enphase Microinverter System Reference Manual

Reference Manual
Troubleshooting an Enphase Microinverter System
Contents
Enlighten Messages and Alerts 4
ACFOOR (AC Frequency Out of Range) 4
ACVOOR (AC Voltage Out of Range) 5
Critical Temperature 7
Envoy/EMU not Reporting 9
Grid Gone 10
Module Failed to Report 11
Over Temperature 11
Zigbee Device Failed to Report 11
Zigbee USB Stick Removed 11
ENVOY and Communications Issues 12
General Envoy Issues 12
A physical Ethernet connection is not practical at this site 12
LCD is completely blank 12
LCD displays “Reset Clock” 12
LCD displays “Envoy Failure” 12
Internet Problems (Local Area Networking) 13
LCD shows a non-routable/self-assigned IP address and also shows “-Web” 13
LCD periodically shows “-Web” for minutes or hours at a time. 14
LCD shows a good IP, but also shows “-Web” 15
The DSL modem at the site has only one Ethernet port, and it is being used 15
The Envoy cannot get a “+Web” even though all premises networking is intact 15
Internet service is not available on site 15
Can I use a dial up Internet connection with the Envoy? 16
Are My Power Line Communication Bridges Working? 16
The Envoy is using a static IP and cannot get a web connection 17
Communication Issues between Envoy & Microinverters (Power Line Communication) 17
Inverters are not detected / Power line communication level is low/poor 18
How to identify an interfering load 20
This is a Line-side Tap (or Supply-Side, or PLC) Installation 21
When do I need an additional Envoy? 22
How to get further training on Enphase power line communication 22
Microinverter / PV Module Issues 23
Microinverter LEDs and What they Mean 23
The Microinverter LEDs are blinking red 23
The Microinverter LEDs are blinking orange 24
The Microinverter LEDs are not lit 24
Power Production 25
The unit under review shows low production. 25
Why is one unit showing 0W production when adjacent units are productive? 25
My panels are dark in Enlighten and no production value is displayed 28
Enlighten will not allow me to select the panel 28
I would like to see my panel’s production history 28
Run a report to view production history 28
Use the Graph widget to view production history 29
There is an event or alert message on the system 29
Troubleshooting An Enphase Installation
This document describes trouble-shooting ows and procedures only. For product and instal­lation information, refer to http://www.enphase.com/support/downloads.
Troubleshooting areas covered in this document include:
Enlighten Messages and Alerts
ENVOY and Communications Issues
Microinverter / PV Module Issues
Enlighten Messages and Alerts
The following event messages may appear in Enlighten or in the Envoy interface. If you have received an Enlighten alert in email, read the email through. It includes informa­tion on whether or not action is required and what that action should be.
ACFOOR (AC Frequency Out of Range)
The inverter reports that the frequency coming from the utility is
either too low or too high as specied by UL standards (UL1741).
The nominal frequency range for M190, M210 and D380 microin­verters is 59.3 to 60.5; typical is 60.0.
Frequency out of range events are usually transient and indicate an anomaly from the utility; usually this is self-correcting by the utility. If the condition persists, troubleshoot as follows.
These events can happen because of an actual frequency out­of-spec condition, but more likely, they trip because of either a poorly shaped AC waveform or excessive THD (Total Harmonic Distortion) emanating from the utility service. This type of er­ror rarely affects just one unit, and is usually indicative of an AC service issue.
Along with ACFOOR events, Grid Gone events may also be occur­ring. This is an indication of Anti-Islanding, which sometimes
What does “Anti­Islanding” mean?
“Anti-islanding” is pro­tection against the con­tinuous operation of the inverter and part of the utility load while isolated from the remainder of the electric utility system.
This means that if power from the utility is discon­nected, the utility-inter­active inverter will stop exporting power within two seconds. This is to protect utility line workers and loads.
goes hand-in-hand with ACVOOR (AC Voltage Out of Range) and ACFOOR.
4 Copyright © Enphase Energy, Inc. 2011 06/15/2011
ACVOOR (AC Voltage Out of Range)
The inverter reports that the AC voltage coming from the utility is either too low or too high
as specied by UL standards (UL1741).
Acceptable ranges for AC service are shown in the table below:
240 Volt AC Split Phase 208 Volt AC Three Phase
L1 to L2 211 to 264 Vac L1 to L2 to L3 183 to 229 Vac
L1, L2 to neutral 106 to 132 Vac L1, L2, L3 to neutral 106 to 132 Vac
This condition should correct itself, as there are often periodic variations in Utility voltage. If the condition persists, troubleshoot as follows.
When an entire branch or multiple branches are impacted
Things to check:
1. Measure voltages for L-L and L-N for all phase-conductors at the service entrance (PCC), at each Enphase branch circuit breaker, at each Enphase branch circuit junction box, at each Enphase branch circuit AC pigtail (if used in this installation), and at the last micro­inverter of each Enphase branch circuit.
2. Verify that the AC pigtail or cabling to the junction box is correctly terminated per wire color. (See the installation manual for the microinverter being used.)
3. Verify that the correct circuit breaker has been used. (Is the amperage rating correct? Are the number of termination poles correct?)
If the breaker is undersized, the branch may experience nuisance tripping at peak production times.
If the breaker is oversized, the branch may have been damaged with too much current ow through the microinverters.
5 Copyright © Enphase Energy, Inc. 2011 06/15/2011
4. Verify that the service entrance power is not coming from a 240 Vac “DELTA” or 240 Vac “STINGER” secondary transformer.
5. Make sure that the site does not have undersized conductors, either to the Enphase branch circuit or between the primary load center and the subpanel (if a subpanel exists).
In the case where the array branch circuits land on a PV subpanel, and there is ad­ditional wire run back to the main service tie-in, additional voltage drop calculations must be completed. A typical voltage drop limit is 3% for AC branch circuits; however, this is not adequate for utility-interactive inverters. Enphase recommends a voltage drop of less than 1.5 volts or 0.6 percent.
For more information, refer to our Application Note “Voltage Drop Calculations: http://
www.enphase.com/support/downloads.
When only a few microinverters are impacted
1. If the condition alternates among microinverters, incorrect cabling may be in use. The following Enlighten snapshot shows the result of using 208 Volt cabling at a site with 240 Volt service. Notice that only every third unit is productive.
2. If there is only one unit affected by the ACVOOR, and the condition persists with consis­tent, out of spec readings, the problem is likely with the microinverter, and it may need to be replaced.
3. If there are multiple units consistently affected by ACVOOR events, this is most likely caused by an installation/wiring error during installation.
If the affected units are contiguous or if an entire branch is affected, there is probably an On/Off switch, or a homemade AC combiner, or an incompatible AC disconnect in­between the circuit breaker and the AC pigtail of the PCU branch circuit. Or, it may be faulty wiring, terminations, or circuit breakers only for those affected Enphase branch circuits. Sometimes something as simple as a wire terminated on a circuit breaker that is not screwed down tightly will cause ACVOOR on a given branch circuit.
It may be that an AC pigtail is defective, or that it’s AC connector (or one of the microinverters on the branch’s AC connector) is damaged or defective. If, for example,
6 Copyright © Enphase Energy, Inc. 2011 06/15/2011
on a branch circuit the rst three units are ne, but the remaining 8 or 9 units on the
branch are in a state of ACVOOR, there is something wrong either at location #3 or #4 in the branch circuit, affecting the AC Voltage from that point and on downstream into the branch circuit.
If the ACVOOR is not an installation or wiring defect, and there are multiple units im­pacted on an intermittent basis, it may be that the site’s utility service is simply high. One of the following may be causing this on the utility side:
- The utility transformer bringing service to the site is damaged or defective.
- The utility is purposely pushing the higher AC voltage into some areas during times of peak demand.
- The homerun conductors from the Enphase branch circuits to their respective circuit breakers are undersized. For more information, refer to the Application Note on Voltage Drop Calculations: http://www.enphase.com/downloads
- Is the site using a step-up transformer in-between the primary load-center and the Enphase branch circuits? If so, this can create ACVOOR conditions.
• If all of the above have been checked and veried, and ACVOOR nuisance tripping is
still occurring, and neither the installer nor the utility can mitigate, Enphase can up­grade all of the microinverters to a parameter table which allows for slightly expanded trip-points, while still remaining within spec.
Critical Temperature
This rare condition occurs if the inverter reports an internal temperature that exceeds it rated range. It reacts by producing less power to reduce internal temperature. Once the internal temperature of the inverter diminishes, the microinverter resumes full power production and the error message will clear. No action is required unless the condition persists. If it persists, contact Enphase Energy customer support.
This reects internal temperature coming from a sensor inside the microinverter, not the
ambient temperature. For more information, see the Enphase Technical Brief on tempera­ture: http://www.enphase.com/downloads
7 Copyright © Enphase Energy, Inc. 2011 06/15/2011
DC Too Low
The inverter reports that DC input voltage from the PV module is too low. This is a normal condition that occurs in the morning and in the evening, but during the day may results from any of the following conditions:
This message can appear during extended periods of low solar irradiance (for example, a period that includes the night hours plus a few hours of low sunlight after sunrise).
This event may indicate a bad or missing DC connection to the inverter. If this condition occurs during daylight hours, we recommend that a qualied electrician inspect the DC
connection between the module and the inverter. The connection may need to be tight­ened or may be experiencing wear and tear and require replacement.
If the microinverter is having DC Too Low events during daylight hours, it may have been paired with an incompatible PV module. Is the PV module on the Enphase Compat­ibility list? If the PV module is not compatible it may work sometimes, but will not work consistently or effectively. Some incompatible PV modules will not produce enough DC to start up the microinverter. To check DC input measurements to a microinverter, see
“Check DC measurements” in this document.
Is it producing at all, or does it show zero production? If it shows zero production, does the site use adaptors (or jumpers) between the PV module and the microinverter? It may be that polarity is reversed. Verify by measuring the PV modules VOC (Open Circuit Voltage) and inspect the positive and negative markings on the PV module and microin­verter.
To determine if the problem is with the microinverter or with the PV module, it may be necessary to swap the DC leads from the suspect unit and an adjacent unit. If after checking Enlighten periodically (this may take up to 30 minutes), the problem moves to the adjacent module, this indicates that the PV module isn’t functioning correctly. If it stays in place, the problem is with the microinverter. Call Enphase Customer for help in reading most current microinverter data and for help in obtaining a replacement microin­verter, if needed.
Never rule out the possibility of a damaged or defective PV module. They are somewhat fragile, directly exposed to the elements, and have a very long service-life expectation. The glass on the surface of the PV module can become cracked, lowering the PV mod­ule’s output or causing it to trip a “Ground Fault” (GFI).
DC Too High
The inverter reports that DC input voltage from the PV module is too high.
If the microinverter is having DC Too High events, it may have been paired with an in­compatible PV module. It may be that the PV module generates a higher voltage than is recommended for the inverter. Check that the PV module and inverter are compatible by referring to the Module Compatibility List: http://www.enphase.com/support/downloads.
If the DC Too High is being reported across multiple units, and incompatible PV modules have been ruled-out, contact Enphase customer support to verify the rmware version
running on the microinverters.
8 Copyright © Enphase Energy, Inc. 2011 06/15/2011
Envoy/EMU not Reporting
The broadband Internet connection that the Enphase Envoy uses to communicate to the Enlighten servers is experiencing a problem.
If the Envoy displays a status of –Web in the LCD window, it is not currently communicating with the Enlighten servers. The Internet service may be down or the router may be un­plugged or turned off.
Internet connections often have temporary outages. If the situation persists, contact your ISP (Internet Service Provider). When the connection is restored, the Enphase Envoy com­munication gateway will catch up with the transmission of all energy data it has stored.
It could be that Internet service is dropping out periodically. Call your ISP if you notice that other devices at the site are also losing Internet connectivity.
Do you have dial up Internet service? Dial up internet service is not supported on the Envoy.
The Envoy may have an internal error, see “General Envoy Issues”.
See “2. Did the Envoy previously have an Internet connection at this site?”
Gateway Failure
The Envoy has detected a software problem. To clear this message:
Unplug the Envoy from the electrical outlet and then plug it back in. Do this only once. If it returns to failure mode, contact Enphase Customer Support.
GFDI / GFI trip
A microinverter has detected ground fault current greater than one amp on the DC side.
You can attempt to clear this condition through the Envoy Interface by sending the Clear­GFI message to the affected microinverter.
If the Envoy is on a Local Area Network, you can access it from another computer which is also on that same LAN (start with step 4 below). If the Envoy is not on a LAN, then you can directly connect an Ethernet cable between the Envoy and your laptop by performing all of the following steps:
1. Connect one end of the Ethernet cable supplied with the Envoy to the Ethernet port on the Envoy (or browse to it on your Local Area Network).
2. Connect the other end of the Ethernet cable to the RJ45 network port of the computer.
3. Open the Internet browser application on the computer.
4. In the browser address window, enter the IP address displayed in the Envoy’s LCD win­dow (e.g., 192.168.1.101).
5. If you fail to make a connection at this point, you can manually congure your subnet to
169.254.120.2 and subnet mask to 255.255.0.0.
6. Once the browser has successfully connected with the Envoy, the home screen is dis­played in the browser window.
9 Copyright © Enphase Energy, Inc. 2011 06/15/2011
Loading...
+ 20 hidden pages