ENTES EMM-04S, EMM-04CS, EMM-04 User manual

EMM Series Multimeters
User Manual
www.entes.com.tr
1
Index
Introduction .......................................................................................................... 3
Safety and warnings ......................................................................................... 3
Standards ......................................................................................................... 4
Technical Specications ................................................................................... 4
Connection Diagram ......................................................................................... 6
LED Indicator and GUI design .......................................................................... 9
Key Functions .................................................................................................. 9
Measurement ....................................................................................................... 10
Voltage ............................................................................................................. 10
Current ............................................................................................................. 11
Neutral Current ................................................................................................. 11
Frequency ........................................................................................................ 12
Cos Phi ............................................................................................................. 12
Total Cos Phi .................................................................................................... 12
Total Run Hour ................................................................................................. 13
Run Hour .......................................................................................................... 13
Settings ................................................................................................................ 14
User Settings .................................................................................................... 14
Security Settings .............................................................................................. 14
Password Setting ............................................................................................. 15
Connection Settings ......................................................................................... 15
Connection Type .............................................................................................. 16
Frequency ........................................................................................................ 17
Demand Period (Based on Model) ................................................................... 17
Voltage Transformer Setting ............................................................................. 18
Current Transformer Setting ............................................................................. 19
Communication Settings .................................................................................. 19
Output Settings ................................................................................................. 21
Alarm Settings .................................................................................................. 22
Alarm Messages ............................................................................................... 31
2
Introduction
Safety and Warnings
Caution
Failure to follow the instructions below may result in serious injuries or even death..
Disconnect all power when installing the device.
Do not remove the front panel while the device is connected to the mains.
Do not clean the device with solvent or similar material. Use only a dry cloth.
Check that the connections are correct before operating the device.
Contact your authorized dealer if you have any questions about your device.
The device is for panel mounting only.
The fuse to be used must be type F and the current limit value must be 1A.
The manufacturer cannot be held responsible for unwanted situations that may emerge due to failure to follow the measures above.
Security
Read the entire operating manual before using the device.
Connect a button or a circuit breaker between supply inlets of the product and the mains.
This button or circuit breaker must be close to the product.
Place a mark to indicate that this button or circuit breaker will be used to separate the product from
the mains.
Warranty
The warranty period of the device is 2 (two) years. In case of a malfunction, the product should be repaired by the manufacturing company only. Otherwise, the warranty will be void.
General Specications
Wide supply range
Slim design for narrow panels
3-Phase Voltage 3-Phase Current measurement
Alarm options (based on model)
Run Hour
2x Relay Output (based on model)
Modbus communication (based on model)
96 x 96 panel mounting
3
Mechanical and Environmental Conditions
Operating Conditions Value Range
Dimensions 96x96 Maximum Depth
(Inside the Panel) Installation Panel type IP protection 20 Display LED display Button 4 x Universal interface Storage Temperature -30 / +80°C Operating Temperature -20 / +70°C Maximum Humidity 95% (noncondensing)
44.5 mm
Standards
EN 61326,61000-6-4,61000-6-2 emc
EN 61010-1 Safety EN 60529 Mechanic
EN 60068-2-1,60068-2-2 ,60068-2-30 Environmental
Technical Specications
Operating Voltage (Un) 100-270 VAC (-15%+10%) Operating Frequency (f) 50-60 Hz Input Power Consumption <5 VA Measuring Inputs Power Consumption <1 VA Measuring Voltage Input (Vin) 10-300 VAC(VLN) 10-480 VAC(VLL) Measuring Current Input (Iin) 0.05-5.5 A
Class
Voltage 0,5% Current 0,5% Frequency ±0.02 Hz cosφ ± 0.02 Demand Time Adjustable
60/120/300/600/1200/1800/3600 sec
Communication (Insulated) 4kV Baud Rate Adjustable 2400/ 4800/
9600/19200/38400/57600/115200
Address Adjustable 1-256
Parity Adjustable Single/Double Relay Ouputs 2x (5A 250 VAC/ 1250VA) Connection 3P3W, 3P4W, Aron, 3P3W(B), 3P4W(B) Ambient Temperature -20+70°C Storage Temperature -30+80°C Humidity 95% Indicator LED Display Dimensions 96x96x44.5 Device Protection Class IP 20
4
Parameter Unit Description Range Sensitivity Maximum
Value
Voltage V1, V2, V3 V Phase-Neutral, Rms Voltage 10-300 VAC 0,5% 6 MV U1, U2, U3 V Phase-Phase, Rms Voltage 10-480 VAC 0,5% 9.6 MV Frequency Hz Voltage Frequency 50-60 Hz ±0.02 Hz 60
Current I1, I2, I3 A Phase Current 0.05-5.5 A 1% 10kA
Power
Cosϕ Cos Phi -1.000 -
+1.000
± 0.02 -1.000 -
+1.000
Technical Drawing
+0,03
3,63 inch
-0,0
+0,8
92 mm
-0,0
44,5
22,8
4,02 inch
102 mm
1,75 inch
44,5 mm
3,90 inch
99 mm
0,44 inch
11 mm
3,63 inch
92 mm
Max 0,11 inch Max 3 mm
+0,03
-0,0
+0,8
-0,0
61,6
102
5
Connection Diagram
2- Relay Outputs
1- Voltage Inputs 3- Auxiliary Supply Input
5- RS-4854- Current Inputs
Terminal Structure;
Connection Range Klemens Tipi
1 Voltage Inputs 3 x 10 – 480 VAC 50/60Hz 4 x 7.62 mm socket
2.5 mm², 4 mm²
2 Relay Outputs 2 x 250 VAC 5A 1250 VA 4 x 5.08 mm socket
2.5 mm² / 4 mm²
3 Auxiliary supply input 100-270 VAC / 50-60 Hz 3 x 5.08 mm socket
2.5 mm² / 4 mm²
4 Current Inputs 3 x 0.05 – 5.5A / AC 50-60 Hz 6 x 5.08 mm socket
2.5 mm² / 4 mm²
5 RS-485 Max. ±12V 3 x 3.81 mm socket
1.5 mm² / 2.5 mm
6
1. 3P4W (Three-Phase Four-Wire) Connection
GND B(-) A(+)
GND B(-) A(+)
GND B(-) A(+)
In this type of connection, three voltage and three current connections are made.
2. 3P3W (Three-Phase Three-Wire) Connection
In this type of connection, three voltage and three current connections are made.
3. Aron Connection without Neutral
In this type of connection, three voltage and two current connections are made.
7
4. 3P4W BLN (Three-Phase Four-Wire Balanced) Connection
GND B(-) A(+)
GND B(-) A(+)
In this type of connection, four voltage and one current connections are made. The device displays the value measured at the current input connected to the rst phase on the screen of the same value for other phases.
5. 3P3W BLN (Three-Phase Three-Wire Balanced) Connection
In this type of connection, three voltage and one current connections are made. The device displays the value measured at the current input connected to the rst phase on the screen of the same value for other phases.
Connection types may vary depending on the device model.
8
LED Indicator and GUI design
Key Functions
Phase 1 / 2 / 3 LEDs
VLN Measurement LED
It informs you that voltage is taken from the phases. (e.g. LED L1 lights up if voltage is being taken from phase
L1.)
It lights up when the screen showing phase-neutral voltages is on
VLL Measurement LED
Current Measurement LED
Frequency LED
cosф Measurement LED
Latch Symbol
Unit Symbols
Percentage Symbol
Second Symbol
Total Symbol
Language Navigation LED
Lock Navigation LED
Mains Navigation LED
It lights up when the screen showing phase-phase voltages is on
It lights up when the screen showing phase currents is on
It is the frequency LED
It lights up when the screen showing phase cosф is on
It lights up when there is a phase sequence error.
It lights up when the alarm is activated and continues to light up until you press and hold the 3rd-second key after
the alarm is deactivated.
The screen for THD and Hysteresis also lights up.
It lights up when the screen where the menu and display language of the device can be set is on
It lights when the main setting screen of the password protection values is on
It lights up when the screen where the mains settings of the meter are completed is on
Transformer Navigation LED
Communication Navigation LED
Input-Output (I/O) LED
Alarm Navigation LED
Reset Navigation LED
Info Navigation LED
Relay 1 Output LED
Relay 2 Output LED
It lights up when the screen with voltage transformer and current transformer master view and settings is on
It lights up when the screen where the Modbus Communication settings are displayed and changed is on
This LED lights up when the input and output settings of the device are being made
It lights up when the screen where you can access the alarm settings is on
It lights up when the setting screen where Min, Max, Demand values are deleted is on
It lights up when the menu for displaying information such as software, hardware versions, serial number, date,
time of the device is on
It lights up when the relay output is active
It lights up when the relay output is active
9
Measurement
Voltage
This screen shows the phase-neutral voltage values for each phase. You can see Min Voltage (Phase-Neutral) and Max Voltage (Phase-Neutral) values by pressing the OK button. Depending on the connection type in the Phase-Neutral voltage (3P3W, 3P3W balance and Aron), this screen will not be displayed.
This screen shows the phase-phase voltage values for each phase. You can see Min Voltage (Phase­Phase) and Max Voltage (Phase-Phase) values by pressing the OK button.
10