Enterasys Matrix VSER-RPU-SYS Hardware Installation Manual

Matrix V-Series
VSER-RPU-SYS
Redundant Power Supply
Hardware Installation Guide
P/N 9033948
ELECTRICAL HAZARD: Only qualified personnel should perform installation procedures.
NOTICE
The hardware, firm ware, or softw are describe d in this document i s subject to change without notice.
IN NO EVENT SHALL ENTERASYS NETWORKS BE LIABLE FOR ANY INCIDENT AL, INDIRECT, SPECIAL, OR CONSEQUENTIAL DAMAG ES WHATSOEVER (INCLUDING BUT NOT LIMITED TO LOST PROFITS) ARISING OUT OF OR RELATED TO THIS DOCUMENT , WEB SITE, OR THE INFORMATION CONTAINED IN THEM, EVEN IF ENTERASYS NETWORKS HAS BEEN ADVISED OF, KNEW OF, OR SHOULD HAVE KNOWN OF, THE POSSIBILITY OF SUCH DAMAGES.
Enterasys Networks , I n c. 50 Minuteman Road Andover, MA 01810
2004 Enterasys Networks, Inc. All rights reserved. Printed in Taiwan
Release Date: March 2004
ENTERASYS NETWORKS, ENTERASYS MATRIX, LANVIEW, MATRIX, NETSIGHT, WEBVIEW, and any logos associate d t herewith, are tradem ar ks or registered trademarks of Enterasys Networks, Inc. in the United States and other countries.
All other product names mentioned in this manual may be trademarks or registered tr ademarks of their respective companies.
Matrix V-Series Documentation URL: http://www.enterasys.com/support/manuals
i
Notice
Regulatory Compliance Information
Federal Communications Commission (FCC) Notice
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interfere nce, and (2) this device must accept any interference received, including interferen ce that may caus e undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection aga in st harmful interference when the equipment is operated in a commercial environment. This equipment uses, gen er at es, and can radiate radio frequency energy and if not installed in accordance with the operator’s manual, may cause harmful interference to ra dio communi cation s. Operat ion of th is equi pment in a reside ntial a rea is lik el y to cause inte rference in wh i c h case the user will be required t o correct the interference at hi s own expense.
WARNING: Changes or mo di fica tions made to this device w hi ch are not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
Industry Canada Notice
This digital apparatus does not exceed the class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communicatio ns.
Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils num ériques de la cla ss A p re sc ri t es dans le Règleme nt sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.
VCCI NOTICE
This is a class A product based on the standard of the Voluntary Control Council for Interference by Information Technology Eq uipment (VCCI). If th is equipment is use d i n a domestic environme nt , radio disturbance may arise. Wh en such trouble oc curs, the user ma y be required to take corrective actions.
WARNING: This is a class A pr oduct. In a dome st i c environment this product may cause radio interference in which case the user may be required to take adequate measures.
ii
Class A ITE Notice
Notice
BSMI EMC Statement — Taiwan
This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Safety Compliance
Please read the following safety information carefully before installing the RPS:
WARNING: Instal la tion and removal of the unit must be carried out by qua li fied per sonnel only.
• The unit must be connected to an earthed (grounded) outlet to comply with international safety st andards.
• Do not connect the unit to an A.C. outlet (power supply) without an earth (ground) connection.
• The appliance coupler (the connector to the unit and not the wall plug) must have a configuration for mating with an EN 60320/IEC 320 ap pl ia nce inlet.
• The socket outlet must be near to th e unit a nd easily accessib le. You c an only r emove power from the uni t by disconnecti ng the power co rd from the out le t.
• This unit op erates under SEL V (Safety Extra Low V ol ta g e ) conditions according to IEC 60950. The conditions are only maintained if the equipment to which it is connected also operates under SELV conditions .
France and Peru only
This unit cannot be powered from IT powered by 230 V (2P+T) via an isolation transformer ratio 1:1, with the secondary connection point labelled Neutra l, connected directly to e art h (ground).
Impédance à la terre
supplies. If your supplies are of IT type , this unit mu st be
iii
Notice
Power Cord Set
U.S.A. and Canada The cord set must be UL- app roved and CSA certified.
The minimum specifications for the flexible cord are:
- No. 18 AWG - not longer than 2 meters, or 16 AWG.
- Type SV or SJ
- 3-conductor The cord set must have a rated current capacity of at least 10 A The attachment plug must be an earth-grounding type with NEMA 5-15P
(15 A, 125 V) or NEMA 6-15P (15 A, 250 V) configuration.
Denmark The supply plug must comply with Section 107-2-D1, Standard DK2-1a
or DK2-5a. Switzerland The supply plug must comply with SEV/ASE 1011. U.K. The supply plug must comply with BS1363 (3-pin 13-amp) and be fitted
with a 5 A fuse which compl ie s with BS1362.
The mains cord must be <HAR> or <BASEC> marked and be of type
HO3VVF3GO.75 (minimum). Europe The supply plug must comply with CEE7/7 (“SCHUKO”).
The mains cord must be <HAR> or <BASEC> marked and be of type
HO3VVF3GO.75 (minimum).
IEC-320 recept ac le .
Veuillez lire à fond l'information de la sécurité sui vant e ava nt d'installer le RPS:
AVERTISSEMENT: L’installation et la dépose de ce groupe doivent être confiés à un personnel
qualifié.
• Ne branchez pas votre appareil sur une prise secteur (alimentation électrique) lorsqu'il n'y a pas de connexion de mise à la t err e (mise à la masse).
• Vous devez raccorder ce groupe à une sortie mise à la terre (mise à la masse) afin de respecter les normes internationales de sé curité.
• Le cou ple ur d’appareil (le connecteur du groupe et non pas la prise murale) doit respecter une configuration qui permet un bran chement sur une entr ée d’appareil EN 603 20/ IEC 320.
• La prise sec te ur doit se trouver à proximité de l’appareil et son accès do it êtr e facile. Vous ne pouvez mettr e l’ap pareil hors circuit qu’en débranch ant son cordon électrique au niveau de ce tt e prise.
L’appareil f onctionne à une ten sion extrêmemen t basse de sécurité q ui est conforme à la nor me IEC
60950. Ces conditio ns ne sont maintenues que si l’équipement auquel il est ra cc ordé fonctionne dans les mêmes conditions.
iv
Notice
France et Pérou uniquement:
Ce groupe ne peut pas être alimenté par un dispositif à impédance à la terre. Si vos alimentations sont du type impédance à l a terre, ce groupe doit être alim enté par une tension de 23 0 V ( 2 P+T ) par le biais d’un transform a te ur d’isolement à rapport 1:1, avec un point secondaire de connexion portant l’appellation Neutre et avec raccordement direct à la terre (masse).
Cordon électrique - Il doit être agréé dans le pays d’util isati on
Etats-Unis et Canada:
Danemark: La prise mâle d’alimentation doi t resp ecter la section 107-2 D1 de la
Suisse: La prise mâle d’alimentation d oi t respecter la norme SEV/ A S E 1 011. Europe La prise secteur doit être conforme aux no rm es CEE 7/7 (“SCHUKO”)
Le cordon doit av oir reçu l’homologation des UL et un certifica t de la CSA.
Les spe'cifica tions minima les pour la corde flexib le sont AWG No. 18, ou AWG No. 16 pour une longueur infe'rieure a` 2 me'tres:
- type SV ou SJ
- 3 conducteurs Le cordon doit être en mesure d’acheminer un courant nominal d’au
moins 10 A. La prise femelle de branchement doit être du type à mise à la terre (mise
à la masse) et respecter la configu rat io n N E MA 5-15 P (15 A , 125 V) ou NEMA 6-15P (15 A, 250 V).
norme DK2 1a ou DK2 5a .
LE cordon secte ur doit porter la menti on <HAR> ou <BAS EC> et doit être de type HO3VVF3GO.75 (minimum).
Bitte unbedingt vor dem Einbauen des Switches die folgenden Sicherheitsan­weisungen durchlesen:
WARNUNG: Die Installation un d der Ausbau des Geräts darf nur du rch Fachpersonal erfolgen.
• Das Gerät sollte nicht an eine ungeerdete Wechselstromsteckdose angeschlossen werden.
• Das Gerät mu ß an e ine geerdete Steckdose an ge schlossen werden, welche die inte rnationalen Sicherheitsnormen erfüllt.
• Der Gerät estecker (der Anschluß an das Ge rät , nic ht der Wandsteckdosenstecker) m uß e in en gemäß EN 60320/IEC 320 konfigurierten G e räteeingang haben.
• Die Net zsteckdose muß in der Nähe des Ge rät s und l ei ch t zu gänglich sein. Die Stromversorgung des Geräts kann nur durch Herausziehen des Gerätenetzkabels aus der Netzsteckdose unterbrochen werden.
Der Betrieb diese s Gerä ts erfolgt unter den SELV-Bedingungen (S icherheitskleinstspannung)
gemäß IEC 60950. Di ese Bedingungen sind nu r gegeben, wenn auch die an da s G erä t angeschlossenen G eräte unter SELV-Beding ungen betrieben werde n.
v
Notice
Stromkabel. Dies muss von dem La nd, in dem es benutzt wird geprüft werden: Schweiz Dieser Stromstecker muß die SEV/ASE 1011Bestimmungen e inhalten. Europe Das Netzkabel muß vom T yp H O3VVF3GO.75 (Min destanforderung)
sein und die Aufschrift <HAR> oder <BASEC> tragen. Der Netzstecker muß die Norm CEE 7/7 erfüllen (”SCHUKO”).
Declaration of Conformity
Applicatio n of Council Di rective(s): 89/336/EEC
73/23/EEC
Manufacturer’s Name: Enterasys Networks, Inc.
Manufacturer’s Address: 50 Minuteman Road
Andover, M A 01810 USA
European Representative Address: Enterasys Networks, Ltd.
Nexus House, N ewbury Business Park London Road, Newbury Berkshire RG14 2PZ, England
Conformance to Directive(s)/Product Standards: EC Dire ctive 89/336/E E C
EC Directiv e 73/23/EEC EN 55022 EN 55024 EN 60950
Equipmen t Ty pe/Environment : Networking Equipment, for use in
a Commercial or Light Industrial Environment.
Enterasys Net works, Inc. declares that the equipme nt packaged
with this noti c e confo rms to th e above direc tives.
vi
Contents
Chapter 1: About the Redundant Power Supply 1-1
Overview 1-1 Features and Benefits 1-1 Front and Rear Panels 1-1 LEDs 1-2
Chapter 2: Installing the Redundant Power Supply 2-1
Installation 2-1 Selecting a Site 2-1 Equipment Checklist 2-1
Package Contents 2-2
GettingHelp 2-2
Optional Rack-Mounting Equipment 2-3
Mounting 2-3
Rack Mounting 2-3 Desktop or Shelf Mounting 2-5
Connecting Switches to the RPS 2-5
Appendix A: Troubleshooting A-1
Diagnosing RPS Indicators A-1 Power and Cooling Problems A-1 Installation A-1
Appendix B: Specifications B-1
Physical Characteristics B-1 Compliances B-2
Index
vii
Tables
Table 1-1. Port Status LEDs 1-2 Table A-1. Troubleshooting Chart A-1
viii
Figures
Figure 1-1. Front and Rear Panels 1-1 Figure 1-2. LEDs 1-2 Figure 2-1. Attaching the Brackets 2-4 Figure 2-2. Installing the RPS in a Rack 2-4 Figure 2-3. Attaching the Adhesive Feet 2-5 Figure 2-4. Power Receptacle 2-5 Figure 2-5. Connecting Several Switches to an RPS 2-6
ix
Figures
x
Chapter 1: About the Redundant Power Supply
Overview
Note: The VSER-RPU-SYS is compatible with V2H124-24 and V2H124-24T only.
This VSER-RPU-SYS External Redundant Power Supply (RPS) can supply 600 Watts of backup power to four switching devices in the event of an AC loss or failure of an internal power supply.
The system operates in a parallel capacity with a switch’s internal power supply. If a switch's internal power supply fails, the RPS will support the full load of the switch without affecting network operation.
Features and Benefits
• Supports four switching devices with 12V DC output
• Easy management LEDs located on the front panel
• AC line cord can draw power from a different supply circuit
• DC line cord provides backup power to the attached device
• The power supply will operate under a no-load condition.
Front and Rear Panels
Four power indicators (LEDs) and one fan indicator are located on the RPS’s front panel. The AC supply and DC backup receptacles are located on the RPS’s rear panel.
Figure 1-1. Front and Rear Panels
VSER-RPU-SYS
2
1
3
4
Fan
Rear Panel
1-1
1
About the Redundant Power Supply
LEDs
The following diagram and table describe the functions of the LEDs on the Front Panel.
Figure 1-2. LEDs
VSER-RPU-SYS
2
1
3
4
Fan
Table 1-1. Port Status LEDs
LED Condition Status
RPS 1, 2, 3, 4 On Green Power is being supplied to the RPS, the unit is functioning
normally, and the RPS port is connected to a switch.
Flashing Green Power is being supplied to the RPS, the unit is functioning
normally, but no switch is connected to the RPS port.
Off Power is off, or a failure has occurred.
Fan On Green The fans are functioning normally.
Flashing Red One or more fans have failed.
Off The unit is not connected to an AC power source.
1-2
Chapter 2: Installing the Redundant Power Supply
Installation
Note: The VSER-RPU-SYS is compatible with V2H124-24 and V2H124-24T only.
The RPS may be placed on a desktop or mounted in a rack.
Caution: DO NOT place the RPS on the floor as the case is not waterproof. It is recommended that this RPS be installed in a network equipment rack.
Selecting a Site
RPS units can be mounted in a standard 19-inch equipment rack or on a flat surface. Be sure to follow the guidelines below when choosing a location.
• The site should:
be at the center of all the devices you want to link and near a power outlet.
be able to maintain its temperature within 0 to 40 °C (32 to 104 °F) and its humidity within 5% to 95%, non-condensing
provide adequate space (approximately two inches) on all sides for proper air flow
be accessible for installing, cabling and maintaining the devices
allow the status LEDs to be clearly visible
Make sure that a separate grounded power outlet that provides 100 to 240 VAC, 50-60 Hz, is within 2.44 m (8 feet) of each device and is powered from an independent circuit breaker. As with any equipment, using a filter or surge suppressor is recommended.
Equipment Checklist
After unpacking the RPS, check the contents to be sure you have received all the components. Then, before beginning the installation, be sure you have all other necessary installation equipment.
2-1
2
Installing the Redundant Power Supply
Package Contents
• Redundant Power Supply Unit
• One AC Supply Power Cord — US, Continental Europe or UK
• Four DC Backup Power Cords with IEC connectors on both ends (length 152 cm [60 in.] each)
• Rack Mounting Kit containing brackets and screws
• Adhesive feet
• This Manual
• User Agreement Envelope
• Registration Card
GettingHelp
For additional support related to the RPS or this document, contact Enterasys Networks using one of the following methods:
/
Web http://www.enterasys.com/support
Phone 603-332-9400
1-800-872-8440 (toll-free in U.S. and Canada)
For the Enterasys Networks Support toll-free number in your country:
http://www.enterasys.com/support/gtac-all.html
Internet mail support@enterasys.com
To expedite your message, please type [eth] in the subject line.
To send comments or suggestions concerning this document to the Technical Writing Department: techwriting@enterasys.com
To expedite your message, please type [techwriting] in the subject line, and include the document Part Number in the email message.
Before contacting Enterasys Networks for technical support, have the following information ready:
Your Enterasys Networks service contract number
A description of the failure
A description of any action(s) already taken to resolve the problem (e.g.,
changing mode switches, rebooting the unit, etc.)
The serial and revision numbers of all involved Enterasys Networks products in
the network
A description of your network environment (layout, cable type, etc.)
Network load and frame size at the time of trouble (if known)
2-2
Mounting
The device history (i.e., have you returned the device before, is this a recurring problem, etc.)
Any previous Return Material Authorization (RMA) numbers
Optional Rack-Mounting Equipment
If you plan to rack-mount the RPS, be sure to have the following equipment available:
• Four mounting screws for each device you plan to install in a rack—these are not
included
• A screwdriver (Phillips or flathead, depending on the type of screws used)
Mounting
RPS units can be mounted in a standard 19-inch equipment rack or on a desktop or shelf. Mounting instructions for each type of site follow.
2
Rack Mounting
Before rack mounting the unit, pay particular attention to the following factors:
• Temperature: Since the temperature within a rack assembly may be higher than
the ambient room temperature, check that the rack-environment temperature is within the specified operating temperature range.
• Mechanical Loading: Do not place any equipment on top of a rack-mounted unit.
• Circuit Overloading: Be sure that the supply circuit to the rack assembly is not
overloaded.
• Grounding: Rack-mounted equipment should be properly grounded. Particular
attention should be given to supply connections other than direct connections to the mains.
2-3
2
Installing the Redundant Power Supply
To rack-mount devices:
1. Attach the brackets to the device using the screws provided in the Rack Mounting Kit.
Figure 2-1. Attaching the Brackets
1
VSER-RPU-SYS
2
3
4
Fan
2. Mount the device in the rack, using four rack-mounting screws (not provided).
Figure 2-2. Installing the RPS in a Rack
1
VSER-RPU-SYS
2
3
4
Fan
2-4
Connecting Switches to the RPS
Desktop or Shelf Mounting
1. Attach the four adhesive feet to the bottom of the first RPS unit.
Figure 2-3. Attaching the Adhesive Feet
anel
P
Rear
2
2. Set the device on a flat surface near an AC power source, making sure there are at least two inches of space on all sides for proper air flow.
Connecting Switches to the RPS
Caution: DO NOT connect the RPS to an AC power source until DC power cords have been connected to the supported switches.
To connect switches to the RPS, refer to Figure 2-4 and Figure 2-5 and proceed as follows:
1. Power up the switch by connecting one end of the AC cord to the AC receptacle on the supported switch, and the other end to a grounded power outlet.
Figure 2-4. Power Receptacle
2. Connect one end of a DC cord to the redundant power receptacle on the supported switch and the other end to an available receptacle on the RPS.
3. Repeat steps 1 and 2 for connecting up to four supported switches to the RPS.
2-5
2
Installing the Redundant Power Supply
4. Power up the RPS by connecting one end of the AC cord to the AC receptacle on the RPS, and the other end to a grounded power outlet.
5. Check the LEDs on the RPS to ensure proper operation. The Fan LED and the RPS LED for connected switches should light up. If the LEDs indicate otherwise, see "Troubleshooting" on page A-1 for more information.
Figure 2-5. Connecting Several Switches to an RPS
Stack
RPS input port
100-240V,50/60Hz 12.5A
RPS Unit
RPS output port
AC Power
Supply No.1
AC Power
Supply No.2
Note: For International use, you may need to change the AC line cord. You must use a
line cord set that has been approved for the receptacle type in your country.
2-6
Appendix A: Troubles hooting
Diagnosing RPS Indicators
Table A-1. Troubleshooting Chart
Symptom Action
LEDs are Off • Internal power supply is disconnected.
• Check connections between the RPS, the power cord, and the wall outlet.
• Contact Technical Support.
Fan LED is Flashing Red • One or more fans are malfunctioning. Have the unit replaced as soon
as possible.
Power and Cooling Problems
If the fan LED does not turn on when the power cord is plugged in, you may have a problem with the power outlet, power cord, or internal power supply. However, if the unit powers off after running for a while, check for loose power connections, power losses or surges at the power outlet, and verify that the fans on the unit are unobstructed and running prior to shutdown. If you still cannot isolate the problem, then the internal power supply may be defective. In this case, contact your distributor for assistance.
Installation
Verify that all system components have been properly installed. If one or more components appear to be malfunctioning (such as the power cord or RPS cable), test them in an alternate environment where you are sure that all the other components are functioning properly.
A-1
A
Troubleshooting
A-2
Appendix B: Specifications
Physical Characteristics
Ports
4 RPS DC power outlets
LEDs
Ports 1 to 4, and fan status LEDs.
Weight
5 kg (27.6 lbs)
Size
44.0 x 28.4 x 4.3 cm (17.34 x 11.19 x 1.69 in.)
Temperature
Operating: 0 to 40 °C (32 to 104°F) Storage: -40 to 70 °C (-40 to 158 °F)
Humidity
Operating: 5% to 95%
AC Input
100 to 240 V, 50 to 60 Hz
EIA Ratings
115V/10A 230V/10A
Power Consumption
264 Watts maximum
900.5 BTU
DC Power Cable Connector
14-pin plastic cable
B-1
B
Specifications
Power Supply
Internal, auto-ranging: 100 to 240 VAC, 50 to 60 Hz Output 12 VDC Current: 0 A (minimum), 13 A (maximum) Line regulation: +/- 1% Load regulation: +/- 10% Overshoot and undershoot: 5%
Maximum Current
10 A @ 110 VAC 5 A @ 230 VAC
Fan
Voltage +12 VDC Operating voltage range: 7 V to 13.8 V Speed: 8200 RPM Air delivery: 9.43 CFM Noise: 30.5 dB
Compliances
Product Safety
UL 60950 CSA C22.2 No. 60950 73/23/EEC EN 60950 IEC 60950
Electromagnetic Compatibility (EMC)
47 CFR Parts 2 and 15 CSA C108.8 89/336/EEC EN 55022 EN 61000-3-2 EN 61000-3-3 EN 55024 AS/NZS CISPR 22 VCCI V-3
B-2
Index
A
adhesive feet, attaching 2-5 air flow requirements 2-1
B
brackets, attaching 2-4
C
contents of package 2-2 cooling problems A-1 cord sets, international 2-6
D
desktop mounting 2-5
E
equipment checklist 2-2
F
front panel of RPS 1-1
G
grounding for racks 2-3
I
installation
desktop or shelf mounting 2-5 power requirements 2-1 problems A-1 rack mounting 2-3 site requirements 2-1
L
LED indicators
problems A-1
location requirements 2-1
M
mounting the RPS
in a rack 2-3 on a desktop or shelf 2-5
P
package contents 2-2 power, connecting to 2-5 problems, troubleshooting A-1
R
rack mounting 2-3 rear panel of RPS 1-1 rubber foot pads, attaching 2-5
S
screws for rack mounting 2-3 site selelction 2-1 specifications
compliances B-2 environmental B-1 physical B-1 power B-2
standards
compliance B-2 IEEE B-2
surge suppressor, using 2-1
T
temperature within a rack 2-3 troubleshooting
in-band access A-1 power and cooling problems A-1 RPS indicators A-1
Index-1