POWER FACTOR CONTROLLER
RG-6B/BS/8B/BS/12B/BS
CURRENT and VOLTAGE TRANSFORMER RATIO SETTINGS,
PHASE ANGLE and NETWORK VOLTAGE PROGRAMMING
In order to have correct power values for capacitor steps, current and voltage transformer
ratios must be entered correctly. Current and voltage transformer ratios are entered
in trF menu. If no value is entered in the menu, these ratios are assumed to be 1
and capacitor powers are calculated according to these values.
Current Transformer Ratio
CT ratio can be programmed between 1 and 2000. This value must be the Current
Transformers ratio.
Exp: For 150 A/5 A current transformer, CT ratio must be entered as "30".
Program Selection
Press SET button for 3 sec.
2
Step Number Setting
The maximum number of steps that the device can control depends on the device
model. It can be 6, 8 or 12 . Each of these steps can be programmed oFF, oN or
Auto in the
10th
program.
AUto : Programming capacitor power (kVAr) menu.
on : Capacitor programmed as a steady.
oFF : Meaning of there is no capacitor connection at output.
When other programs are selected, 1st steps capacitor power can be programmed.
Other steps power can be programmed according to selected program.
* Recommended program mode.
RG-B/BS series has 10 different program modes which determines the power ratio
sequences of capacitor steps. These are given on the tables below.
If capacitors sequence is set just like 2nd program (P-02) (1.1.1.1.....), many identical
connection compenents are required. Selecting between 3th program (P-03) to 8th
program (P-08),less connection components are used (exp: 1.2.2......). 9th program
(P-09) provides different group powers. 9th programs capacitor sequence working
principle is one groups power can be higher than previous groups sums by first
group power. With this method, less capacitors can be used. For 10th program (P-
10), there is no rule of arranging the steps from low to high. With auto setup, capacitor
steps can be calculated automatically or user can enter the capacitor values manually.
User can select used or not used capacitor steps from CAP menu at 10th program.
RG-B/BS series counts the number of switch on/off of every capacitor step and
switches on required steps every time. With this method, it prolongs capacitors life
time duration. Enter your required program by following the steps below.
Press SET button for 3 sec. and select Auto option.
Press SET button and enter AUto menu. (A-on is displayed)
Select A-on or A-oF option by using UP/DOWN buttons.
In order to activate the selection, press SET button.
Press SET button for 3 sec.
Select Prog menu by using UP/DOWN buttons.
Press SET button in order to see preset program number (Exp: 10).
Select desired program number (1-10) by using UP/DOWN buttons
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save your changes or ESC button to exit without
saving.
Phase Angle Setting
Phase angle is changed for all possibility of current and voltage connections in this
menu. If user knows phases, which are connected to measurement inputs, phase
angle can be set manually in this menu. Automatic setup (ASEt) is recommended for
this application. At the end of ASEt application, present connection is displayed at
this menu.
-It can be programmed between 0 and 360 in 30 degree differences (0, 30, ...., 330).
Press SET button for 3 sec.
Select trF menu by using UP/DOWN buttons.
Press SET button and select Utr option.
Select An9L/U-no option by using UP/DOWN buttons.
Press SET button to enter Phase Angle / Operating Voltage value.
Enter phase angle between -150° to 180° (programmed 30 degress
differences) or operating voltage value by using UP/DOWN buttons
(Use SET or ESC button to set next digit or previous digit)
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save or ESC button to exit without saving.
Operating Voltage Programming
Nominal voltage of the network where the device is connected in this menu. For insuring
a true compensation, measured voltage value must be higher than min. 0.5 times of
programmed nominal network voltage.
Select trF menu by using UP/DOWN buttons.
Press SET button and select Utr option.
Select Utr / Ctr option by using UP/DOWN buttons.
Press SET button to enter Voltage / Current Transformer Ratio.
Enter VT or CT ratio between 1-2000 by using UP/DOWN buttons.
(Use SET or ESC button to set next digit or previous digit)
Press SET button to confirm your selection.
Press ESC button until SAVE is displayed.
Press SET button to save or ESC button to exit without saving.
Voltage Transformer Ratio
VT ratio can be set between 1-2000. This value must be the Voltage Transformers
ratio.
Exp: For 34,5 KV / 100 V voltage transformer, VT ratio must be entered as 345.
L2
L3
Phase 0°
L2
L3
Phase 180°
L2
L3
Phase 240°
L2
L3
Phase 60°
L2
L3
Phase 120°
L2
L3
Phase 300°
L2
L3
Phase 30°
L2
L3
Phase 210°
L2
L3
Phase 150°
L2
L3
Phase 330°
L2
L3
Phase 270°
L2
L3
Phase 90°
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
Auxiliary
Supply
Voltage
Measurement
Input
Current
Measurement
Input
PROGRAM SEQUENCE
01
02
03
04
05
06
07
08
09
*10
linear
1.1.1.1................
1.1.2.2................
1.2.2.2................
1.2.3.3................
1.2.4.4.................
1.1.2.4................
1.2.3.4................
1.2.4.8................
Any sequence can be selected by user.
Available Programs