Entrelec MU 10/13.SF2, MU 10/14.5.SF2 Catalog Page

T01089
011010
Fuse holder terminal blocks
for 6,35 x 25,4 mm 1/4 x 1 in. and 6,35 x 32 mm 1/4 x 1 1/4 in. fuses
Compression clamp
DIN 1 - DIN 3
End stop End stop
th. 9,1 mm th. 9,1 mm
Other end stops : See Accessories section
Rail PR30 Rail Rail PR5 Rail
35 x 7,5 x 1 35 x 15 x 2,3 PR4 0168 500.12 35 x 15 x 1,5 32 x 15 PR1Z2 0163 050.04
Other rails : See Accessories section
Notes
The use of some accessories may decrease the block's voltage rating. For more information, consult us.
Accessories
1
2
3
4, 5, 6,
7
8
BADL V0 0199 408.02 BAM 0103 002.26
prepunched
0173 220.05
prepunched
0101 598.26
1 End section black 2 Test plug
3 Test socket
4 Standard jumper bar 5 Screw for BJ 6 Washer for BJ 7 Fuse 6,35 x 32 mm
Quick blow fuse cartridge as per UTE 93435
8 Blown fuse indicator
MU 10/13.SF2
Spacing 13 mm (.512")
13 mm block for blown fuse indicator (to be ordered separately).
Spacing 14,5 mm (.570")
14,5 mm block for blown fuse indicator (to be ordered separately).
MU 10/14,5.SF2
Color Type Part numbers Color Type Part numbers
Black V0
MU 10/13.SF2 0199 014.11
Black V0
MU 10/14,5.SF2 0199 013.10
Characteristics Characteristics
Wire size
NFC DIN UL CSA NFC DIN UL CSA
Compression clamp
0,5-16 mm² 22-10 AWG 6 AWG max.
Solid wire Stranded wire
0,5-10 mm² 22-10 AWG 6 AWG max.
Voltage
Rated Pulse Pollution degree
750 V Gr.C (1) 600 V (1) 600 V (1)
Current
Rated
16 A 16 A 16 A
Wire size
Rated / Gauge
Wire stripping Recomm. Recomm. Protection
length screwdriver torque
12 mm 5,5 mm 1,2-1,4 Nm IP 20
.47" .22" 10.6-12.3 Ib.in NEMA 1
10 mm² 10 AWG 6 AWG
Type Part numbers FEM13U V0 1,5 mm 0199 635.24
FC2 2 mm 0007 865.26 FC4 4 mm 0167 860.01 AL2 2 mm 0163 043.21 AL3 3 mm 0163 261.00 AL4 4 mm 0163 262.01 BJS131 10 0175 991.11
th. DIA. DIA. DIA. DIA. DIA.
poles
VJS11 0163 394.26 RDJ11 0168 783.01 FU633 6,35 x 32
0,25 A 0168 554.03 0,63 A 0168 555.04
1A 0168 556.05 1,6 A 0168 557.06 2,5 A 0168 558.17
4A 0168 559.10
6,3 A 0168 560.15
10 A 0168 561.02
16 A 0168 562.03
LEN 110 - 230 VAC 0167 075.25
Neon Neon
480 VAC 0103 909.00
Leakage current with neon indicator
< 0,5 mA (110 & 480 VAC) < 0,7 mA (230 VAC)
Wire size
Compression clamp
0,5-16 mm² 22-10 AWG 6 AWG max.
Solid wire Stranded wire
0,5-10 mm² 22-10 AWG 6 AWG max.
Voltage
Rated Pulse Pollution degree
750 V Gr.C (1) 600 V (1) 600 V (1)
Current
Rated
Wire size
Rated / Gauge
Wire stripping Recomm. Recomm. Protection
length screwdriver torque
12 mm 5,5 mm 1,2-1,4 Nm IP 20
.47" .22" 10.6-12.3 Ib.in NEMA 1
10 mm² 10 AWG 6 AWG
Type Part numbers
delivered with the block
FC2 2 mm 0007 865.26 FC4 4 mm 0167 860.01 AL2 2 mm 0163 043.21 AL3 3 mm 0163 261.00 AL4 4 mm 0163 262.01
DIA. DIA. DIA. DIA. DIA.
FU633 6,35 x 32
0,25 A 0168 554.03 0,63 A 0168 555.04
1A 0168 556.05 1,6 A 0168 557.06 2,5 A 0168 558.17
4A 0168 559.10
6,3 A 0168 560.15
10 A 0168 561.02
16 A 0168 562.03
LEN 110 - 230 VAC 0167 075.25
Neon Neon
480 VAC 0103 909.00
Leakage current with neon indicator
< 0,5 mA (110 & 480 VAC) < 0,7 mA (230 VAC)
R
R See section on markers
marking method
11 17 26
Sides of block
11 17 26
Sides of block
Note : (1) Insulation voltage of terminal block - operating voltage : In accordance with fuse rating.
143