ENTES EPM-04, EPM-04C, EPM-04CS User guide

1
MULTIMETER
EPM-04 / 04C / 04CS
INDEX
Precautions for Installation and Safe Usage.........................................................................1
Front Panel and Usage of Buttons.............................................................................1
Using the Buttons............................................................................................2
Transformer Menu (Ctr / trn / Utr / ConnECtýon) ........................................................................2
User Password Settings (Pin Menu).......................................................................2
Activating the User Password (Pin Act Menu)......................................................2
Changing the User Password (Pin CHg Menu).........................................................2
Output Setting Menu ..............................................................................3
Current Setting Menu (SP Current Menu) ................................................................3
High/Low Current Settings (SP Cur Hý, SP Cur Lo Menu)..........................................3
Hysteresis Settings for High/Low Currents (I-H Hys, I-L Hys Menu).................3
Delay-on Time for High/Low Currents (I-H ond, I-L ond Menu)..............................3
Delay-off Time for High/Low Currents (I-H ofd, I-L ofd Menu).......................................3
Start and Auto Function (StArt dEL and Auto rSt Menu).........................................4
Instant Trip Function (CUr ýnS trP Menu).................................................................4
Voltage Setpoint Menu (SP Volt Menu) ..................................................................4
High/Low Voltage Settings (SP UoL Hý, SP UoL Lo Menu)..................................4
Hysteresis Settings for High/Low Voltages (U-H Hys, U-L Hys Menu)............5
Delay-on Time for High/Low Voltages (U-H ond, U-L ond Menu).............5
Delay-off Time for High/Low Voltages (U-H ofd, U-L ofd Menu)................5
Frequency Menu .........................................................................................................6
High/Low Frequency Settings (Frq Hý, Frq Lo Menu).............................................6
Hysteresis Settings for High/Low Frequencies (F-H HyS, F-L HyS) ..............................6
Delay-on / Delay-off Time for High/Low Frequencies (Frq ond, Frq oFd)....6
Phase Sequence (Voltage Sequence Menu) and Instant Trip (UoL ýnS trP Menu) Menu ........6
Erasing the Max., Min. and Max. Demand Values (Reset Menu)........................6
Demand Time for Demand and Max. Demand (dE tý Menu)....................................................7
Communication Menu (RS-485) .........................................................................7
Technical Features and Default Factory Settings ................................................................7
Connection Diagram ................................................................................................8
Output, SP Current and SP Volt menus are available for EPM-04C/04CS; RS-485 menu is available for EPM-04CS.
Dimensions
General information
EPM-04/04C/04CS is designed for measuring Phase current, frequency, neutral current and voltages (Phase-Phase and Phase-Neutral) in a 3-Phase system.
EPM-04C/04CS; Device has 2 warning
output
which named as Out1 and Out2. (NO-Normally
Open) Please refer to Output menu for the functions of the relays.
Connection Diagram
MULTIMETER
EPM-04 / 04C / 04CS
8
A4034 / Rev.8
Available only for EPM-04C/04CS Available only for EPM-04CS
Panel Cut-out
91mm
91mm
Type PR 19 (96x96)
70mm
Wall
79.3mm
90mm
Tip 19
50mm
1 .......
Phase LEDs:The LEDs turn on when the voltage value, which is applied to one of the current inputs, reach 30 V
2 ....... First displays k LED (for L1). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
3 ....... Display for
L1.
4 ....... Second displays k LED (for L2). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
5 ....... Display for
L2.
6 ....... Third displays k LED (for L3). Measurement parameter is the unit of kilo
when LED is turned on. ie: kA, kV
7 ....... Display for
L3.
8 ....... Displays network frequency when Hz LED is turned on.
9 ....... k LED for neutral current. Measurement parameter is displayed in unit of
kilo when this LED is turned on.
10 ....... Display for neutral current and frequency (for EPM-04C/04CS).
11 ....... First warning output LED (Out1). Turned on when the output is activated.
12 ....... Second warning output LED (Out2). Turned on when the output is activated.
13 ....... Over current / voltage warning output for L1. (EPM-04C/04CS)
14 ....... Low current / voltage warning output for L1. (EPM-04C/04CS)
15 ....... Over current / voltage warning output for L2. (EPM-04C/04CS)
16 ....... Low current / voltage warning output for L2. (EPM-04C/04CS)
17 ....... Over current / voltage warning output for L3. (EPM-04C/04CS)
18 ....... Low current / voltage warning output for L3. (EPM-04C/04CS)
19 ....... Over current / frequency warning output for frequency and neutral current
(EPM-04C/04CS).
20 ....... Low current / frequency warning output for frequency and neutral current
(EPM-04C/04CS).
21 ....... Monitoring the L1, L2, L3 voltages values when V LED is turned on and
displays the frequency in 4th display.
22 ....... Monitoring the L1, L2, L3 currents values when A LED is turned on and
displays the neutral current in 4th display.
23 ....... Indicates the activating delta connection when
is turned on. Neutral
current protection is disactivated even if is activated.
24 ....... H LED for max. instant current and voltage. Max. instant currents and
voltages are displayed when this LED is turned on.
25 ....... L LED for min. instant current and voltage. Min. instant currents and
voltages are displayed when this LED is turned on.
26 ....... M LED for max. demand. Max. demand values are displayed when this
LED is turned on.
27 ....... SET button. It is used to enter into the menu and to save the values.
If SET button is pressed for 3 sec. in the measurement mode, you can enter into menus. This button is used for monitoring the max. (H), Min.
(L) current values and max. demand values in measurement mode.
28 ....... Downward selection button.
29 ....... Upward selection button.
30 .......
ESC button. Escaping from the menu. And also used for switching off the Latch function while this function has activated.
Failure to follow those instructions will result in death or serious injury.
- Disconnect all power before working on equipment.
- When the device is connected to the network, do not remove the front panel.
- Do not try to clean the device with solvent or the like.Only clean with dry cloth.
- Verify correct terminal connections when wiring.
- Electrical equipment should be serviced only by your component seller.
- Only for rack panel mounting.
- Fuse must be F type and limit value doesnt exceed 1A.
- No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
~
U
n
Out 2 Out 1
PK-26
IL3IL2I
L1
k
l
K L
k
l
K L
k
l
K L
L1 L2 L3 N
GND A B TR
N
L1
L2 L3
1
A
Current Measurement
Inputs
Auxiliary
Supply
Relay output
System
Choose according to
contactor current
Voltage Measurement
Inputs
RS485
70mm
79.3mm
90mm
Type PR 19 (96x96)
96mm
96mm
60.6
106.0
10.8
30.1 7.6 9.5
26.5 21.5
53.0
58.0
10.0
8.5
14.0
45.0
90.0
Type PK 26
* **
12 4 63 5 7
8 9
10
19 20
30
27
28 29
25
24
26
21 22 23
12 11
17
18
15
16
13
14
2
3
4
5
6
7
8
9
10
15
17
19
18
16
13
14
2021 22 23
27
25
24
30
28
29
26
1 11 12
Note: For CT-25 models:
PR-19
k
l
K L
k
l
K L
k
l
K L
I
L1
I
L2
I
L3
Out 1
Out 2
GND B A TR
17 18
19 20
RS485
System
N
L1
L2
L3
1 A
L1 L2 L3 N
Current Measurement Inputs
Auxiliary
Supply
1 2 3 4 5
6
11 12
Output Relay
13 14
15 16
Choose according to
contactor current
7 8 9 10
Voltage Measurement Inputs
In CT-25 (120A) compliant models, only CT-25 current transformer must be used. Other type of CTs have a high risk to damage to device.
PRECAUTIONS FOR INSTALLATION AND SAFE USE
Summary of the Contact Operations
Voltage Frequency Current Phase Seq.
Voltage Frequency Current
Under Under Under
Over Over Over
ALTERNATIVE 2 (H-L)
Current
Voltage Frequency Phase Seq.
Under/Over
Under/Over Under/Over
ALTERNATIVE 1 (U-I)
Out 1
Out 2
-->
-->
-->
-->
-->
-->
-->
-->
-->
Valid for EPM-04C/04CS
k: When CT-25 is used, Red cable is connected to k terminal. l: When CT-25 is used, Black cable is connected to l terminal.
User Password Setup:
In this menu user password is defined and activated. You must define and activate a 4 digit user password for preventing device settings from the illegal usage. There are 2 sub menu in the Pýn menu.
ESC
SET
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
This menu is used for activating the user password. After the user password is activated for entering to the menus; if the button is pressed for 3 sec., while the instant values are observed, user password is required. If the user password is entered wrong device does not latch.
Note: Factory default value of user password is 0000
Activating the user password :
Press SET button for 3 sec. (trA Fo menu is displayed)
Find the Pýn menu by scrolling UP/DOWN buttons.
Press SET button (Pýn ACt IUA tE is displayed.)
SET
SET
SET
SET
2
MULTIMETER
EPM-04 / 04C / 04CS
Using the Buttons:
Some buttons and button groups are used for the below special function when device is in the measurement mode (Without selecting a menu).
: Switching to the previous menu and escaping the programming
menu without saving the changes.
If the Latch function is turned on (EPM-04C/04CS); output will be released when current(s) of system is exceed the defined values. When the systems current turns back to normal values then output doesnt react. Output can be trigged by the ESC button.
Monitoring for phase currents (A LED is activated) or phase voltages
(V LED is activated).
Used for changing the menu settings and parameters in programming
mode.
ESC
Commissioning the EPM-04C/04CS and menu setting:
Energize the device after implementing the connections respected to the user manual. Enter the proper menu settings in order to correct measurements and applications.
Current Transformer Ratio Setup:
In this menu, current transformer ratio is set between 1 - 2000. (This menu is not available in the devices which are adapted with CT-25.) Note: If the current transformer is not used between the system and device, current transformer ratio is entered as 1. Example: If a current transformer which has a ratio of 30/5A is used between the system and device; Current transformer ratio is entered as = 30/5 = 6.
SET
: Used for monitoring min. / max. currents and voltages or max. demand values. Switching to the programming mode if it pressed for 3 sec. In programming mode; it is used for switching to the menu and saving changes for the parameters.
SET
SET
ESC
SET
Press SET button; trA Fo Ctr menu is displayed (In CT-25 adapted devices, trA Fo trn is displayed instead.) (Not: trA Fo Utr or Con nEC týo n menu can be displayed by scrolling the UP/DOWN buttons.)
Press SET button. Blinking the first digit of displayed value appears. (trA Fo Utr or Con nEC týo n menu can be programmed similarly.)
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button, trA Fo Ctr is displayed.
(Data is entered but is not activated yet. For activating the new data please follow the below steps).
SET
Press SET button for 3 sec. (trA Fo menu is displayed)
Voltage Transformer Ratio:
In this menu, voltage transformer ratio is set between 0000,1 - 4000,0. Note: If the voltage transformer is not used between the system and
EPM-04, voltage transformer ratio is entered as 1.
Example: If a voltage transformer which has a ratio of 34.5KV/100V is used between the system and device; Voltage transformer ratio is entered as 345. (34500/100)
Selecting the Connection Type :
Connection can be selected as Star or Delta in this menu.
Phase-Neutral voltage monitoring can be implemented if the Star connection is selected.
Phase-Phase voltage monitoring can be implemented if the Delta connection is selected.
NOTE: When the Delta connection is selected, neutral current monitoring can not be implemented even if it is activated.
SET
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Press SET button. Blinking the first digit of displayed value appears.
Enter the blinking digit value by scrolling UP/DOWN buttons. Switch to the other digits by using SET button, use ESC button to go to previous digit. After you entered the last digit press SET button, Pýn ACt oF is displayed.on can be selected by scrolling UP/DOWN buttons.
(Data is entered but is not activated yet. For activating the new data please follow the below steps).
SET
Programming the Turn Number:
This menu is available for CT-25 adapted devices. User defines the turn number, which is the number of how many tour the current cable has rounded into the CT-25. Numbers can be selected between 1-20. Greater the number of turn means greater the sensivity.
Press SET button 3 sec. (trA Fo menu is displayed.)
Find the Pýn menu by scrolling UP/DOWN buttons.
Press SET button (Pýn ACt IUA tE is displayed.)
SET
SET
Find the Pýn CHA n9E menu by scrolling UP/DOWN buttons.
Changing of User Password:
This menu is used for changing the user password . Note: Factory default value for user password is 0000
Press ESC button one by one until SAU E SEt yES is displayed.
ESC
SET
MULTIMETER
EPM-04 / 04C / 04CS
7
Serial Communication (for EPM-04CS)
EPM-04S have MODBUS RTU communication protocol which is optical isolated. All measured parameters can be transfer to the computer.Transformer ratios and communication parameters can be set. Saved values can be reset. Programmed parameter for communication explained below.
Press SET button 3 sec. (trA Fo menu is displayed.)
Find RS-485 menu by scrolling UP/DOWN buttons.
Press SET button (Adr ESS menu is displayed.)
Enter the parameter values by scrolling UP/DOWN buttons (001...247 / 2400...38400 /no, EUEn, odd).
Press SET button, Adr ESS / bAU d / PArýty is displayed.
(Data is entered but is not activated yet. For activating the new data please follow the below steps)
Press ESC button one by one until SAU E SEt yES is displayed.
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Find 
Adr ESS / bAU d / PArýty
menu
by scrolling UP-DOWN buttons.
SET
SET
SET
SET
ESC
SET
03H READ HOLD REGISTERS 06H PRESET SINGLE REGISTER 10H PRESET MULTIPLE REGISTERS
MODBUS RTU PROTOCOL
(
Available only for
EPM-04CS)
Standart MODBUS RTU message is shown below.
T
ADDRESS
8 BIT
FUNCTION 8 BIT
DATA NX8BIT
CRCH CRCL T
The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave. CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes.
Available Modbus Function:
Read Hold (03) function is used for reading measured values and set value. If any request of reading of a register, excepted mentioned in register table, device will send an error message. For example to read phase1 voltage by sending a message to the device.
01 03 00 00 00 02 XX XX 01
Device address
03
Function
00
MSB address
00
LSB address
00
Register number MSB
02 Register number LSB XX CRC MSB XX CRC LSB
Preset Multiple Register(10H) is used to set more then one register at same time. i.e. Setting CT as 100, Ut as 20.0; 01 10 80 00 00 02 04 00 C8 00 64 XX XX 01 Device Address 10 Function 80 MSB address 00 LSB address 00 Register number MSB 02 Register number LSB 04 Byte count 00 Data MSB C8 Data LSB 00 Data MSB 64 Data LSB XX CRC MSB XX CRC LSB
Preset Single Register (06) function is used for writting the setting values, erasing the energy counter or resetting the min., max., max. demand values. Current transformers ratio can be set 0-2000, voltage transformer ratio can be set 1-40000. i.e. Setting CT as 100; 01 06 80 02 00 64 XX XX 01 Device address 06 Function 80 MSB address 02 LSB address 00 Data MSB 64 Data LSB XX CRC MSB XX CRC LSB
Default Settings
Ctr - 0001
Utr - 0001
trn - 01
ConnEC - StAr
Frq Hý - 63
F-H HyS - 01.00
Frq Lo - 47
F-L HyS - 01.00
Frq ond - 003.0
Frq oFd - 003.0
bAUd - 9600
AddrES - 001
PArty - no
I-H L-1 - 5.000
I-H L-2 - 5.000
I-H L-3 - 5.000
I-H L-n - 5.000
I-H HyS- 0.100
I-H ond - 010.0
I-H oFd - 010.0
I-L L-1 - 0.000
Pin Act - oF
Pin - 0000
dt - 15
Out relay - U-I
Latch - oFF
Out Inverse - oFF
I-L L-2 - 0.000
I-L L-3 - 0.000
I-L L-n - 0.000
I-L HyS - 0.200
I-L ond - 010.0
I-L oFd - 010.0
Str Art dEL - 0.000
Auto reset - oFF Cur ýns trip - oFF
U-H L-1 - 250
U-H L-2 - 250
U-H L-3 - 250
U-H HyS - 10
U-H ond - 003.0
U-H 0Fd - 003.0
U-L L-1 - 180
U-L L-2 - 180
U-L L-3 - 180
U-L HyS - 010.0
U-L ond - 003.0
U-L oFd - 003.0
VoL PHS SEq - oFF
VoL ýnS trýP - oFF
Press SET button. When SAU E SEt yES is displayed (If you press ESC button or choose no option instead of yES then new data will be cancelled and previous value will be activated).
Technical Features
Rated Voltage (Un)
:
Please look at back side of the device.
Operating frequency (f)
: 45-65 Hz
Auxiliary Supply Power Consumption
: < 4 VA
Measuring Input Power Consumption
: < 1 VA Measurement range Current : 0.05-5.5A~
: 2 - 120 A~ for CT-25 Voltage : 10-300 V AC (Phase - Neutral)
10-500 V AC (Phase - Phase)
Class : 1±1% digit [(10%-100%) x full scale]
Current Transformer Ratio
: 1 ... 2000
Turn number for CT-25 adapted models : 1 .... 20
Voltage Transformer Ratio
: 1 ... 4000 Max. Ctr x Vtr : 40.000
Communications (for EPM-04CS) : MODBUS RTU (RS 485)
Optic isolated, programmable Baud Rate (for EPM-04CS) : 2400-4800-9600-19200-38400 bps Address (for EPM-04CS) : 1-247 Parity (for EPM-04CS) : No, Odd, Even, 8 Data Bits, 2 Stop Bits
Output Relays(for EPM-04C/04CS) : 2 NO, 250 V AC, 5A, 1250 VA Ambiant Temperature : -5°C; +50°C Display : Red LED display Dimensions : PR-19, PK-26 E
quipment Protection Class
: Double Insulation - Class II ( )
Box Protection Class
: IP 40
Terminal Protection Class
: IP 00
Box Material
: Nonflamable
Mounting
:
Panel Mounted
(PR-19)
Rail Mounted
(PK-26)
Wire Cross section (for terminals) : 2.5 mm
2
Weight :
0.56 kg (PR-19)
0.52 kg (PK-26)
Mounting Category
: Class III Panel Size : 91x91 mm (PR-19)
46x107 mm (PK-26)
Below measurement and application can be implemented with EPM-04/04C/04CS.
1) Phase currents (IL), Neutral current (IN), Phase-Phase and Phase-Neutral
voltages can be measured .
2)
Existence of live phases can be observed by L1-L2-L3 LEDs on the device.
3) Min. and max. values for measured currents and voltages can be monitored with only one button.
4) Max. demand values for measured current can be monitored, demand time can be defined in dE tý menu.
5)
A 4 digit password can be defined from pin menu in order to prevent the
change of settings by unauthorized person.
6) Current transformer ratio is programmable. (1 .... 2000)
Current transformer ratio can be programmed in term of turn number
between 1.....20 (for CT-25 adapted devices).
Voltage transformer ratio is programmable. (0.1 .... 4000)
7) A user defined measurement range is used for monitoring the voltages
and currents; and Out1 & Out2 outputs are used for warning the user and disconnecting the device in case of exceeding the limits of measurement range.
8) In case of using the device for measuring the current values of motors etc.,
start delay (AUto rSt) function can be used for preventing the equipment against the improper tripping, which is because of the demurrage current.
9) When a failure has occured use the Latch function, in order to keep the
device with saving its position (Latched), even if the failure conditions are removed.
7th, 8th and 9th subjects are valid for EPM-04C/04CS.
Press SET button (001 / 9600 /no menu is displayed.)
EPM-04CS COMPUTER CONNECTION
31 DEVICES CAN BE CONNECTED AT THE SAME LINE
GNDTR B A
GNDTR B A
GNDTR B A
GND
B
A
RS485/RS232 CONVERTER
PC
..
.
EPM-04CS-1EPM-04CS-2EPM-04CS-31
MAX. 1200 mt.
MAX. 247 DEVICES CAN BE CONNECTED AT SAME LINE BY USING REPEATER.
GND
TR
B
A
..
.
EPM-
04CS
-247
GND
B A
RS485/RS232 CONVERTER
PC
..
.
EPM-
04CS
-1EPM-
04CS
-2EPM-
04CS
-31REPEATER
MAX. 1200 mt.
MAX. 1200 mt.
1
2.00 120
2
1.00
60.0
3
0.66
40.0
4
0.50
30.0
5
0.40
24.0
6
0.33
20.0
7
0.28
17.1
8
0.24
15.0
9
0.22
13.3
10
0.20
12.0
11
0.18
10.9
12
0.16
10.0
13
0.15
9.23
14
0.14
8.57
15
0.13
8.00
16
0.12
7.50
17
0.11
7.05
18
0.11
6.66
19
0.10
6.31
20
0.10
6.00
I-H L-1 - 100.0
I-H L-2 - 100.0
I-H L-3 - 100.0
I-H L-n - 100.0
I-H HyS - 2.000
I-H ond - 010.0
I-H oFd - 010.0
I-L L-1 - 0.000
I-L L-2 - 0.000
I-L L-3 - 0.000
I-L L-n - 0.000
I-L HyS - 2.000
I-L ond - 010.0
I-L oFd - 010.0
Str Art dEL - 0.000
Auto reset - oFF Cur ýns trp - oFF
CT-25 type
.../5A type
For activating the user password, in the measurement mode
For activating the user password, in the measurement mode