ENTES EPM-4A, EPM-4C, EPM-4D, EPM-4P User guide

Selection of Current Transformer Primary Value (For EPM-4A, 4C, 4D and 4P)
AMMETER EPM-4A / EPM-4C / EPM-4D / EPM-4P
EPM-4A (Ammeter with Demand) : With additional features to EPM-4D, current transformer ratio is selected
as drCt, CT-25 current transformer which can measure between 0,07 A - 200 A must be used.
SET
SET
SET
Press SET button for 3 sec.
Press SET button.
Press UP or DOWN button until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly). Press SET button to save.
5000
Setting of Demand Time (For EPM-4A, 4C, 4D
and 4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until dE t is displayed.
Press SET button. Press UP or DOWN button until requested
value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
0015
0020
Setting of High Setpoint Value (For EPM-4C
and 4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until SP h is displayed.
Press SET button. Press UP or DOWN button until requested
value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
2500
2750
Setting of Low Setpoint Value (For EPM-4C
and 4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until SP L is displayed.
Press SET button.
Press SET button to save.
2500
2250
Press UP or DOWN button until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Setting of Hysteresis Value (For EPM-4C and 4P)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until hYS is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
5.000
6.000
Setting of On Time Value (For EPM-4C and
4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until on t is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Setting of Off Time Value (For EPM-4C and
4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until oF t is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Setting of Start Time Value (For EPM-4C and
4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until Strt is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed. (If buttons are pressed continuously, displayed value is changed quickly).
Press SET button to save.
Setting of Auto Start Mode (For EPM-4C and
4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until AUto is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed.
Press SET button to save.
Setting of Instant Tripping Function (For EPM-4C and
4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until trP is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed.
Press SET button to save.
.
Setting of Turn Number (For EPM-4A, 4C and 4P)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until trn is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed.
Press SET button to save.
0001
0010
MEASUREMENT RANGES
EPM-4D (Ammeter with Demand) : EPM-4D is designed to measure RMS value of AC current which flows
from the line and saving the instant and average demands. The current transformer ratio can be set between 5/5A and 10000/5A by the buttons on the panel.
(drCt is not available for EPM-4D.) (drCt valid when CT-25 is used)
1
EPM-4C (Ammeter with Setpoint) : EPM-4C measures the RMS value of AC current which flows from the
line. If the measured AC current is over the high setpoint or it is under the low setpoint, output relay is switched on at the end of adjusted time delay. Also, it includes all functions of EPM-4A.
EPM-4P (Ammeter with Pick-Up) : In addition to EPM-4C, it also has Pick-Up relay. If the measured AC
current is over the high setpoint or it is under the low setpoint, Pick-Up relay is switched on without delay. If current value returns within preset limits before the end of programmed delay time, Pick-Up relay is switched off without delay.
* Important Notice: The secondary value of current transformer must be limited at 5A.
Turn ( ) : Turn number of cable, which passes inside of CT-25 is selected in this menu. This number can
be selected between 1 and 10. If only drCt is selected under Ctr menu, turn number will be activated.
Demand Time ( ) : Device records measured demand and maximum demand values. Demand is the
average current value measured in demand time. Maximum demand is the maximum average current value measured in demand time. Maximum demand value remains stored, even if the power supply is off and demand value becomes 0 (zero).
Setpoint (s p v e s p
): When the AC current which flows through the device is over the high setpoint
value or it is under the low setpoint value, the output relay is switched on in order to generate an error signal at the end of programmed delay time. If the AC current value returns within preset limits, before the end of the delay time, the relay resets itself and no tripping occurs.
Latch Function ( ) : Latch function is used to select the output relay operation mode. Either oF
or on position may be selected. At position oF: If the current value returns to preset limits, output relay is switched off. At position on: Even if the current value returns to preset limits, output relay remains switched on and switches off only by pressing the Set button.
Instant Tripping ( ) : If the AC current value is over the1,5 times of setting value or it is under the 0,5
times of setting value, the output relay is switched on without any delay time. This function is user-selectable.
Start Time Delay ( ): When the current starts to flow initially, the setpoint values are ignored for the
determined time. If auto start mode is activated, after the AC current is cutted, the device returns into its initial state.
Automatic Start Mode ( ): If this function is disabled (off), start-up delay (Strt) is activated only when
initial current is applied to the measurement input of device. However, when this function is enabled (on), if measured current value decreases to 0 (zero) value and increases again, start-up delay is activated.
Note : If the current on the measurement input of the device is over 6 A or measurement according to entered primary value of current transformer is over 9999 A, there will be hý on the display.
Example: If a current transformer which has a ratio of 80/5 A is used, current transformer primary value is entered as 80.
* Please check the device label for proper value. * Different supply voltages are adjustable upon request.
A3921/Rev.5
AMMETER EPM-4A / EPM-4C / EPM-4D / EPM-4P
Pcs per Package : 16 Pcs (for PR 18) Package Weight : 5 kg Pcs per Package : 12 Pcs (for PR 25) Package Weight : 4,2 kg Pcs per Package : 20 Pcs (for PR 20) Package Weight : 5.5 kg
Packaging Information
Programming of Contact Situation (For EPM-4C and
4P
)
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until oUt is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed.
Press SET button to save.
Dimensions
c
SET
Precautions For Installation and Safe Use
Failure to follow below instructions will result in death or serious injury. Disconnect all power before working on equipment. When the device is connected to the network, do not remove the front panel. Do not try to clean the device with solvent or the like. Only clean the device with a dried cloth. Verify correct terminal connections when wiring. Electrical equipment should be serviced only by your compedent seller. No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material. Only for rack panel mounting.
Warning :
a) A switch or circuit breaker must be connected between the network and the auxiliary supply input of device. b) Connected switch or circuit breaker must be in close proximity to the device. c) Connected switch or circuit breaker must be marked as the disconnecting device
for the equipment. d) The type of the used fuse must be FF type and the current of the used fuse must be 1A. e) No need of a vantilator in the installation area f) Practical user manuel must be put on the panel.
Connection Diagrams
Deleting the Demand Values (For EPM-4A,
4C, 4D
and 4P)
Press UP and DOWN buttons at the same time
Displaying of Max. Demand (For EPM-4A,
4C, 4D
and 4P)
Press and hold the UP button to see the max. demand value
Displaying of Demand (For EPM-4A
, 4C, 4D
and 4P)
Press and hold the DOWN button to see the demand value.
Escaping the Set Menu (For EPM-4A, 4C, 4D and 4P)
SET
If you do not request to change any adjustment in the menu;
Press UP or DOWN button until ESC is displayed.
Press SET button.
Setting of Latch Function (For EPM-4C and
4P
)
SET
SET
SET
Press SET button for 3 sec.
Press UP or DOWN button until LAtC is displayed.
Press SET button.
Press UP or DOWN button until requested value is displayed.
Press SET button to save.
761A43
0,5m
CT-25
k l K L
l
in
EPM-4A
5
Un
Factory Settings :
Ctr = 0005 trn = 0001 dE t = 0015 SP h = 4.000
SPL = 0.250 hYS = 0.100 on t = 010.0
trP = oF LAtC= oF oUt = no
oF t = 010.0 Strt = 006.0 AUto= oF
Technical Data
Operating Voltage (Un),* Operating Range (DU) : Please look at labels on the device. Operating Frequency (f) : 45-65 Hz Accuracy : 1% ±1 digit [(10%-100%) full scale] Measuring Input (Iin) : 0,05-5,5 A
0,07-200 A (with CT-25 (for EPM-4A, 4C and 4P))
Measuring Range : 0,05 -10.000 A (with X5 CT)
0,07-200 A (with CT-25 (for EPM-4A, 4C and 4P)) Current Transformer Ratio (Ct) : 5...10000 / 5 A and drCt (for EPM-4A, 4C and 4P) Power Consumption(P
cons
) : <4 VA Burden : <1 VA Output Contact : 5 A, 250 V, 1250 VA (Resistive)
(for EPM-4C and 4P)
Pick-Up Contact : 5 A, 250 V, 1250 VA (Resistive)
(for EPM-4P)
Ins. Tripping : >1,5 x SP H or <0,5 x SP L
(for EPM-4C and 4P) Hysteresis : 0-0,5 x Full scale (for EPM-4C, 4P) Delay Times : 0,0 - 999,9 sec. (for EPM-4C, 4P) Demand Time (Average) :1-60 min. Enclosure : Non-flammable Equipment Protection : Double Insulation ( ),
Measuring Category III Ambient Temperature : -5 OC; +50 OC Degree of Protection : IP 40 (Front Panel) Wire Thickness : 2,5mm2 (for terminal block)
16 mm
2
(Measuring Input Wire Thickness
for CT-25) Installations : Flush mounting with rear terminals Dimensions : Type PR 18, PR 25, PR 20 Weight : 0,31 kg (for PR 18)
: 0,35 kg (for PR 25)
: 0,28 kg (for PR 20)
The Area Measurements on The Control Panel
Control Panel Cut Out
65.5mm
82.5mm 75mm
50mm
TYPE PR 18
WALL
42mm
66mm
66mm
TYPE PR 18 (72x72)
91mm
91mm
TYPE PR 25 (96x96)
TYPE PR 25 (96x96)
96mm
96mm
WALL
90mm
46mm 40mm
50mm
TYPE PR 25
TYPE PR 18 (72x72)
72mm
72mm
48mm
96mm
TYPE PR 20 (48x96)
TYPE PR 20 (48x96)
91mm
44mm
43mm
63mm 54 mm
50mm
TYPE PR 20
WALL
1A
0,5m
k l K L
l
in
EPM-4A
761A53
0,5m
Output
Contact
k l K L
l
in
EPM-4C
CT-25 CT-25
41 27653 4
Un Un
1A
k l K L
l
in
EPM-4D
7653
Un
981A75
0,5m
Output
Contact
k l K L
l
in
EPM-4C
CT-25
63 4
Un
981A75
0,5m
Output
Contact
k l K L
l
in
EPM-4P
CT-25
63 4
Un
1 2
Pick-up
981A75
k l
K L
l
in
EPM-4D
Un
76
1A
43
0,5m
CT-25
k l
K L
l
in
EPM-4C
5
89
Output
Contact
Un
761A43
0,5m
CT-25
k l K L
l
in
EPM-4P
Pick-Up
1 2 5
89
Output
Contact
Un
76
1A
3
k l K L
l
in
EPM-4D
5
Un
2
PR 25
(96x96)
PR 25
(96x96)
PR 25
(96x96)
PR 25
(96x96)
PR 18
(72x72)
PR 20
(48x96)
PR 18
(72x72)
PR 18
(72x72)
PR 20
(48x96)
PR 20
(48x96)
If current
transformer is
selected as drCt
If current
transformer is
selected as 0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as drCt
If current
transformer is
selected as 0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as
0005-A000
If current
transformer is
selected as drCt
If current
transformer is
selected as 0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as
0005-A000
If current
transformer is
selected as drCt
If current
transformer is
selected as 0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as drCt
If current
transformer is
selected as
0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as drCt
If current
transformer is
selected as 0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as drCt
If current
transformer is
selected as 0005-A000
Mesaurement
Input
(I
in
)
If current
transformer is
selected as 0005-A000
43mm
16mm
15.5mm
500mm
2x0,35mm
2
44.5mm
43mm
CT-25