ENTES EPR-04, EPR-04S User manual

POWERMETER
EPR-04 / EPR-04S
FUNCTIONS OF BUTTONS
When W led lights,it shows max.power values which are measured instantaneously and it shows total max demand values. Also it is used for moving upwards in the menu.
When W led lights,it shows min.power values which are measured instantaneously and it shows total demand values. Also it is used for moving downwards in the menu.
It is used for passing between parameters such as W, Var, VA, KWh, KVArh, cosj. When it is pressed for 3 second, adjustment mode is entered. In the adjustment mode it is used for saving parameters and moving to the sub menu.
ESC
SET
In the adjustment mode, it is used for entering to the upper menu or it is used for quiting from the adjustment mode without saving the values.
1
Using of EPR-04/04S:
Parameters (Cosj; W; VAr; VA; kWh, kVarh) are monitored in L1, L2, L3 displays by scrolling UP/DOWN buttons. Total Active (SW), Total Reactive Power (SVAr), Total Apparent Power (SVA) and Cosj values and average values of these parameters are monitored in 4th display.
Monitoring of Min.,Max. and Max. Demand Values:
Min. and max. values are defined for W, VAr, VA, SW, SVAr, SVA; demand values are defined for W, VAr, VA, SW, SVA, SVAr. If measured instant value is smaller than min. value which was stored before, it is stored as new min. value. If measured instant value is greater than max. value which was stored before, it is stored as new max. value. Demand value is the average value of the measured values in demand time (15 minute). If one of defined parameters is displayed (ie. W) when deman button is pressed min., max or max. demand values are displayed. When an undefined parameter is displayed (ie. Cosj) if demand button is pressed, instant value is continued to display.
H-L-M LEDs
H-L-M LEDs are dedicated to displaying the min., max. and max. demand values according to selected parameters.
H: Maximum Value, L: Minimum Value, M: Max. Demand Value
Energy Pulse Outputs
EPR-04/04S has 2 Energy Pulse Outputs. These outputs give the pulses only for E-1 (Energy Counter). Pul1 and Pul2: In o-1 (Pulse1), o-2 (Pulse2) menus which are in the pulse menu, device give pulse according to selected energy parameters as [Active energy (ACt, A-I, A-E), Reactive energy (rEA, r-L, r-C)]. Please refer to the pulse menu for the coefficients of energies.
Measured Parameters:
Digital Input
EPR-04/04S has 2 digital inputs. Digital inputs have 2 functions:
- When a remote device has activated, situation of this device which is conncected to the digital input, can be monitored according to data register (Battery, thermostat, circuit breaker and motor position).
- Controlling energy counters and determining which energy counter will be active (Example: It is used for measuring of energy separately at the using of network and generator).
General :
EPR-04/04S is a microprocessor based device which is developed for measuing the power and energy values in an Electrical Network. Measured parameters are displayed in 4 displays separately EPR-04S has an MODBUS serial communication interface.
Cosj AI ( kWh) (Import Active Energy)SW (Total Active Power) W (Active Power) AE (kWh) (Export Active Energy)SVAr (Total Reactive Power) VAr (Reactive Power) rI (kVArh) (Import Reactive Energy)
S
VA (Total Apparent Power)
VA (Apparent Power) rE(kVArh) (Export Reactive Energy)
(This menu is not available in the devices which are adapted with CT-25.) In this menu, current transformer ratio is set between 1 - 2000.
Current Transformer Ratio Setup
Note: If the current transformer is not used between the system and EPR-04/04S, current transformer ratio is entered as 1. Example: If a current transformer which has a ratio of 250/5A is used between the system and EPR-04/04S; Current transformer ratio is entered as 50 (250/5).
Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted devices, trA Fo trn is displayed instead.) (Not: trA Fo Utr menu can be displayed by scrolling the UP/DOWN buttons.)
Press SET button. Blinking the first digit of displayed value appears. (trA Fo Utr menu can be programmed similarly.)
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button, trA Fo Ctr / trA Fo trn / trA Fo Utr is displayed. on can be selected by scrolling UP/DOWN buttons.
(Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press SET button for 3 seconds (trA Fo menu is displayed)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
If user password is activated and set button is pressed for 3 seconds, a pin code is required in order to enter to the menu.
A3615/Rev.5
8
POWERMETER
EPR-04 / EPR-04S
TECHNICAL DATA
Operating Voltage (Un) : Please look at the back labels on
the device Operating frequency (f) : 45-65 Hz Auxiliary supply Power Consumption : < 4 VA Measuring Input Power Consumption : < 1VA V
In
: 10-300VAC 45-65Hz. (L-N)
: 10-500VAC 45-65Hz. (L-L) I
In
: 0.05 - 5.5 A~
2-120 A ~ (for CT-25) Measuring Range :
0...215 M(W,VAr,VA)
: 999999999.999 kWh,kVArh
Measuring Category : CAT III Class : 1±1digit [(%10-%110) xFull Scale] Voltage Transformer Ratio : 0.1 ... 4000.0 Current Transformer Ratio : 1 ... 2000 Max. Ctr x Vtr : 40.000
Demand Time : 1-60 min. (programmable) Serial Interface (for EPM-04S) : MODBUS RTU (RS 485)
: Optically Isolated, programmable Baud Rate (for EPM-04S) : 2400-38400 bps Address (for EPM-04S) : 1-247 Parity (for EPM-04S) : No , odd, Even, 8 Data Bits, 2 Stop Bits Pulse Output : NPN Tr
ansistor
Switch Period :
Min. 100 msec pulse perriod
80 msec pulse width
Operation Current : Max. 50 mA
Operation Voltage : 5.....24 V DC, max. 30 VDC
Input : 12...48 V DC Ambient Temprature : -5°C; +50°C Display : Red LED Display Dimensions : PR-19, PK-26 Equipment Protection Class : Double Insulation-Class II ( ) Box Protection Class : IP 40 Box Material : Non-flammable Installation : Panel Mounted (PR-19)
Rail Mounted (PK-26)
Wire Crossection (for terminal block) : 2.5 mm²
Weight : 0.45 kg (PR-19, PK-26) Installation Category : Class III
Trafo :
Ctr (Current Transformer Ratio) : 0001 trn (Turn number for CT-25 device): 01 Utr (Voltage Transformer Ratio) : 0001.0 CAL (Calculation Method) : 1
Pin : 0000 (Not Activated)
RS-485 :
Adr (Address) : 1 Bau (Baud Rate) : 9600 PAr (Parity) : no
Eng Cnt :
E-1 (Energy Counter 1) : on E-2 (Energy Counter 2) : on
PULSE :
rAt ýo (Ratio) : 1k o-1 (Output 1) : A-I o-2 (Output 2) : r-L
dEtý (Delay Time) : 15
Factory Settings
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment..
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Calculation Methods for Active / Reactive Power Values
If the led on the most right side blinks it represents that active / reactive powers direction is inversed. There are two methods for calculating total active and total reactive powers:
1) Active / Reactive power can be calculated by summing import and export values and displaying as a single value.
2) Active / Reactive power can be calculated according to direction as import / export.
Note :
1) The dot at the most right digit of the fourth display (During SW is displayed) represents that displayed value is export active power value. Vice versa, displayed value is import active power value.
2) The dot at the most right digit of the fourth display (During SVAr is displayed) represents that displayed value is capacitive reactive power value. Vice versa, displayed value is inductive reactive power value.
3) The displayed parameter will not change if power is off after 30 seconds of stand-by (ie. W).
Phase
Displays
Total Display
SET button
Max. LED
Minimum LED Demand LED
ESC button
UP
button
DOWN button
In CT-25 (120A) compliant models, only CT-25 current transformer must be used.
Other type of CTs have a high risk to damage to device.
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
Total Display
SET button
Max. LED
Phase Displays
UP button
DOWN button
Minimum LED Demand LED
ESC button
POWERMETER
EPR-04 / EPR-04S
7
POWERMETER
EPR-04 / EPR-04S
2
Reactive Energy Calculation Method Setting
Press SET button for 3 seconds (trA Fo menu is displayed)
Press SET button (trAFo Ctr menu is displayed)
Press SET button (Calculation value 1 blinks)
Press set button, CAL CLt is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps.
Press ESC button one by one until SAUE SEt yES is displayed.
Press SET button. When SAUE SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
By using UP-DOWN buttons, find CAL CLt menu.
By using UP-DOWN buttons, select energy calculation method.
ESC
SET
SET
SET
SET
SET
Press SET button for 3 seconds (trA Fo menu is displayed)
By using UP-DOWN buttons find dE tý menu.
Press SET button (First digit blinks.)
By using UP-DOWN buttons, enter the value to the first digit.
Press SET button (Second digit blinks)
In this menu, demand time is set between 1-60 minutes.
By using UP-DOWN buttons, enter the value to the second digit.
Press SET button, dE tý is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press ESC button one by one until (SAU E SEt yES) is displayed.
Press SET button. When SAU E SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
Press SET button 3 seconds (trA Fo menu is displayed)
By using the UP-DOWN buttons find the rES Et menu.
Press SET button.(rES Et HL menu is displayed)
Press SET button, (Data is entered but is not activated yet. For activating the new data please follow the below steps).
Press SET button. When SAUE SEt yES is displayed, if you press ESC button or choose no option instead of yES option by using UP-DOWN buttons, new data will be cancelled and previous value will be activated.
By using the UP-DOWN buttons, other parameters can be selected. If you want to delete the value, choose yEs, if not choose no.
Monitoring and Erasing of minimum and maximum values:
In this menu, values of min., max., demand or energymeters are erased. It saves the instantaneously measured min. and max. values of EPR-04/04S into its memory. Please kindly look at to the section of FUNCTIONS OF BUTTONS for min. and max. values.
SET
ESC
SET
SET
SET
Press ESC button one by one until SAUE SEt yES is displayed.
Programming the Turn Number:
Note: If the voltage transformer is not used between the system and EPR-04/04S, voltage transformer ratio is entered as 1. Example: If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and EPR-04/04S; Voltage transformer ratio is entered as 345. (34500/100)
Voltage Transformer Ratio Setup
In this menu, voltage transformer ratio is set between 0000,1 - 4000,0.
Demand Time Setup:
This menu is available for CT-25 adapted devices. User enter the turn number, which is the number of how many tour the current cable has rounded into the CT-25. Numbers can be selected between 1-20. Greater the number of turn means greater the sensivity.
0
2
4
1
3
5
Description
It is the most preferred reactive power calculation methode.
Total value of the multiplication of V
n
and In values up to 19 th harmonics. This calculation methode is mostly preferred for network analysers.
S
Vn.In.sin(jn)
n=1
¥
Reactive Energy
(Q)
Digital Energymeter
(Each phase seperately)
Mechanical Energymeter
(Vectoral summation of 3-phase)
90° rotation of voltage vector and multiply with current
S2-P
2
S2-P
2
Power Triangle Methode : According to this methode; Q = (Q : Reactive power, S : Active power, P : Apparent power)
Three different methods exist for reactive energy calculation in EPR-04/04S. Brief informations about these methods are explained in below table. Related values which must be entered in the menu are also indicated in the table in order to select reactive power calculation method for mechanical and digital energymeters.
Note:
Measured electrical parameters which are saved to the memory are not affected from the electric interruptions. In the rES Et dE E-1 / E-2 menu; when you choose yES and quit from all menus, if you confirm the changes, min. and max. values of all parameters or values of energymeters are erased at the same time. Follow the below steps in order
to erasing the values of min., max., E-1 and E-2; In the measurement position.
PK 26
Box Connection Diagram
*Available only for EPR-04S
~
U
n
TR A BGnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
IL2I
L1
+
_
L3
L2
L1
1A
-+-
+
(12-48V DC)
k
l
K L
k
l
K L
k
l
K L
~
U
n
TR A BGnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
IL2I
L1
+
_
Max: 30 VDC
L3
L2
L1
-+-
+
(12-48V DC)
1A
k
l
K L
k
l
K L
~
U
n
TR A BGnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
IL2I
L1
+ _
Max: 30 VDC
L3
L2
L1
1A
-+-
+
(12-48V DC)
k
l
K L
k
l
K L
~
U
n
TR A BGnd
IN2H
IN2L
IN1H
IN1L
PUL2H
PUL2L
PUL1H
PUL1L
I
L3
IL2I
L1
+ _
Max: 30 VDC
N
L3
L2
L1
1A
-+-
+
(12-48V DC)
k
l
K L
k
l
K L
k
l
K L
Auxiliary
Supply
Voltage Measuring Input
Current Measuring Input
3 Phase neutral
L1
L2
L3
N
RS-485
1
2.00 120
2
1.00
60.0
3
0.66
40.0
4
0.50
30.0
5
0.40
24.0
6
0.33
20.0
7
0.28
17.1
8
0.24
15.0
9
0.22
13.3
10
0.20
12.0
11
0.18
10.9
12
0.16
10.0
13
0.15
9.23
14
0.14
8.57
15
0.13
8.00
16
0.12
7.50
17
0.11
7.05
18
0.11
6.66
19
0.10
6.31
20
0.10
6.00
Note: For CT-25 models:
Auxiliary
Supply
Voltage Measuring Input
Current Measuring Input
3 Phase without neutral current input with Aron wiring configuration
L1
L2
L3
N
RS-485
N
Auxiliary
Supply
Voltage Measuring Input
Current Measuring Input
3 Phase without neutral
L1
L2
L3
N
RS-485
N
Max: 30 VDC
Auxiliary
Supply
Voltage Measuring Input
Current Measuring Input
3 Phase without neutral current input with Aron wiring configuration
L1
L2
L3
N
RS-485
N
k: When CT-25 is used, Red cable is connected to k terminal. l: When CT-25 is used, Black cable is connected to l terminal.