2.0 COMPONENTS OF THE SE-5175................................................................................................................................... 2
3.2.1 Power Supply .............................................................................................................................................................. 5
5.2.1 Zero Adjust ................................................................................................................................................................ 11
5.2.2 Gas Span ................................................................................................................................................................... 12
5.2.3 Alarm Set Points ....................................................................................................................................................... 13
5.2.4 Span Set ..................................................................................................................................................................... 13
6.0 REPLACEMENT PARTS ................................................................................................................................................ 15
7.0 TECHNICAL DATA AND SPECIFICATIONS ............................................................................................................. 15
The SE-5175 sensor/transmitter (S/T) instrument is a 3 wire, 24 VDC, 4-20mA S/T, that measures and detects various types of
toxic gases utilizing an electrochemical sensor. The SE-5175 is NOT in an enclosure rated for use in a Class I, Div 1, Groups
B, C, D classified area and C
Features of the SE-5175:
continuous monitoring of the sample air
continuous LCD display of gas and vapor concentrations
menu driven operational and maintenance controls
menu driven calibration procedure
mA outputs for target gas
Sensor/Transmitter are three wire device, with two of the wires forming a 4-20mA loop
N
OTE
: All specifications stated in this manual may change without notice.
1.1 Unpack
Unpack the SE-5175 and examine it for shipping damage. If such damage is observed, notify both ENMET customer service
personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
N
OTE
: It is your responsibility to follow these instructions. If they are not followed, the carrier will not honor
any claims for damage.
This shipment was carefully inspected, verified and properly packaged at our company and delivered to the carrier in
good condition.
When it was picked up by the carrier at ENMET, it legally became your company’s property.
If your shipment arrives damaged:
•Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local office and
request immediate inspection of the carton and the contents.
•After the inspection and after you have received written acknowledgment of the damage from the carrier, contact
ENMET Customer Service for return authorization and further instructions. Have your Purchase Order and Sales Order
numbers available.
ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage,
usually $100.00. Repair or replacement charges above that value are your company’s responsibility.
The shipping company may offer optional insurance coverage. ENMET only insures shipments with the shipping
company when asked to do so in writing by our customer. If you need your shipments insured, please forward a written
request to ENMET Customer Service.
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days of
receipt at the following address:
AN NOT
be installed in a hazardous location, as defined by the National Electric Code (NEC).
ENMET Corporation
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 734-761-3220 Fax
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the SE-5175 is received as ordered. Each SE5175 is labeled with its target gas.If there are accessories on the order, ascertain that they are present. Check the contents of
calibration kits. Notify ENMET customer service personnel of any discrepancy immediately.
1.3 Serial Numbers
Each SE-5175 is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.
1
SE-5175 ENMET Corporation
Menu
Select
Strain Relief
Visual In
dicators:
Sensor
Visual Indicator
Power/Fault
Front Cover
2.0 Components of the SE-5175
2.1 SE-5175 elements
See Figure 1 for location of elements:
Feature Description
Enclosure
Front Cover
2.2 SE-5175 Operational Features
The Display Panel is attached to the enclosure cover and is released by unscrewing the 4 screws located in the corners. After
releasing the screws and lifting the cover and exposing the interior of the enclosure, see section 3.0 for installation and wiring
instructions.
See Figure 1 for location of features.
Feature Description
Display
Visual Indicators and
Alarms
Membrane Switches
A fiberglass-reinforced polyester 5 x 4 x 3, with a detachable front cover.
Four holes for mounting the enclosure to a vertical surface. Located at the corners of the
bottom of the enclosure. See Figure 3
Detachable front cover of SE-5175 with Display Panel. See Section 2.2 and Figure 1
There are 4 Screws that hold the front cover in place.
A single line, 8 character LCD with backlight. Indicates the level of gas detected by sensor.
The numerical value of gas concentration and other information is displayed.
LED indicators:
Power / Fault Indicator LED, Green / Red
Alarm (3) Indicator LED, Red
2 Pushbutton Switches on front panel control the instrument maintenance functions. The
pushbutton switch locations are indicated by:
M
ENU
↓: Advances the instrument display through operation information and maintenance
menus
S
ELECT
: Disables audio alarm temporally and
Selects the maintenance menu operations such as, Zero, Span, Exit menu or sets
proper calibration values for Zero or Span
See Section 4.0 and 5.0 for operational and maintenance flow charts.
Three alarm points are preprogrammed into the SE-5175. At each alarm point, an LED on the front panel is activated. These
internal alarm settings are independent of the 4-20mA output alarm values that can be set at a controller.
Alarm1, Alarm2, Alarm3
Display
Pushbutton Switches
Retaining Screws
4 places
Figure 1: External SE-5175 Features
2
SE-5175 ENMET Corporation
J4 Terminal
Terminal J8
To Sensor Wiring
2.3 Circuit Board Features
The Display Panel is attached to the enclosure cover and is released by unscrewing the 4 screws located in the corners. After
releasing the screws and lifting the cover and exposing the interior of the enclosure, see section 3.0 for installation and wiring
instructions. The Circuit Board is mounted at the back surface of the enclosure Cover.
Circuit Board Features are shown in Figure 2.
Feature Description
Output Terminals
Sensor Wiring
J4 plug – Terminals to controller
J8 plug – Terminals to sensor wiring
4-20mA Output
Figure 2: SE-5175 Circuit Board Features
3
SE-5175 ENMET Corporation
Heavier than Air Gas
Sensor Location
Avoid locating anywhere near a vent or window or near an outside
Lighter than Air Gas
Sensor Location
Ammonia
Hydrogen
Same Density as Air Gas
Sensor Location
Mounting Holes
R .128, 4 places
3.0 Installation
The SE-5175 sensor/transmitter detects gas only at the sensor location.
N
OTE
: Sensor Location
Gases have different densities. Some are heavier than air and concentrate at the bottom of a space. Some are lighter than air
and gather at the top. Consider the density of the gas you want the sensor to detect when you install the sensor. Some
examples are given below.
Hydrogen sulfide Interior wall; 18-24" from floor.
• DO N
•
Near ceiling.
• DO N
Carbon Monoxide 4-6 feet above the (generally uniform) floor.
• DO N
If you have a question involving the location of a unit or sensor, please contact your distributor or ENMET personnel. A
technician will analyze the question and recommend a location.
OT
locate directly above or beside gas appliances (ovens,
heaters).
doorway.
OT
locate directly above appliances where it is subject to
direct exposure to heat or steam.
OT
locate in direct air currents of windows, doors, or vents.
3.1 Mounting SE-5175
Mount the SE-5175 instrument on an appropriate vertical surface, using the mounting holes provided. Avoid areas with
excessive vibration or temperature extremes. The holes in the bottom of the enclosure are 0.18 inch in diameter and form a
4.09″ square. See Figure 3
Side View
Dimensions are in inches.
Figure 3: Mounting SE-5175
4
Loading...
+ 14 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.