ENTES RG-6B, RG-BS, RG-8B, RG-12B User guide

POWER FACTOR CONTROLLER
RG-6B/BS/8B/BS/12B/BS
DIMENSIONS
Do not use device without checking terminal connections.
CONTROLS and OPERATIONS
Capacitor values are recognized and saved with ASEt operation. For doing this, enter program menu on the device and find ASEt menu. ASEt menu includes 2 parameters which are S-oF and S-on. When S-on is selected and SET button is pressed; the device will find and correct any connection failures (such as wrong connection at voltage and current inputs) first and then recognize all capacitor steps. If 10th program (PS-10) is selected, all capacitor powers will be measured. In other programs, only first capacitor step power is measured and other capacitor steps are calculated and recorded according to selected program. If S-oF is selected and SET button is pressed during capacitor recognition, automatic recognition will be ended.
Note: If there are loads other than compensation on the system, the device may find the connection after several tries. If the device doesnt complete the automatic connection process, it cant do the step calculation process. In order to have correct power values for capacitor steps, current and voltage transformer ratios must be entered correctly. If current and voltage transformer ratios are not entered, these ratios are assumed to be 1 and capacitor powers are calculated according to these values (Refer to VT and CT ratio settings). If automatic setup is selected as S-on, automatic mode starts immediately without waiting to escape from the menu. Note: A parameter that is calculated automatically by the device can be changed by the user.
Automatic Capacitor Recognition and Phase Setup Mode
1
For proper operation, current and voltage connections must be connected as
shown in the connection diagram.
After current and voltage terminal connections, capacitor steps connection must
be done according to the connection diagram.
Lastly, computer communication connection must be done. Do not power-up the device before verifying terminal connections.
1. RG-B/BS Series Connection
a)
b)
c) d)
Device can detect wrong connection on the way of active power. For correcting connection fault, automatic setup must be done or suitable phase value must be programmed from AngL menu, which is for programming phasor angle, from transformer menu. When user does automatic setup (ASEt), device will open and close 3 phase capacitor in 1st step during correction of connection failure. Sudden changes in loads and nonlinear loads (Thyristor or triac controlled frequency inverter, UPS etc.) existing, automatic setup may not be done. In this condition, user should disconnect the device and restart it and make the same operation. This operation can do with selecting S-on under ASEt menu. In this case device corrects the errors and then calculates the capacitor values.If user does not want calculating capacitor values, selecting S-oF parameter provides this. User must enter capacitor values after entering current and voltage transformer ratios. Capacitor values can be calculated automatically or maually. Capacitor powers are measured automatically by entering S-on under devices ASEt setting (for details please look Operating Mode Settings). If 10th program (PS-10) is selected in program menu, all capacitor values are measured by switching on/off of the capacitors in sequence. In this program, 3 phase capacitors can be connected as desired according to system requirements. If capacitor steps have been calculated as in the previous step, this step is not necessary. Selecting other program condition device only calculate 1st step and other steps will be calculated according to selected program. Device calculates the capacitor values which will be switched ON according to selected program; so device switches on/off the required steps. Connection of circuit breaker or automatic fuse between the network and RG-B/BS series is highly recommended. Circuit breaker must be in close proximity to the device. All used fuses must be FF type and the current values of the fuses must be 2A or 3A and 6A (Refer to Connection Diagram). Generator input must be done only when the network is supplied by the generator. Otherwise device will be switched to the generator position for each generator starts including the maintaining purpose.
a)
b)
c)
d)
e)
2.
Commissioning
RG-B/BS Series
Generator Input
When 110-250 V AC connection is connected to devices generator input, COS1 position will be passive and COS2 will be active. So, compensation will be done according to target COS2 as long as a voltage is present at generator input.
CONNECTION DIAGRAM
Press SET button and enter ASEt menu (S-oF is displayed)
Select S-on option by using UP/DOWN buttons.
(This parameter should be selected as ON in order to start the Automatic Capacitor Recognition.)
Press SET button in order to activate your selection.
Press SET button 3 sec. and select Auto option.
Select ASEt parameter by using UP/DOWN buttons.
Operating Mode (Automatic/Manual Mode) Settings
RG-B/BS series has two operating modes which are automatic mode and manual mode. Operating mode can be selected by selecting A-on (automatic) or A-oF (manual) option. Manual mode is used for test purpose. In this mode, capacitor steps are switched on&off to test the relay outputs of the device. In the manual mode, capacitor steps are switched on by pressing SET button and also capacitor steps are switched off by pressing ESC button. Factory set values for switching on (ond) and switching off (oFd) time is 10 seconds. These time values can be programmed in the Delay (dELy) menu (Refer to delay time setting). In the manual mode, step numbers, which will be switched on&off, can be programmed in Step menu (Refer to step number setting). Even if manual mode is selected, after 5 minutes, device starts to work in automatic mode and continues to operate in automatic mode.
When automatic mode is selected, AUTO/MAN LED lights on continuously. When manual mode is selected, AUTO/MAN LED blinks.
Warning: Device warns user by blinking (short ON, long OFF) the capacitor steps which will be switched on. Also device warns user by blinking (long ON, short OFF) the capacitor steps which will be switched off. For switching capacitors; voltage inputs must be connected and measured voltage must be higher than (min. 0.5 times) programmed nominal network voltage.
* Current value of 3-Fuses, which are connected to protect the capacitors, is chosen according to the nominal current value of capacitors. ** At 3 phase 4 wire applications L1 and Neutral must be connected devices voltage measurement inputs, at 3 phase 3 wire applications L2 and L3 phases must be connected. L1 phases current transformer must be connected to current measurement input. If load is unbalanced, current cable which is nearest value of total average value must be connected to current transformer. In this condition voltage inputs must be set refer to current. When device programmed to automatic setup, it will program suitable phase angle. So it will measure true values and true compensation. *** Communication terminals are only available in BS models.
Precautions for Safe Use and Installation
This user manual is prepared for quick commisioning and operating of the device. Please read this manual carefully before commisioning or operating RG-B/BS series
Maintenance, installation and operation of RG-B/BS series must be performed only by the qualified technicians. RG-B/BS series is connected to the network with current transformer. Do not disconnect the current transformer terminals. If you disconnect them, be sure to short-circuit or connect them to another parallel load which have low impedance. In case of failure, dangerously high voltage at the secondary side of current transformer may cause an electric shock. Device is suitable only for panel mounting. Verify terminal connections when wiring. Do not use this product for any other purpose than its original task. Do not operate undervoltage. When device is connected to the network, do not remove the front panel. Do not open the RG-B/BS series housing. There are no user servicable parts inside it. Do not clean the device with solvent or similar items. Only clean with a dry cloth. Electrical equipment should be serviced only by your competent seller.
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
1) Panel cut-out dimension must be 91 mm x 91 mm for Type PR19 and 143 mm x 143 mm for Type PR16.
2) Before installation, remove the mounting brackets.
3) Mount the device to front panel.
4) Insert the mounting brackets.
5) Wire thickness for voltage and current terminals must be 2,5 mm2, but it is suitable for cables which have up to 4 mm2 section.
6) CAT5 cable is recommended for RS-485 input terminal.
Excessive force can damage the device. Turn the screw into the terminals and tighten until the RG-B/BS series is secured in place.
70mm
79.3mm
90mm
96mm
96mm
Type PR 19
15 17 18 19 20 21 22
5 6 9 10
6A
Alarm Relay
11 12
C1 C6 C7 C12
23 24 25 26 27 30 31 32 33
N L3
L2
L1
Fan Relay
13 14
1 2 3 4
Un V
in
I
in
Generator
Input
110~250 V AC
16
1A
K L
l1k
1
~ ~
L2 L3
**
**
Type
PR16
(144x144)
143
99
121
138.4 143
18
34.5
67
RG-6B/BS RG-8B/BS
****
Voltage Measurement
Input
Auxiliary
Supply
Current Measurement
Input
Generator
Input
Fan Relay
Alarm Relay
RG-12B/BS
RG-6B/BS RG-8B/BS
TR B GNDA
RS485
POWER FACTOR CONTROLLER
RG-6B/BS/8B/BS/12B/BS
CURRENT and VOLTAGE TRANSFORMER RATIO SETTINGS, PHASE ANGLE and NETWORK VOLTAGE PROGRAMMING
In order to have correct power values for capacitor steps, current and voltage transformer ratios must be entered correctly. Current and voltage transformer ratios are entered in trF menu. If no value is entered in the menu, these ratios are assumed to be 1 and capacitor powers are calculated according to these values.
Current Transformer Ratio
CT ratio can be programmed between 1 and 2000. This value must be the Current Transformers ratio. Exp: For 150 A/5 A current transformer, CT ratio must be entered as "30".
Program Selection
Press SET button for 3 sec.
2
Step Number Setting
The maximum number of steps that the device can control depends on the device model. It can be 6, 8 or 12 . Each of these steps can be programmed oFF, oN or
Auto in the
10th
program. AUto : Programming capacitor power (kVAr) menu. on : Capacitor programmed as a steady. oFF : Meaning of there is no capacitor connection at output. When other programs are selected, 1st steps capacitor power can be programmed. Other steps power can be programmed according to selected program.
* Recommended program mode.
RG-B/BS series has 10 different program modes which determines the power ratio sequences of capacitor steps. These are given on the tables below.
If capacitors sequence is set just like 2nd program (P-02) (1.1.1.1.....), many identical
connection compenents are required. Selecting between 3th program (P-03) to 8th
program (P-08),less connection components are used (exp: 1.2.2......). 9th program
(P-09) provides different group powers. 9th programs capacitor sequence working principle is one groups power can be higher than previous groups sums by first group power. With this method, less capacitors can be used. For 10th program (P-
10), there is no rule of arranging the steps from low to high. With auto setup, capacitor steps can be calculated automatically or user can enter the capacitor values manually. User can select used or not used capacitor steps from CAP menu at 10th program. RG-B/BS series counts the number of switch on/off of every capacitor step and switches on required steps every time. With this method, it prolongs capacitors life time duration. Enter your required program by following the steps below.
Press SET button for 3 sec. and select Auto option.
Press SET button and enter AUto menu. (A-on is displayed)
Select A-on or A-oF option by using UP/DOWN buttons.
In order to activate the selection, press SET button.
Press SET button for 3 sec.
Select Prog menu by using UP/DOWN buttons.
Press SET button in order to see preset program number (Exp: 10).
Select desired program number (1-10) by using UP/DOWN buttons
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save your changes or ESC button to exit without saving.
Phase Angle Setting
Phase angle is changed for all possibility of current and voltage connections in this menu. If user knows phases, which are connected to measurement inputs, phase angle can be set manually in this menu. Automatic setup (ASEt) is recommended for this application. At the end of ASEt application, present connection is displayed at this menu.
-It can be programmed between 0 and 360 in 30 degree differences (0, 30, ...., 330).
Press SET button for 3 sec.
Select trF menu by using UP/DOWN buttons.
Press SET button and select Utr option.
Select An9L/U-no option by using UP/DOWN buttons.
Press SET button to enter Phase Angle / Operating Voltage value.
Enter phase angle between -150° to 180° (programmed 30 degress differences) or operating voltage value by using UP/DOWN buttons (Use SET or ESC button to set next digit or previous digit)
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save or ESC button to exit without saving.
Operating Voltage Programming
Nominal voltage of the network where the device is connected in this menu. For insuring a true compensation, measured voltage value must be higher than min. 0.5 times of programmed nominal network voltage.
Select trF menu by using UP/DOWN buttons.
Press SET button and select Utr option.
Select Utr / Ctr option by using UP/DOWN buttons.
Press SET button to enter Voltage / Current Transformer Ratio.
Enter VT or CT ratio between 1-2000 by using UP/DOWN buttons. (Use SET or ESC button to set next digit or previous digit)
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save or ESC button to exit without saving.
Voltage Transformer Ratio
VT ratio can be set between 1-2000. This value must be the Voltage Transformers ratio. Exp: For 34,5 KV / 100 V voltage transformer, VT ratio must be entered as 345.
L2
L3
Phase 0°
L2
L3
Phase 180°
L2
L3
Phase 240°
L2
L3
Phase 60°
L2
L3
Phase 120°
L2
L3
Phase 300°
L2
L3
Phase 30°
L2
L3
Phase 210°
L2
L3
Phase 150°
L2
L3
Phase 330°
L2
L3
Phase 270°
L2
L3
Phase 90°
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
PROGRAM SEQUENCE
01 02 03 04 05 06 07 08 09 *10
linear
1.1.1.1................
1.1.2.2................
1.2.2.2................
1.2.3.3................
1.2.4.4.................
1.1.2.4................
1.2.3.4................
1.2.4.8................
Any sequence can be selected by user.
Available Programs
Please look at the rear label of the device
(0.9-1.1)xUn 50mA-5.5A 50 Hz / 60 Hz 1% ±1digit (V,I,Cosj), 2%±1 digit (W, VAr, VA) <2 VA(Current) 3 VA - 10 VA (Voltage) 5 A, 250 V AC, 1250 VA 110V AC ~ 250 V AC In case of power failure longer than 20 msec., all capacitor steps are disconnected automatically.
-0.800 ... +0.800
-0.800 ... +0.800 1 - 2000 1 - 2000
Switching on&off and discharge times can be set seperately between 2-1800 sec. 6, 8(PR-16, PR-19), 12(PR-16) Selectable.
-5° C - 55° C
00.0 - 100 °C Red LED Display with 4 Digits Double Insulation ( )
2.5 mm
2
IP 00 IP 40 (front panel) Terminal Type PR19, Type PR19 91x91 mm(PR-19), 139x139 mm(PR-16)
0.85 kg.(PR-16), 0,45 kg.(PR-19)
1-247
1.200 Kbps, 2.400 Kbps, 4.800 Kbps, 9.600 Kbps, 19.20 Kbps, 38.40 Kbps no, odd, even
1,000 0,900 P-10 10 sec. 10 sec. 14 sec.
265.0 V AC
3.0 sec. oF
5.0%
3.0 sec. oF
25 15 240 hour
55 °C oF 53 °C
45 °C 40 °C
1 1 0° 230 V
1
9.600 Kbps no 1234 oFF
Operating Voltage (Un) Operating Voltage Ratio DU Operating Current Range DI Frequency Measurement Class
Power Consumption
Output Contact Generator Input No-Volt Feature
Setting Range
COS1 Setting COS2 Setting CT Ratio VT Ratio
Switching on&off and, Discharge Time Setting
Step Number Over Voltage Value Ambient Temp. Range Measurement Temp. Range Display Equipment Protection Class Cable Section (for terminals) Terminal Protection Class Box Protection Class Connection Type Dimension Panel Cut-out Weight RS-485 Communication*
Address Baud Rate Parity
Default Factory Settings
Target COS1 Target COS2 Program
t-on (Switching on delay) t-off (Switching off delay) Discharge time
Over Voltage
Delay Step Protection
Over Harmonic
Delay Step Protection
Inductive Ratio Range Capacitive Ratio Range Ratio Time
Temperature Protection
Alarm Value Step Protection Lower Alarm
Fan Setting
Operation Temperature Lower Temp. Value
CT Ratio VT Ratio Connection Angle Nominal Line Voltage RS-485 Communication
Address Baud Rate Parity
Password Password Activation
Technical Features
: : : : :
:
: : :
: : : :
:
: : : : : : : : : : : : :
: : :
: : : : : : : : : : : : : : :
: : :
: : : : : :
: : : : :
POWER FACTOR CONTROLLER
RG-6B/BS/8B/BS/12B/BS
3
In case of any failure, alarm relay is switched on and alarm led lights. When measured temperature value increase fan measured value after 10 second fan led light will be on. The LEDs of the steps that are to be switched on or off. They indicate the switched on steps for compensation. The LED of the switched on step lights up. Indicates if the operating mode is automatic or manual. (If it is continuously ON, RG-B/BS series operates in Automatic Mode. If it blinks, RG-B/BS series operates in Manual Mode) Press SET button for 3 seconds, when Cosj/Auto Setup LED is open, automatic setup is done. In measurement mode Cosj value is displayed. Press SET button for 3 seconds, when V / Cosj LED is open COS1 and COS2 is programmed. In measurement mode voltage value is displayed. Press SET button for 3 seconds, select PROGRAM/I light to select power sequence program. In the measurement mode, current values of related phases are displayed. Press SET button for 3 seconds, select TIME/W led to set switching on delay time, switching off delay time and discharge time. In the measurement mode, active power value is displayed. Press SET button for 3 seconds, select CAPACITORS/VAr led to set capacitor values and capacitor connections (AUto, on, oFF). In the measurement mode, reactive power values are displayed. Press SET button for 3 seconds, select RESET/VA LED for erasing alarms. In measurement mode apparent power value is displayed. Press SET button for 3 seconds, select NETWORK/% LED to set current transformer ratio (Ctr), Voltage transformer ratio (Vtr), phase angle (AngL) and capacitor nominal voltage value (U-no) is set. In measurement mode inductive and capacitive ratio values are displayed as %. Press SET button for 3 seconds, select ALARM / °C LED to set alarms for over voltage, reactive/active ratio, temperature and harmonics. In measurement mode temperature is displayed.
1.
2.
3. 1,2,...,8 LEDs
4. OTO/MAN LED
5. Cosj /Auto Setup LED
6. V / Cosj LED
7. I / Program LED
8. W / Time LED
9. VAr / Capacitor LED
10. VA / Reset LED
11. % / Network LED
12. °C / Alarm LED
: :
:
:
:
:
:
:
:
:
:
:
Press SET button 3 seconds, select RS-485/THD LED for setting address, baudrate and parity values for RS-485 communication protocol. In measurement mode THD values (19th harmonics) is displayed by pressing SET button. Press SET button 3 seconds, select PIN/ERR LED for setting and changing password in measurement mode if any error happens this LED will be on (If there are more than one error, errors code is displayed by pressing SET button). Go to next menu or increase related value. Exit from a menu. In the measurement mode, it is used to exit from harmonic menu. Enter to a menu or confirm the data entry. In the measurement mode, it is used to observe the harmonic values of current, voltage and power values. Go to the previous menu or decrease related value. This LED represents that RG-B/BS is waiting to switch capacitor steps on. This LED represents that RG-B/BS wil not switch any capacitor steps on&off This LED represents that RG-B/BS is waiting to switch capacitor steps off. If capacitor is not connected to the related step, 
 lights is ON. If reactive energy ratios exceed adjusted set values, % led lights. If voltage harmonic ratios exceed adjusted set values, 
 led lights. When the value of voltage exceeds adjusted set value or devices measured the value of voltage less than 30V or when devices can not measure current during auto setup, V> light is ON. Represents measurement values with kilo unit (x10
3
).
Represents measurement values with mega unit (x10
6
).
13. THD / RS-485 LED
14. Err / Pin LED
15. Up Button
16. Esc Button
17. Set Button
18. Down Button
19. C+ LED
20. Normal LED
21. C- LED
22.
23.
24.
25. V>
26. k LED
27. M LED
:
:
: :
:
: : : : : : : :
: :
Delay Time Setting
Switch ON delay (ond), Switch OFF delay (oFd) and discharge time (rC) is programmed for the steps in this menu. Delay time can be set between 2 and 1800 seconds in this menu.
Press SET button for 3 sec.
Select dELy menu by using UP/DOWN buttons.
Press SET button and select ond parameter. (Exp:10)
Select ond / oFd / rC option by using UP/DOWN buttons.
Press SET button.
Enter delay time between 2-1800 sec. by using UP/DOWN buttons. (Use SET or ESC button to set next digit or previous digit)
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save your changes or press ESC button to exit without saving.
NOTE: Icon explanations are the same for type PR-19 and PR-16 models. The figure above shows the front panel of PR-19 RG-B/BS 08. The step numbers of the device shown with number 3 will change according to the model number.
4
27
22
26
31 2
5 6 7 8
9 10 11
12 13 14
15 16 17
18
23
24
25
19
20
21
4
A4182/Rev.7
POWER FACTOR CONTROLLER
RG-6B/BS/8B/BS/12B/BS
These programs are set for protecting capacitors by user.
Programmable Alarm Protection
Over Voltage Protection Setup
This protects capacitors from over voltage. It has 3 parameters. SP-U : It can be programmed between 0-500 V. Setting to 0 means alarm is turned off.
dELy : Delay time. It can be programmed between 0-999.9 sec. CAP : It shows step state in alarm condition. Selecting on will cause
the steps to remain the same. Selecting oF will cause to switch off the capacitor steps.
Over THDV Protection Setup
Device gives an alarm if THDV value exceeds entered set value. It has 3 parameters. SP-t : THD% can be set between 0-99.9. Setting to 0 means alarm is turned off.
dELy : Delay time. It can be programmed between 0-9999 sec. CAP : It shows step state in alarm condition. Selecting on will cause
the steps to remain the same. Selecting oF will cause to switch off the capacitor steps.
Ratio Protection Setup
Device gives an alarm if the capacitive and inductive ratio exceeds the value entered by the user in programmed time. It has 3 parameters. ýnd : Ýnductive ratio can be set between 0-99.9 %. Setting to 0 means alarm is turned off. CAP : Capacitive ratio can be programmed between 0-99.9 %. Setting to 0 means alarm is turned off.
HoUr : Programmed between 1-240 hours. NOTE : Device shows ýnd and CAP ratios according to programmed xxx hour, so user can see parameters only for last xxx hours.
Over Heat Protection Setup
After the temperature measured by the device increases the set value and stays over that value for 10 seconds, device gives an alarm. It has 3 parameters.
SP-H : Temperature alarm turned off down. SP-L : Back to temperature alarm value can be set between 0-99.9 °C.
A value higher than SP-H can not be used. CAP : It shows step state in alarm condition. Selecting on will cause the steps to remain the same. Selecting oF will cause to switch off the capacitor steps.
This function is used for switching-on and switching-off the fan output contact according to measured temperature. There are two submenus as F-on and F-oF. F-on : This is the assignment menu for programming the switch-on temperature value. After the temperature measured by the device increases the set value and stays over that value for 10 seconds, contact will be switched-on and fan LED will be on. Value can be defined between 00.0-
99.8 °C. If this value is set as 0.00, fan function will be disabled and F­oF value will be set as 00.0 automatically. F-oF : This is the assignment menu for programming the switch-off temperature value. A value higher than F-on can not be used.
Fan Relay Settings
Monitoring the measured temperature
In order to make a correct measurement, device must be in operation at least 30 min. In order to observe the measured environmental temperature, press UP/DOWN buttons untill flashing C°/Alarm LED.
Related Alarm LED is on if any failure is occured for any reason. When user wants to monitor the errors, UP/DOWN buttons are used until the E-xx number is displayed. All the error codes are displayed respectively by pressing the SET button. This parameter is not displayed if there is no error. For example, E-07 means over voltage condition error.
Displaying the Alarm Codes which are given by the device
NO DESCRIPTION REASON
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
ALARM CODES
Optional
Angle between phase voltages doesnt equal to 120° Reverse phase sequence One or more phase voltages dont exist Phase 1 Current Phase 2 Current Phase 3 Current THD for voltage exceeds the preset value Voltage value of any phase exceeds the preset value Reactive capacitive ratio exceeds the preset value Reactive inductive ratio exceeds the preset value Temperature of the capacitors exceeds the preset value Automatic connection could not be found Over compensation Insufficient compensation Phase sequence is not correct Capacitor power for phase 1 is not appropriate Capacitor power for phase 2 is not appropriate Capacitor power for phase 3 is not appropriate Capacitor step 1 is defected Capacitor step 2 is defected Capacitor step 3 is defected Capacitor step 4 is defected Capacitor step 5 is defected Capacitor step 6 is defected Capacitor step 7 is defected Capacitor step 8 is defected Capacitor step 9 is defected Capacitor step 10 is defected Capacitor step 11 is defected Capacitor step 12 is defected
Neutral and Voltage terminal connections may be wrong Voltage terminal connections may be in counter clockwise direction Voltage terminal connections may be wrong Current transformer connections for phase 1 may be wrong or fist capacitor step may be defected Current transformer connections for phase 2 may be wrong or first capacitor step may be defected Current transformer connections for phase 3 may be wrong or first capacitor step may be defected Excessive harmonic may be exist in the system Voltage value of the system may be increased Compensation Error Compensation Error Over Temperature Defected capacitor step or variable loads Target Cosj is capacitive even if all capacitor steps are switched off Capacitor powers are not sufficient for target Cosj 3-phase capacitor powers were not selected properly Capacitor powers for phase 1 were not selected properly Capacitor powers for phase 2 were not selected properly Capacitor powers for phase 3 were not selected properly In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown In the capacitor step measurement, 3-phase capacitor step is unbalanced or the fuse of any phase is blown
LED
Loading...