MCB-200 MULTIFUNCTION DIGITAL TIME RELAY With 1 CO contact Operating Manual
Dudullu OSB; 1. Cadde; No: 23 34776 Umraniye - ISTANBUL / TURKEY Tel : +90 216 313 01 10 Fax : +90 216 314 16 15
Page 2
1
2
Precautions for Installation and Safe Use
If below precautions are not properly observed and carried out, it may result in cases with injury or death.
· Disconnect power before working on the device.
· When device is connected to the network, do not remove the front panel.
· Do not clean the device with solvent or similar items. Only clean with dry cloth.
· Verify correct terminal connections before energizing the device.
· Install the device on the electrical panel.
· Contact your authorized reseller in case problems occur with your device.
·No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences rising out of not following above precautions.
1. INTRODUCTION
MCB-200 is a multifunction digital timer with 1 CO contact. It offers wide time adjustment range between 0.2-9999 seconds and 0.1-9999 minutes.
MCB-200 has 15 different functions with wide adjustable time ranges. The main application area is the industrial and automation control systems. Wide supply voltage range and one output relay with C/O contacts offer the highest flexibility for many applications. MCB-200 has two dry contacts for START and STOP inputs
1.1 Product Features
MCB-200 has the following features:
· Lithium battery
· 15 different functions
· 0.2-9999 seconds/0.1-9999 minutes time range
· 1 relay output
· Start-Stop dry contact inputs
· Custom design LCD with green backlight
· SET, ESC, UP, DOWN buttons are located on front panel for easy programming
· Degree of protection for enclosure IP 40, for terminals IP 20
· PK25 DIN Rail mounting
1.2 Hardware Features
To operate functions with external triggering, MCB-200 has the necessary START and STOP dry contacts.
LCD
UP BUTTON
SET BUTTON
ESC BUTTON
DOWN BUTTON
Stop
Start
4 5 6
C NC
NO
R1
Page 3
3 4
1.2.1. Display
1.2.3 Output
MCB-200 has one changeover relay output. According to VDE 0110 and IEC 60947-1 standards; switching capacity of relay output is 8A, 2000VA, 250 V. and maximum electrical life time is 1x 10^6.
1. ONSrt : Indicates that the relay will start as closed.
2. OFFSrt: Indicates that the relay will start as open.
3. Srt-Input Icon: Indicates that the function is started with external input.
4. Indicates whether function trigger is Level or Edge.
5. Battery 6 and 8. min sec : Indicates whether timing unit is minute or second
7. Time setting indicator for Star-Delta function
9. Numeric Two Digits: Show function number.
10. Stop: Indicates that stop input is active. Start: Indicates that stop input is active.
11. When R1 or R2 relays are activated, the center of the circles are turned on. R and L letters are used to indicate left or right direction when inverser relay function is selected. Star-Delta: Indicate the output relay state in Star-Delta function.
12. Indicates the time type of functions.
13. In the main menu, it shows the elapsed time.
14. In the main menu, it shows the entered time. In the settings menu, it shows the function names.
1.2.2 Button functionality
SET, ESC, UP and DOWN buttons help to select functions and set their times.
UP button goes to previous menu item in Settings Menu and increase selected parameter value. DOWN button goes to next menu item in Setting Menu and decrease selected parameter value. SET button is for entering data. When pressed at least 3 seconds, Setting Menu is selected. ESC button exits from a menu.
Page 4
6
1.2.4 Inputs
1.2.4.1 Start Input and Stop Input:
These inputs are voltage-free dry inputs. Start Input: For some of the functions, output depends on the state of the start input or input pulses from start input. When user shorts two terminals of this input, start input activates. Stop Input: When stop input applies, the timing pauses with stop input's leading edge. When stop input is removed, the timing continues to count from it's last value with stop input's trailling edge. Stop input affects all functions as the same without any exception. When user shorts two terminals An Example: This function needs td delay time to release relay. When stop input is applied, it stops counting and saves the time t1. With stop input's trailing edge, counting continues from the saved time t1 until delay time td (Here td=t1 + t2). While stop input is active, the relay doesn't change its position.
5
2. OPERATING INSTRUCTIONS
When the device is taken out of the box, an installation menu will be displayed. Language and function settings are done in this menu as seen in the figure below. Afterwards, device returnss to main menu and starts operating.
Stop : Stop Input R : R1 Relay td : Delay Time t1 : Time elapsed until Stop Input is activated (t1<td) t2 : Time elapsed after Stop Input is deactivated (td=t1+t2)
ON
OFF
Page 5
8
7
1. On Delay / Start by external trigger leading edge
This funcition is controlled by start input. Time counting starts with the leading edge of the start pulse; at the end of time td the output relay is activated and remain activated while start input pulse is ON
Basic settings map is shown below. There are two main submenus as function selection and display settings. Function Selection Submenu: A new function is set from function selection menu. In this submenu, user chooses a function, sets t parameter/parameters for selected function; assigns relay output. Display Configurations Submenu: Changing password, adjusting contrast, activating backlight or changing language is done from this submenu.
S : Start Input R : R1 Relay td : Delay Time
<td
td
td
R
S
OFF
ON
NO
C
<td
Page 6
9 10
2. On Delay / Start by external edge re-trigger
This funcition is controlled by start input. Time counting starts with the leading edge of the start pulse; at the end of time td the output relay is activated and remain activated until next start pulse is applied.
3. Off Delay / Start by external trigger trailing edge
This function is controlled by start input. Output Relay is activated when start pulse is applied and remain on; time counting starts with the trailing edge and output relay is deactivated at the end of delay time td lf trigger pulse occur during time counting period, elapsed time is reset.
R
S
OFF
ON
NO
C
td td
R
S
OFF
ON
NO
C
td
Page 7
1211
4. Symmetric Flasher / Start by external trigger leading edge / Relay ON start
This function is controlled by start input. With the leading edge, output relay is activated and remain on during ton. After that, it is deactivated and  toff  starts. This cycle is repeated while start pulse is on (high).
5. Symmetric Flasher / Start by external trigger leading edge / Relay OFF start
Function is similar to the ON Start version (function 4) with the exception that the output relay start as passive.
ON
KAPALI
S
R
NO C
OFF
OFF
S
R
NO C
ON
Page 8
S
R
NO
C
OFF
ON
ton ton ton ton ton
ton
toff toff toff toff
13 14
6. Asymmetric Flasher / Start by external trigger leading edge / Relay ON start
This function is controlled by start input. With the leading edge, output relay is activated and remain on during ton. After that, it is deactivated and  toff  starts. This cycle is repeated while start pulse is on (high).
7. Asymmetric Flasher / Start by external trigger leading edge / Relay ON start
Function is similar to the ON Start version (function 6) with the exception that the output relay start as passive.
S
R
NO
C
OFF
ON
toff toff toff toff toffton ton ton ton ton
Page 9
15 16
8. Symmetric Flasher / Start by external edge - retrigger / Relay ON start
This function is controlled by start input. With the leading edge, output relay is activated and remain on during ton. After that, it is deactivated and toff starts. This cycle is repeated until the next edge­ retrigger pulse. If a trigger pulse occur during ton, time counting is reset and ton time counting is restarted.
9. Symmetric Flasher / Start by external edge - retrigger / Relay OFF start
Function is similar to the ON Start version (function 8) with the exception that the output relay start as passive.
ON
KAPALI
S
R
NO C
OFF
ON
KAPALI
S
R
NO C
OFF
Page 10
17
18
10. Asymmetric Flasher / Start by external edge - retrigger / Relay ON start
Function is similar to the Symmetric version (function 8) with the exception that ton and toff times can be set differently.
11. Asymmetric Flasher / Start by external edge - retrigger / Relay OFF start
Function is similar to the Symmetric version (function 9) with the exception that ton and toff times can be set differently.
R
S
OFF
ON
NO
C
ton ton ton ton tontoff toff toff toff
R
S
OFF
ON
NO
C
toff toff toff toff toffton ton ton ton tont
Page 11
19 20
12. Adjustable ON Delay by external trigger leading edge
This function is controlled by start input. The cycle starts with adjustable toff delay time. At the end of delay time, output relay is activated and remain activated during ton. If the Start input is deactivated and activated, function will be reset.
13.Adjustable and Resettable ON Delay Pulse by external trigger leading edge
This function is controlled by start input. The cycle starts with adjustable toff delay time after a pulse is created at the Start input. At the end of delay time, output relay is activated and remain activated during ton. If a re-trigger pulse occurs during toff, elapsed time is reset and toff counting is restarted.
S
ON
OFF
R
NO
C
t1
t1
t2
t1
t
t<t2
S
ON
OFF
R
NO
C
t<t1
t1
t2
t1
t2
Page 12
21 22
14. Adjustable OFF Delay Pulse by External Trigger Leading Edge
This function is controlled by start input. With the leading edge of the external trigger, output relay is activated and remain on during td.
15. Adjustable OFF Delay Pulse by External Trigger Leading Edge Re-trigger
This funcition is controlled by start input. The cycle starts with adjustable td delay time and output relay is activated. It remains activated during this period. If a re-trigger pulse occurs during td period, elapsed time is resett and td counting is restarted.
S
ON
OFF
R
NO
C
t
t
S
ON
OFF
R
NO
C
t
t
Page 13
23 24
2.2 Settings
2.2.1 Function Selection:
Function sub-menu is reached by pressing SET button in Settings menu. The functions that the device offers can be browsed with UP or DOWN buttons. The user selects the desired function enters its adjustment menu by pressing SET button.
Page 14
25 26
2.2.2 Time Setting :
After selecting the function, user sets t value/values according to the application need. Time range for t is between 0.1 seconds-9999 seconds and 0.1 minutes-9999 minutes. Setting starts from left digit towards right digit. User uses UP button to increase value of the digit and DOWN button to decrease. The user presses SET button to move to the next digit on the right and the ESC button to move back to a previous digit. After entering a number, user selects unit (minutes or seconds) by pressing UP or DOWN. Finally, the selected values are stored by pressing SET button.
FUNCTION SETTINGS ON Delay :
Example Interval (0.1 - 9.9) :
Example Interval (10 - 9999) :
0000
SET
ESC
0000
SET
ESC
0030
SET
ESC
003
SET
ESC
SET
ESC
0 003 8 003 8
2000
SET
ESC
2500
SET
ESC
2570
SET
ESC
2578
SET
ESC
2578
s
dk
Page 15
27 28
Flasher :
Single Shot
Page 16
30
29
One Shot :
2.2.3 Display Settings :
In this submenu; user can set password, contrast, backlight, language and return to factory settings. In password submenu, user can activate or deactivate the password. To change password, user enters current password first, then new password twice. User can change contrast level from 1 to 5. Also user can choose the backlight operation as on, off, on for 5 seconds. Five languages as Turkish, English, German, French, Spanish can be selected.
Page 17
31 32
3 MAIN DISPLAY
This is an example to explain main screen use.
- Top line displays the function. In this case; Onstrt (ON start), Strt- Input (Start Input) and Edge Trigger is selected.
- First line displays the set time value; min. icon indicates the time scale.
- Second line displays the elapsed time value; min. icon indicates the time scale
- start icon indicates that Strt-Input is active.
- The number 01 indicate that 1st function is selected.
- icon is turned on and indicate that R1 relay is activated.
When UP or DOWN button is pressed while on the main menu, the name of the selected function is displayed. By pressing the ESC button, main display is accessed again.
Connection Diagram : Dimensions :
TYPE PK25
Page 18
33 34
Technical Features
Input Circuits Battery Battery Life Input Contacts
Time Setting Time Range
Reset Time Repetition Error Time Setting Error
Output Circuits Output Contact Switching Capacity Voltage according to VDE 0110, IEC 60947-1 Maximum Electrical Life
General Features Dimensions
Cable Selection
Weight Installation Enclosure and Terminal Protection Class Operating Temperature
Standards Product Standard
EMC Directives Electromagnetic Compliance ESD HF Radiation Resistance Burst Surge HF Line Emission Low Voltage Directive RoHs Directive
Isolation Data Rated impulse withstand voltage between all isolated circuits Test voltage between all isolated circuits Pollution Category Overvoltage Category
2 dry contacts (Start, Stop)
Selectabale
0.2 . 9999 seconds
0.1 . 9999 minutes < 100 ms ±0.2% of the set time < 0.5 %
1 C/O Contact 8 A , 2000VA 250 V 1x 10^6
Width 36.0 mm Length 90.0 mm Depth 59.7 mm
2,5mm^2 stranded 4,0mm2 solid
0.25 kg Ray Montaj IP40 / IP20 +5...+50 °C
IEC 61812-1 10.1996, EN 61812-1 + A11/8.1999, DIN VDE 0435 part 2021 2004/108/EC IEC 61000-6-2, EN 61000-6-4 IEC 61000-4-2, EN 61000-4-2 (level 3 6 kV / 8 kV) IEC 61000-4-3, EN 61000-4-3 (level 3 10 V/m) IEC 61000-4-4, EN 61000-4-4 (level 3 2 kV / 5 kHz) IEC 1000-4-5, EN 61000-4-5 (level 4 2 kV L-L) IEC 1000-4-6, EN 61000-4-6 (level 2 10 V) 2006/95/EC 2002/95/EC
VDE 0110, IEC 664 (4 kV / 1.2-50 ?s)
2.5 kV, 50 Hz, 1 min. IEC/EN 60664-1, VDE 0110, UL 508 (3) IEC/EN 60664-1, VDE 0110, UL 508 (III)
2 pcs. Lithium Battery 10 years or 1 million relay operations