Ensy AHU-300 HV, AHU-300 HH User Manual And Installation Manual

User manual and Installation Guide
AHU-300 HV AHU-300 HH
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 1
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 2
User manual. Page 1 to 13
(Front page and pictures on pages 1-5 shows AHU-300 HV)
To
open the front hatch you will find a key for the quarter turn latches in the folder together with the following documents. Keep this key in a place so it is out of reach for children.
To open the locks, turn the key toward the center of the unit.
Left latch Right latch
To operate this product people should have necessary skills, or under the
supervision of a qualified person.
Children should be told to not play with the appliance.
Before any access into the electrical connections boxes, power must be disconnected by pulling out the plug from the socket.
It is only allowed for authorized persons to enter into the electrical connection boxes. (Sketch shows AHU-300 HH)
If any electrical components are damaged, they must be replaced by the manufacturer, dealer or a qualified person in order to avoid dangerous situations.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 3
The hatch has three hinger that holds it permanently to the housing. If the unit is placed high under a ceiling, then is mandatory to get help from another person to take down the hatch. It can be done by unscrewing 6 pcs of screws from the housing or front hatch.
Th
e safety wire can be removed from inside of the front hatch so that the hatch can be
opened or removed. The safety wire must be reinstalled before the hatch closes.
To close, after putting the hatch back on place, turn the latches the opposite way. You may use some pressure towards the hatch to close it.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 4
Adjustment of the unit.
A
humidity sensor is, from factory, mounted inside the unit. It is set to “0” that
means it is set to not active.
No
te!
This switch is not used on units produced before february 2015.
A
fter startup, where the unit is placed into a new building with high humidity, you can let this humidity sensor be turned off for a period to avoid the full speed of the fan at night. To get the humidity sensor to operate as intended, you need at one time to put it active. Than you need to set the switch in position "1".
I
f the ventilation unit is placed in a house without high humidity, you should switch to position "1" after you putting ventilation unit into operation.
T
his switch will also affect any extra external humidity sensor that is
plugged into the device.
Adjusting the humidity sensor.
If it is necessary to adjust the sensitivity of the humidity sensor then you just can remove the black plug and you then can see the adjusting knob and the RH% scale.
Note! This black plug is not on
units produced before february
2015.
If bad light condition, it may be easier to remove the cover so that you easier seethe RH% scale.
The sensor is set to 80% RH from factory.
If you do adjustments, this only affect the sensor integated inside the unit.
The sensitivity for the integrated sensor you can adjusted from 50% (low) to 90% (high) in accordance to what are the needs. The arrow points the value chosen.
If you have a second external sensor that means you need to adjust that one from its settings.
Replace the cover and / or plug after finish adjusting.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 5
Replacing the filter.
The filters should be replaced every 6. 9. or 12. months.
Before the filters can be removed, you have to unscrew a little bit two crews for each locking bracket. Push the bracket away from you to release the filters.
Should than be extracted without use of any tools.
To guarantee optimal properties of the ventilation unit, use the original filters from EnSy. The use of spurious filters will limit the warranty on the product
Ensy art number for filter set is:
011460860-2 FILTERSETT ENSY AHU 300 Himling. F7: 140x240x94.
To insert a new filter you then first have to puch the bracket away from yourself. Then put the filter in place and then pull the bracket against yourself and tighten the skrews on the bracket.
Remember to enter the control panel menu (4.3 Filter) and press Filter OK after the filters has been replaced.
Cleaning the fans.
This must be done by a qualified person.
Be
fore removing fans the main power must be disconnected by pulling out the main supply plug from the socket, or fans to be programmed to position “AV” or “OFF
Disconnect the 3-pole and 5-pole plugs.
Before you are able to remove the fans you first have to unscrew two screws for each fan that holds the fan in correct position.
T
he fans can then be pulled out of the
ventilation unit without the need for any tools.
W
hen the fan is placed back into the unit, then make sure the screws are tightened so that there is no danger that they loosen during operation.
Clean with mild soap and water.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 6
Maintenance and cleaning of rotary heat exchanger
This must be done by a qualified person.
If the unit is placed high under a ceiling, then it might be an advantage to get help from another person to hold the rotor exchanger in correct position till all four “safety” screws are loosen.
D
isconnect the 3-poled plug , and then unscrew those four “safety” screws that holding the rotor
exchanger in place.
(Sketch shows AHU-300 HH, but the princip is the same for AHU-300 HV)
C
an be pulled out of the ventilation
unit without the need for any tools.
R
otor exchanger can easily be removed for cleaning by unscrewing 12 screws that hold it together.
Clean parts with mild soap and water.
Do not expose the rotor motor or connector for moisture.
The exchanger you also can clean with mild soap and water. Do not use ammonia­containing detergent, as this will prey on and discolor aluminum in rotary heat exchanger. Flushed with hand shower and blow gently clean with compressed air.
Ensure that all 12 screws are tightened sufficiently so that they do not come loose during operation.
Preferably use a screwdriver to tight the screws. If use of electrical screwdriver, make
sure that you use low torque to prevent destroying the threads in the sheet metal parts.
To make sure that the drive belt can adjust itself into correct position you must rotate the exchanger some few turns. Then insert back into the ventilation unit. Be sure that rotor exchanger is properly inserted in all the guides inside the unit. If not, this can lead to vibration in the system and internal air leak in the unit. Make sure that all four “safety” screws are tightened so that there is no danger that they loosen during operation.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 7
Main menu
1. Control Button indicator for fan.
2
. C
ontrol Button indicator set point.
3
. C
ontrol Button indicator information.
4
. C
ontrol Button indicator settings.
Overview of control panel
The main screen consists of, from top, left:
Time Indication, hour, minute
Ti
mer, Weekly schedule (if programmed)
Reheating coil (if connected)
T
emperature readings, Outdoor / Indoor
S
tatus airflow – fan speed setting
OFF MIN NORM or MAX
Tem
perature set point, 15 - 21 °C
R
eheating coil – (here refers active element)
R
otary exchanger Indicator - (here refers
active rotary wheel)
Indicators in the menu screen:
"
Sun" indicates that the rotor has stopped, the air handling unit is in the summer operation mode.
"Snowflake" low temperature indicates that the air handling unit is in defrosting mode.
"
Steaming pot" and blinking fan blades indicates that the kitchen exhaust is activated.
"
Timer" and the countdown of the fan symbol indicate that the forced ventilation is enabled. From 10 up to 240 minutes
"
Away" indicates when the feature is enabled, this feature will override timer.
"Clock over the fan symbol" indicates that the timer is activated.
Co2 over the fan symbol" indicates that the carbon sensor is activated.
"Ex
clamation point" indicates that moisture recorded over the sensor is higher than the set value. May also indicate that the motion sensor is activated if connected on D2
signal output.
Control Button 1.
2.
3.
4.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 8
1.Fan speed
Ventilation unit has three options for choice of airflow.
M
in, Normal and Max.
For programming of values within each step, see 4.5.1.3 Using the control button 1, and - / + buttons can change between the pre­programmed selections.
1
.1 Fan boost
Forced ventilation, fan speed increases to max speed. (Means to the speed that is set in menu 4.5.1.3.) The function is for use if high humidity in bathrooms and laundry room.
Forced ventilation can be activated with button
then
I
nterval adjustable from 10 - 240 min with +
and -
T
his picture shows 10 min forcing time, but not activated. To activate the fan boost use control button 4.
Y
ou can see that the fan are running with Max speed and the clock will start countdown. You can easy deactivate the fan boost again before the countdown automatically stops it.
First control buttom 1
and then 4.
This feature can also be operated with an external pulse switch. The switch is placed in the bathroom or adjacent rooms. Connected to contact D1 in top of the ventilation unit. (Look at page 19 or 20 in this manual.) If this option via D1 is intended for use against wood stove or fireplace then it is recommended that Max speed under Fan control in menu 4.5.1.3. is set to Supply 100% and adjust Extract to be 80 to 85%. (Look at page 10 in this manual)
2. Temperature
Choose from pre-programmed temperature settings set point between 15 - 21 °C. Setting is changed by operating the switch buttons below - / + symbols.
Heating element can here be set ON or OFF by operating the switch button 4 in this screen, but only if heater is connected.
(To see if heating coil is connected or disconnected, see 4.5.1.1 Heater)
Indicator for activated heating coil.
Small picture show not activated.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 9
3. Information.
3. I
nformation / 3.1.Alarms
When alarm you can find a source of error here, as well as info on how the alarm is reset. (See pages 29 and 30 in this manual)
3.
Information / 3.2 Program version
Information about the software version. This information must be provided to service personnel at the failure of the unit.
W
hich display is defined as Display 1 or Display 2 appears here if the plant has mounted two displays.
See 4.5.1.10 selection of the displays.
3.
Information / 3.3. General info
H
ere you can see defrost mode that has
been chosen.
(
See 4.5.1.9 if you want to change mode.)
4. Preferences
To navigate within the various sub-menus when using the control buttons below the up / down cursor key that displays on the display.
4. P
references / 4.1 Time/date
Setting menu for Time/date. This setting is important since the information forming the basis for the weekly schedule function if this is to be activated. Also for the filter alarm function it is needed.
393870-2 Rev 0: 11.07.2018 BBV
We reserve the right to change technical data without notice. http://www.ensy.no Page 10
4. Preferences / 4.2 Weekly schedule
Programming of the Weekly schedule, fan speed and temperature set point. Here it can be programmed for two periods each day. Ex. day - night.
E
very day must be programmed individually. Monday - a period of time, select the start time. To activate the period, X - over period number is removed, use the - / + keys.
Use enter to move between the different fields.
C
hoose airflow (fan speed) Speed dialing ­MIN when one fan blade on the indicator is black. NORM = two black fan blades on the indicator. MAX speed = three black fan blades on the indicator.
Select the desired supply air temperature you want during the period. Settings between 15 ­21°C.
If weekly schedule looks something like this without any reason then you must
punch in all the data again.
It do not help to update software.
4.P
references / 4.3 Filter
Setting the time interval for filter change, current choices are 6, 9 or 12 months. Make your choices by using the cursor keys + / -.
A
larm reset elapsed period by pressing the
menu button 4, under "Filter OK"
4. Preferences / 4.4 Adjust Screen
Adjusting the contrast and color on the display.
Y
ou can also adjust how long it should be light
in the display after the operation.
4. Preferences / 4.5 Setup
To proceed, use PIN code 1000
P
ress
+ once till it shows 1000 in
display. Then press 4 times on
T
hen press button 3 for OK 4.5.1
Start time
Stop time
Fan speed
Activation of the period. Here not active
Loading...
+ 25 hidden pages