SMART-LV SERIES 160 - 200 - 250KVA ABOUT THE MANUAL
1 Person
<18 kg (<40 lb)
2 People
18-32 kg (40-70 lb)
3 People
32-55 kg (70-120 lb)
Carrying vehicles or handling
accessories
>55 kg (>120 lb)
Thank you for choosing this product of SMART-LV UPS 160-2000-250kVA range.
EnSmart Power is highly specialised in the development and production of uninterruptible
power supplies (UPS). The UPS device described in this manual is designed and
manufactured with care to guarantee uninterrupted power for your equipments and give you
the best performace.
This manual contains detailed instructions for product use and installation.
For information on using and getting the best performance from your UPS, this
manual must be stored in a safe place and CONSULTED BEFORE TAKING ANY
ACTION ON THE UPS.
Please obey the instructions and all the warning stated in the manual or on the UPS. Do not
run the UPS before finishing reading the safety and operation instructions.
Shipment
Carrying vehicles or handling accessories must have enough features and characteristics to
carry UPS’s weight.
DO NOT LIFT HEAVY DUTY WEIGHT WITHOUT HELP
Be more careful of sudden movements, especially when batteries are inside of cabinet.
2.1 General Information ........................................................................................................................................... 13
2.1.1 Static Transfer Switch ............................................................................................................................... 13
2.1.2 Battery Temperature Regulation .......................................................................................................... 14
2.3.1 Advanced Functions (Battery tests) Auto Battery Test ............................................................... 16
2.4 User Panel ............................................................................................................................................................... 17
2.4.2 Main Menu Screen ....................................................................................................................................... 19
2.4.3 Navigation through the menu ................................................................................................................ 19
2.4.5 Control Menu .............................................................................................................................................. 20
2.4.6 Status Menu ................................................................................................................................................... 21
2.4.7 Setup Menu .................................................................................................................................................... 22
2.4.8 Logging Menu ................................................................................................................................................ 24
2.4.8 Service Menu ................................................................................................................................................. 25
4.1.2 First start-up ................................................................................................................................................. 43
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
1 SAFETY AND WARNINGS
1.1 Warnings
This manual must be read before installing the UPS. The device can be installed and started only
by ENSMART POWER authorized personnel.
Installation or start-up by unauthorized personal may cause damage to the device and serious
injury or death.
The UPS is designed to be used in continuous vertical fixed position applications.
Warning:
THE UPS MUST BE USED WITH GROUND CONNECTION.
Connect the ground cable before connecting the mains.
Ground currents may be as high as 0.4A
THE UPS MUST BE DISCONNECTED FROM THE MAINS AND BATTERIES
BEFORE SERVICING. ALSO WAIT FOR AT LEAST 5 MINUTES FOR THE DC
BUS CAPACITORS TO DISCHARGE AFTER POWER OFF.
Service-Maintenance
All servicing and maintenance is done internally. All parts in the device can be serviced and
replaced only by a trained technician.
Preventative maintenance is recommended at least once a year from
the installation by authorized technical personnel. (This service will be
provided for a fee by our authorized ENSMART POWER personnel.)
Battery Voltage may rise up to 450V DC!
Battery terminal voltages can be at hazardous levels (450Vdc). Nobody except trained personnel
should touch batteries.
Batteries must not be thrown into fire. The damaged batteries and batteries with completed life
cycle must not be thrown to nature. For the collection and disposal batteries must delivered to
ENSMART POWER authorized technicians or to the foundations which are authorized for
collecting waste batteries by the Ministry of Environment.
Fire extinguishing equipment must be kept nearby the UPS.
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
1.2 Clearance and Access
Clearance
There is no any air inlet or outlet grill on the left or right sides of our 160 – 200 – 250 kVA UPS. All
air goes in to UPS from the front and is evacuated from the rear through fans. There must be spaces
at least 1 meter for UPS's front side and back side. Should not be permanent or temporary use
within the limits specified. Otherwise, the UPS performance will decrease.
Access
Operator reaches UPS via front panel on 160 - 200 – 250 kVA UPS. Therefore, enough area must
be left for operator. Also, UPS can be intervened in the back of it for service and maintenance.
Because of this reason, enough area for personal must be left at the rear side of UPS. There are no
limitations on the sides of the UPS.
1.3 Storage
UPS should be kept in a room or area where is protected from excessive moisture and heat before
commissioning. UPS and battery cabinets must be kept in the original packaging.
WARNING:
Unused batteries must be charged at regular intervals. This time interval are
determined by the battery supplier. Charging can be performed periodically
by connecting to a proper mains for a while.
1.4 Shipment
Carrying vehicles must have be equipped properly and have features and characteristics sufficient
to carry UPS.
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
The UPS device shipment must be done on pallets.
The 160- 200 – 250 kVA UPS are delivered on the pallet sized 850 x 1100 x 1900 mm (WxDxH).
The height of device together with pallet is approximately 200mm.
Cabinet is equipped with four-wheel. In this way, it can be placed by moving easily. These wheels
are to be used on smooth surfaces only.
The front wheels of UPS must be locked after positioning properly. The rear side wheels are fixed.
Be more careful of sudden movements, especially when batteries are inside of cabinet. Move the
UPS as rarely as possible
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
2.1 General Information
General operation topology of SMART-LV Series can be recognized as follows:
The UPS is connected to the mains voltage through the CB1 breaker. As DC bus is ramped up, the
rectifier starts to operate. Rectifier converts the AC mains to DC voltage and charges the batteries.
When the mains voltage is not available, the necessary the DC bus voltage is generated with use
of the battery voltage. DC DC bus voltage is then converted to mains synchronized AC voltage by
the inverter. This is a high quality voltage. Generated AC power is applied to loads through the
static semi-conductor switches and output (load) breakers.
When maintenance or repair is needed, before the Input (CB1) and Output switches (CB3) are put
to the open circuit (OFF) position, the device must be switched to static bypass mode (please see
4.1.3.2). Consequently the maintenance switch (CB2) is put to the position closed circuit (ON).
After that first Output breaker (CB3), then Input switches (CB1) are turned OFF respectively.
2.1.1 Static Transfer Switch
Some blocks are named as “static switches” as can be seen above. These blocks consist of inverse
parallel connected thyristors. Controlled by the main board control unit (DSP) these switches
provide feeding of the loads through either mains or inverters. The loads are supplied through
inverter during the normal operating mode. Therefore, Inverter static switches are active if there
are no problems with the system.
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
System provides the loads to be fed smooth and seamless by mains or inverter. In order to manage
this process at minimum risk, UPS synchronizes the inverter output and static (mains) bypass as
phase and frequency. Therefore, Inverter frequency can be considered same with mains as long
as it is within frequency limit.
User can switch between mains and inverter by using front panel. When the inverter is ready,
while the loads are fed through the bypass line, in case of either power failure or if mains values
are out of tolerances, the loads automatically will be fed through the inverter.
2.1.2 Battery Temperature Regulation
In the external battery cabinets the battery temperature is measured and detected by
"temperature sensor”. UPS adjusts battery charge parameters according to the detected
temperature.
2.2 UPS’s Operation Modes
SMART-LV series is on-line double conversion device. Our products operate in the following
modes:
In this mode, UPS feeds the load through the inverters. Rectifier unit is fed by the AC mains power.
Inverter and battery charge units are fed by DC supply generated by rectifier unit.
2.2.2 Battery (Stored) Mode
When the mains voltage is bad the UPS runs on battery mode. UPS feeds the critical load through
the inverter; the energy is obtained from batteries.
2.2.3 Bypass Mode
In case when UPS is overloaded or if inverter cannot generate a quality AC output due to any
problem and if bypass voltage and frequency values are within the limits, the loads will be fed
from the static bypass source (mains). UPS without interruption switches from inverter to AC
source (mains) via static transfer switches. The inverter source and mains must be synchronized
in order to manage smooth switching. If inverter output and mains are not synchronized,
switching may take up to 15 msec, varying according to load type.
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
2.2.4 Auto Restart Mode
In case of any failure of the mains, UPS will continue feeding the critical loads until the batteries
will reach the end of discharge voltage level. UPS will be working until the batteries are drained
and then will shutdown. When mains are restored to normal conditions UPS automatically will
start its operation, in the period determined by the user. UPS continues to operate in normal
(online) mode as long as the mains values are within desired limits. For SMART-LV Series, this
feature is not activated in the initial factory set-up.
2.2.5 Maintenance Mode
On the maintenance mode loads are switched to the maintenance bypass line with a breaker, so
that the UPS can be serviced without cutting off the power to loads. The breaker is in full
conformity with capacity of loads.
2.3 Battery Management
Lead-acid batteries are used.
Constant Charge Current
Constant current at 1/10 rate of the battery capacity is applied to battery, until it reaches the
float voltage.
Float Charge
Depending on the battery discharge current the 1/3 of the battery energy is charged at this level.
With this level of charging batteries are kept ready for use at maximum capacity. For lead-acid
batteries, this voltage varies between values 2.2-2.35 V/cell. This voltage may differ slightly with
temperature adaptation. Option of setting this coefficient is provided with our UPS, we
recommend using the temperature sensor.
Deep Discharge Protection
While the system is operating in the battery mode, if battery voltage has dropped below the
discharge level UPS shuts down and stops taking energy from the batteries. This value varies
between 1.6-1.75 V/cell for Lead-Acid batteries, and between 0.9-1.1 V / cell for Ni-Cd batteries.
Low Battery Warning
While the system operates on battery (stored) mode, according to actual loads, if the battery
capacity drops below 40% of its value, device will give audible and visible alarms. This value is
adjustable and can be set by user between 20%-70%.
SMART-LV SERIES 160 - 200 – 250 KVA PRODUCT DESCRIPTION
2.3.1 Advanced Functions (Battery tests) Auto Battery Test
The auto battery test discharges 10% of the battery energy in a user defined period. Default is 90
days. Test reports the battery condition as good, weak or replace. Results of the latest test can be
seen on the battery screen from the status menu.
WARNING: If the test result is “replace”, then batteries are completely
drained during the test. This may cause the interruption in the power
supply to the critical loads in case of the mains failure.
This test command can be given from front panel monitor, via TELNET interface, via RS232
smart communication or via UPSMAN (SNMP, see the options).
The purpose of the battery test is to check if the batteries can supply the minimum back-up time
needed in case of mains failure. We recommend checking the test results on the regular basis.