ENTES RG-6T User manual

POWER FACTOR CONTROLLER
RG-6T
1. INTRODUCTION
1.1 About User Manual
This User Manual is designed to help you for quick installation of RG-6T. Before installation and operation, please read this section very carefully.
1.2 Precautions for Safe Use and Installation
- Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment.
- When the device is connected to the network, do not remove the back panel.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
- An F type fuse must be used and its current limit value must be 6A.
- No responsibility is assured by ENTES A.S or any of its subsidiaries for any consequences arising out of the use of this material.
2. GENERAL
Power Factor Controllers are used for measurement and control of power factor control units for central reactive power compensation. The Power Factor measured by RG-6T is compared with the set point values and in order to provide necessary compensation, Power Factor Controller switches capacitor banks ON and OFF automatically. RG-6T is a microcontroller relay, designed for above application in 144x144 and 96x96 (only RG-6T) case for flush mounting with rear plug-in connectors. In addition to displaying the system’s Cosϕ in Automatic
Operating Mode, RG-6T displays the RMS values of Voltage(V) and Current (I), Active Power (W), Reactive Power (VAr) and Apparent Power (VA) of measuring phase.
3. FRONT PANEL SPECIFICATIONS
1
21
RG-6T
20
M
19 18
17 16 15
W
VAr
OVER V.
VA
2 3
4 5 6 7 8 9 10
22 11
12 13 14
10.Over V. /VA Light: By pressing SET button 3 seconds; you enter to Menu and Protection
11.UP Button : To move up in the Menu.
12.SET Button : Enter button for different settings and values.
13.DOWN Button
14.Automatic
C/k Setting : Automatical C/k adjustment is started by pressing UP and DOWN
15. C+ Light : This light is ON when RG-6T switches capacitor steps on.
16. NORMAL Light : This light is ON when the targeted compensation is achieved.
17. C- Light : This light is ON when RG-6T switches capacitor steps off.
18.Insufficient
Compensation Light : This warning light is ON when insufficient compensation occurs.
19.Over Compensation Light : This warning light is ON when over compensation occurs.
20.Over Voltage Light : This warning light is ON when over voltage occurs. (Refer to:6.1.1)
21.K (Kilo) Light : When this light is ON displayed value must be multiplied by 1000.
22.M (Mega) Light : When this light is ON displayed value must be multiplied by 10
4. CONNECTION DIAGRAM
In Automatic Mode when this light is selected by pressing UP and
DOWN buttons, system’s Reactive Power (VAr) is displayed.
(Refer to: 5.14)
of Capacitor Steps Against Over Voltage function is made by selecting this light. (Refer to:5.9)
In Automatic Mode when this light is selected by pressing UP and
DOWN buttons, system’s Apparent Power (VA) is displayed.
(Refer to: 5.15)
: To move down in the Menu.
buttons together at the same time. (Refer to:5.2)
(Refer to:6.1.2)
(Refer to:6.1.3)
6
.
Phase-Neutral Connection*
7 8 9 10 11 12 13 14
N L3 L2 L1
On the front panel of RG-6T, there are warning lights, display and 3 buttons for settings.
3.1 Buttons and Lights
1. 1,2,.........,12 : Shows the status of each capacitor steps.
2.SET Menu : Shows the Menu options that correspond to the lights.
3. AUTO/MAN Light : If this light is continuously ON, RG-6T is in Automatic Mode. If it is
blinking, RG-6T is in Manual Mode. By pressing SET button 3 seconds, you enter to Menu and change operating Mode . (Refer
to: 5.1)
4. Cosϕ Light : By pressing SET button 3 seconds ; Cosϕ Adjustment can be made
by selecting this light. (Refer to: 5.3). In Automatic Mode, when Cosϕ light is selected by pressing UP and DOWN buttons, system’s Cosϕ and ind/cap state is displayed.
(Refer to: 5.10)
5.TIME/PF Light : By pressing SET button 3 seconds; you enter to Menu and Step
Time adjustment is made by selecting this light. (Refer to: 5.4) In Automatic Mode, when this light is selected by pressing UP and DOWN buttons, system’s Power Factor is displayed. (Refer to: 5.11)
6.STEP/V Light : By pressing SET button 3 seconds; you enter to Menu and Step Number adjustment is made by selecting this light. (Refer to:5.5) In Automatic Mode, when this light is selected by pressing UP and DOWN buttons phase voltage (V) is displayed. (Refer to:5.12)
7. PROGRAM/I Light: By pressing SET button 3 seconds; you enter to Menu and Power Sequence adjustment is made by selecting this light. (Refer to:5.6) In Automatic Mode, when this light is selected by pressing UP and DOWN buttons phase current (I) is displayed (Refer to:5.12)
8.C/k - W Light : By pressing SET button 3 seconds; you enter to Menu and Manual C/k adjustment is made by selecting this light.(Refer to:5.7)
In Automatic Mode when this light is selected by pressing UP and
Warnings: a) Connection of a circuit breaker between the network and the power supply
input of the device is highly recommended.
b) Circuit breaker must be in close proximity to the device. c) Circuit breaker must be marked as the disconnecting device for the equipment. d) All used fuses must be FF type and the current values of the fuses must be
2A, 3A and 6A.
DOWN buttons, system’s Active Power (W) is displayed.
(Refer to: 5.13)
9.CTR - VAr Light : By pressing SET button 3 seconds; you enter to Menu and Current
Transformer Ratio adjustment is made by selecting this light.
(Refer to:5.8)
1
N L3 L2
L1
1 2 3 4
Phase-Phase Connection*
15
16
6 A
K
k
5
21
17 18
19 20
C6
C1
L
l
2 A
1
6
2
3
22
6 A
4
5 6
24
25 26
23
C7 C12
27
28
Alarm Relay
3 A
12
11
POWER FACTOR CONTROLLER
RG-6T
5. CONTROLS AND MENU OPERATIONS
All settings are made by Menu. The set values except operating mode are kept in memory
5.4 Step Time Adjustment
SET
even if the device is switched off.When it is switched on, it starts compensation with the values stored in the memory in Automatic Operating Mode. After entering Menu by pressing SET button for 3 seconds and if you don’t make any adjustments during 20 seconds ,RG­6T operates with the previously stored values. To quit Menu without any storing operation, UP or DOWN buttons are pressed
UP
until the ESC symbol is displayed and then SET button is pressed. The details of controls and adjustments are explained in the following sections.
5.1 Selection of Operating Mode(Automatic / Manual Mode )
SET
Two Operating Modes are available for switching on/off the capacitor steps.
1) Automatic Operating Mode: The capacitor steps are controlled by RG-6T, automatically.
2) Manual Operating Mode: the capacitor steps are switched on/off, manually. RG-6T returns to Automatic mode if any button is not pressed within 5 minutes.
Mode selection is done as followed.
UP
By pressing SET button 3 seconds SET Menu is started.
SET
Display
DOWN
AUTO/MAN light is selected by using UP-DOWN
UP
UP
buttons. symbol is displayed.
AUTO/MAN setting is selected by pressing SET button. If the device is in Manual Mode,
SET
symbol is displayed.If the device is in Automatic Mode,
symbol is displayed.
DOWN
Automatic Mode ( ) or Manual Mode ( ) is selected by using UP-DOWN buttons.
When targeted operating mode is displayed, it is selected by pressing SET button. If
SET
Manual Mode is selected, AUTO/MAN light starts blinking and blinks during this mode.If Automatic Mode is selected, AUTO/MAN light is continuouslly ON during this mode.
RG-6T
M
W
VAr
OVER V.
VA
SET
5.5 Step Number Selection
SET
UP
SET
UP
SET
By pressing SET button 3 seconds, SET Menu is started.
Display
DOWN
TIME light is selected by means of UP-DOWN buttons.
While TIME light is ON, t 0n symbol is displayed by means of UP-DOWN buttons and time delay adjustment for connection of capacitor steps to system is selected by pressing SET button. While TIME light is ON, t 0F symbol is displayed by means of UP-DOWN buttons and time delay adjustment for disconnection of capacitor steps to system is selected by pressing SET button.
DOWN
A value between 2-1800 sec. is adjusted by using UP-DOWN buttons.
When targeted value is displayed, it is stored by pressing SET button and RG-6T returns to its normal operating mode.
By pressing SET button 3 seconds, SET Menu is started.
Display
STEP light is selected by means of
DOWN
UP-DOWN buttons. StEP symbol is displayed.
STEP number adjustment is selected by pressing SET button.Previously selected value is shown on the display
A preferred step number is selected by
DOWN
means of UP-DOWN buttons.
When targeted value is displayed, it is stored by pressing SET button and RG-6T returns to its normal operating mode.
5.1.1 Switching of the Capacitor Steps Manually
When RG-6T is in Manual Mode, capacitor steps are connected by pressing UP button.
5.6 Switching Program Selection
SET
Each time UP button is pressed, C+ light turns ON and one step is connected accordingly; NORMAL light will be ON after the connection of the step. This operation must be repeated to connect more steps. Capacitor steps are disconnected by pressing DOWN button. Each time UP button is pressed, C- light turns ON and one step is disconnected after a delay time; NORMAL light
UP
will be ON after the disconnection of the step.This operation must be repeated to disconnect more steps.
SET
5.2 Automatic C/k Adjustment
DOWN
C/k adjustment is started by pressing UP-DOWN
UP
buttons together.
UP
SET
5.3 Cosϕ Adjustment
5.7 Selection of C/k Value by the User
SET
By pressing SET button 3 seconds, SET Menu is started.
Display
DOWN
Cosϕ light is selected by using UP
UP
SET
UP
SET
and DOWN buttons. COS symbol is displayed
Cosϕ adjustment is selected by pressing SET button. Previously adjusted value is shown at the display.
DOWN
A value between 0.85-1.00 is adjusted by using UP-DOWN buttons.
When targeted value is displayed, it is strored by pressing SET button and RG-6T returns to its normal operating mode.
SET
UP
UP
SET
SET
By pressing SET button 3 seconds, SET Menu is started.
Display
DOWN
PROGRAM light is selected by means of UP-DOWN buttons. displayed.
Switching Program is selected by pressing SETbutton.Previously selected value is shown on the display
DOWN
A value between PS1-PS5 is selected by using UP-DOWN buttons.
When targeted program is displayed, it is stored by pressing SET button and RG-6T returns to its normal operating mode.
symbol is
By pressing SET button 3 seconds, SET Menu is started.
Display
DOWN
C/ k light is selected by means of UP-DOWN buttons. displayed.
Manual C/ k adjustment is selected by pressing SET button. Previously manually selected or automatically calculated C/ k value is shown on the display
DOWN
A value between 0.02-1 is selected by using UP-DOWN buttons.
When targeted value is displayed, it is stored by pressing SET button and RG-6T returns to its normal operating mode.
symbol is
M
W VAr VA
OVER V.
2