Entes DCA-10, DCA-10S, DCA-10A, DCA-10CS, DCA-11A User Manual And Menu Map

...
Page 1
A4741 / Rev.1
www.entes.com.tr
DC AMMETER
DCA-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS User Manual and Menu Map
Page 2
2
1
Read the user manual completely before using the device.
The box is under dangerous high voltage. The device must be installed and serviced only by a qualified service personnel.
Is not displayed when limit is crossed in opposite direction.
If a current higher than the defined current value flows through the shunt resistor, a warning is displayed like the one on the left.
H CURRENT
Warnings
- Connect a button or a circuit breaker between the grid and the supply inputs of the device.
- This button or circuit breaker must be in close proximity of the device.
- This button or circuit breaker must be marked to indicate that it is used to separate the device from the grid.
Standards That Are Applied To The Device
EN 61010-1, EN 60255-5, EN 60255-22-5, EN 60255-22-4, EN 60255-22-2, EN 60255-11, EN 60255-22-3
Guarantee
The device has a 2 year guarantee. In case of a malfunction, repairs of the device must be done only by the authorised technical service or the guarantee will be void.
1. INTRODUCTION............................................................................................1
1.1. APPLICATIONS..................................................................4
1.2. GENERAL FEATURES...........................................................4
1.3. FRONT PANEL.....................................................................5
1.4. HARDWARE FEATURES......................................................7
2. USAGE OF DEVICE......................................................................8
2.1. MENU USAGE AND SETTINGS..........................................8
2.2. MAIN MENUS.....................................................................8
2.2.1. SHUNT MENU.............................................................10
2.2.2. PERIOD SETTING MENU.............................................11
2.2.3. ALARMS MENU............................................................11
2.2.4. ANALOG OUTPUT SETTING MENU............................19
Index
ATTENTION
- Disconnect all power before connecting the device.
- Dont remove the front panel while the device is connected to the network.
- Dont clean the device with solvent or similar substances. Only clean with a dry cloth.
- Verify correct terminal connections when wiring.
- Electrical devices should be serviced only by your component seller.
- Device is for rack panel mounting only.
- Fuse which will be used must be F type and its current limit value must be 1A.
- No responsibility is assured by the manufacturer or any of its subsidiaries for any problems arising out of the disregard of these conditions.
SECURITY
Page 3
3
4
2.2.5. RS-485 SERIAL COMMUNICATION SETTING MENU..........21
2.2.6. RESET MENU.................................................................25
2.2.7. DISPLAY SETTING MENU...............................................26
2.2.8. LANGUAGE SETTING MENU..........................................27
2.2.9. FACTORY SETTING MENU.............................................28
2.2.10. SECURITY SETTING MENU................................................29
2.2.11. LEAVING THE MAIN MENU............................................30
3. INSTALLATION..........................................................................................31
3.1. DIMENSIONS AND INSTALLATION........................................31
3.2. CONNECTION DIAGRAM..........................................................32
3.3. PC CONNECTION....................................................................33
4. FACTORY DEFAULT VALUES.......................................................34
5. TECHNICAL FEATURES......................................................................36
6. REGISTER TABLE..........................................................................38
7. MENU MAP..................................................................................46
1.INTRODUCTION
1.1.APPLICATIONS: You can achieve the following measurements and applications with the device.
- Current values of various DC systems can be measured with adjustable shunt current and voltage values.
- All measured parameters can be transferred via RS485 line with MODBUS protocol and menu settings can be set remotely. (DCA-10S/10CS/11S/11CS)
- With 2 programmable Alarm Relays, a range in which the monitored system current should reside can be determined and a warning signal can be created for the user with Alarm1 (C1) and Alarm2 (C2) contact outputs if this monitored current goes out of the determined range. (DCA-10C/10CS/11C/11CS)
- With a programmable Analog Output, the device can be programmed to give a voltage or current output according to the measured current value. (DCA-10A/11A)
- Measured maximum-minimum values can be monitored by using UP/DOWN buttons.
- Settings can be accessed easily and read comfortably with the back-lit LCD feature.
- Measurement results can be calculated in a desired time with an adjustable measurement period of 1­600 s.
- The device provides flexible usage with wide supply voltage range. 85-265 V AC/DC (DCA-10/10A/10C/10S/10CS), 10-56V DC (DCA-11/11A/11C/11S/11CS )
- The device settings can be protected from changes by unauthorized personnel by specifying a 4 digit user password.
1.2 GENERAL FEATURES
The device is designed to measure the current on a DC system through an externally connected shunt resistor.
Page 4
5 6
1.3 FRONT PANEL
The device has a back-lit 2.5 LCD which contains two lines as numeric and alpha-numeric, warning symbols and notification signs. There are three buttons for programming the device. Explanations about the display and buttons are listed on the right side.
Usage of Front Panel and Buttons
1. Up button
2. Set button, for entry to menu and value entry
3. Down button
4. Indicates that the password protection is active.
5. Indicates the existence of communication. It blinks during communication. (DCA-10S/10CS/11S/11CS)
6. The line where measured parameters are displayed.
7. Indicates the direction of the measured voltage.
8. Indicates the notification messages or the menu where the user is.
9. Units belonging to measurements and analog output parameters.
10. Indicates that the contact or contacts are in a high fault state. When entering a value in High Alarm type, it lights up continuously. When entering a low value for Range Alarm type, it lights up continuously and when entering a high value for Range Alarm type, it blinks.(DCA-10C/10CS/11C/11CS)
11. Indicates that the contact or contacts are in a low fault state. When entering a value in Low Alarm type, it lights up continuously. When entering a high value for Range Alarm type, it lights up continuously and when entering a low value for Range Alarm type, it blinks.(DCA-10C/10CS/11C/11CS)
12. 1st Contact Output (DCA-10C/10CS/11C/11CS)
13. 2nd Contact Output (DCA-10C/10CS/11C/11CS)
14.15. Indicates that the contacts are closed.(DCA-10C/10CS/11C/11CS)
DC AMMETER
C1
C2
Rx/Tx
%
PASSWORD
88888
A
DCA-10S
4 5
6
8
1
2
3
9
7
10
11 12 14
13 15
Page 5
7
8
Special Functions for Buttons
UP button: In monitoring mode, it is used to display the maximum current value.
In program mode, it is used to change the device parameters.
SET button: When it is pressed for 3 seconds, the user enters MAIN MENU. It is then used to
enter SUB MENUs from the MAIN MENU and to save the changes in parameters. If Latch function is active, it opens the alarm output contacts when the system current leaves the programmed range. When the current enters the programmed range, alarm output contacts dont close (lock-hold). Output contacts are closed by using the SET button.
DOWN button: In monitoring mode, it is used to display the minimum voltage value.
In program mode, it is used to change the device parameters.
1.4 HARDWARE FEATURES
- Current measurement connector (2-pin, I+, I-)
- 0/2-10V, 0-4/20 mA Analog Output connector (3-pin, V, GND, I)(DCA-10A/11A)
- RS-485 connector (4-Pin)(DCA-10S/10CS/11S/11CS)
- 2 Relay connectors ( 4-pin)(DCA-10C/10CS/11C/11CS)
- Supply input (2-pin) (85-265V AC/DC (DCA-10/10A/10C/10S/10CS), 10-56V DC (DCA-11/11A/11C/11S/11CS))
2- USAGE OF DEVICE:
2.1 MENU USAGE AND SETTINGS:
After the device is installed according to the connection diagram in the user manual, energise the device.(Refer to: Connection diagram) In order for the measurements and applications to be accurate, necessary adjustments must be made by using menus.
2.2 MAIN MENUS:
There are 10 main menus on the device for measurement and usage settings. The user can access MAIN MENUs by pressing the SET button for 3 seconds on measurement screen. By pressing the SET button on any MAIN MENU, SUB MENUs of the related MAIN MENU is entered. Note: In order for a change that you committed in the menu to be in effect, you must give approval for those changes when exiting the menu. Otherwise, changes will not be in effect.
Page 6
2.2.1 SHUNT MENU
Current and voltage values of the external shutn resistor which will be connected to the device to measure the current is set in this menu. There are 2 submenus under SHUNT menu.
SHUNT C, SHUNT V.
SHUNT C Shunt Current Setting Menu
The current value of the shunt resistor which will be connected to the device is entered in this menu. Shunt current can be entered between 1A and 10000A (10 kA). When this parameter is changed, maximum and minimum current values stored up until that time are deleted. Note: The shunt that you will connect to the system must have a current characteristic 1.5 times than the current need of your system. Example: If your current need is 100A, the minimum current value of the shunt that you will connect must be 150A. If you connect a 100A shunt to a 100A system, it may cause the shunt to burn up over time. Additionally; in order for the shunt to be compatible with the measuring class of the device, it must be minimum 0.5% class. Otherwise, you cant obtain a 0.5% accuracy with the measurements made with the device.
10
BACK MENUSHUNT VSHUNT CSHUNT C V
SET
SET
00100 150
A mV
SHUNT C SHUNT C
0100
SHUNT C
SET
0005
00050
SET SET
00100
A
SHUNT C
A
9
MAIN MENU FLOW
001.00
Only valid for DCA-10C/10CS/ 11C/11CS.
Only valid for DCA-10A/11A.
Only valid for DCA-10S/10CS/ 11S/11CS.
RESETDISPLYSETLANGUAGE
ENG
FCTRY SETSECURITY
ESCAPE
RS 485
SHUNT C V
PERIOD
001
ALARMS
ANLG OUT
NO
SET
Press for 3 seconds.
Page 7
SHUNT V Shunt Voltage Setting Menu
The voltage value of the shunt resistor which will be connected to the device is entered in this menu. Shunt voltage can be entered between 50mV and 150mV. When this parameter is changed, maximum and minimum current values stored up until that time are deleted.
SHUNT V
50
SHUNT V
SET
05
050
SET SET
150
SHUNT V
SHUNT V
mV
mV
11 12
ALARMS
SET
ALARM 1
SET
TRIPALARM 2
NO
LATCH
NO
BACK MENU
2.2.2 PERIOD Period Setting Menu
After the device samples for a specified time, it displays the measurement result by calculating the mean value of those samples. You can set the sampling time in this menu. Period value can be entered between 1-600 seconds.
PERIOD
PERIODPERIOD
01
PERIOD
SET
001
05
050
SET SET
2.2.3 ALARMS Alarms Menu
DCA -10C/10CS/11C/11CS devices have two normally open (NO) contact outputs. Operating modes of the alarms are set in this menu. Each alarm can be set to one of six operating modes. These modes are high alarm, low alarm, high-low (range) alarm and their 3 inverted counterpart modes. This menu has 4 sub-menus.
ALARM1, ALARM2, TRIP, LATCH.
ALARM1Alarm 1 Setting Menu
Operating mode of the relay on the device and the parameter according to that operating mode is set in this menu. All settings belonging to 1. Alarm relay is done in this menu. Settings belonging to 2nd Alarm relay can be done in ALARM2 menu. This menu has 1 sub-menu.
ALARM 1
SET
ALRM STAT
BACK MENU
SET
Page 8
14
When the alarm type is selected as High Alarm, first contact output opens after an on-delay time (H ON DEL) if the measured current becomes more than the entered maximum current value (HGH VALUE) and
immediate opening option is inactive. In this case, up segment on the LCD and the dot in the C1 segment turn on. When the measured current drops below the set maximum value (HGH VALUE) as much as the high hysteresis value (HIGH HYS) and immediate opening option is inactive, first output contact closes after an off-delay time (H OFF DEL). In this case, up segment on the LCD and the dot in the C1 segment turn off.
13
CONTC POS
SET
OFF
CONTC POS
CONTC POS
ON
SET
ALRM STAT
SET
SET
SET
OFF
ALRM STAT
CONTC POS
OFF
ALRM TYPE
HIGH
BACK MENU
SET
"ALRM STAT" Alarm Status Setting Menu
Alarm function of the relay is activated in this menu. If "OFF" option is selected in this menu, alarm parameters of the corresponding relay cant be accessed. If the alarm function will be used, "ALRM STAT" option must be set as "ON" in this menu. When alarm status is set as ON, the 2 sub-menus of this menu become accessible. These menus are "CONTC POS" and "ALRM TYPE" menus.
CONTC POS Contact Position Setting Menu
The starting position of the alarm relay output is set in this menu. If this option is selected as OFF, contact output starts as open when there isnt a fault condition. If this option is selected as ON, contact output will be closed when there isnt a fault condition. It is set OFF as factory default.
ALRM TYPE Alarm Type Setting Menu
Operating mode of the alarm is set in this menu. Alarm has 3 operating modes which are High, Low and Range (High-Low).
ALRM TYPE
ALRM TYPE
SET
HIGH
ALRM TYPE
LO
SET
Page 9
15 16
When the alarm type is selected as Low Alarm, first contact output opens after an on-delay time (L ON DEL) if the measured current becomes less than the entered minimum current value (LOW VALUE) and immediate opening option is inactive. In this case, down segment on the LCD and the dot in the C1 segment turn on. When the measured current rises above the set minimum value (LOW VALUE) as much as the low hysteresis value (LOW HYS) and immediate opening option is inactive,
first output contact closes after an off-delay time (L OFF DEL). In this case, down segment on the LCD and the dot in the C1 segment turn off.
When the alarm type is selected as High-Low Alarm (Range), LOW VALUE operates as low alarm and HGH VALUE operates as high alarm. While this alarm type is selected, minimum current value (LOW VALUE) cant be entered higher than maximum current value (HGH VALUE).
H ON DEL
It is the delay time for the high current alarm to activate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.
H ON DEL
50.0
H ON DEL
SET
005.
005.0
SET SET
050.0
H ON DEL
H ON DEL
HIGH ALARM HGH VALUE
The highest value that you want the measured current to reach is entered in this menu. A value between
-/+ Shunt Current can be entered. If the value is entered as 0 (zero), high alarm is deactivated.
HGH VALUE
00
HGH VALUE
SET
05
050
SET SET
100
HGH VALUE
HGH VALUE
A A
HIGH HYS
Return value (to the normal operation) from the high current fault which is the hysteresis current value is entered in this menu. A value between 0...Shunt Current/2 can be entered.
HIGH HYS
50
HIGH HYS
SET
03
030
SET SET
050
HIGH HYS
HIGH HYS
A A
H OFF DEL
It is the delay time for the high current alarm to deactivate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.
H OFF DEL
H OFF DEL
SET SET SET
H OFF DEL
H OFF DEL
50.0 005.
005.0
050.0
LOW ALARM LOW VALUE
The lowest value that you want the measured current to reach is entered in this menu. A value between
-/+ Shunt Current can be entered. If the value is entered as 0 (zero), low alarm is deactivated.
LOW VALUE
00
LOW VALUE
SET
05
050
SET SET
100
LOW VALUE
LOW VALUE
A A
Page 10
17 18
TRIP
If the measured current value becomes more than 1.5 times of set maximum current value when the TRIP function is selected as YES, related alarm contact will open without a delay. In this case, up segment on the LCD and the dot in the C1 segment turn on. If the measured current value becomes less than 0.5 times of set minimum current value, related alarm contact will open without a delay. In this case, down segment on the LCD and the dot in the C1 segment turn on.
TRIP
SET
NO
TRIP
TRIP
YES
SET
LOW HYS
Return value (to the normal operation) from the low current fault which is the hysteresis current value is entered in this menu. A value between 0...Shunt Current/2 can be entered.
LOW HYS
50
LOW HYS
SET
03
030
SET SET
050
LOW HYS
LOW HYS
A A
L ON DEL
It is the delay time for the low current alarm to activate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.
D ON T
D ON T
SET SET SET
D ON T
D ON T
50.0 005.
005.0
050.0
L OFF DEL
It is the delay time for the low current alarm to deactivate. The value is entered as seconds. It can be entered between 000.0 and 999.9 seconds.
D OFF T
D OFF T
SET SET SET
D OFF T
D OFF T
50.0 005.
005.0
050.0
LATCH
When the latch function is selected as YES, a predefined alarm contact will open in case an alarm state arises. When the alarm state is resolved, the contact remains open (It latches). To close the alarm outputs after the alarm state is resolved, SET button is pressed. When the latch function is selected as NO, the opened alarm output will close after the predefined delay time.
LATCH
SET
NO
LATCH
LATCH
YES
SET
Page 11
19
20
2.2.4 ANLG OUT Analog Output Setting Menu ANLG OUT
The device can give a voltage or current output with respect to the measured current according to your selection. Analog output value can be selected as 0-10V, 2-10V, 0-20mA or 4-20mA. The user can set the analog output type, turn off the analog output, learn the active analog output type or set the minimum and maximum values which the device will take into consideration when generating an analog output.
ANLG OUT
SET
ANLG OUT
SET
mA
0-20
ANLG OUT
ANLG OUTANLG OUT ANLG OUT
SET SET SET SET
BACK MENU
HIGHEST
200
LOWEST
000
SET
mA mA V V
V V
HIGHEST
The current value corresponding to the maximum value of the selected analog output type is set in this menu. This value can be entered between -/+ Shunt Current values. Example: When the analog output type is selected as 0 - 20 mA and HIGHEST value is set as 100A, current value on the analog output will be 20 mA when the measured current becomes 100A.
LOWEST
The current value corresponding to the minimum value of the selected analog output type is set in this menu. This value can be entered between -/+ Shunt Current values. Example: When the analog output type is selected as 0 - 20 mA and LOWEST value is set as 10A, current value on the analog output will be 0 mA when the measured current becomes 10A.
LOWEST
00
LOWEST
SET
03
030
SET SET
000
LOWEST
LOWEST
A
A
HIGHEST
00
HIGHEST
SET
10
SET SET
200
HIGHEST
A
HIGHEST
100
A
Page 12
21 22
2.2.5 RS-485 Serial Communication Setting Menu
All measured parameters can be transferred via RS485 line with MODBUS protocol and menus can be set remotely. Note: Communication feature is available only on DCA-10S/10CS/11S/11CS models. In order for the communication to be accomplished; Address, Baudrate and Parity values must be entered to the device correctly. RS  485 menu has 3 sub-menus. ADDRESS , BAUDRATE , PARITY.
ADDRESS Address Setting
Address information can be entered between 1 and 247.
ADDRESS
ADDRESSADDRESS
01
ADDRESS
SET
001
03
030
SET SET
PARITYBAUDRATE
9600
ADDRESS
001
RS-485
SET
BACK MENU
NONE
SET
PARITY Parity Setting
Parity can be entered as none, odd or even.
BAUDRATE Baudrate Settings
Enter one of the 2400 bps, 4800 bps, 9600 bps, 19200 bps, 38400 bps values as stated in the communication software.
BAUDRATE
BAUDRATE
BAUDRATE
SET
9600
9600
SET
Selected
parameter
is
displayed
PaRITY
PaRITY
PaRITY
SET
NONE
EVEN
SET
Selected
parameter
is
displayed
Page 13
23 24
Read Hold (03H) function is used for reading the measured parameter (intantenaous measurement value, minimum and maximum measurement values) and other setting values of the device. If any register other than this area has been tried to reead, the device will send an error message. For example; below message can be sent to read the measured current value:
Preset Single Register (06H) function is used for change device settings (shunt voltage/current etc.) and resetting the measured minimum/maximum values. For example; below message can be sent to set the shunt voltage value to 100:
Preset Multiple register (10H) function is used for changing more than one register value. For example; below message can be sent to set the shunt voltage and shunt current values to 100:
Read device info (2BH) function is used to learn the manufacturer name, the device code, hardware version and software version. The query packet to read the device info is as following: 01 2B 0E 01 00 70 77
MODBUS RTU PROTOCOL
Standart MODBUS RTU message is shown below.
T
ADDRESS
8 BIT
FUNCTION 8 BIT
DATA
N x 8 BIT
CRCH CRCL T
Modbus Functions:
The T times corresponds to a time in which data must not be exchanged on the communication bus to allow the connected devices to recognize the end of one message and the beginning of another. This time must be at least 3.5 characters at the selected baud rate. Adress range (1-247) is address of the connected device. The data field contains data sent to the slave by master or data sent to master by slave. CRC is a error check method by using MODBUS RTU protocol and consists of 2 bytes.
03H READ HOLD REGISTERS
06H PRESET SINGLE REGISTER
10H PRESET MULTIPLE REGISTERS
2BH READ DEVICE INFO
01
Device
Address
03
Function40MSB
Address
00
LSB
Address
00
Register
number
MSB
01
Register
number
LSB
91 CRC MSB
CA
CRC
LSB
E1
CRC
LSB
01
Device
Address
06
Function
80
MSB
Address
00
LSB
Address
00 Data MSB
64
Data
LSB
A1 CRC MSB
01
Device
Address
10
Function80MSB
Addr.
00
LSB
Addr.
00
Register
number
MSB
02
Register
number
LSB
04
Byte
count
00
Data MSB
64 Data LSB
00 Data MSB
64
Data
LSB
D2 CRC MSB
ED
CRC
LSB
Page 14
25 26
BACKLIGHT LCD Backlight Setting Menu
Backlight feature of the device is configured in this menu. Available choices are as following: NO Off. YES Continuously on. "30 s" On for 30 seconds, "60 s" On for 1 minute, "300 s" On for 5 minutes, "900 s" On for 15 minutes. Backlight turns off after the selected time if no button is pressed at the end of that time.
2.2.6 RESET Reset Menu
Minimum and maximum values among measured current values are stored on the device. Reset menu is used in order to delete these values. There are 2 sub-menus under Reset menu: RESET MIN, RESET MAX. To see the measured minimum and maximum values, refer to the Special Functions for Buttons section of this user manual.
NOTE: Stored values are not affected from power outages. After you select YES option under the value that you want to reset and approve the changes when you exit or a zero (0) value is written into the addresses that these values are stored, measured minimum and maximum values are deleted.
BACK MENURESET MAXRESET MINRESET
SET
SET
RESET MAX Maximum Value Reset Menu
It is the menu where stored maximum current value is deleted.
RESET MIN Minimum Value Reset Menu
It is the menu where stored minimum current value is deleted.
RESET MAX
RESET MAX
RESET MAX
SET SET
RESET MIN
RESET MIN
RESET MIN
SET SET
2.2.7 DISPLYSET Display Setting Menu
Settings about the device display are done in this menu. Display setting menu has 2 sub-menus:
BACKLIGHT, CONTRAST.
BACK MENU
CONTRAST
15
BACKLIGHT
YES
DISPLYSET
SET
SET
Page 15
27 28
BACKLIGHT
BACKLIGHT
BACKLIGHT
SET
30 S
SET
Selected
parameter
is
displayed.
YES
CONTRAST Contrast Setting Menu
Contrast of the device display is set in this menu. It can be set to a value between 00 and 15.
2.2.8 LANGUAGE Language Setting Menu
Language of the device is set in this menu. There are 2 language options as Tr Turkish and Eng English.
CONTRAST
CONTRASTCONTRAST
5
CONTRAST
SET
15
1
10
SET SET
DIL
LANGUAGE
LANGUAGE
SET SET
TRENG
2.2.9 FCTRY SET Factory Setting Menu
Factory settings are loaded in this menu. A 4 digit password is asked when entering this menu. If password protection is active, the password isnt asked again when entering this menu because it was entered during entering the main menu. If YES option is selected in this menu and SAVE confirmation is approved at the exit of main menu, factory settings are loaded (Refer to: Factory Default Values).
FCTRY SET
FCTRY SET
ENTR PASSENTR PASS
000
SET
000
If password is inactive.
If password is active.
If password is wrong.
ENTR PASS
ERROR
SETTINGS
DONE
If password is correct.
SET
SET
NOTE: When factory settings are loaded, language setting stays unchanged. The language will be the same
as the on selected last.
Page 16
29 30
2.2.10 SECURITY Security Setting Menu
Device password settings are done in this menu. There are 2 sub-menus under SECURITY menu. PASS ACTV, PASS CHNG. Password activation and changing operations are done under these menus. Factory default password is 0000.
BACK MENU
PASS CHNGPASS ACTVSECURITY
SET
SET
NO
PASS ACTV Password Activation Menu
Password protection is activated or deactivated in this menu.
CHNG PASS Change Password Menu
Password is changed in this menu.
2.2.11 ESCAPE Exiting Main Menu
It is used to exit the main menu. If any changes has been made in the menus, a confirmation is asked to save those changes. If there are no changes, measurement results are displayed without a confirmation.
SAVE
ESCAPE
SET
SET
SET
Changes
are saved.
Changes
are
discarded.
024.00
MEASUREMENT
SCREEN
ACTVE
Selected
parameter
is
displayed.
PASS ACTV
SET
ENTR PASSENTR PASS
000
SET SET
000
PASS ACTV
PSIVE
SET
CHNG PASS
SET
OLD PASSOLD PASS
000
SET SET
000
NEW PASS
NEW PASS
000
SET
SET
REENTER
111
REENTER
SET
SET
PAS CHNGD
111
000
A
Page 17
31 32
3.2. CONNECTION DIAGRAM
85-265 V AC/DC
Un
+
14 15
-
+
12 13
-
Iin
RS-485
8 9 10 11
1A
RELAY 1
1 2 3 4 5 6 7
RELAY 2 V GND A
* **
TR B A GND
***
*****
********
+
-
DC
SOURCE
LOAD
ENTES
500 A 60 mV
Cl 0.5
* Only for DCA-10C/10CS/11C/11CS ** Only for DCA-10A/11A *** Only for DCA-10S/10CS/11S/11CS **** Only for DCA-11/11A/11C/11S/11CS ***** DCA-10/10A/10C/10S/10CS 85-265V AC/DC, DCA-11/11A/11C/11S/11CS 9-56V DC
Control Panel Area Dimensions
TYPE PR 20 (48x96)
48mm
96mm
Dimensions
43mm
54mm
Wall
50mm
TYPE PR 20 (48x96)
63mm
TYPE PR 20 (48x96)
44mm
91mm
Panel Cutout Dimensions
3. INSTALLATION
3.1. DIMENSIONS AND INSTALLATION
Page 18
4. FACTORY DEFAULT VALUES: Alarms:(DCV-10C/10CS/11C/11CS)
1.Alarm:
Alarm Status : Passive Latch : Off Trip : Off Contact Position (Output Inverse) : Off Alarm Type : High Alarm High Alarm Value : 100A Low Alarm Value : 10A High Alarm Hysteresis : 10A Low Alarm Hysteresis : 5A High Alarm On Delay (d_on_time) : 20s High Alarm Off Delay (d_off_time) : 10s Low Alarm On Delay (d_on_time) : 20s Low Alarm Off Delay (d_off_time) : 10s
2.Alarm:
Alarm Status : Passive Latch : Off Trip : Off Contact Position (Output Inverse) : Off Alarm Type : High Alarm High Alarm Value : 100A Low Alarm Value : 10A High Alarm Hysteresis : 10A Low Alarm Hysteresis : 5A
33
34
GND
GND
B A
PC
...
REPEATER
MAX. 1200 mt. MAX. 1200 mt.
TR
B
A
...
RS-485 / RS-232
Converter
247 DEVICES CAN BE CONNECTED ON THE SAME LINE BY USING A REPEATER
DCA-10S/10CS -247. DCA-11S/11CS -247.
DCA-10S/10CS -31. DCA-11S/11CS -31.
DCA-10S/10CS -2. DCA-11S/11CS -2.
DCA-10S/10CS -1. DCA-11S/11CS -1.
3.3. PC CONNECTION
GNDTR B A
GNDTRB A
GNDTR B A
GND
B A
PC
..
.
DCA-10S/10CS -31. DCA-11S/11CS -31.
MAX. 1200 mt.
RS-485 / RS-232
Converter
MAX. 31 DEVICES CAN BE CONNECTED ON THE SAME LINE
DCA-10S/10CS -2. DCA-11S/11CS -2.
DCA-10S/10CS -1. DCA-11S/11CS -1.
Page 19
High Alarm On Delay (d_on_time) : 20s High Alarm Off Delay (d_off_time) : 10s Low Alarm On Delay (d_on_time) : 20s Low Alarm Off Delay (d_off_time) : 10s
Shunt Parameters:
Shunt Current : 150A Shunt Voltage : 150 mV
RS 485: (DCA-10S/10CS/11S/11CS )
Address : 1 Baudrate : 9600 Parity : None
Analog Output: (DCA-10A/11A)
Analog Output : 0 - 20 mA Assign Hi : 200A Assign Lo : 0A
Period : 1 (second) Display
Backlight : On Contrast : 15
Security
Password Protection : Off Password : 0
35 36
5. TECHNICAL FEATURES: Operating Voltage (Un) : 85-265V AC/DC (DCA-10/10A/10C/10S/10CS),
10-56V DC (DCA-11/11A/11C/11S/11CS)
Frequency :50/60 Hz (DCA-10/10A/10C/10S/10CS) Supply Input Power Consumption :< 4 VA Measuring Input Power Consumption :< 1 VA Measuring Input Resistance (Rin) :< 1K Iin :+/- 150mV Measuring Current Range : +/-10000A Accuracy :0.5% ±1 Digit [(10% - 100%) x full scale] Shunt Current :1A- 10000A (10kA) Shunt Voltage : 50mV - 150mV Relay Outputs (2 pieces) :2 NO, 5A 1250 VA (DCA-10C/10CS/11C/11CS) Communication :MODBUS RTU (RS-485) Programmable.(DCA-10S/10CS/11S/11CS)
Baudrate :2400 - 38400 Address :1-247 Parity :None, Odd, Even
Analog Output :(DCA-10A/11A)
Analog Voltage Output :0-10 V or 2-10 V Load Resistance :>= 1K2 Update Period :100ms (milliseconds). Analog Current Output :0-20 mA or 4-20 mA Load Resistance :<= 500ohm Update Period :100ms (milliseconds).
Accuracy :±0.01 FS%
Period :1 - 600 seconds
Page 20
37
38
Ambient Temperature : -20 ... 70°C Display :2.5 inches Backlit LCD Dimensions :PR-20 Device Protection Class :Double Insulation - Class II ( ) Casing Protection Class :IP 40 Terminal Protection Class : IP 00 Wire Width (For Terminals) : 2.5mm2 Casing Material :Nonflammable Installation Type :Flush Mounting ( PR-20 ) Weight : 0.240 kg Installation Class :Class III Panel Cutout Dimensions :48X96 mm (PR-20)
6. REGISTER TABLE:
Trip Active
Latch Inactive Latch Active
Description Range
W/R Unit
Multiplier Format
Trip Inactive
DC Voltage Value
Max. Measurement Value
Min. Measurement Value Shunt Current Shunt Voltage Alarm 1 Activation
Alarm 1 Latch Function
Alarm 1 Trip Function
Protection Inactive Protection Active
16 Bit Register Table
150 mV
150 mV
150 mV
Page 21
39
40
Description Range
W/R Unit
Multiplier Format
A
A
A
A
Description
Range
W/R Unit
Multiplier Format
Normal Inverted
High Protection Active Low Protection Active Range Protection Active
Alarm 1 High Warning Value
Alarm 1 Low Warning Value
Alarm 1 High Hysteresis
Alarm 1 Low Hysteresis
Alarm 1 High Alarm ON Delay
Alarm 1 High Alarm OFF Delay
Alarm 2 Latch Function
Alarm 2 Trip Function
Alarm 1 Low Alarm ON Delay
Alarm 1 Low Alarm OFF Delay
Alarm 2 Activation
Protection Inactive Protection Active
Trip Active
Latch Inactive Latch Active
Trip Inactive
Inverted
Normal
High Protection Active Low Protection Active Range Protection Active
Alarm 1 Contact Position
Alarm 1 Alarm Type
Alarm 2 Contact Position
Alarm 2 Alarm Type
second
second
second
second
Shunt Current
Shunt Current
Shunt Current/2
Shunt Current/2
Page 22
41
42
Description
Range
W/R Unit
Multiplier Format
A
A
A
A
Description Range
W/R Unit
Multiplier Format
Alarm 2 High Warning Value
Alarm 2 Low Warning Value
Alarm 2 High Hysteresis
Alarm 2 Low Hysteresis
Alarm 2 High Alarm ON Delay
Alarm 2 High Alarm OFF Delay
Alarm 2 Low Alarm ON Delay
Alarm 2 Low Alarm OFF Delay
second
second
second
second
Relay Status
b0: 0 Relay 1 open b0: 1 Relay 1 closed
b2: 0 Relay 1 High Alarm Fault b2: 1 Relay 1 Low Alarm Fault
b3: 0 Relay 1 High Alarm ON delay doesnt count b3: 1 Relay 1 High Alarm ON delay counts
b4: 0 Relay 1 High Alarm OFF delay doesnt count b4: 1 Relay 1 High Alarm OFF delay counts
b5: 0 Relay 1 Low Alarm ON delay doesnt count b5: 1 Relay 1 Low Alarm ON delay counts
b6: 0 Relay 1 Low Alarm OFF delay doesnt count b6: 1 Relay 1 Low Alarm OFF delay counts
b7: 0 Relay 2 open b7: 1 Relay 2 closed
b8: 0 Relay 2 High Alarm b8: 1 Relay 2 Low Alarm
b9: 0 Relay 2 High Alarm ON delay doesnt count b9: 1 Relay 2 High Alarm ON delay counts
b10: 0 Relay 2 High Alarm OFF delay doesnt count b10: 1 Relay 2 High Alarm OFF delay counts
b11: 0 Relay 2 Low Alarm ON delay doesnt count b11: 1 Relay 2 Low Alarm ON delay counts
b12: 0 Relay 2 Low Alarm OFF delay doesnt count b12: 1 Relay 2 Low Alarm OFF delay counts
Shunt Current
Shunt Current
Shunt Current/2
Shunt Current/2
Page 23
43
44
Description Range
W/R Unit
Multiplier Format
Description Range
W/R Unit
Multiplier Format
Off
On
Description Range
W/R Unit
Multiplier Format
A
A
Analog Output Type/Range
Assign Hi
Assign Lo
Comm. Address
Baud Rate
Parity
Pass. Protection
Password
None Odd Even
1 OUTPUT TYPE VOLT RANGE = 0-10 V
2 OUTPUT TYPE VOLT RANGE = 2-10 V
3 OUTPUT TYPE CURRENT RANGE = 0-20 mA
4 OUTPUT TYPE CURRENT RANGE = 4-20 mA
0 OUTPUT INACTIVE
Backlight Status
Contrast Average Period Language
Backlight Off
Backlight On continuously
Backlight On for 30 seconds
Backlight On for 1 minute
Backlight On for 5 minutes
Backlight On for 15 minutes
second
32 Bit Register Table
DC Current Value
Max. Measurement Value
Min. Measurement Value
- / + (Shunt Current)
- / + (Shunt Current)
Page 24
46
sHUNT C V sHUNT C
00100
sHUNT V
050
BACK MENU
sHUNT V
sHUNT V
50
15
sHUNT C
sHUNT C
0100 1000
Last entered value is displayed.
Last entered value is displayed.
45
DEVICE ID &&
VERSION NO
SERIAL NO
DEVICE ID DEVICE TYPE DEVICE ID DEVICE TYPE DEVICE ID DEVICE TYPE DEVICE ID DEVICE TYPE
Supported Modbus Functions:
03H READ HOLD REGISTERS
06H PRESET SINGLE REGISTER
10H PRESET MULTIPLE REGISTERS
2BH READ DEVICE INFO
When a reading operation from addresses that are not present on the device is done, 0 (zero) value will be read. When a writing operation to addresses that are not present on the device is done, no writing is done and no error code is returned.
DEVICE ID
3 s
PASSWORD
If password
is correct.
PASSWORDPASSWORD
000
024.00
000
If password is inactive.
is displayed if password is active.
7. MENU MAP
A
ERROR
If password
is wrong.
001
PERIOD
PERIOD
PERIOD
01
05
Last entered value is displayed.
Page 25
47 48
ALARMS
ALARM1
ALARM 2
ALARM STAT
OFF
BACK MENU
It returns to one from which alarm setting is returned.
ALARM STAT ALARM STAT
CNTCT POS
OFF
CNTCT POS CNTCT POS
ALRM TYPE
HIGH
BACK MENU
ALRM TYPE ALRM TYPE ALRM TYPE
LOW HYS
005
A
HGH VALUE
100
A
LOW VALUE
010
A
HIGH HYS
005
A
H ON DEL
020.0
HGH VALUE
100
A
TRIP
NO
TRIP TRIP
LATCH
NO
BACK MENU
Only valid for DCA-10C/10CS/11C/11CS.
Selected parameter is displayed.
Selected parameter is displayed
Selected parameter is displayed
Selected alarm type is displayed.
HIGH HYS
010
A
H ON DEL
020.0
H OFF DEL
010.0
LOW VALUE
010
A
LOW HYS
010
A
L ON DEL
020.0
L OFF DEL
010.0
BACK MENU
L ON DEL
020.0
BACK MENU
H OFF DEL
010.0
LATCH LATCH
L OFF DEL
010.0
BACK MENU
Page 26
5049
PARITY
NONE
BACK MENU
9600
BAUDRATE
001
ADDRESSRS 485
BAUDRATE
Last selected parameters is displayed.
Last selected parameters is displayed.
PARITY
01
24
ADDRESS
Last entered value is displayed.
Only valid for DCA-10S/10CS/11S/11CS.
ANLG OUT ANLG OUT
0-20
ANLG OUT
mA
mA
ANLG OUT
mA
ANLG OUT
V
ANLG OUT
V
HIGHEST
100
A
LOWEST
000
A
BACK MENU
Sadece DCA-10A/11A için geçerlidir.
00 20
00 01
HIGHEST HIGHEST
LOWEST
LOWEST
Last entered value is displayed.
Last entered value is displayed.
Page 27
5251
ENG
LANGUAGE
FCTRY SET
If password is wrong.
ENTR PASS
If password is correct.
If password is inactive.
If password is active.
LANGUAGE
LANGUAGE
ENTR PASS
ENTR PASS
000
000
FCTRY SET
SETTINGS
DONE
Selected parameter is displayed
RESET RESET MIN RESET MAX BACK MENU
RESET MIN RESET MAX
DISPLYSET BACKLIGHT CONTRAST BACK MENU
15YES
BACKLIGHT
CONTRAST
CONTRAST
5
1
Selected parameter is displayed.
Last entered value is displayed.
ERROR
Page 28
54
53
ESCAPE
SECURITY
NO
PASS ACTV PASS CHNG BACK MENU
If password is wrong.
If password is correct.
ENTR PASS
ENTR PASS
000
000
PASS ACTV
ENTR PASS
Selected parameter is displayed.
SAVE
Changes are
saved.
Changes are
discarded.
120.00
OLD PASS
OLD PASS
000
000
NEW PASS
000
AGAIN
000
AGAIN
111
PAS CHNGD
If password is correct.
OLD PASS
NEW PASS
111
AGAIN
A
ERROR
ERROR ERROR
If password is wrong. If password is wrong.
Loading...