ENTES EPM-06, EPM-06C, EPM-06CS User manual

Page 1
1
MULTIMETER
EPM-06 / 06C / 06CS
INDEX
Precautions for Installation and Safe Usage.........................................................................1
Front Panel and Usage of Buttons.............................................................................1
Using the Buttons............................................................................................2
Transformer Menu (Ctr / trn / Utr / ConnECtýon) ........................................................................2
User Password Settings (Pin Menu).......................................................................2
Activating the User Password (Pin Act Menu)......................................................2
Changing the User Password (Pin CHg Menu).........................................................2
Output Setting Menu ..............................................................................3
Current Setting Menu (SP Current Menu) ................................................................3
High/Low Current Settings (SP Cur Hý, SP Cur Lo Menu)..........................................3
Hysteresis Settings for High/Low Currents (CUr Hý Hys, CUr Lo Hys Menu).................3
Delay-on Time for High/Low Currents (Hý on dEL, Lo on dEL Menu)..............................3
Delay-off Time for High/Low Currents (Hý oFF dEL, Lo oFF dEL Menu).......................................3
Start and Auto Function (StArt dEL and Auto rSt Menu).........................................4
Instant Trip Function (CUr ýnS trP Menu).................................................................4
Voltage Setpoint Menu (SP Volt Menu) ..................................................................4
High/Low Voltage Settings (SP UoL Hý, SP UoL Lo Menu)..................................4
Hysteresis Settings for High/Low Voltages (UoL Hý Hys, UoL Lo Hys Menu)............5
Delay-on Time for High/Low Voltages (Hý on dEL, Lo on dEL Menu).............5
Delay-off Time for High/Low Voltages (Hý oFF dEL, Lo oFF dEL Menu)................5
Frequency Menu .........................................................................................................6
High/Low Frequency Settings (Frq Hý, Frq Lo Menu).............................................6
Hysteresis Settings for High/Low Frequencies (Frq Hý HyS, Frq Lo HyS) ..............................6
Delay-on / Delay-off Time for High/Low Frequencies (Frq on dEL, Frq oFF dEL)....6
Phase Sequence (Voltage Sequence Menu) and Instant Trip (UoL ýnS trP Menu) Menu ........6
Erasing the Max., Min. and Max. Demand Values (Reset Menu)........................6
Demand Time for Demand and Max. Demand (dE tý Menu)....................................................7
Communucation Menu (RS-485) .........................................................................7
Technical Features and Default Factory Settings ................................................................7
Connection Diagram ................................................................................................8
Output, SP Current and SP Volt menus are available for EPM-06C/06CS; RS-485 menu is available for EPM-06CS.
Dimensions
Connection Diagram
MULTIMETER
EPM-06 / 06C / 06CS
8
A3794 / Rev.5
Available only for EPM-06C/06CS Available only for EPM-06CS
Panel Cut-out
91mm
91mm
Type PR 19 (96x96)
70mm
Wall
79.3mm
90mm
Tip 19
50mm
1 .......
Phase LEDs:The LEDs turn on when the voltage value, which is applied to one of the current inputs, reach 30 V
2 ....... First displays k LED (for L1). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
3 ....... Display for
L1.
4 ....... Second displays k LED (for L2 and neutral current). Measurement parameter
is the unit of kilo when LED is turned on. ie: kA, kV
5 ....... Display for
L2 and neutral current.
6 ....... Third displays k LED (for L3). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
7 ....... Display for
L3.
8 ....... Displays network frequency when Hz LED is turned on.
9 ....... Display for frequency and Cosj (forEPM-06C/06CS).
10 ....... First warning output LED (Out1). Turned on when the output is activated.
11 ....... Second warning output LED (Out2). Turned on when the output is activated.
12 ....... Over current / voltage warning output for L1.
(EPM-06C/06CS)
13 ....... Low current / voltage warning output for L1. (EPM-06C/06CS)
14 ....... Over current / voltage warning output for L2. (EPM-06C/06CS)
15 ....... Low current / voltage warning output for L2. (EPM-06C/06CS)
16 ....... Over current / voltage warning output for L3. (EPM-06C/06CS)
17 ....... Low current / voltage warning output for L3. (EPM-06C/06CS)
18 ....... Over current / frequency warning output for frequency (EPM-06C/06CS).
19 ....... Low current / frequency warning output for frequency (EPM-06C/06CS).
20 ....... H LED for max. instant current and voltage. Max. instant currents and
voltages are displayed when this LED is turned on.
21 ....... L LED for min. instant current and voltage. Min. instant currents and
voltages are displayed when this LED is turned on.
22 ....... M LED for max. demand. Max. demand values are displayed when this
LED is turned on.
23 ....... SET button. It is used to enter into the menu and to save the values.
If SET button is pressed for 3 sec. in the measurement mode, you can enter into menus. This button is used for monitoring the max. (H), Min. (L) current values and max. demand values in measurement mode.
24 ....... Downward selection button. And also switching between the phases for
EPM-06C/06CS.
25 ....... Upward selection button. And also switching between the phases for
EPM-06C/06CS.
26 .......
ESC button. Displaying the neutral current during the measurement mode. Escaping from the menu. And also used for switching off the Latch function while this function has activated.
27 ....... Over voltage warning LED which is
displayed
in fourth display.
28 ....... Low voltage warning LED which is
displayed
in fourth display.
29 ....... These LEDs are used for which phase refers to measurement of voltage
in 4th display.
30 ....... Display for monitoring the phase voltages (According to related phase).
31 ....... This LED; indicates Cosj when L1, L2 or L3 activated for monitoring
voltage values in 4th display.
Indicates average value of inductive Cosj when L1-L2 are activated.
Indicates average value of capacitive Cosj when L2-L3 are activated.
32 ....... k LED for monitored phase in 4th display.
~
U
n
Out 2 Out 1
PK-26
IL3IL2I
L1
k
l
K L
k
l
K L
k
l
K L
L1 L2 L3 N
GND A B TR
PR-19
k
l
K L
k
l
K L
k
l
K L
I
L1
I
L2
I
L3
Out 1
Out 2
GND B A TR
70mm
79.3mm
90mm
Type PR 19 (96x96)
96mm
96mm
60.6
106.0
10.8
30.1 7.6 9.5
26.5 21.5
53.0
58.0
10.0
8.5
14.0
45.0
90.0
Type PK 26
* **
30 9
1 10 11
12
13
14
15
16
17
27
28
18
19
23
21
20
26
24
25
22
29
8 31 32
5
4
6
7
2
3
112 14 163 5 7
28 27
30
26
23
24 25
21
20
22
931 8
19 18
4
6
15 1713
29
2
10
11
32
General information
EPM-06/06C/06CS is designed for measuring the below parameters in a 3-Phase system. Phase current, frequency, neutral current and voltages (Phase-Phase and Phase-Neutral).
EPM-06C/06CS; Device has 2 warning
output
which named as Out1 and Out2. (NO-Normally Open)
Please refer to Output menu for the functions of the relays
.
Note: For CT-25 models:
Summary of the Contact Operations
Voltage Frequency Current Phase Seq.
Voltage Frequency Current
Under Under Under
Over Over Over
ALTERNATIVE 2 (H-L)
Current
Voltage Frequency Phase Seq.
Under/Over
Under/Over Under/Over
ALTERNATIVE 1 (U-I)
Out 1
Out 2
-->
-->
-->
-->
-->
-->
-->
-->
-->
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment.
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
- Fuse must be F type and limit value doesnt exceed 1A.
In CT-25 (120A) compliant models, only CT-25 current transformer must be used. Other type of CTs have a high risk to damage to device.
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Valid for EPM-06C/06CS
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
17 18
19 20
RS485
System
N
L1
L2
L3
1 A
L1 L2 L3 N
Current Measurement Inputs
Auxiliary
Supply
1 2 3 4 5
6
11 12
Output Relay
13 14
15 16
Choose according to
contactor current
7 8 9 10
Voltage Measurement Inputs
k: When CT-25 is used, Red cable is connected to k terminal. l: When CT-25 is used, Black cable is connected to l terminal.
N
L1
L2 L3
1
A
Current Measurement
Inputs
Auxiliary
Supply
Relay utput
System
Choose according to
contactor current
Voltage Measurement
Inputs
RS485
Page 2
User Password Setup:
In this menu user password is defined and activated. You must define and activate a 4 digit user password for preventing device settings from the illegal usage. There are 2 sub menu in the Pýn menu.
ESC
SET
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
This menu is used for activating the user password. After the user password is activated for entering to the menus; if the button is pressed for 3 sec., while the instant values are observed, user password is required. If the user password is entered wrong device does not latch.
Note: Factory default value of user password is 0000
Activating the user password :
Find the Pýn menu by scrolling UP/DOWN buttons.
Press SET button (Pýn ACt IUA tE is displayed.)
SET
SET
SET
SET
2
MULTIMETER
EPM-06 / 06C / 06CS
Using the Buttons:
Some buttons and button groups are used for the below special function when device is in the measurement mode (Without selecting a menu).
: Switching between neutral current and phase current in measurement
mode. Switching to the previous menu and escaping the programming menu without saving the changes.
If the Latch function is turned on (EPM-06C/06CS); output will be released when current(s) of system is exceed the defined values. When the systems current turns back to normal values then output doesnt react. Output can be trigged by the ESC button.
Switching between the phase-phase voltages in fourth display.
Used for changing the menu settings and parameters in programming
mode.
ESC
Commissioning and menu setting
(for EPM-06/06C/06CS)
Energize the device after implementing the connections respected to the user manual. Enter the proper menu settings in order to correct measurements and applications.
Current Transformer Ratio Setup:
In this menu, current transformer ratio is set between 1 - 2000. (This menu is not available in the devices which are adapted with CT-25.) Note: If the current transformer is not used between the system and device, current transformer ratio is entered as 1. Example: If a current transformer which has a ratio of 30/5A is used between the system and device; Current transformer ratio is entered as = 30/5 = 6.
SET
: Used for monitoring min. / max. currents and voltages or max. demand values. Switching to the programming mode if it pressed for 3 sec. In programming mode; it is used for switching to the menu and saving changes for the parameters.
SET
SET
ESC
SET
Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted devices, trA Fo trn is displayed instead.) (Not: trA Fo Utr or Con nEC týo n menu can be displayed by scrolling the UP/DOWN buttons.)
Press SET button. Blinking the first digit of displayed value appears. (trA Fo Utr or Con nEC týo n menu can be programmed similarly.)
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button, trA Fo Ctr is displayed.
(Data is entered but is not activated yet. For activating the new data please follow the below steps).
SET
Press SET button for 3 sec. (trA Fo menu is displayed)
Voltage Transformer Ratio:
In this menu, voltage transformer ratio is set between 0000,1 - 4000,0. Note: If the voltage transformer is not used between the system and
EPM-06, voltage transformer ratio is entered as 1.
Example: If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and device; Voltage transformer ratio is entered as 345. (34500/100)
Selecting the Connection Type :
Connection can be selected as Star or Delta in this menu.
Phase-Neutral voltage monitoring can be implemented if the Star connection is selected.
Phase-Phase voltage monitoring can be implemented if the Delta connection is selected.
NOTE: When the Delta connection is selected, neutral current monitoring can not be implemented even if it is activated and displaying function of ESC button will be disabled also.
SET
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Press SET button. Blinking the first digit of displayed value appears.
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button, Pýn ACt oF is displayed.on can be selected by scrolling UP/DOWN buttons.
(Data is entered but is not activated yet. For activating the new data please follow the below steps).
SET
Programming the Turn Number:
This menu is available for CT-25 adapted devices. User defines the turn number, which is the number of how many tour the current cable has rounded into the CT-25. Numbers can be selected between 1-20. Greater the number of turn means greater the sensivity.
Find the Pýn menu by scrolling UP/DOWN buttons.
Press SET button (Pýn ACt IUA tE is displayed.)
SET
SET
Find the Pýn CHA n9E menu by scrolling UP/DOWN buttons.
Changing of User Password:
This menu is used for changing the user password. Note: Factory default value for user password is 0000
Press ESC button one by one until SAU E SEt yES is displayed.
ESC
SET
MULTIMETER
EPM-06 / 06C / 06CS
7
Serial Communication (for EPM-06CS)
EPM-06CS have MODBUS RTU communication protocol which is optical isolated. All measured parameters can be transfer to the computer.Transformer ratios and communication parameters can be set. Saved values can be reset. Programmed parameter for communication explained below.
Press SET button 3 sec. (trA Fo menu is displayed.)
Find RS-485 menu by scrolling UP/DOWN buttons.
Press SET button (Adr ESS menu is displayed.)
Enter the parameter values by scrolling UP/DOWN buttons (001...247 / 2400...38400 /no, EUEn, odd).
Press SET button, Adr ESS / bAU d / PArýty is displayed.
(Data is entered but is not activated yet. For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Find 
Adr ESS / bAU d / PArýty
menu
by scrolling UP-DOWN buttons.
SET
SET
SET
SET
ESC
SET
03H READ HOLD REGISTERS 06H PRESET SINGLE REGISTER 10H PRESET MULTIPLE REGISTERS
MODBUS RTU PROTOCOL
(
Available only for
EPM-06CS)
Standart MODBUS RTU message is shown below.
T
ADDRESS
8 BIT
FUNCTION 8 BIT
DATA NX8BIT
CRCH CRCL T
The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247 ) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave. CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes.
Available Modbus Function:
Read Hold (03) function is used for reading measured values and set value. If any request of reading of a register, excepted mentioned in register table, device will send an error message. For example to read phase1 voltage by sending a message to the device.
01 03 00 00 00 02 XX XX 01
Device address
03
Function
00
MSB address
00
LSB address
00
Register number MSB
02 Register number LSB XX CRC MSB XX CRC LSB
Preset Multiple Register(10H) is used to set more then one register at same time. i.e. Setting CT as 100, Ut as 20.0; 01 10 80 00 00 02 04 00 C8 00 64 XX XX 01 Device Address 10 Function 80 MSB address 00 LSB address 00 Register number MSB 02 Register number LSB 04 Byte count 00 Data MSB C8 Data LSB 00 Data MSB 64 Data LSB XX CRC MSB XX CRC LSB
Preset Single Register (06) function is used for writting the setting values, erasing the energy counter or resetting the min., max., max. demand values. Current transformers ratio can be set 0-2000, voltage transformer ratio can be set 1-40000. i.e. Setting CT as 100; 01 06 80 02 00 64 XX XX 01 Device address 06 Function 80 MSB address 02 LSB address 00 Data MSB 64 Data LSB XX CRC MSB XX CRC LSB
Default Settings
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Technical Features
Rated Voltage (Un)
:
Please look at back side of the device.
Operating frequency (f)
: 45-65 Hz
Auxiliary Supply Power Consumption
: < 4 VA
Measuring Input Power Consumption
: < 1 VA Measurement range Current : 0.05-5.5A~
: 2 - 120 A~ for CT-25 Voltage : 10-300 V AC (Phase - Neutral)
10-500 V AC (Phase - Phase)
Class : 1±1% digit [(10%-100%) x full scale]
Current Transformer Ratio
: 1 ... 2000
Turn number for CT-25 adapted models : 1 .... 20
Voltage Transformer Ratio
: 1 ... 4000 Max. Ctr x Vtr : 40.000
Communications (for EPM-06CS) : MODBUS RTU (RS 485)
Optic isolated, programmable Baud Rate (for EPM-06CS) : 2400-38400 bps Address (for EPM-06CS) : 1-247 Parity (for EPM-06CS) : No, Odd, Even, 8 Data Bits, 2 Stop Bits
Output Relays (for EPM-06C/06CS) : 2 NO, 5A 1250 VA Ambiant Temperature : -5°C; +50°C Display : Red LED display Dimensions : PR-19, PK-26 E
quipment Protection Class
: Double Insulation - Class II ( )
Box Protection Class
: IP 40
Terminal Protection Class
: IP 00
Box Material
: Nonflamable
Mounting
:
Panel Mounted
(PR-19)
Rail Mounted
(PK-26)
Wire Crossection (for terminals) : 2.5 mm
2
Weight : 0.56 kg (PR-19)
0.52 kg (PK-26)
Mounting Category
: Class III Panel Size : 91x91 mm (PR-19)
46x107 mm (PK-26)
Below measurement and application can be implemented with EPM-06/06C/06CS.
1) Phase currents (IL), Neutral current (IN), frequency and Cosj
(EPM-06C/06CS); Phase-Phase and Phase-Neutral voltages can be measured.
2)
Existence of live phases can be observed by L1-L2-L3 LEDs on the device.
3) Min. and max. values for measured currents and voltages can be monitored with only one button.
4) Max. demand values for measured current can be monitored, demand time can be defined in dE tý menu.
5)
A 4 digit password can be defined from pin menu in order to prevent the
change of settings by unauthorized person.
6) Current transformer ratio is programmable. (1 .... 2000)
Current transformer ratio can be programmed in term of turn number
between 1.....20 (for CT-25 adapted devices).
Voltage transformer ratio is programmable. (0.1 .... 4000)
7) A user defined measurement range is used for monitoring the voltages
and currents; and Out1 & Out2 outputs are used for warning the user and disconnecting the device in case of exceeding the limits of measurement range.
8) In case of using the device for measuring the current values of motors etc.,
start delay (AUto rSt) function can be used for preventing the equipment against the improper tripping, which is because of the demurrage current.
9) When a failure has occured use the Latch function, in order to keep the
device with saving its position (Latched), even if the failure conditions are removed.
7th, 8th and 9th subjects are valid for EPM-06C/06CS.
Press SET button (001 / 9600 /no menu is displayed.)
EPM-06CS COMPUTER CONNECTION
31 DEVICES CAN BE CONNECTED AT THE SAME LINE
GNDTR B A
GNDTR B A
GNDTR B A
GND
B
A
RS485/RS232 CONVERTER
PC
..
.
EPM-06CS-1EPM-06CS-2EPM-06CS-31
MAX. 1200 mt.
MAX. 247 DEVICES CAN BE CONNECTED AT SAME LINE BY USING REPEATER.
GND
TR
B
A
..
.
EPM-
06CS
-247
GND
B A
RS485/RS232 CONVERTER
PC
..
.
EPM-
06CS
-1EPM-
06CS
-2EPM-
06CS
-31REPEATER
MAX. 1200 mt.
MAX. 1200 mt.
1
2.00 120
2
1.00
60.0
3
0.66
40.0
4
0.50
30.0
5
0.40
24.0
6
0.33
20.0
7
0.28
17.1
8
0.24
15.0
9
0.22
13.3
10
0.20
12.0
11
0.18
10.9
12
0.16
10.0
13
0.15
9.23
14
0.14
8.57
15
0.13
8.00
16
0.12
7.50
17
0.11
7.05
18
0.11
6.66
19
0.10
6.31
20
0.10
6.00
Ctr - 0001
Utr - 0001
trn - 01
ConnEC - StAr
Frq Hý - 63
Frq Hý HyS - 01.00
Frq Lo - 47
Frq Lo HyS - 01.00
Frq on dEL - 003.0
Frq oFF dEL - 003.0
bAUd - 9600
AddrES - 001
PArty - no
CUr Hý L-1 - 5.000
CUr Hý L-2 - 5.000
CUr Hý L-3 - 5.000
CUr Hý L-n - 5.000
CUr Hý HyS - 0.100
Hý on dEL - 010.0
Hý oFF dEL - 010.0
CUr Lo L-1 - 0.000
Pin Act - oF
Pin - 0000
dt - 15
Out relay - U-I
Latch - oFF
Out Inverse - oFF
CUr Lo L-2 - 0.000
CUr Lo L-3 - 0.000
CUr Lo L-n - 0.000
CUr Lo HyS - 0.200
Lo on dEL - 010.0
Lo oFF dEL - 010.0
Str Art dEL - 0.000
Auto reset - oFF
Cur ýns trp - oFF
UoL Hý L-1 - 250
UoL Hý L-2 - 250
UoL Hý L-3 - 250
UoL Hý HyS - 10
Hý on dEL - 003.0
Hý oFF dEL - 003.0
UoL Lo L-1 - 180
UoL Lo L-2 - 180
UoL Lo L-3 - 180
UoL Lo HyS - 010.0
Lo on dEL - 003.0
Lo oFF dEL - 003.0
UoL PHS SEq - oFF
UoL ýnS trP - oFF
CUr Hý L-1 - 100.0
CUr Hý L-2 - 100.0
CUr Hý L-3 - 100.0
CUr Hý L-n - 100.0
CUr Hý HyS - 2.000
Hý on dEL - 010.0
Hý oFF dEL - 010.0
CUr Lo L-1 - 0.000
CUr Lo L-2 - 0.000
CUr Lo L-3 - 0.000
CUr Lo L-n - 0.000
CUr Lo HyS - 2.000
Lo on dEL - 010.0
Lo oFF dEL - 010.0
Str Art dEL - 0.000
Auto reset - oFF
Cur ýns trp - oFF
CT-25 type
.../5A type
To activate the user password; in measurement mode Press SET button for 3 sec. (trA Fo menu is displayed)
To change the user password; in measurement mode Press SET button for 3 sec. (trA Fo menu is displayed)
Page 3
3
MULTIMETER
EPM-06 / 06C / 06CS
Enter the new password by scrolling UP/DOWN/SET buttons.
Enter the new password again by scrolling UP/DOWN/SET buttons.
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
SET
SET
SET
ESC
SET
Enter the old password by scrolling UP/DOWN/SET buttons.
SET
Output menu (only for EPM-06C/06CS) :
In this menu, using of
oUt PUt
function is explained with details below.
Out Relay function:
In this menu high-low or voltage-current monitoring is determined for Out1 and Out2
outputs
. Note: When U-I (voltage-current) is selected; Out2 is monitoring according to high or low voltage, frequency values and phase sequence, Out1 is monitoring according to high or low-current value. When H-L (high-low) is selected; Out2 is monitoring according to high values for voltage, frequency and low­current, Out1 is monitoring according to low values for voltage or current. Please refer to page 8 for a summary of the contact operations.
SET
ESC
SET
Press SET button, oUt rEL AY is displayed.
(Data is entered but is not activated yet. Activating the new data, please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Press SET button for 3 secs. (trA Fo menu is displayed).
Find oUt PUt menu by scrolling UP-DOWN buttons.
Press SET button oUt rEL AY / oUt LAt CH / oUT ýnU ErS are displayed.
Press SET button, U-I blinks in 4th display. (oFF blinks for oUt LAt CH and oUT ýnU ErS)
Select U-I or H-L by scrolling UP/DOWN buttons. (Select on or oFF for oUt LAt CH and oUT ýnU ErS)
SET
SET
SET
Out Latch function:
If the Latch function is turned on; OUT1-OUT2 outputs, which are released when a failure has occured, keep remained at its position even if the failure is over. Press button in order to triggering the relay when the failure situation is removed. If the Latch function is turned off; Released outputs triggered at the end of delay off time when the failure situation is removed.
ESC
Out inverse function:
If oUt ýnU ErS function is selected off; Device is started with closed output contacts (out1, out2) in the normal network conditions according to settings. Otherwise devices started with open position of the contacts. Default setting is off.
In this menu, max. current value for
IL1 is programmed.
The current value can be programmed between;
0,001....5,000 A (Ctr = 1);
000,1....120,0 A (for CT-25 adapted device trn=1).
If the value is set to zero (0), the high current warning is disabled (
CUr Hý L-2 and CUr Hý L-3 are programmed
similarly).
Refer
SP Cur Hý for details.
In this menu, min. current value for
IL1 is programmed.
The current value can be programmed between;
0,001....5,000 A (Ctr = 1);
000,1....120,0 A (for CT-25 adapted device trn=1).
If the value is set to zero (0), the low current warning is disabled (
CUr Lo L-2 and CUr Lo L-3 are
programmed similarly).
Refer
SP Cur Lo for details.
Note: Low Current values are programmed for
IL1, IL2, IL3
and IN
separately but CUr Lo HyS (hysteresis), Lo on dEL (delay on time) and Lo oFF dEL (delay off time) values are common and they have same values for
IL1, IL2, IL3 and IN
.
Delay time for activating the output for high current warning. It is common for all currents (
IL1, IL2, IL3
and IN
) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP Cur Hý for details.)
In this menu, required hysteresis current for high current warning is programmed.
(same for IL1, IL2,
IL3 and IN.)
The current value can be programmed between;
0,001....2,500 A (Ctr = 1)
000,1....60,00 A (for CT-25 adapted device trn=1)
Refer
SP Cur Hý for details.
In this menu, required hysteresis current for low current warning is programmed.
(same for IL1, IL2, IL3 and
IN.)
The current value can be programmed between;
0,001....2,500 A (Ctr = 1)
000,1....60,00 A (for CT-25 adapted device trn=1)
Refer
SP Cur Lo for details.
Press SET button, Pýn CHA n9E is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps)
(Refer to Page-5)
MULTIMETER
EPM-06 / 06C / 06CS
In this menu, values of min., max., max. demand are erased. It saves the instantaneously measured min. and max. values of the device into its memory. Please kindly look at to the section of
functions of buttons for min. and max. values. Note:
Measured electrical parameters which are saved to the memory are not affected from the electric interruptions. In the rES Et HL or rES Et dE menu; when you choose yES and quit from all menus, if you confirm the changes, min., max. and max. demand values of all parameters are erased at the same time.
Press SET button for 3 sec. (trA Fo menu is displayed.)
Find
rES Et
menu by scrolling UP-DOWN buttons.
Press SET button (rES Et HL menu is displayed.)
Press SET button, rES Et dE / rES Et HL is displayed.
(Data is entered but is not activated yet. Activating the new data, please follow the below steps)
By using the UP-DOWN buttons, other parameters can be selected. If you want to delete the value, choose yES, if not choose no.
SET
SET
SET
Find
rES Et dE / rES Et HL
menu by
scrolling UP-DOWN buttons.
Press SET button (rES Et dE no / rES Et HL no is displayed.)
SET
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
SET
Max. Demand time can be defined between 01-60 minute in this menu.
Press SET button for 3 sec. (trA Fo menu is displayed.)
Find
dE tý
menu by scrolling UP-DOWN
buttons.
Press SET button. Blinking the first digit of displayed value appears.
SET
ESC
SET
6
Setpoints for Frequency :
In this menu, Frequency range can be defiend according to High and Low values of Frequency measurement. If the frequency of the system decreases the Frq Hý value; output is switched on and LED is turned on. (Refer to Output menu) and H LED for frequency is turned off. If the frequency of the system exceeds the high set value, H LED relating to frequency blinks, output switched off at the end of defined time (Frq on dEL), LED turned off (Refer to Output menu) and H LED for frequency is turned on continuously. If the frequency of system are under the high set value (Frq Hý) as a hysteresis (Frq Hý HyS), output is turned on at the end of defined time (Frq oFF dEL), LED is turned on and H LED is turned off. at the end of the adjusted time (Frq oFF dEL), output1 LED turns on and Hý LEDs turn off. If the frequency of the system is over the low set value (Frq Lo), output is turned on, LED is turned on L LED is turned off. If the frequency of the system decreases the low set value (Frq Lo), L LED blinks; output is turned off at the end of defined time (Frq ond), LED is turned off and L LED is turned on continuously. If the frequency of the system is over the low set value (Frq Lo HyS) as a hysteresis (Frq Hys), output is turned on at the end of defined time (Frq oFF dEL), LED is turned on and L LED is turned off.
Note: System frequency is measured for L1.
There are 6 submenus. Frq Hý, Frq Lo, Frq Hý HyS, Frq Lo HyS, Frq on dEL, Frq oFF dEL.
Max. value for system frequency, this value can be defined between 0...70.00 Hz. If the value is set to zero (0), the high frequency warning is disabled.
Min. value for system frequency, this value can be defined between 0...70.00 Hz. If the value is set to zero (0), the low frequency warning is disabled.
Note: Attention for common using of output and relay LED for voltage. In this menu, required hysteresis value can be defined between 0...20.00 Hz. in order to switching off the high frequency warning.
Delay-on time for activation of alarm for high and low frequency value. This value can be defined between
000.0..999.9 in term of second..
Phase sequence can be turned on/off in this menu. Inversed phase voltage which is applied to the measurement inputs (L1-L2-L3), can be monitored. Default setting is off. In order to let the device to warn user in case of inversed phase situation please change the off position as on in UoL PHS SEq menu. Phase sequence function is disabled if the selection is selected off. L1, L2 and L3 LEDs blink and output output released immediately when UoL PHS SEq is turned on and phase sequence is inverted with any reason. Note: Output 2 is used if U-I is selected and Output1 is used if H-L is selected in Output menu for the Phase Sequence monitoring.
Press SET button. Blinking the first digit of displayed value appears.
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
SET
SET
ESC
SET
SET
Press SET button, [(Hý on dEL / Hý oFF dEL / Lo on dEL / Lo oFF dEL) / (Hý on dEL / Hý oFF dEL / Lo on dEL / Lo oFF dEL)] are displayed.
(Data is entered but is not activated yet. For activating the new data please follow the below steps)
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button, dE tý is displayed.
(Data is entered but is not activated yet. For activating
the new data please follow the below steps).
SET
In this menu, high set points for current values are programmed. Hý values for
IL1, IL2, IL3 and IN
can be entered one by one. If all the current values are under the Hý value; Out1 output is switched on, LED of Output1 turned on and LED of H turned off. If any current (
IL1, IL2, IL3 and IN)
exceeds the high set value, H LED blinks. Output 1 output switches off at the end of the defined time (
Hý on dEL
), Output 1 LED turned off and H LED turned on continuously. If all currents (
IL1, IL2, IL3 and IN)
are below the high set value
(Hý) as a hysteresis current (
CUr Hý HyS
), output 1 output switches on at the end of the defined time (Hý oFF dEL), output 1 LED turned on and H LED turned off. This menu has 7 sub menus.
CUr Hý L-1, CUr Hý L-2, CUr Hý L-3, CUr Hý L-n, CUr Hý HyS, Hý on dEL, Hý oFF dEL
Note: High Current values are programmed for
IL1, IL2, IL3
and IN
separately but CUr Hý HyS (hysteresis), Hý on dEL (delay on time) and Hý oFF dEL (delay off time) values are common and they have same values for
IL1, IL2, IL3 and IN
.
In this menu, low set points for current values are programmed. Lo values for
IL1, IL2, IL3 and IN
can be entered one by one. If all the current values are over the Lo value; Out1 output is switched on, LED of Output1 turned on and LED of L turned off. If any current (
IL1, IL2, IL3 and IN)
exceeds the low set value, L LED blinks and Output 1 output switches off at the end of the defined time (
Lo on dEL
), Output 1 LED turned off and L LED turned on continuously. If all currents (
IL1, IL2, IL3 and IN)
are over the low set value (Lo)
as a hysteresis current (
CUr Lo HyS
), output 1 output switches on at the end of the defined time (Lo oFF dEL), output 1 LED turned on and L LED turned off. This menu has 7 sub menus.
CUr Lo L-1, CUr Lo L-2, CUr Lo L-3, CUr Lo L-n, CUr Lo HyS, Lo on dEL, Lo oFF dEL
Delay time for activating the output for low current warning. It is common for all currents (
IL1, IL2, IL3
and IN
) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP Cur Lo for details.)
Delay time for releasing the output for high current warning. It is common for all currents (
IL1, IL2, IL3
and IN
) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP Cur Hý for details.)
Delay time for releasing the output for low current warning. It is common for all currents (
IL1, IL2, IL3
and IN
) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP Cur Lo for details.)
Enter the value by scrolling UP/DOWN buttons and confirm it by SET button. Press ESC button for switching the previous menu.
In this menu, required hysteresis value can be defined between 0...20.00 Hz. in order to switching off the low frequency warning.
Delay-off time for disactivation of alarm for high and low frequency value. This value can be defined between
000.0..999.9 in term of second..
Reset function.
Demand Time.
In case of using the device for measuring the current values
of motors etc., start delay (AUto rSt) function can be used for preventing the equipment against the improper tripping, which is because of the demurrage current. If the system current decreases 50mAxCtr then start-up delay is resetted and related output detect the system automatically. This feature must be observed in case of using this function.
Programming SP CUr rnt :
Using purposes of submenus of SP CUr rnt explained below with details.
Instant Tripping Function.
At position ON, if any VL-L / VL-N values exceeds 1.5 times of high voltages
(UoL Hý L-1/L-2/L-3)
values; the voltage output switches OFF instantly, output LED turned OFF and H LED, for related voltage, is turned ON . (Please refer to Output.)
If any phase voltage decrease 0.5 times low voltages
(UoL L-1/L-2/L-3)
; the voltage output switches OFF instantly, output LED turned OFF and Lo LED, for related voltage, is turned ON .
(Refer to Page-4 for CUr ýnS trP, AUt o rSt and UoL ýnS trP)
Page 4
MULTIMETER
EPM-06 / 06C / 06CS
Press SET button for 3 sec. (trA Fo menu is displayed.)
Find 
SP CUr rnt / SP UoL t
menu by scrolling UP-DOWN buttons.
SET
SET
Press SET button, SP CUr Hý / SP UoL Hý menu is displayed.
Press SET button [(CUr Hý L-1/CUr Lo L-1) / (UoL Hý L-1/UoL Lo L-1) menu is displayed.]
Press SET button. Blinking the first digit of displayed value appears.
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
SET
SET
ESC
SET
Find
[(SP CUr Hý/SP CUr Lo) / (SP UoL
Hý/SP UoL Lo)]
menu by scrolling UP-
DOWN buttons.
Auto Reset Function :
If Auto Reset function is selected as ON; Each time that the current decreases 50mAxCtr value, start-up delay time is reset and when the current value increases 50mAxCtr, start-up delay function is activated. If Auto Reset function is selected as OFF; If the power supply is switched off and then switched
on, start-up delay function is activated.
Start-up delay:
Start Delay Time is used to prevent from faulty switchings caused by motor start-up current (demurrage current). Out1 remain switched ON in this time period (When U-I is selected); In this time period, even if the current value exceeds the limits device doesnt sense it as a warning. The device doesnt give a warning even if the current value isnt in the setting interval. This function is used with Auto Reset function.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Find 
SP CUr rnt / SP UoL t
menu by scrolling UP-DOWN buttons.
Press SET button (SP CUr Hý / SP Uol Hý menu is displayed.)
Press SET button [(CUr ýnS trP on / AUt o rSt on) / UoL ýnS trP off] is displayed.
Select on in order to activating the instant trip function (AUt o rSt), select off in order to disactivating the instant trip function, by scrolling UP/DOWN buttons.
Press SET button, [(CUr ýnS trP / AUt o rSt) / UoL ýnS trP] is displayed.
(Selection is entered but is not activated yet. For activating the new selection, please follow the below steps).
Press ESC button one by one until SAU E SEt yES is displayed.
SET
SET
SET
SET
ESC
SET
Find
[(CUr ýnS trP / AUt o rSt) / UoL ýnS trP]
menu by scrolling UP-DOWN buttons.
Press SET button for 3 sec. (trA Fo menu is displayed)
In this menu, high set points for voltage values are programmed. Hý values for Phase-Neutral / Phase­Phase (according to Star / Delta selection) can be entered one by one.
Note: High Voltage values are programmed for (Phase-Neutral / Phase-Phase) separately but UoL Hý HyS (hysteresis) and Hý on dEL (delay on time) and Hý oFF dEL (delay off time) values are common; these parameters have same values for Phase-Neutral / Phase-Phase. When Connection type (Star/Delta) is selected (refer to Connection menu), device will change the
UoL Hý L-1, L-2 and L-3
values automatically according
to connection.
If all the voltage values (Phase-Neutral / Phase-Phase) are under the Hý value; releated relay is switched on, its LED turned on (please refer Output) and releated H LEDs are turned off. If all the voltage values (Phase-Neutral / Phase-Phase) are over the Hý value, H LED blinks and releated
output is switched off at the end of delay on time (Hý on dEL), its LED turned off (please refer Output) and releated H LEDs are turned on.
If all voltage (Phase-Neutral / Phase-Phase) are below the high set value (Hi) as a hysteresis voltage (
UoL Hý
HyS
), releated
output
is switched on at the end of the delay off time (Hý oFF dEL), its LED turned on (please refer Output) and H LED is turned off.
Programming SP UoL t :
Using purposes of submenus of SP UoL t explained below with details.
Example : If the connection type is selected as Star (with neutral); UoL Hý HyS=10V UoL Hý L-1=250V, UoL Hý L-2=255V, UoL Hý L-3=260V and then this connection type is selected as Delta (without neutral), device will change the values after calculated them according to Phase-Phase values.
New values;
UoL Hý L-1 (L1-L2 Phase to phase voltage) = 433 V UoL Hý L-2 (L2-L3 Phase to phase voltage) = 441 V UoL Hý L-3 (L3-L1 Phase to phase voltage) = 450 V UoL Hý HyS = 10 V.
There are 6 submenus. UoL Hý L-1, UoL Hý L-2, UoL Hý L-3, UoL Hý HyS, Hý on dEL, Hý oFF dEL.
4
Programming CUr ýnS trP, AUt o rSt and UoL ýnS trP
Programming the SP CUr Hý, SP CUr Lo, SP UoL Hý and SP UoL Lo.
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button,
CUr Hý L-1/CUr Lo L-1) / (UoL Hý L-1/UoL Lo L-1
is displayed.
(Data is entered but is not activated yet. For activating
the new data please follow the below steps).
SET
Instant Tripping Function.
At position ON, if any phase current (
IL1, IL2, IL3 and
IN
) exceeds 1.5 times of high
(CUr Hý L-1, L-2, L-3,
L-n)
values, the current
output
 switches off instantly, output LED turned off and H LEDs for related currents turned on. (Please refer to Output.) At position OFF, if any phase current (
IL1, IL2, IL3 and
IN
) decrease 0.5 times of low
(CUr Lo L-1, L-2, L-3,
L-n)
values, the current
output
 switches off instantly, output LED turned off and L LEDs for related currents turned on. (Please refer to Output.) At position OFF, instant tripping function is cancelled.
MULTIMETER
EPM-06 / 06C / 06CS
Low value for L1, when the Star is selected; low value for L1-L2, when the Delta selected can be defined in this menu.
0....300 for Star connection and
0....500 for Delta connection can be
defined. If the value is set to zero (0), the high voltage warning is disabled. Refer
SP
Uol Lo for details.
Note: L2 and L3 phases can be programmed similarly.
(Refer to Page-4 for SP CUr Hý, SP CUr Lo, SP UoL Hý ve SP UoL Lo)
When Connection type (Star/Delta) is selected (refer to Connection menu), device will change the
UoL Lo L-1, L-2 and L-3
values automatically according
to connection.
In this menu, low set points for voltage values are programmed. Lo values for Phase-Neutral / Phase­Phase (according to Star / Delta selection) can be entered one by one.
Example : If the connetion type is selected as Star (with neutral); UoL Lo Hys=10V UoL Lo L-1=180V, UoL Lo L-2=175V, UoL Lo L-3=170V and then this connection type is selected as Delta (without neutral), device will change the values after calculated them according to Phase-Phase values.
New values;
UoL Lo L-1 (L1-L2 Phase to phase voltage) = 311 V UoL Lo L-2 (L2-L3 Phase to phase voltage) = 303 V UoL Lo L-3 (L3-L1 Phase to phase voltage) = 294 V UoL Lo HyS = 10 V.
If all the voltage values (Phase-Neutral / Phase-Phase) are over the Lo value; releated
output
is switched on, its LED turned on (please refer Output) and releated L LEDs are turned off. If any of the voltage valueses (Phase-Neutral / Phase­Phase) decrease the Lo value, L LED blinks and releated
output
is switched off at the end of delay on time (Lo on dEL), its LED turned off (please refer Output) and releated L LED is turned on continuously. If all voltage (Phase-Neutral / Phase-Phase) values increase the low set value (Lo) as a hysteresis voltage (
UoL Lo HyS
), releated relay is switched on at the end of the delay off time (Lo oFF dEL), its LED turned on (please refer Output) and L LED is turned off. Note: Low Voltage values are programmed for (Phase­Neutral / Phase-Phase) separately but UoL Lo HyS (hysteresis), Lo on dEL (delay on time) and Lo oFF dEL (delay off time) values are common; these parameters have same values for Phase-Neutral / Phase-Phase.
High value for L1, when the Star is selected; high value for L1-L2, when the Delta selected can be defined in this menu.
0....300 for Star connection and
0....500 for Delta connection can be
defined. If the value is set to zero (0), the high voltage warning is disabled. Refer
SP
Uol Hý for details.
Note: L2 and L3 phases can be programmed similarly.
In this menu, required hysteresis voltage for high voltage warning is programmed. (same for Phase-Neutral/Phase-Phase.)
0....200V for Star connection and
0....200V for Delta connection can
be defined. Refer
SP UoL Hý for details.
In this menu, required hysteresis voltage for low voltage warning is programmed. (same for Phase-Neutral/Phase-Phase.)
0....200V for Star connection and
0....200V for Delta connection can
be defined. Refer
SP UoL Lo for details.
Press SET button for 3 sec. (trA Fo menu is displayed.)
SET
SET
Press SET button (SP UoL Hý / SP CUr Hý menu is displayed.)
Press SET button [(UoL Hý L-1/UoL Lo L-1) / (CUr Hý L-1/CUr Lo L-1) menu is displayed.]
Press SET button. Blinking the first digit of displayed value appears.
Press ESC button one by one until SAU E SEt yES is displayed.
SET
SET
ESC
SET
Find
[(SP UoL Hý / SP UoL Lo) / (SP CUr Hý
/ SP CUr Lo)]
menu by scrolling
UP-DOWN buttons
Find
[(UoL Hý HyS / UoL Lo HyS) / (CUr Hý HyS / CUr Lo HyS)]
menu
by scrolling UP-DOWN buttons.
Delay on time for activating the output for high voltage warning. It is common for all voltages (same for Phase-Neutral/Phase­Phase.) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP UoL Hý for details.)
Delay on time for activating the output for low voltage warning. It is common for all voltages (same for Phase-Neutral/Phase­Phase.) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP UoL Lo for details.)
Delay off time for activating the output for high voltage warning. It is common for all voltages (same for Phase-Neutral/Phase­Phase.) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP UoL Hý for details.)
Delay off time for activating the output for low voltage warning. It is common for all voltages (same for Phase-Neutral/Phase­Phase.) The value can be programmed between 000,0 and 999,9 in terms of seconds.
(
Refer
SP UoL Lo for details.)
5
Programming the U-H HyS, U-L HyS, I-H HyS, I-L HyS
Press SET button for 3 sec. (trA Fo menu is displayed.)
SET
SET
Press SET button (SP UoL Hý / SP CUr Hý menu is displayed.)
Press SET button [(UoL Hý L-1 / UoL Lo L-1) /(CUr Hý L-1 / CUr Lo L-1) menu is displayed.]
SET
Find
[(SP UoL Hý / SP UoL Lo) / (SP CUr Hý
/ SP CUr Lo)]
menu by scrolling
UP-DOWN buttons.
Find
[(Hý on dEL / Hý oFF dEL / Lo on dEL / Lo oFF dEL) / (Hý on dEL /
Hý oFF dEL / Lo on dEL / Lo oFF dEL)]
menu by scrolling UP-DOWN
buttons.
Hý on dEL, Hý oFF dEL, Lo on dEL, Lo oFF dEL settings are explained for SP UoL t and SP CUr rnt
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button,
[(UoL Hý HyS / UoL Lo HyS) / (CUr Hý HyS / CUr Lo HyS)]
is displayed. (Data is entered but is not activated yet. For activating the new data please follow the below steps).
SET
Please refer to below graphics for the operating principle of
StA rt dEL
and
Aut o rSt
functions
There are 6 submenus. UoL Lo L-1, UoL Lo L-2, UoL Lo L-3, UoL Lo HyS,Lo on dEL, Lo oFF dEL.
Find 
SP UoL t / SP CUr
menu by scrolling UP-DOWN buttons.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Find 
SP UoL t / SP CUr
menu by scrolling UP-DOWN buttons.
5A
4A
3A
2A
1A
Un (on)
Un (off)
I L1
Switch-on
Switch-off
Switch-on
Switch-off
Out1
Out2
Auto
on
Auto
of
Out1
Out2
Switch-on
Switch-off
Switch-on
Switch-off
Hý on dEL = 10 sec.
Lo on dEL = 10 sec.
Hý oFF dEL = 5 sec.
Lo oFF dEL = 5 sec.
Start = 15 sec.
CUr Hý L1 = 3A
CUr Lo L1 = 1A
Ins. trp = on
Start Start Start
t(s)
Start
Start
Start
Hý on dEL
Hý on dEL
Hý oFF dEL
Hý on dEL
t(s)
t(s)
t(s)
t(s)
t(s)
Hý on dEL
Hý oFF dEL
Lo oFF dEL
Ins. trp.
Lo oFF dEL
Ins. trp.
Lo on dEL
Lo oFF dEL
Lo on dEL
Lo oFF
dEL
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
Hý on dEL
Hý oFF dEL
Loading...