Entrelec 48 V DC / 0.7 A Catalog Page

FL_00005
010103
Switching Power Supply
48 V DC / 0.7 A
systron® PS
+48 V DC Common GND
green LED: ON: output voltage
OK.
Marker
The switching power supplies, systron® PS, offer many advantages over conventional supplies:
DIN Rail mount compact modules Low weight High efficiency Low heating Wide range of supply voltage Constant output voltage with good regulation UL, CSA listed, EN 50178 (VDE 0160) Short-circuit and overload proof Fused input
Power high
Approvals:
Power supply systron® PS P/N:
systron® PS 48 V DC / 0.7 A 2 423 418 60
Technical data
Input
Supply voltage 90...260 V AC
Frequency, AC input 47... 440 Hz Output load hold time With input voltage drop out, min. 10 ms at 100% load Input current at nominal load Inrush current 25° C ( 2 ms) 33 A (260 V AC) Internal input fuse 3.0 A (slow blow)
Output
Output voltage 48 V DC ± 3 % Output current / power at... 0.7 A Current derating at temperature > 45°C - 10 mA/°C Current derating at input voltage < 105 V AC / 120 V DC - 6,667 mA/V Residual ripple / noise max. 300 mVpp Deviation of output with input change max. ± 0.5 % Deviation of output with static load change max. ± 0.5 % Deviation of output with dynamic load change max. 5 % Short circuit protection overcurrent switch off with automatic restart Overload protection overtemperature and overcurrent switch off Reset after thermal overload disconnection of AC power input min. 30 s
Norms, tests
Electrical safety standards EN 50178 (VDE 0160)/EN 60950/UL 508/CSA 22.2 Galvanic isolation reliable isolation acc. to EN 60950, DIN VDE 0106-101 Voltage withstand input <-> output 2.5 kV AC, 3 kV AC type test Clearance and creepage distances according to overvoltage category 2, pollution degree 2 Electromagnetic immunity (EM) in acc. to EN 50082-2: ESD: EN 61000-4-2 level 3 6/8 kV
Electromagnetic compatibility (EMC) in acc. EN 50081-2 radiated noise EN 55011, class B Input current harmonics no limitation Protection against contact Terminals IP 20 Housing IP 30 Protection class 1
General characteristics
Efficiency (nominal load) approx. 83...85 % (90...260 V AC) Status indication green LED, power OK Operating temperature 0° ... 55°C Storage temperature -25° ... +75°C Terminals screw terminals, 2 x 14 AWG (2.5 mm Weight approx. 0.22 kg (0.49 Ib) Dimensions (W x H x D) 1.77 x 3.07 x 3.94" (45 x 78 x 100 mm) Mounting hints Normal position: horizontal onto DIN rail. Spacing to other
max. 0.8 A (90 V AC)/typ. 0.7 A (115 V AC)/typ. 0.35 A (230 V AC)
RF field: EN 61000-4-3 level 3 10 V/m Burst: EN 61000-4-4 level 4 4 kV Surge: EN 61000-4-5 3 kV conducted RF: EN 61000-4-6 level 3 10 V
modules: left side min. 1 cm, vertical distances min. 5 cm
Neural
Ground
Supply voltage
Class I & II, Div. 2
105...260 V DC
2
)
652