Entergize T8532OCC Quick Start Manual

24 VAC Unswitched
QUICK START GUIDE
FAN LOW
SET CLOCK, YEAR, MONTH, DAY
NOTE: Display of Clock is not available when
for non­programmable operation.
1. Press ▲/ ▼ to select 12 / 24 Hr mode, then press Next.
2. Press ▲/ ▼to select hour, then press Next.
3. Press ▲/▼to select minutes, then press Next.
4. Press ▲/ ▼ to select current year, then press Next.
5. Press ▲/ ▼ to select current month, press Next.
7. Press Done to complete operation.
note: Select More > Clock, to access after setup.
PERFORMANCE PRO MULTI-
OCCUPANCY THERMOSTAT
41
WIRE TERMINAL DESIGNATIONS
1. connect wires for appropriate system type (Table 1).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
!
• CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
• Use care to avoid electrostatic discharge to thermostat
• CAUTION: Do not connect unused wires together
• ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C (24 VAC).
TABLE 1. TERMINAL BLOCK
Fan Coil (Conventional) Heat Pump
C 24 VAC, Unswitched side C 24 VAC, Unswitched side
W1 Stage 1 Heat B/O Reversing Valve
W2 Stage 2 Heat AUX Auxiliary Heat (Stage 2 or 3)
G FAN High G FAN High
A FAN Medium A FAN Medium
E FAN Low E FAN Low
Y1 Stage 1 Cool Y1 Compressor Stage 1
FAN
2
ACCESS SERVICE MENUS
1. Hold lower right and left keys for fi ve seconds.
2. Press Next or Go Back to select a Service Menu.
3. Press ▲/ ▼ to select option.
4. Press Done when complete.
3
CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require confi guration. Please verify that these are set for your specifi c application. additional confi guration may be required. refer to Table 2 for all available Service Menus.
SM 100 = Programmable or nonprogrammable
• SM 110 = System Type
SM 121 = number of fan Speeds
SM 130 = reversing valve
SM 135 = W1 heat output no or nc
SM 170 = remote Sensors
SM 265 = Single or dual Setpoint operation
Service
Menu
Current
option
Y2 Stage 2 Cool Y2 Compressor Stage 2
RH
RC
SC Sensor Common SC Sensor Common
S1 Indoor Remote Sensor S1 Indoor Remote Sensor
S2 Occupancy Sensor S2 Occupancy Sensor
S3
5
24 VAC Power for heating, switched side
24 VAC Power for cooling, switched side
Seasonal Changeover Switch OPEN=Cooling in Summer CLOSED=Heating in Winter
TYPICAL FAN COIL WIRING DIAGRAM
24 VAC Power for heating,
RH
switched side
24 VAC Power for cooling,
RC
switched side
S3 NA
FAN SPEED
6
SELECTION
1. Press the Fan button to
select speed/operation.
C
WI
Y1
G
A
E
RH
RC
SC
S1
S2
S3
Heat Valve
Cool Valve
FAN HIGH
FAN MED
FAN LO
24 VAC Switched Side
Sensor Common
Remote Sensor
OCC Sensor
Aquastat
OPEN= Summer CLOSED = Winter
2. Press
fan Speed is noted as follows:
on = continuous fan operation
AUTO = Fan Cycles with Heating and Cooling
24 VAC
Done when complete.
FAN HIGH
FAN MED
© COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED. P/N 71969 3220-2345 REV 00=E
1
SETBACK OPERATION NOTES
The T8532OCC Thermostat has an onboard occupancy sensor that will setback operation when a room becomes vacant. Service Menu 325 Occupied Sensor
Operation is turned on to enable this operation.
Occupancy Sensor Detection Performance
Detection Distance: 16.4 Ft (5 meters) Detection Range: 94° Horizontal x 82° Vertical
Occupied Timer (SM 326) - Sets the amount of time that must pass without a detection before the control goes to Setback and starts the Ramping process.
Setback Ramping (SM 327) - Determines how the control will ramp to setback values. Economy setting goes directly to setback values. Comfort 1 setting will allow a 1°F per hour setback of the control set point. Comfort 2 sets back at 2°F per hour until the selected setback value is reached.
Setback Values (SM 310 and SM 320) - Set the HEAT and COOL set points for setback. Values can be set to OFF or 50-90F. Selection of OFF will result in a
Input Power:
Output Rating
Temperature Control Range:
Operating Temperature Range:
24 VAC (20-30 VAC) 50/60 Hz and/or 2 AA Batteries
Terminal W,Y,A - 20-30 VAC 0.02-1.0 A Terminal G - 20-30 VAC 0.02-0.6 A Total Load not to Exceed 2.5 A
50° to 90° F (10° to 32° C)
0° to 120° F (-18° to 49° C)
set point of OFF.
Night Lock ON Protection (SM 328) – When enabled the control holds the user set point between 10 PM and 8 AM, anytime occupancy is detected during that time period. Note: This control has Low/ High Temp Protection. Freeze protection on this control is set at 40°F (heat). Over temp protection is set at 110°F (cool).
Table 2. a dvanced configura Tion: S ervice Menu S
Some Service Menus may not be available, depending on system type (SM 110).
MENU FEATURE OPTIONS STD. DEFAULT DESCRIPTION / COMMENTS
100 Schedule Format 0-3 1 Select the schedule format on the T8000 Series. (Menu not available on non-programmable
101 Daylight-Saving
Time
110 System Type 1-13 1
120 Fan Control
(heating)
121 Fan Speeds 1, 2, 3, 4 3 Allows selection of multiple fan speeds.
130 O/B Reversing
valve
135 W1 Output
150 Backlight 0,1 0 0 = Backlight temporarily on
0,1 0 Select daylight-saving time as it follows standard format in U.S.: It begins second Sunday of
0,1 1 0 = Fossil Fuel; Gas/Oil/Propane heat (equipment controls heating fan)
0,1 0 When 0, output is active for cooling. When 1, output is active for heating.
0,1 0 Changes operation of W1 for Active to Open (NC Normally Closed) to Active to Close (NO
thermostats.) NOTE: Set the clock before changing to non-progammable. 0 = nonprogrammable 1 = programmable 2 = 5-1-1 schedule 3 = 5-2 schedule
0 = Disabled 1 = Enabled (2007 U.S. Format)
1 = 1 Heat/1 Cool conventional 2 = 1 Heat/1 Cool heat pump 3 = Heat only without fan (2-wire systems) 4 = Heat only with fan 5 = Cool only 6 = 2 Heat/1 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 7 = 2 Heat/2 Cool multistage conventional 8 = 2 Heat/ 1 Cool multistage conventional 9 = 1 Heat/ 2 Cool multistage conventional 10 = 2 Heat/ 2 Cool heat pump (no auxiliary heat) 11= 3 Heat/ 2 Cool heat pump (with auxiliary heat) and Emergency (Em) heat 12 = NA 13= NA
1 = Electric Furnace (thermostat controls heating fan)
1 = Single speed Fan (G terminal) 2 = 2-speed Fan (G and E Terminals) 3 = 3-speed Fan (G,A and E Terminals) 4 = 3-speed Staged Fan
0 = (O) Active with cooling 1 = (B) Active with heating
Normally Open). 0 = NC Operation 1 = NO Operation
1 = Backlight always on (low intensity, 24V only)
© COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED. P/N 71969 3220-2345 REV 00=E
2
Loading...
+ 2 hidden pages