1s
6. Release the LEARN BUTTON after 6 flashes (LED is out).
7. Identify the current lock unlocked status:
The ERROR LED flashes an amount of short flashes that correspond to the status number. After a short pause the LED will repeat the status number and so on.
8. Changing the status:
If you push the LEARN BUTTON once, the status number will increase. When you have reached the highest status number it will start at number one again.
• Push the button until you get the requested status.
1= Lock is unlocked when door is not closed. 2= Lock is unlocked when door is 0-10 degrees from closed position, during opening.
• Disconnect the mains.
Next time the mains is connected, the operator will use the new status setting.
5
01123456
DAB105CU
10
Page 40
40
IP2159EN - 2017-06-12
18. Extension unit DAB905ESA (optional)
There is a command extension card for managing motion sensors, alarm indications and door status.
Remove the jumpers if a safety sensor is connected to terminals 1-2 and 1-3.
18.1 Commands
Contact Function - Accessory Description
1
2
GND-PIMP
NC REVERSAL SAFETY CONTACT
INTERNAL SENSOR
The opening of the contact during the closure manoeuvre causes the movement to invert (reopening). NB: the opening of the contact of the motion sensor installed on double doors causes both doors to re-open. The sensor is not active in DOOR CLOSED mode (set via the function selector switch), or when the door is opened manually due to a power failure or emergency closure (KILL).
1
3
GND-PDET
NC OPENING SAFETY DEVICE
EXTERNAL SENSOR
The opening of the contact causes the movement to stop during the opening phase. When the contact closes again, the automation resumes the interrupted opening opera­tion. If the automation is closed, the opening of the contact prevents the opening operation. Adjust the safety exclusion trimmer so that the sensor does not detect the wall during the opening phase. During the opening phase, the safety sensor takes priority over the motion sensor. NB: the opening of the contact of the motion sensor installed on double doors causes both doors to stop, except in the case of double exit doors. Modify the operation of the double doors by changing the pre-configured parameters as explained in chapter 13. The sensor is not active in DOOR CLOSED mode (set via the function selector switch), or when the door is opened manually.
5
4
24V-QTST
SAFETY TEST Connect the QTST terminal of the control panel to the corresponding test terminal on the
safety device. A test will be carried out on the safety device before every operation.
DAB905ESA
(optional)
DAB905ESE
(optional)
Torx T10
Long pin used for 2 Extension Unit
Short pin used for 1 Extension Unit only
5 mm nut driver
612345
67812345
12 345678910111213
Fix the label to the terminal board, taking care to apply it in the correct direction (see the figure above).
24 V DC
-
Sicurezza di inversione lato interno
Sicurezza in apertura lato esterno
Safety test
67812345
NO COM
NON USARE
NON USARE
LED
ESCLUSIONE
SICUREZZA
TRIMMER
ESCLUSIONE
SICUREZZA
NON USARE
NC
QTST PDET PIMP GND
J1
J2
Uscita 24 V 1 A
i
i
(optional)
Torx T10
5 mm nut driver
(optional)
Long pin used for 2 Extension Unit
Short pin used for 1 Extension Unit only
SAFETY
EXCLUSION LED
24V output 1 A
DO NOT USE
DO NOT USE
DO NOT USE
Safety test Safety contact on external side opening
Reversal safety contact on
internal side
SAFETY EXCLU-
SION TRIMMER
Page 41
41
IP2159EN - 2017-06-12
Output Description
+24V DC
GND
1 ... 5
Output for the power supply to the accessories 24V 400 mA max.
NB: the maximum absorption of 400 mA corresponds to the sum of all the accessories installed.
SAFETY SENSOR
Connect a self-checking safety sensor on the door wing.
Connect the closing side sensor to terminals 1-2 (GND-PIMP). Connect the opening side sensor to terminals 1-3 (GND-PDET).
12-24 V
AC-DC
COM NC NO
CO
M NO NC
1
5
1
3
1
2
5
4
GREEN
BROWN
YELLOW
WHITE
BLACK
PINK
GREY
PURPLE
RED**
BLUE**
POWER SUPPLY
STOP SIGNAL (OPENING SIDE)
REVERSE SIGNAL (CLOSING SIDE)
MONITORING
NB: in the event of a safety sensor fault during opening, the door closes and stays closed. It can only be opened manually. In the event of a safety sensor fault during closing, the door stays open. By switching the function selector switch to DOOR CLOSED, the door can operate in Low Energy mode. It can only be opened manually.
678
NO
COM
NC
Relay contact 24 V 1A.
678
NO COM NC
N
O
N
C
The relay contact can be used as:
- an output for the parallel connection of the EMERGENCY CLOSURE command on several fire barriers;
- an output for connecting a block with a power supply other than 12/24V DC;
- an output for connecting an error warning device (light or acoustic). The COM-NO contact opens and the control panel detects an error (flashing LED on the DAB105CU control panel). If there is no alarm/error, the COM-NO contact is closed. In the event of an error, refer to the “Alarms” paragraph (24.1).
678
NO COM NC
OM
A device for indicating the open door can be connected. The open door position is adjusted by the opening safety exclusion trimmer. For a "door open" indication (from 45° to 90°), open the door with any opening command and adjust the trimmer until the LED on the DAB905ESA card lights up when the door is open (or is in the required open­ing position).
18.2 Outputs and accessories
Remove jumpers 1-2 and 1-3.
For more information, refer to the REM sensor manual
i
i
Page 42
42
IP2159EN - 2017-06-12
18.3. Adjustments
Trimmer
Trimmer Description
Adjustment of the opening safety exclusion, from 45° to 90°. During the door opening phase, this excludes the functioning of the safety device installed on the door wing, so that the wall is not detected. When the safety device is excluded, the LED lights up.
Jumper
678
NO COM NC
Indication of external error / Output for parallel connection of Emergency Closure (KILL) / Block output
678
NO COM NC
Indication of door open
J2
OFF
ON
678
NO COM NC
M
C
Test on external sensor (GND-PDET)
OFF
ON
678
NO COM NC
CO
M
Test on internal sensor (GND-PIMP)
ON
ON
678
NO COM NC
N
O
COM N
C
No test
OFF
OFF
678
NO COM NC
Test on internal and external sensors (GND-PIMP / GND-PDET)
Signals
ON
OFF
LED
Opening safety device disabled Opening safety device enabled
Page 43
43
IP2159EN - 2017-06-12
19. Example of an application with optional extension units
PASS24 (OIMP - DAB905ESE)
PASS24 (IIMP)
COM400MHB (DAB905ESE)
Locking Device (DAB905ESE)
Open/close (DAB905ESE)
Closing timer (DAB905ESE)
Emergency
closing Reset (DAB905ESE)
Emergency
closing (DAB905ESE)
DAB105
REM
(DAB905ESA)
Battery
(DAB905ESE)
Error indication or door open (DAB905ESA)
Error indication or door open (DAB905ESA)
Emergency closure reset
(DAB905ESE)
Emergency closure (DAB905ESE)
Battery
(DAB905ESE)
Locking Device (DAB905ESE)
Open/close (DAB905ESE)
Closing timer (DAB905ESE)
Page 44
44
IP2159EN - 2017-06-12
20. Parallel automations (DAB905SYN)
20.1 Settings
Connect the two automations to the plug on the control panel, using the synchronisation cable (DAB905SYN). Depending on the type of installation, cut the jumpers on the MASTER or SLAVE cable, as shown in the table:
MASTER SLAVE
black
2000 mm
yellow
blue
red
Operating mode Type of application Jumper to be cut
Opening Closure Overlap Skim MASTER SLAVE
Synchronous Synchronous NO NO / /
Synchronous Asynchronous YES NO BLACK /
Asynchronous Asynchronous YES YES / RED
Double exit / / BLACK RED
Operating mode
Settings
MASTER SLAVE
Program selection X
Opening time X
Closure time X
Closure time adjustment X
Closure / Opening attempt when the door is obstructed
X
Enable / Disable PAG X
Level of servo-assistance X X (*)
Closure force X X (*)
Pulse of motion sensor or mat X
Selection of operating mode during battery functioning
X
Lock/release signal tension X X
Block powered / Unpowered X X
Enable / Disable block release X X
Open door delay X X
Enable / Disable snap block X X
The electric locks / electric strikes must be connected to the MASTER and SLAVE control panels.
The opening devices must be connected to either the MASTER or SL AVE control panel, or to both.
The OPD motion sensor must be connected to the MASTER control panel except for double exit doors where each OPD motion sensor must be connected to the corresponding control panel
The sensors fitted on the wing must always be connected to the corresponding control panel.
SORMONTO SFIORAMENTO SENZA SFIORAMENTO DOPPIA USCITA
The MA STER automation is the one that opens first.
i
i
(*) In double exit doors, these functions have to be set separately on the MASTER and SLAVE doors because the arm system and air pressure may differ.
OVERLAP
SKIM WITHOUT SKIM
DOUBLE EXIT
Page 45
45
IP2159EN - 2017-06-12
BROWN
YELLOW
WHITE
BLUE
RED
WHITE
YELLOW
BROWN
GREEN
BLUE
RED
WHITE
YELLOW
BROWN
GREEN
GREEN
OUTER OPEN SENSOR
SAFETY SENSOR SAFETY SENSOR
FUNCTION SELECTOR
612345
GND
IIMP
XIMP
OPD
LOUT
24 V
MASTER
MASTER
SLAVE
SLAVE
DAB905SYN (see applications chapter 21)
INNER OPEN SENSOR
SAFETY
SENSOR
INNER
OPEN SENSOR
FUNCTION SELECTOR
OUTER
OPEN SENSOR
SAFETY
SENSOR
BROWN
YELLOW
WHITE
GREEN
612345
ON
LTQ
LRN
HOT
PAG
MAT
SOS
ARM1
ARM2
LED
12345
GND
IIMP
XIMP
OPD
LOUT
24 V
+24 V DC
GND
EXIT
OFF
OPEN
5
KILL
KEY
O/C
OIMP
GND
12 345678910111213
EXIT
OFF
UNL
KRST
OPEN
12-24 V
AC-DC
COM
NC
NO
COM
NO
NC
12-24 V
AC-DC
COM
NC
NO
COM
NO
NC
24 V DC
678
12345
NO
COM
NC
QTST
PDET
PIMP
GND
24 V DC
678
12345
NO
COM
NC
QTST
PDET
PIMP
GND
DAB105CU
DAB105CU
DAB905ESEDAB905ESA
DAB905ESA
20.2 Example of installation of parallel doors (DAB905SYN)
FUNCTION SELECTOR
SAFETY
SENSOR
SAFETY
SENSOR
INNER
OPEN SENSOR
OUTER
OPEN SENSOR
FUNCTION SELECTOR
SAFETY SENSOR SAFETY SENSOR
OUTER OPEN SENSOR
INNER OPEN SENSOR
(see applications chapter 21)
BROWN
BROWN
YELLOW
WHITE
GREEN
YELLOW
WHITE
GREEN
WHITE
GREEN
BLUE
RED
BLUE
RED
VIOLET
VIOLET
PINK
WHITE
YELLOW
BROWN
GREEN
PINK
YELLOW
BROWN
Page 46
46
IP2159EN - 2017-06-12
20.3 Interlocked automations (DAB905SYN)
MASTER
DOOR A
DOOR B
SLAVE
MASTER
SLAVE
DOOR B MAGNET SWITCH
DOOR A MAGNET SWITCH
In applications for interlocked doors, a micro switch must be installed on the MASTER A automation in order to disable opening of the MASTER B automation and vice versa.
When both doors are closed, the 3-GND 7-KILL contact is open. The first automation that opens closes the contact and prevents the other automation from moving. When the first automation has closed, the second automation can open by way of a second opening command.
NB: If a KILL command is given to the SLAVE automation, only the SLAVE door will stop. NB: If single interlocked doors are installed, the same connections indicated above are used.
C
NC NO
12345
ON
+24 V DC
KILL
KEY
O/C
OIMP
GND
12 345678910111213
OPEN
EXIT
OFF
UNL
KRST
DOOR B
MAGNET
SWITCH
DOOR A
MAGNET
SWITCH
12345
ON
+24 V DC
KEY
O/C
OIMP
GND
12 345678910111213
OPEN
EXIT
OFF
UNL
KRST
DOOR A
DOOR B
C
NC
KILL
DAB905ESE
DAB905ESE
NO
DOOR A
MAGNET
SWITCH
DOOR B
MAGNET
SWITCH
DOOR B
MAGNET
SWITCH
DOOR A
MAGNET
SWITCH
DOOR A
DOOR B
DOOR A
DOOR B
Page 47
47
IP2159EN - 2017-06-12
22. Routine maintenance plan
Perform the following operations and checks ever y 6 months, according to the intensity of use of the automation. Disconnect the 230V~ power supply and batteries (if present), and position the ON-OFF switch on OFF:
• Clean and lubricate the moving parts.
• Check the securing screws are firmly in place.
• Check all the electrical connections.
• Make sure the batteries are in good working order. Restore the 230V~ power supply and batteries (if present), and position the ON-OFF switch on ON:
• Check the stability of the door, and make sure it moves smoothly.
• Check the condition of the pivots or hinges.
• Make sure all the command and safety devices are working properly.
NB: for spare parts, see the spares price list.
i
21. Electrical start-up
1. Connect the motor and encoder cables to the DAB105CU control panel.
2. Turn on the power supply.
3. Press the LRN button for automatic self-learning.
4. In the case of parallel installations, the self-learning procedure must be carried out on the MASTER door first, then the SLAVE door. The self-learning procedures on the two doors can be carried out separately, before connecting the synchronisation cable. In the case of parallel doors with overlap, the MASTER door must stay open until the SLAVE door has completed its self-learning
procedure.
5. Set the automatic closing time by means of the HOT trimmer.
6. Adjust the opening speed with the OPSP trimmer.
7. Adjust the closing speed with the CLSP trimmer.
8. Connect the accessories and check they are functioning.
Before performing any type of operation, make sure that the automation is turned off and the batteries are discon-
nected.
The trimmers can only be adjusted with the automation idle.
i
i
Only use original spare parts when repairing or replacing products. The installer must supply all information concerning the automatic, manual and emergency operation of the motorised door or gate, and must provide the user with the operating instructions. The installer must prepare and keep a maintenance record showing all the routine and extraordinary maintenance work carried out.
Page 48
48
IP2159EN - 2017-06-12
23. Troubleshooting
Problem Possible cause Solution / Explanation
The door does not open
a) The motor does not start The function selector is set on OFF Change the function selector setting
There is no mains power supply Check the mains power supply
The command unit does not work Check the connections of the command ac-
cessories
The motion sensor has been activated Remove any objects from the detection area
Emergency closure activated Deactivate the emergency closure
SPTE trimmer not set to 0° Rotate the SPTE trimmer to 0°
b) The motor starts Mechanical lock blocked Release the lock
Obstacle Remove any obstacles
Door stop jammed Select block release
The arm system is coming loose Rotate the SPTE trimmer until the door stop is
on the limit switch. Bring the door to its open position. Tighten the arm system. Rotate the SPTE trimmer to 0°
The door does not close The selector is set on DOOR OPEN Change the function selector setting
The motion sensor contact has been activated Remove any objects from the detection area
Obstacle Remove any obstacles
The spring pre-tensioning on the automatic system is unrecognised
Too many adjustments have been made 1. Rotate the SPTE trimmer until the end
stop can be loosened.
2. Remove the end stop and the arm system.
3. Disconnect the mains power supply.
4. Disconnect the motor cable
5. Replace the arm system and locate the non-pretensioning point by moving the door wing backwards and forwards.
6. Loosen the arm.
7. Reconnect the motor cable.
8. Reconnect the mains power supply.
9. Adjust the SPTE trimmer at 210° and wait for the shaft to stop rotating.
210°
10. Fix the end stop on the closure limit switch.
11. Set the SPTE trimmer to 0°.
THE AUTOMATIC SYSTEM HAS RETURNED TO THE FACTORY SETTINGS.
12. Repeat the door start-up operations explained in chapter 12
Page 49
49
IP2159EN - 2017-06-12
24. Signs
800 mm
1100 mm
40 mm
A
B
C
D
E
F
G
J
H
Ref. Description
A
xxxxxxxxxxxxx xxxxxxxxxxxxx
TYPEART. NO. YEAR+WEEK
XX
EN ISO 9001 Certificate No: 911828, 956538
SITAC1422
xxxxxxxxx
1002
XX/XXXXXXXX
Hz
PROJECT SERIAL NO.
XXXXXXXXXX
DAB105
W
XXXX
AVAC
Product label. Obligatory.
B
Supervision of children. Obligatory, if applicable. Attach to both sides of the door. Attach to doors used by children, the elderly and disabled (as shown by a risk analysis).
C
Automation suitable for the transit of disabled people. Recommended, if applicable. Attach to both sides of the door.
D
Automatic
door
Automatic door. Obligatory in the UK only.
E
Keep clear
Do not block the passageway. Obligatory in the UK only.
F
No entry
No access. Indicates one-way transit. Obligatory in the UK and USA only, if applicable.
G
Emergency break-out. Obligatory if approved for escape routes.
H
Door label. Obligatory, if applicable. Warns of the presence of glass door wings. Attach to all mobile glass door wings.
J
Click!
The automation can be activated by disabled people. Recommended, if applicable.
Make sure the signs are in good condition, and attach them. Obligatory indicates that this sign is required by the European directives and equivalent national legislation outside the EEC.
Page 50
IP2159EN - 2017-06-12
Entrematic Group AB
Lodjursgatan 10 SE-261 44, L andskrona Sweden www.entrematic.com
Loading...