ENTES EPC-12 User manual

Page 1
www.entes.com.tr
EPC-12 User Manual
Page 2
1
2
PULSE CONCENTRATOR User Manual EPC-12
WARNING
Ignoring the instructions in this manual may result in serious injuries or death.
No responsibility is assured by manufacturer or any of its subsidiaries for any consequences arising out of disregard the above precautions.
SECURITY
Read the User Manual entirely before using the device.
Warnings
 Connect a button or a circuit breaker between mains and the device.  Connected button or circuit breaker must be in close proximity of the device.  Connected button or circuit breaker must be marked to indicate that it disconnects the device from the mains.  Battery life is 5 years at +45°C storing temperature. It is between 8 and 10 years for typical applications. The battery can only be replaced by ENTES A.Þ. The battery is used to keep the internal real time clock in case of power outages.  During power outages, the device will not count incoming pulses.
Standards Applied to the Device
EN 61010-1, EN 62053-31, EN 62054-21
WARRANTY
The device has a 2 (two) year warranty. In case of a fault, the device must only be serviced by manufacturing company. Otherwise, the warranty of the device will be void.
Page 3
3
4
1. INTRODUCTION
1.1. APPLICATIONS
EPC-12, is a microprocessor-based device that can separately collect incoming pulses from various meters (electricity, water, gas, etc.) connected to its 12 inputs according to 8 tariffs based on time, record them in real time with its internal clock chip and flash memory and transmit data via RS-485 line with Modbus RTU protocol.
1.2. GENERAL FEATURES
Device Features
1) Total counter indexes of 12 pulse inputs with tariff and unit information, date and time information and alarm states can be displayed on the 2x12 characters LCD screen automatically with intervals of 5 seconds or manually by pressing up and down buttons,
2) Enabling the backlight for 20 seconds by pressing any button to provide easy reading on the screen,
3) Data communication with a PC via RS-485 output,
4) Storing the contents of each pulse input with tariff information in 1-60 minutes intervals on the 2 MB permanent memory of the device with date and time information,
5) Preventing changes to settings by unauthorized users by defining a 4-digit user password.
EPC-12 Configuration Software Features
1) Transferring stored parameters to a PC and reviewing them,
2) Entering different multiplier and denominator coefficients for each pulse input,
3) Defining different units for each pulse input,
4) Changing date and time settings,
5) Changing communication settings,
2.2.
SETTINGS THAT ARE CHANGED FROM THE PC
..........................
2.2.1. RS-485 SETTINGS..................................................................
2.2.2. GENERAL SETTINGS...............................................................
2.2.3. COUNTER SETTINGS...............................................................
2.2.4. DATE - TIME SETTINGS....................................................
2.2.5. TARIFF SETTINGS..................................................................
2.2.6. DEVICE INFORMATION............................................................
2.2.7. TOTAL COUNTER INDEXES..............................................
2.2.8. COUNTER INDEXES WITH TARIFF.............................................
2.2.9 DEVICE STATUS....................................................................
2.3. MEMORY - LOGGING FEATURES.................................................
3.
EPC-12 CONFIGURATION (INTERFACE) SOFTWARE
........................
4. DIMENSIONS..............................................................................................
4.1. CONNECTION DIAGRAM........................................................................
5. TECHNICAL DATA..............................................................................
1. INTRODUCTION............................................................................................
1.1. APPLICATIONS...................................................................
1.2. GENERAL FEATURES............................................................
1.3. FRONT PANEL............................................................................
1.4. HARDWARE FEATURES......................................................
2. UTILIZATION OF DEVICE.....................................................................
2.1.
SETTINGS THAT ARE CHANGED FROM THE DEVICE...........
2.1.1. RS-485 (Information for communicating with a PC) MENU.......
2.1.2. PASSWORD MENU..................................................
2.1.3. ESCAPE MENU........................................................
Index
4 4 4 5 6 7 7 10 13 17 18 18 19 19 22 23 32 32 36 46 48 48 49 50 55
Page 4
5
6
6) Activating password protection and defining a new password,
7) Changing the log save period,
8) Activating DST(Daylight Savings Time),
9) Holiday, saturday, sunday and week day tariffs can be programmed (8 for each)*,
10) Monitoring counters with tariff and total counters,
11) Resetting counters with tariff and total counters,
12) Assigning index to counters with tariff when Counter Set from device menu is activated,
13) Monitoring date and time, tariff, next record number to be written and alarm states at that time,
* A tariff between 1 and 8 can be selected but a selected tariff (for example T1) can be selected more
than one time as long as its time range doesn't overlap with another tariff.
1.3. FRONT PANEL
1.4. HARDWARE FEATURES
1) Pulse and Com Inputs (12 pin Pulse Inputs, 4 pin Com Input)
2) Supply Input (2 pin)
3) RS-485 terminals (4 pin)
1) Up and Down Button : It is used to display total counter indexes of 12 pulse inputs, date and time information and alarm states on the monitoring screen. While in the menu screen, they are used to browse between menu items and to increase/decrease a numerical value.
2) Set button : It is used to enter the menu screen when pressed for 3 seconds. It is used to enter a sub-menu or upper-menu, to exit from a menu, to switch the indicator to the right while entering a numerical value and to save the committed change.
3) Count (C) : It indicates which pulse input's total counter index is displayed at that moment.
4) Tariff Information (T) : It indicates which tariff is active at that moment. If there is a tariff overlap or the clock is faulty, pulses at that moment are saved to T1 tariff and a cautionary flashing will occur on the tariff display. In that case, the user will be informed of the problem's cause in the Alarm section of display (For Example; Wrong Time, No Tariff, etc.). Additionally, the problem can be monitored by using the Alarm section on the Configuration Software.
5) Unit : It indicates the unit of the index counted by pulse input displayed at that moment.
6) Total Counter Index : It is the total counter index of the pulse input displayed at that moment. It can have a maximum value of 34.359.738.360 (8x2word). Total counters consist of the summation of 8 counters with tariff. Each counter with tariff has a capacity of 2 word which means it can have a maximum value of 4.294.967.295. Each counter with tariff that fills its 2 word capacity is reset to zero automatically and continues to count.
7) Pulse LEDs : It is for indicating an incoming pulse to the associated pulse input by flashing.
8) 2x12 characters LCD screen.
9) Backlight
Page 5
7
8
2. UTILIZATION OF DEVICE
For security reasons, only a portion of the settings are permitted to be changed directly from the device. Therefore, device settings will be explained under two headlines as Changed from the Device and Changed via Modbus protocol using PC.
2.1. Settings that are changed from the device
After you connected the device as described in the connection diagram, energize the device. In order for your measurements and applications to be accurate, make the necessary adjustments by using the menus.
Monitoring Screen
The display changes automatically in 5 second intervals on the monitoring screen. You can also browse between displays by using up and down buttons. Total counter indexes, tariffs and unit information of all counters from 1st to 12th, clock, date and alarm information is displayed on this screen and after alarm display, it shows the 1st counter again.
Count 1 Tariff Unit Total Counter Indexes
Time
hour:minute:second
Date
Day/month/Year
Count 2 Tariff Unit Total Counter Indexes
Count 3 Tariff Unit Total Counter Indexes
Count 4 Tariff Unit Total Counter Indexes
Count 5 Tariff Unit Total Counter Indexes
Count 6 Tariff Unit Total Counter Indexes
Count 7 Tariff Unit Total Counter Indexes
Count 8 Tariff Unit Total Counter Indexes
Count 12 Tariff Unit Total Counter Indexes
Count 11 Tariff Unit Total Counter Indexes
Count 9 Tariff Unit Total Counter Indexes
Count 10 Tariff Unit Total Counter Indexes
Alarm!
Page 6
9 10
Main Menus
There are 3 main menus on the device. These menus are RS-485, PASSWORD and ESCAPE. When SET button is pressed for 3 seconds on the monitoring screen, main menu is accessed. Sub-menus are accessed while on any main menu by pressing set button. If the password protection feature is active, a
password* will be asked before entering the main menu when set button is pressed for 3 seconds.
* Factory setting for password is 1234. Enter your password with Up, Down and Set buttons. Finally, main
menu will appear when you press the Set button. By using Up and Down buttons, you can browse main menu options. The device does not get blocked when the password is entered incorrectly. Committed changes are saved to device memory and do not get lost in case of a power outage. If none of the buttons are pressed for 20 seconds while on the menu, monitoring screen is displayed. Any committed change will be discarded.
In order for a change that you made in the menu to take effect, you must approve the Save query. Otherwise, committed changes will not take effect..
2.1.1. RS-485 (Information for communicating with a PC) Menu
The device has MODBUS RTU communication protocol. All measured values can be transferred to a PC by using the EPC-12 configuration software. Also, you can adjust all the settings that you can adjust directly from the device except Counter Set by using this configuration software on a PC. In order for the communication with a PC to occur; Baud Rate, Parity, Address values must be entered on the device.
Baud Rate
9600
RS-485
Parity
No
Address
001
Counter Set
Disable
Back
Monitoring Screen
press for 3 seconds
RS-485
PASSWORD ESCAPE
Page 7
11
12
Selecting Baud Rate value
You can select Baud Rate value as 1200, 2400, 4800, 9600, 19200 or 38400 bps.
Selecting Parity value
You can select Parity option as No, Odd or Even.
Entering Address information
Address information can be entered between 1 and 247.
Parity
No
Parity
Even
Parity
Odd
Parity
No
Parity
Even
Baud Rate
19200
Baud Rate
38400
Baud Rate
1200
Baud Rate
9600
Baud Rate
4800
Baud Rate
2400
Baud Rate
19200
Baud Rate
9600
Address
001
Address
001
Address
247
Address
247
Page 8
13
14
Counter Set Setting (Activating index writing to counters with tariff)
If Counter Set menu is set as Disable, no other value than 0 is allowed to be written to counters with tariffs with the configuration software. However; if Counter Set menu is set as Enable, you can write index between 0 and 4.294.967.295 (2 word) to counters with tariff.
2.1.2. PASSWORD Menu
User password is defined and activated in this menu. In order to prevent changes to device settings by unauthorized users, you must define a 4-digit password in this menu and activate it.
Enable (Activating user password protection)
Password protection is activated or deactivated in this menu.
Counter Set
Disable
Counter Set
Enable
Counter Set
Enable
Counter Set
Disable
PASSWORD Enable Change Back
Enable
ENTER PASS
0000
Enter the present password
If the right
user
password is
entered
INVALID
PASS!
ENTER PASS
000
0
If the wrong
user password
is entered
Enable
Yes
Enable
No
Page 9
15 16
Change (Changing user password)
User password is changed in this menu.
Change
Old Pass
0000
Enter the press ent passoword
If the right
user
password is
entered
INVALID
PASS!
Old Pass
000
0
If the wrong user
password is
entered
New Pass
0000
enter the new password
New Pass
000
0
Confirm Pass
0000
Confirm Pass
000
0
INVALID
PASS!
enter the new password again
If the right
user
password is
entered
If the wrong user
password is
entered
Page 10
17
18
2.1.3. ESCAPE Menu
It is used to exit from the main menu. An approval is asked to save any changes that has been made in the main menus. If no change has been made, monitoring menu is displayed directly.
2.2. Settings that are changed from the PC
2.2.1. RS-485 Settings
You can change RS-485 settings that you can change from the device such as Baud Rate, Parity and Address by using the configuration software. When you change EPC-12 RS-485 settings, communication between device and PC will be disconnected. You can establish communications by setting the RS-485 Settings of the device and PC the same and you can continue to adjust settings from the PC.
BAUD RATE: PARITY: 0 = 1200 bps 0 = No 1 = 2400 bps 1 = Odd 2 = 4800 bps 2 = Even 3 = 9600 bps 4 = 19200 bps 5 = 38400 bps
ADDRESS
RS-485
SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32768
32770
32769
8000
8002
8001
BAUD RATE
PARITY
COMMUNICATION ADDRESS
R/W
R/W
R/W
0-5
0-2
1-247
unsigned int
unsigned int
unsigned int
Save
No
Save
Yes
Monitoring
Screen
Saved!
Commited change is
not saved!
ESCAPE
Commited change is
saved!
Page 11
19
20
2.2.2. General Settings
Under general settings, you can do password defining (changing) and password activating/deactivating operations which you can do from the device too. Additionally, you can define how often (in minutes) you want to receive log records and you can activate/deactivate DST (Daylight Savings Time) option. When you activate DST, the clock of the device is moved forward 1 hour from 3:00 AM to 4:00 AM on the last sunday of March and is moved backward 1 hour from 4:00 AM to 3:00 AM on the last sunday of October.
PASSWORD ACTIVATION: DAYLIGHT SAVINGS TIME: 0 = Inactive 0 = Inactive 1 = Active 1 = Active
2.2.3. Counter Settings
Under counter settings, you can specify multiplier and denominator coefficients separately for each pulse input and you can define the unit of the pulse that you measure. For example; if a multiplier of 5, a denominator of 2 and a unit of Wh is entered for 1st pulse input and 4 pulses arrive at 1st pulse input, the measurement of the device will be 4x5:2 = 10 Wh.
ADDRESS
COUNTER SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32775
32777
32776
8007
8009
8008
IN1 MULTIPLIER
R/W
R/W
R/W
0-65535 unsigned int
unsigned int
unsigned int
32778
800A R/W unsigned intIN4 MULTIPLIER
IN3 MULTIPLIER
IN2 MULTIPLIER 0-65535
0-65535
0-65535
32779
32781
32780
800B
800D
800C
IN5 MULTIPLIER
R/W
R/W
R/W 0-65535 unsigned int
unsigned int
unsigned int
32782
800E R/W unsigned intIN8 MULTIPLIER
IN7 MULTIPLIER
IN6 MULTIPLIER 0-65535
0-65535
0-65535
32783
32785
32784
800F
8011
8010
IN9 MULTIPLIER
R/W
R/W
R/W 0-65535 unsigned int
unsigned int
unsigned int
32786
8012 R/W unsigned intIN12 MULTIPLIER
IN11 MULTIPLIER
IN10 MULTIPLIER 0-65535
0-65535 32787 8013 R/W unsigned intIN1 DENOMINATOR 1-65535 32788
32790
32789
8014
8016
8015
IN2 DENOMINATOR
R/W
R/W
R/W 1-65535 unsigned int
unsigned int
unsigned int
32791
8017 R/W unsigned intIN5 DENOMINATOR
IN4 DENOMINATOR
IN3 DENOMINATOR 1-65535
1-65535
1-65535
0-65535
ADDRESS
GENERAL
SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32771
32773
32772
8003
8005
8004
PASSWORD
PASSWORD ACTIVATION
LOG RECORD PERIOD
R/W
R/W
R/W
0-9999
0-1
1-60
unsigned int
unsigned int
unsigned int
32774
8006 DAYLIGHT SAVINGS TIME R/W 0-1 unsigned int
Page 12
21
22
ADDRESS
COUNTER SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32792
32794
32793
8018
801A
8019
IN6 DENOMINATOR
R/W
R/W
R/W
1-65535 unsigned int
unsigned int
unsigned int
32795
801B R/W unsigned intIN9 DENOMINATOR
IN8 DENOMINATOR
IN7 DENOMINATOR 1-65535
1-65535
1-65535
32796
32798
32797
801C
801E
801D
IN10 DENOMINATOR
R/W
R/W
R/W 1-65535 unsigned int
unsigned int
unsigned int
32799
801F R/W unsigned intIN1 UNIT
IN12 DENOMINATOR
IN11 DENOMINATOR 1-65535
0-54
1-65535
32800
32802
32801
8020
8022
8021
IN2 UNIT
R/W
R/W
R/W 0-54 unsigned int
unsigned int
unsigned int
32803
8023 R/W unsigned intIN5 UNIT
IN4 UNIT
IN3 UNIT 0-54
0-54 32804 8024 R/W unsigned intIN6 UNIT 0-54 32805
32807
32806
8025
8027
8026
IN7 UNIT
R/W
R/W
R/W 0-54 unsigned int
unsigned int
unsigned int
32808
8028 R/W unsigned intIN10 UNIT
IN9 UNIT
IN8 UNIT 0-54
0-54
0-54
0-54
32809 8029 R/W unsigned intIN11 UNIT 0-54 32810 802A R/W unsigned intIN12 UNIT 0-54
UNIT: 0 = No Unit 1 = Wh 2 = VAh 3 = VArh 4 = kWh 5 = kVAh 6 = kVArh 7 = ImWh 8 = ExWh
2.2.4. Date-Time Settings
While EPC-12 date and time is adjusted, date and time control is done automatically. Thereby, the user is not permitted to enter a nonexisting date and time. For example; February 30 2012, February 29 2013, April 31, 24:00:00, 23:60:60, etc. are not permitted to be entered. Since the day of the week will be automatically set when you entered the date, the user is not permitted to adjust the day of the week.
9 = IVArh 10 = CVAr 11 = ImkWh 12 = ExkWh 13 = IkVArh 14 = CkVArh 15 = J 16 = kJ 17 = cal
18 = kcal 19 = BTU 20 = TEP 21 = erg 23 = m 24 = ml 25 = cl 26 = in 27 = ft
28 = yd 29 = gal 30 = bbl 31 = gi 32 = pk 33 = pt 34 = qt 35 = g 36 = kg
37 = t 38 = GTN 39 = lb 40 = oz 41 = qrtr 42 = mm 43 = cm 44 = m 45 = km
46 = in 47 = ft 48 = yd 49 = mi 50 = nmi 51 = s 52 = min 53 = h 54 = d
ADDRESS
DATE - TIME
SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32811
32813
32812
802B
802D
802C
DAY
MONTH
YEAR
R/W
R/W
R/W
1-31
1-12 0-99
unsigned int
unsigned int
unsigned int
32814
802E HOUR R/W 0-23 unsigned int
32816
32815
8030
802F
MINUTE
SECOND
R/W
R/W 0-59
0-59
unsigned int
unsigned int
32817
8031 DAY OF THE WEEK R 0-6 unsigned int
3
3
3
3
Page 13
23
24
DAY OF THE WEEK: 0 = Sunday 1 = Monday 2 = Tuesday 3 = Wednesday 4 = Thursday 5 = Friday 6 = Saturday
2.2.5. Tariff Settings
Holiday, saturday, sunday and week day tariffs can be programmed (8 for each) under tariff settings. You can name your set tariffs as numbers from 1 to 8. A selected tariff (for example T1) can be selected more than one time as long as its time range doesn't overlap with another tariff. When you set the tariff as 0, it means that tariff range is deactivated. In this case, the device saves the incoming pulses to T1 tariff. If all tariffs are set to 0 and deactivated to make the device operate without any tariffs, T1 tariff indexes will be equal to total counter indexes.
Tariffs set as holiday have priority over tariffs set as saturday, sunday and week day tariffs. For example; if the 5th day of June is set as holiday tariff at T7, the holidaytariff will be activated on the 5th day of June. Any other tariffs set as saturday, sunday or week day in this time slot will be deactivated for that day. If there are overlapping tariffs or if the device lost its hour settings, T1 tariff will be active for security reasons. Then, the tariff indicator on the device display will start to flash and the cause of the problem will be reported to the user on the ALARM screen. Additionally, the user can see the cause of the problem on the PC from address 249.
Holiday Tariff Settings
Starting year, starting month, starting day, starting hour and ending year, ending month, ending day, ending hour values and finally, the number of the tariff that will be active in that time interval are entered in that order under holiday tariff settings. Since starting year/month, starting day/hour, ending year/month, ending day/hour settings requires the user to enter two information into the same address; the information have to be entered by using the following mathematical formula.
STARTING YEAR / MONTH: Year (between 0 - 99), Month (between 1 - 12) can be entered.* Value to be written = Year x 256 + Month
STARTING DAY / HOUR: Day (between 1 - 31), Hour (between 0 - 23) can be entered.* Value to be written = Day x 256 + Hour
ENDING YEAR / MONTH: Year (between 0 - 99), Month (between 1 - 12) can be entered.* Value to be entered = Year x 256 + Month
ENDING DAY / HOUR: Day (between 1 - 31), Hour (between 0 - 24) can be entered.* Value to be entered = Day x 256 + Hour
* The date you adjust must really exist. Date control is done in tariff settings just like in date-time settings.
For example, it is not permitted to enter a date like February 30 because there is no such date. Additionally, since your tariff settings will not function if your starting dates are bigger than your ending dates or they are each the same these kinds of adjustments are also automatically not permitted.
Page 14
26
25
TARIFF
ADDRESS
HOLIDAY TARIFF SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32848
32850
32849
8050
8052
8051
STARTING YEAR / MONTH
R/W
R/W
R/W 0-99 I 1-12 unsigned int
unsigned int
unsigned int
32851
8053 R/W unsigned intENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR 1-31 I 0-23
32852
32854
32853
8054
8056
8055
TARIFF
R/W
R/W
R/W 0-8 unsigned int
unsigned int
unsigned int
32855 8057 R/W unsigned int 32856
32858
32857
8058
805A
8059
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32859
805B R/W unsigned int 32860 805C R/W unsigned int 32861
32863
32862
805D
805F
805E
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32864
8060 R/W unsigned int 32865 8061 R/W unsigned int 32866 8062 R/W unsigned int
STARTING YEAR / MONTH
ENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
TARIFF
STARTING YEAR / MONTH
ENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
TARIFF
STARTING YEAR / MONTH
ENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
32867 8063 R/W unsigned int
0-99 I 1-12 1-31 I 0-24
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
ADDRESS
HOLIDAY TARIFF SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32869
32868
8064
8066
8065
STARTING YEAR / MONTH
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32870
8067 R/W unsigned intENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
32871
32873
32872
8068
806A
8069
TARÝFF
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32874
R/W unsigned int
32875
32877
32876
806C
806E
806D
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32878
806F R/W unsigned int
32879
8070 R/W unsigned int
32880
32882
32881
8071
8073
8072
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32883
8074 R/W unsigned int
32884
8075 R/W unsigned int
32885
8076 R/W unsigned int
STARTING YEAR / MONTH
ENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
TARIFF
STARTING YEAR / MONTH
ENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
TARIFF
STARTING YEAR / MONTH
ENDING DAY / HOUR
ENDING YEAR / MONTH
STARTING DAY /HOUR
32886
32887
806B
8077
TARIFF R/W
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
0-99 I 1-12 1-31 I 0-23
0-8
0-99 I 1-12 1-31 I 0-24
unsigned int
Page 15
27
Saturday  Sunday  Week Day Tariff Settings
Additional to the holiday tariff setting, the device also has tariff settings that repeat each week. A tariff set as a Saturday tariff will be active every Saturday. Same goes for Sunday and Week Day tariffs. Starting year, starting month, starting day, starting hour and ending year, ending month, ending day, ending hour values and finally, the number of the tariff that will be active in that time interval are entered in that order under Saturday, Sunday and Week Day tariff settings. Since starting hour/minute, ending hour/minute settings require the user to enter two information into the same address; the information have to be entered by using the following mathematical formula.
STARTING HOUR / MINUTE: Hour (between 0 - 23), Minute (between 0 - 59) can be entered. Value to be written = Hour x 256 + Minute
ENDING HOUR / MINUTE: Hour (between 0 - 24), Minute (between 0 - 59) can be entered. Value to be written = Hour x 256 + Minute
28
ADDRESS
SATURDAY TARIFF SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32889
32888
8078
807A
8079
STARTING HOUR / MINUTE
R/W
R/W
R/W
unsigned int
unsigned int
unsigned int
32890
807B R/W unsigned int
32891
32893
32892
807C
807E
807D
TARIFF
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32894
R/W unsigned int
32895
32897
32896
8080
8082
8081
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32898
8083 R/W unsigned int
32899
8084 R/W unsigned int
32900
32902
32901
8085
8087
8086
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32903
8088 R/W unsigned int
32904
8089 R/W unsigned int
32905
808A R/W unsigned int
32906
32907
807F
808B
R/W
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59
0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
ENDING HOUR / MINUTE
unsigned int
Page 16
30
29
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32909
32908
808C
808E
808D
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32910
808F
R/W unsigned int
32911
SATURDAY TARIFF
SETTINGS
ADDRESS
SUNDAY TARIFF SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32913
32912
8090
8092
8091
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32914
8093 R/W unsigned int
32915
32917
32916
8094
8096
8095
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32918
R/W unsigned int
32919
32921
32920
8098
809A
8099
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32922
809B R/W unsigned int
32923
809C R/W unsigned int
32924
8097
TARIFF
STARTING HOUR / MINUTE
ENDING HOUR / MINUTE
TARIFF
0-8
0-23 I 0-59 0-24 I 0-59
0-8
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59
0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59
32931
80A3
R/W
32926
32925
809D
809F
809E
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32927
80A0 R/W unsigned int
32928
80A1 R/W unsigned int
32929
R/W unsigned int
32930
80A2
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
SUNDAY TARIFF SETTINGS
80A4 R/W unsigned int
unsigned int
32932
80A5 R/W unsigned int
32933
80A6 R/W unsigned int
32934
R/W unsigned int
32935
80A7
32937
32936
80A8
80AA
80A9
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32938
80AB R/W unsigned int
32939
80AC R/W unsigned int
32940
R/W unsigned int
32941
80AD
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
WEEKDAY TARIFF
SETTINGS
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
ENDING HOUR / MINUTE
0-23 I 0-59
0-24 I 0-59
0-8 0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8 0-23 I 0-59 0-24 I 0-59
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
TARIFF
0-8
Page 17
32
31
2.2.6. Device Information
These are information that can only be read and not changed by the user. Device ID/version and serial number is assigned to the device internally during manufacturing. This way, you can report your device from the device information addresses and request help when there is a problem with your device.
2.2.7. Total Counter Indexes
Total counter indexes state the summation of 8 counter indexes with tariff. No other value than 0 is allowed to be written to total counters. When total counters are reset, all counter indexes with tariff in relevance to the pulse input will be reset. The index value that you will write to counters with tariff will change the total counter indexes as much.
ADDRESS
WEEKDAY TARIFF SETTINGS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
32943
32942
STARTING HOUR / MINUTE
R/W
R/W
R/W
unsigned int
unsigned int
unsigned int
32944
R/W unsigned int
32945
32947
32946
80AE
TARIFF
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32948
R/W unsigned int
32949
32951
32950
80B0
80B2
80B1
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32952
80B3
R/W unsigned int
32953
80B4
R/W unsigned int
32954
32956
32955
80B5
80B7
80B6
R/W
R/W
R/W unsigned int
unsigned int
unsigned int
32957
80B8
R/W unsigned int
32958
80B9
R/W unsigned int
32959
80AF
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59
0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
0-23 I 0-59 0-24 I 0-59
0-8
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
STARTING HOUR / MINUTE
TARIFF
ENDING HOUR / MINUTE
80BA 80BB
80BD
80BC
80BE 80BF
60417
60416
EC00
EC02
EC01
R
R
R unsigned int
unsigned int
unsigned int
60418
EC03 R unsigned int
60419
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
DEVICE
INFORMATION
0X0111 - 0X01FF
DEVICE ID
SERIAL NO
DEVICE ID / VERSION NO
0X0000 - 0XFFFF 0X0001 - 0XFFFF
0XD201
Page 18
33
34
ADDRESS
TOTAL COUNTER INDEXES
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
R/W unsigned
long long int
IN1 TOTAL COUNTER
0 1 2 3 4
5 6 7 8 9
10 11
12 13
14 15
IN2 TOTAL COUNTER
IN4 TOTAL COUNTER
IN3 TOTAL COUNTER
R/W
R/W
R/W
0
0
0
0
unsigned
long long int
unsigned
long long int
unsigned
long long int
0 1 2 3 4
5 6 7 8 9 A
B C
D E
F
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
R/W unsigned
long long int
IN5 TOTAL COUNTER
16 17 18 19 20
21 22 23 24 25
26 27
28 29
30 31
IN6 TOTAL COUNTER
IN8 TOTAL COUNTER
IN7 TOTAL COUNTER
R/W
R/W
R/W
0
0
0
0
unsigned
long long int
unsigned
long long int
unsigned
long long int
10 11 12 13 14
16 17
19
1A 1B
1C 1D
1E 1F
15
18
TOTAL COUNTER INDEXES
Page 19
35
36
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
R/W unsigned
long long int
IN9 TOTAL COUNTER
32 33 34 35 36 37 38 39 40 41 42
43 44
45 46
IN10 TOTAL COUNTER
IN12 TOTAL COUNTER
IN11 TOTAL COUNTER
R/W
R/W
R/W
0
0
0
0
unsigned
long long int
unsigned
long long int
unsigned
long long int
2A 2B
2D 2E
2F
47
20 21 22 23 24 25 26 27 28 29
2C
TOTAL COUNTER INDEXES
2.2.8. Counter Indexes with Tariff
ADDRESS
COUNTER WITH TARIFF INDEXES
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
48 49 50 51 52 53 54 55 56 57 58
59 60
61 62
IN1 T1 COUNTER WITH TARIFF
R/W
unsigned int
3A 3B
3D 3E
3F
63
30 31 32 33 34 35 36 37 38 39
3C
0-65535
IN2 T1 COUNTER WITH TARIFF
R/W
IN3 T1 COUNTER WITH TARIFF
R/W
IN4 T1 COUNTER WITH TARIFF
R/W
IN5 T1 COUNTER WITH TARIFF
R/W
IN6 T1 COUNTER WITH TARIFF
R/W
IN7 T1 COUNTER WITH TARIFF
R/W
IN8 T1 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
In order to change index values, Counter Set menü on the EPC-12 device has to set as Enable.
Page 20
37
38
51
81
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
64 65 66 67 68 69 70 71 72 73 74
75 76
77 78
IN9 T1 COUNTER WITH TARIFF
R/W
unsigned int
4A 4B
4D 4E
4F
79
40 41 42 43 44 45 46 47 48 49
4C
0-65535
IN10 T1 COUNTER WITH TARIFF
R/W
IN11 T1 COUNTER WITH TARIFF
R/W
IN12 T1 COUNTER WITH TARIFF
R/W
IN1 T2 COUNTER WITH TARIFF
R/W
IN2 T2 COUNTER WITH TARIFF
R/W
IN3 T2 COUNTER WITH TARIFF
R/W
IN4 T2 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
80
50
IN5 T2 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
COUNTER WITH TARIFF INDEXES
63
99
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
82 83 84 85 86 87 88 89 90 91 92
93 94
95 96
IN6 T2 COUNTER WITH TARIFF
R/W
unsigned int
5C 5D
5F 60
61
97
52 53 54 55 56 57 58 59 5A 5B
5E
0-65535
IN7 T2 COUNTER WITH TARIFF
R/W
IN8 T2 COUNTER WITH TARIFF
R/W
IN9 T2 COUNTER WITH TARIFF
R/W
IN10 T2 COUNTER WITH TARIFF
R/W
IN11 T2 COUNTER WITH TARIFF
R/W
IN12 T2 COUNTER WITH TARIFF
R/W
IN1 T3 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
98
62
IN2 T3 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
COUNTER WITH TARIFF INDEXES
Page 21
40
39
75
117
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
100 101 102 103 104 105 106 107 108 109 110
111 112
113 114
IN3 T3 COUNTER WITH TARIFF
R/W
unsigned int
6E 6F
71 72
73
115
64 65 66 67 68 69 6A 6B 6C 6D
70
0-65535
IN4 T3 COUNTER WITH TARIFF
R/W
IN5 T3 COUNTER WITH TARIFF
R/W
IN6 T3 COUNTER WITH TARIFF
R/W
IN7 T3 COUNTER WITH TARIFF
R/W
IN8 T3 COUNTER WITH TARIFF
R/W
IN9 T3 COUNTER WITH TARIFF
R/W
IN10 T3 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
116
74
IN11 T3 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
COUNTER WITH TARIFF INDEXES
87
135
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
118 119 120 121 122 123 124 125 108 127 128
129 130
131 132
IN12 T3 COUNTER WITH TARIFF
R/W
unsigned int
80 81
83 84
85
133
76 77 78 79 7A 7B 7C 7D 7E 7F
82
0-65535
IN1 T4 COUNTER WITH TARIFF
R/W
IN2 T4 COUNTER WITH TARIFF
R/W
IN3 T4 COUNTER WITH TARIFF
R/W
IN4 T4 COUNTER WITH TARIFF
R/W
IN5 T4 COUNTER WITH TARIFF
R/W
IN6 T4 COUNTER WITH TARIFF
R/W
IN7 T4 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
134
86
IN8 T4 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
COUNTER WITH TARIFF INDEXES
Page 22
42
41
136 137 138 139 140 141 142 143
IN9 T4 COUNTER WITH TARIFF
88
89 8A 8B
8C 8D
8E 8F
IN10 T4 COUNTER WITH TARIFF
IN11 T4 COUNTER WITH TARIFF
IN12 T4 COUNTER WITH TARIFF
98
153
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
144 145 146
147 148
149 150
R/W
unsigned int
92
94 95
96
151
90 91
93
0-65535
R/W
R/W
R/W
IN1 T5 COUNTER WITH TARIFF
R/W
IN2 T5 COUNTER WITH TARIFF
R/W
IN3 T5 COUNTER WITH TARIFF
R/W
IN4 T5 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
152
97
IN5 T5 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
99
COUNTER WITH TARIFF INDEXES
154 155 156 157 158 159 160 161
IN6 T5 COUNTER WITH TARIFF
9A 9B 9C 9D 9E 9F A0 A1
IN7 T5 COUNTER WITH TARIFF
IN8 T5 COUNTER WITH TARIFF
IN9 T5 COUNTER WITH TARIFF
AA
171
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
162 163 164
165 166
167 168
R/W
unsigned int
A4
A6 A7
A8
169
A2 A3
A5
0-65535
R/W
R/W
R/W
IN10 T5 COUNTER WITH TARIFF
R/W
IN11 T5 COUNTER WITH TARIFF
R/W
IN12 T5 COUNTER WITH TARIFF
R/W
IN1 T6 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
170
A9
IN2 T6 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
AB
COUNTER WITH TARIFF INDEXES
Page 23
44
43
190 191 192 193 194 195 196 197
IN12 T6 COUNTER WITH TARIFF
BE BF C0 C1 C2
C4 C5
IN1 T7 COUNTER WITH TARIFF
IN2 T7 COUNTER WITH TARIFF
IN3 T7 COUNTER WITH TARIFF
CE
207
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
198 199 200
201 202
203 204
R/W
unsigned int
C8
CA CB
CC
205
C6 C7
C9
0-65535
R/W
R/W
R/W
IN4 T7 COUNTER WITH TARIFF
R/W
IN5 T7 COUNTER WITH TARIFF
R/W
IN6 T7 COUNTER WITH TARIFF
R/W
IN7 T7 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
206
CD
IN8 T7 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
CF
C3
COUNTER WITH TARIFF INDEXES
172 173 174 175 176 177 178 179
IN3 T6 COUNTER WITH TARIFF
AC AD AE AF
B0
B2 B3
IN4 T6 COUNTER WITH TARIFF
IN5 T6 COUNTER WITH TARIFF
IN6 T6 COUNTER WITH TARIFF
BC
189
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
180 181 182
183 184
185 186
R/W
unsigned int
B6
B8 B9
BA
187
B4 B5
B7
0-65535
R/W
R/W
R/W
IN7 T6 COUNTER WITH TARIFF
R/W
IN8 T6 COUNTER WITH TARIFF
R/W
IN9 T6 COUNTER WITH TARIFF
R/W
IN10 T6 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
188
BB
IN11 T6 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
BD
B1
COUNTER WITH TARIFF INDEXES
Page 24
46
45
2.2.9. Device Status
Hour, date and tariff at that moment; the next record number to be written and alarm states are reported to the user under device state menu. In how many minutes the next record number will increase by one is determined by the set log record period setting of the device.
208 209 210 211 212 213 214 215
IN9 T7 COUNTER WITH TARIFF
D0 D1 D2 D3
D4
D6 D7
IN10 T7 COUNTER WITH TARIFF
IN11 T7 COUNTER WITH TARIFF
IN12 T7 COUNTER WITH TARIFF
E0
225
unsigned int
0-65535
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
216 217 218
219 220
221 222
R/W
unsigned int
DA
DC DD
DE
223
D8 D9
DB
0-65535
R/W
R/W
R/W
IN1 T8 COUNTER WITH TARIFF
R/W
IN2 T8 COUNTER WITH TARIFF
R/W
IN3 T8 COUNTER WITH TARIFF
R/W
IN4 T8 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
224
DF
IN5 T8 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
E1
D5
COUNTER WITH TARIFF INDEXES
226 227 228 229 230 231 232 233
IN6 T8 COUNTER WITH TARIFF
D0 D1 D2 D3 D4
D6 D7
IN7 T8 COUNTER WITH TARIFF
IN8 T8 COUNTER WITH TARIFF
IN9 T8 COUNTER WITH TARIFF
ADDRESS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
234 235 236
237 238
239
R/W
unsigned int
DA
DC DD
D8 D9
DB
0-65535
R/W
R/W
R/W
IN10 T8 COUNTER WITH TARIFF
R/W
IN11 T8 COUNTER WITH TARIFF
R/W
IN12 T8 COUNTER WITH TARIFF
R/W
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
unsigned int
0-65535
D5
COUNTER WITH TARIFF INDEXES
Page 25
ADDRESS
DEVICE STATUS
ADDRESS
(HEX)
REGISTER R/W RANGE
FORMAT
240
242
241
F2
F1
DAY
R
R
R 1-31 unsigned int
unsigned int
unsigned int
243
F3 R unsigned intHOUR
YEAR
MONTH 1-12
0-23
0-99
244
246
245
F4
F6
F5
MINUTE
R
R
R 0-59 unsigned int
unsigned int
unsigned int
247
F7 R unsigned intTARIFF
DAY OF THE WEEK
SECOND 0-59
1-8
0-6
248 249
F8 F9
RECORD NO TO BE WRITTEN NEXT
R
R 0-16383 unsigned int
unsigned intALARM 0-7
F0
ALARM: 0 = Normal 1 = Wrong Time 2 = Wrong Date 3 = Wrong Date 4 = No Tariff 5 = No Tariff 6 = No Tariff 7 = No Tariff
2.3. Memory  Logging Features :
The 2MB flash memory stores data with programmable intervals between 1 and 60 minutes. This memory consists of 32 sectors. Each sector contains 65536 byte. Each record occupies 128 byte sized blocks on the flash memory. Each sector holds 512 block records. 16384 block savings can be accomplished on the 2MB flash memory. When the flash memory becomes full, 0th sector is cleaned and records start to be saved from the start to the flash memory. During data logging before the last record of a sector (511st record, including 0) is saved, the next sector is completely deleted. The user can monitor which record the device will log from address 248 on Modbus.
3. EPC-12 CONFIGURATION (INTERFACE) SOFTWARE
A User Interface Software has been prepared for settings that are done from a PC. The purpose of this software is an easier and faster way when changing the settings which has to be done from a PC. You can access the interface software and its manual from the included CD. Details on how to use the interface software are available in the Interface Software User Manual.
47
48
Page 26
4.DIMENSIONS
Dimensions are in millimeters.
4.1.CONNECTION DIAGRAM
* Common Lead (Using any one of them will suffice.)
When a counter with NPN output is connected to EPC-12, collector lead is connected to In (+) input and emitter lead is connected to Com (-) input. When a counter with PNP output is connected to EPC-12, emitter lead is connected to In (+) input and collector lead is connected to Com (-) input.
49
50
44,9
61,6
38,9
90
48
31,5
26,5
58
71,2
90
Page 27
51
52
BY USING A REPEATER, 247 DEVICES CAN BE CONNECTED TO THE SAME LINE.
GND
TR
B
A
..
.
EPC-12 247
GND
B A
RS485/RS232
or
RS-485/USB
CONVERTER
PC
..
.
EPC-12 1EPC-12 2
EPC-12 31
REPEATOR
MAX. 1200 M
MAX. 1200 M
TR B A GND
A MAX. OF 31 DEVICES CAN BE CONNECTED TO THE SAME LINE
GND
B A
PC
..
.
EPC-12 -1.EPC-12 -2.EPC-12 -31.
MAX. 1200 mt.
RS-485 / 232 or RS-485 / USB
CONVERTER
TR B A GNDTR B A GND
Page 28
53
54
............
Page 29
5. TECHNICAL DATA
Operating Voltage (Un) = Please see device labels. Operating Frequency (f) = 45-65Hz Supply Input Power Consumption = <5VA Communication (Insulated) = MODBUS RTU (RS485)
Baud Rate = 1200  38400 bps Adress = 1  247 Parity = No, Odd, Even Stop Bit = 1 Max Communication Distance = 1200 m (MODBUS/RS-485 side, using signal amplifier)
Pulse Inputs (12 pcs, Insulated) = Complies with EN 62053-31.
Minimum Pulse Duration = 10 ms Minimum Time Between Pulses = 30 ms Minimum pulse period = 60 ms Maximum Pulse Frequency = 16 Hz Maximum Contact Resistance = 800 Ohm Pulse Voltage = 10-12V Trigger Edge = Rising and Pulse width control Distance between meters to be connected to EPC-12 = 1000 m Total Counter Capacity = 34.359.738.360
Cable Thickness for RS-485 Connection = CAT 5 cable Weight = 456,4 gr Internal Memory = 2MB
55
Ambient Temperature = -25...+55 C Storage Temperature = -25...+70 C Humidity = %95 Display = Backlight 2x12 LCD Dimensions = DIN4 (PK27) Device Protection Class = Double Insulated Front panel = IP40 Terminals = IP20 Enclosure Material = Nonflammable Installation = Rail mount Cable Thickness for Voltage Connection = max. 2.5 mm Cable Thickness for Pulse Connection = max. 2.5 mm
Factory Default Settings
Baud Rate = 9600 Parity = No Address = 1 Counter Set = Disable PASSWORD = 1234 PASSWORD Enable = No Log Save Period = 30 min. Daylight Savings Time application = Active Multiplier = 1 Denominator = 1 Unit = None Tariff = None Counters = 0 Alarm = Normal
56
2
2
o o
Loading...