ENTES AKC-01A, AKC-03A User guide [ml]

Genel
AKC-01A / AKC-03A Aþýrý Akým Koruma Rölesi; motorlarý ve sistemleri aþýrý akýma karþý korumak için tasarlanmýþtýr. Bir akým ayarý (Iset) ve iki gecikme ayarýna (baþlama ve bekleme) sahiptir. Baþlama (start) gecikmesi, motor kalkýþ (demeraj) akýmý nedeniyle oluþabilecek hatalý açmalarý önlemek amacýyla geliþtirilmiþtir.
Çalýþma Prensibi
AÞIRI / DÜÞÜK AKIM KORUMA RÖLELERÝ
AKC SERÝSÝ
AKC-01A / AKC-03A AÞIRI AKIM KORUMA RÖLESÝ
Boyutlar
A2842/Rev.4
DÝKKAT: CT-25 Akým trafosunun içerisinden 1den fazla tur
geçirilecekse izolasyonlu kablo kullanýnýz. CT-25 Akým trf. cihazla birlikte satýlmaktadýr.
AKC-01D / AKC-03D DÜÞÜK AKIM KORUMA RÖLESÝ
Güvenli Kullaným ve Kurulum Ýçin Uyarýlar
Aþaðýdaki talimatlara uyulmamasý halinde yaralanma veya ölümle sonuçlanabilecek durumlar ortaya çýkabilir. Cihaz üzerindeki herhangi bir iþlemden önce tüm besleme gerilimlerini kesiniz. Cihaz þebekeye baðlý iken ön paneli çýkarmayýnýz. Cihazý solvent veya benzeri maddelerle temizlemeyiniz. Cihazý temizlemek için sadece kuru bez kullanýnýz. Cihazý çalýþtýrmadan önce baðlantýlarýnýn doðru olduðunu kontrol ediniz. Cihazý panoya monte ediniz. Cihazýnýzdaki herhangi bir sorunda yetkili satýcýnýzla temas kurunuz.
Genel
AKC-01D / AKC-03D Düþük Akým Koruma Rölesi; motorlarý ve sistemleri düþük akýma karþý korumak için tasarlanmýþtýr. Bir akým ayarý (Iset) ve iki gecikme ayarýna (baþlama ve bekleme) sahiptir. Baþlama (start) gecikmesi, motor kalkýþ (demeraj) akýmý nedeniyle oluþabilecek hatalý açmalarý önlemek amacýyla geliþtirilmiþtir.
Çalýþma Prensibi
AKC-01D / AKC-03D motor veya koruduðu sistemin akýmýný ölçer ve bu ölçülen akým deðeri ayarlanan akýmýn (Iset) altýnda ise motoru veya koruduðu sistemi devreden çýkarmak için kullanýlýr. Akým Iset deðerinin üzerinde ise çýkýþ rölesi çekili (ON) konumdadýr. Þayet akým Iset deðerinin altýnda bir deðere ulaþýrsa ayarlanabilir bir bekleme gecikmesi sonunda röle býrakýr (OFF) ve baðlý olduðu motoru veya sistemi devreden çýkarýr. Aþaðýdaki grafiklerde bu durumlar açýklanmýþtýr.
Uyarý ýþýklarý
ON (Güç) : Besleme varsa yanar. OUT (Röle) : Röle çekili iken yanar. I>Iset : Akým ayarlanan akým deðerinin üzerinde ise LED yanar.
Ýþletme Gerilimi (Un) : Cihazýn üzerindeki etikete bakýnýz. Ýþletme Aralýðý : (0.9 -1.1) x Un Ýþletme Frekansý : 50 / 60 Hz Akým Ayar Aralýðý : 0.5 - 5A(AC)
AKC-03 serisi için tablo 1e bakýnýz Akým Trafosu Çevirme Oraný : .../ 5A (AKC-01A/AKC-01D için)
: CT-25 (AKC-03A/AKC-03D için) Baþlama Gecikmesi : 1 - 6 sn. Bekleme Gecikmesi : 0.5 - 2.5 sn. Çýkýþ Kontaklarý : 1 C/O, 8A, 2000 VA, Cosj=1
Ortam Sýcaklýðý : -5 0C ; +55 0C Koruma Sýnýfý : IP 20 Boyutlar : Tip PK 25 Baðlantý Þekli : Pano içine dikey veya klemens rayýna Aðýrlýk : 0.3 kg
Teknik Bilgi
AKC-01A/AKC-01D Baðlantý Þemasý
* Sistem akýmýnýz 5Ai aþýyorsa AKC-3A / AKC-3D serisi cihazlarý kullanýnýz.
AKC-03A/AKC-03D Baðlantý Þemasý
AKC-03A / AKC-03D sadece CT-25 akým trafosu ile kullanýlýr. Optimum çözüme ulaþmak için; CT-25 akým trafosunu yandaki verilen akým aralýklarýnda ve tur sayýlarýnda kullanýnýz.
Tablo 1
AKC-03 Serisi cihazý 2-20A aralýðýnda kullanacaksanýz; Akýmýn geçtiði kabloyu CT-25 akým trafosuna 3 tur sarýn, bu esnada öndeki Iset skalasý þu deðerleri alacaktýr. 1,5x=2A, 3x=4A, 6x=8A, 9x=12A, 12x=16A, 15x=20A
Tablo 1e göre
1,5-15 A
x=4
I Set Skalasý Akým Aralýðý Tur Sayýsý
(1 tur)6-60 A
3-30 A
2-20 A
(4 tur)
(3 tur)
(2 tur)x=2
x=4/3
x=1
Yukarýdaki önlemlerin uygulanmamasý sonucu doðabilecek istenmeyen durumlardan üretici firma hiç bir þekilde sorumlu tutulamaz.
T
1
N
C1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
0.5
1
1
0.5
OUTONOUT
ON
I>Iset
AKC-01A/D
2.5
1.5
2
t(s)
Iset
5
4
3
2
123
6
5
4
3
2
1
t(s) start
T
1
N
L1 L2 L3
N
k I
K L
M
3 ~
Un
N L1
l k 23 1
Stop Start
C
1
AKC-01A AKC-01D
C
1
T
1
Tip PK 25 Tip PK 28
T
1
N
C1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
T
1
N
L1 L2 L3
N
k I
K L
M
3 ~
Un
N L1
l k 23 1
Stop Start
C
1
AKC-03A AKC-03D
C
1
T
1
CT-25
kl
lk
K L
CT-25
Tip PK 25 Tip PK 28
0.5
1
3x
1.5x
OUTONOUT
ON
I>Iset
AKC-03A/D
2.5
1.5
2
t(s)
Iset
15x12x
9x
6x
123
6
5
4
3
2
1
t(s) start
TÝP PK25
35 mm
90 mm
45 mm
62 mm
58 mm
32 mm 48 mm
35 mm
TÝP PK 28
CT-25
16mm
15.5mm43mm
500mm2x0,35mm
2
Motor Akýmý
Normal
Çalýþma
Akýmý
Aþýrý Akým Durumu
(Normal Akýmdan Fazla)
Yüksek Akým Ayarý
(Iset)
Baþlangýç Gecikmesi
Akýma Duyarlý
Röle Gecikmeden
Sonra Motoru Durdurur.
(Röle: OFF)
Aþýrý Akým Koruma Rölesi (AKC-01A/03A)
Zaman
Bekleme Gecikmesi
Baþlama Akýmý
Motor Çalýþmasý Baþlangýç
Gecikmesi Baþlangýcý
Baþlangýç Gecikmesi Sonu
Gecikme Baþlangýcý
Gecikme
Sonu
Düþük Akým Koruma Rölesi (AKC-01D/03D)
Baþlama Akýmý
(Iset)
Düþük Akým Durumu
(Normal Akýmdan Düþük)
Akýma Duyarlý
Röle Gecikmeden
Sonra Motoru Durdurur.
(Röle: OFF)
Normal
Çalýþma
Akýmý
Düþük Akým Ayarý
Baþlangýç Gecikmesi
Bekleme Gecikmesi
Motor Çalýþmasý Baþlangýç
Gecikmesi Baþlangýcý
Baþlangýç Gecikmesi Sonu
Gecikme Baþlangýcý
Gecikme
Sonu
Zaman
Motor Akýmý
Bu ürün, 30.05.2008 tarih ve 26891 sayýlý resmi gazetede yayýnlanan EEE Yönetmeliðinin Madde 2 ve Ek-1A madde 9 kapsamýndadýr.
General
AKC-01A /AKC-03A Over Current Monitoring Devices are designed to protect motors and systems against over current with a current adjustment and two delay adjustments (start-up and tripping). Start-up delay is developed in order to prevent false contact turn-off arising from initial motor start-up (demurrage) currents.
Operation Principles
AKC-01A device measures the current of motor or protected systems and are utilized to turn-off the motor or protected systems when measured current is above the adjusted level. When the current value is lower than Iset value, the output relay is switched on. When the current value becomes higher than Iset value, the output relay is switched off after an adjustable tripping delay time and the motor or protected system is turned off. Please see following figures. For circumstances that the current value becomes higher than Iset value, start-up delay (adjustable: 1-6 sec. ) is developed in order to prevent false contact turn-off arising from initial motor start-up currents.
OVER / UNDER CURRENT MONITORING DEVICES
AKC SERIES
AKC-01A / AKC-03A OVER CURRENT MONITORING DEVICE
Dimensions
A2842/Rev.4
TYPE PK25
35 mm
90 mm
45 mm
62 mm
58 mm
32 mm 48 mm
35 mm
WARNING: If CT-25 current transformer has more than 1 turn,
isolated cable must be used. CT-25 current transformer is selling with the device.
AKC-01D / AKC-03D UNDER CURRENT MONITORING DEVICE General
AKC-01D / AKC-03D Under Current Monitoring Devices are designed to protect motors and systems against under current with a current adjustment and two delay adjustments (start-up and tripping). Start-up delay is developed in order to prevent false contact turn-off arising from initial motor start-up (demurrage) currents.
Operation Principles
AKC-01D / AKC-03D device measures the current of motor or protected systems and are utilized to turn-off the motor or protected systems when measured current is below the adjusted level. When the current value is higher than Iset value, the output relay is switched on. When the current value becomes lower than Iset value, the output relay is switched off after an adjustable tripping delay time and the motor or protected system is turned off. Please see following figures. Start-up delay (adjustable: 1-6 sec. ) is developed in order to prevent false contact turn-off arising from initial motor start-up currents.
Warning leds
On
:ON when power exists
Out
:ON When the output relay is switched on.
I>Iset
:LED turns ON when current value is over adjusted level
Rated Voltage (Un) : Please look at the table on the device. Operating Range : (0.9 -1.1) x Un Operating Frequency : 50 / 60 Hz Current Adjustment Interval : 0.5 - 5A(AC)
Please refer to table 1 for AKC-03
Current Transformer Ratio : .../ 5A (for AKC-01A/AKC-01D)
: CT-25 (for AKC-03A/AKC-03D) Start-up Delay : 1 - 6 sn. Tripping Delay : 0.5 - 2.5 sn. Output Contacts : 1 C/O, 8A, 2000 VA, Cosj=1
Ambient Temperature : -5 0C ; +55 0C Protection Class : IP 20 Dimensions : Tip PK 25 Installation : Surface mounting or on the mounting rails. Weight : 0.3 kg
Technical Data
AKC-01A/AKC-01D Connection Diagram
AKC-3A / AKC-3D series must be used if current exceeds 5A.
AKC-03A/AKC-03D Connection Diagram
AKC-03A / AKC-03D is only used with CT-25 current transformer. In order to reach the solution; CT-25 current transformer must be used with turn numbers in the current intervals as in the table.
Table 1
If you use AKC-03 device 2-20A interval, CT-25 current transformator must be encircled with 3 turns of the cable that current flows. At that time, I set scale takes the values below. 1,5x=2A, 3x=4A, 6x=8A, 9x=12A, 12x=16A, 15x=20A
According to Table 1
Precautions For Installation and Safe Use
Failure to follow those instructions will result in death or serious injury.
Disconnect all power before working on equipment.
When the device is connected to the network, do not remove the front panel. Do not try to clean the device with solvent or the like. Only clean the device with a dried cloth. Verify correct terminal connections when wiring.
Electrical equipment should be serviced only by your compedent seller.
Mount device to the panel
No responsibility is assured by the manufacturer or any of its subsidiaries for any consequences arising out of the use of this material.
1,5-15 A
x=4
I Set Scale Current Interval Turn Number
(1 turn)6-60 A
3-30 A
2-20 A
(4 turns)
(3 turns)
(2 turns)x=2
x=4/3
x=1
TYPE PK 28
CT-25
16mm
15.5mm43mm
500mm
2x0,35mm
2
Motor Current
Normal
Operating
Current
Over Current Condition
(Above normal curent)
Over Current Trip Setpoint
(Iset)
Start-Up Delay
Current sensitive
relay trips and
turns motor OFF
Over Current Monitoring Devices(AKC-01A/03A)
Time
Trip
Delay
Start-up current
Start Motor
Start-up Delay
Begins
Start-up Delay Ends
Trip Delay Begins
Trip Delay
Eds
Undercurrent Monitoring Devices (AKC-01D/03D)
Start-upCurrent
(Iset)
Under Current Condition
(Below normal current)
Current sensitive
relay trips and
turns motor OFF
Normal
Operating
Current
Under Current Trip Setpoint
Start Motor
Start-up Delay
Begins
Start-up Delay Ends
Trip Delay Begins
Trip Delay
Ends
Time
Motor Current
Start-Up Delay
Trip Delay
T
1
N
C
1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
0.5
1
1
0.5
OUTONOUT
ON
I>Iset
AKC-01A/D
2.5
1.5
2
t(s)
Iset
5
4
3
2
123
6
5
4
3
2
1
t(s) start
T
1
N
L1 L2 L3
N
k I
K L
M
3 ~
Un
N L1
l k 23 1
Stop Start
C
1
AKC-01A AKC-01D
C
1
T
1
Type PK 25 Type PK 28
T
1
N
C1
T
1
Stop
Start
C
1
L1
L2
L3
N
k I
K
L
M
3 ~
N L1
2 3 1kl
Un
T
1
N
L1 L2 L3
N
k I
K L
M
3 ~
Un
N L1
l k 23 1
Stop Start
C
1
AKC-03A AKC-03D
C
1
T
1
CT-25
kl
lk
K L
CT-25
Type PK 25 Type PK 28
0.5
1
3x
1.5x
OUTONOUT
ON
I>Iset
AKC-03A/D
2.5
1.5
2
t(s)
Iset
15x12x
9x
6x
123
6
5
4
3
2
1
t(s) start