3.2.1 Air Supply..........................................................................................................................................................................6
3.2.2 Power Supply.....................................................................................................................................................................6
5.2.1 Advance/Exit Maintenance Menu .....................................................................................................................................11
5.2.2 Zero Adjust......................................................................................................................................................................11
5.2.3 Gas Span Calibration.......................................................................................................................................................12
5.2.4 Alarm Set Points..............................................................................................................................................................14
The PID-G
air systems utilizing a photoionization sensor. Hydrocarbons (HC) are limited to gases with an ionization potential of 10.6 eV
or less. See Appendix A for a list of gases and IPs. The PID-G
Groups B, C, D classified area and C
Features of the PID-G
N
OTE
: All specifications stated in this manual may change without notice.
1.1 Unpack
Unpack the PID-G
service personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
UARD
is a compressed air monitoring instrument that measures and detects Hydrocarbons in industrial compressed
UARD
AN NOT
:
be installed in a hazardous location.
continuous monitoring of the sample air
continuous LCD display of gas and vapor concentrations
menu driven operational and maintenance controls
menu driven calibration procedure
audio and visual alarms indicate unsafe conditions
alarm relay contacts available on terminals
a fault relay and visual fault alarm
low air flow fault indication and display
alarm acknowledgement capability including audio defeat
mA outputs for target gas
UARD
and examine it for shipping damage. If such damage is observed, notify both ENMET customer
UARD
is NOT in an enclosure rated for use in a Class I, Div 1,
N
OTE
: It is your responsibility to follow these instructions. If they are not followed, the carrier will not honor
any claims for damage.
This shipment was carefully inspected, verified and properly packaged at our company and delivered to the carrier in
good condition.
When it was picked up by the carrier at ENMET, it legally became your company’s property.
If your shipment arrives damaged:
•Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local office and
request immediate inspection of the carton and the contents.
•After the inspection and after you have received written acknowledgment of the damage from the carrier, contact
ENMET Customer Service for return authorization and further instructions. Have your Purchase Order and Sales Order
numbers available.
ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage,
usually $100.00. Repair or replacement charges above that value are your company’s responsibility.
The shipping company may offer optional insurance coverage. ENMET only insures shipments with the shipping
company when asked to do so in writing by our customer. If you need your shipments insured, please forward a written
request to ENMET Customer Service.
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days of
receipt at the following address:
ENMET Corporation
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 734-761-3220 Fax
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the PID-G
G
UARD
is labeled with its target gas.If there are accessories on the order, ascertain that they are present. Check the contents of
calibration kits. Notify ENMET customer service personnel of any discrepancy immediately.
UARD
is received as ordered. Each PID-
1.3 Serial Numbers
Each PID-G
UARD
is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.
1
PID-G
UARD
ENMET Corporation
2.0 Components of the PID-G
2.1 PID-G
UARD
elements
UARD
See Figure 1 for location of elements:
FeatureDescriptionEnclosureA polycarbonate box, approximately 7 x 5 x 3, with a detachable front cover.
4 holes for mounting the enclosure to a vertical surface. Located at the corners of the bottom
of the enclosure, directly beneath the 4 front cover retaining screws. See Figure 3
Input PortThe entrance for the air sample and calibration gas. The quick release fitting mates with one
on the optional Sample air hose and the calibration adapter.
Front Cover
Detachable front cover of PID-G
UARD
with Display Panel. See Section 2.2 and Figure 1
There are 4 Screws that hold the front cover in place.
Sample Air Hose
(Optional)
Regulator
(Optional)
A five foot long hose to conduct a sample of the air from the source to the instrument.
The hose has a Female quick release fitting and regulator. See Figure 1a
To connect to the compressed air line. Sample pressure to the PID-G
55
PSI
. See Figure 1a
UARD
should be set to
Output PortSampled air out: Luer connection provided to connect to tubing
2.2 PID-G
UARD
Operational Features
The Display Panel is attached by a cable and is released by unscrewing the 4 screws located in the corners. After releasing the
panel, it is swung upward, exposing the interior of the enclosure. See Figure 1 for location of features.
FeatureDescription
DisplayA single line, 8 character LCD with backlight. Indicates the level of gas detected by sensor.
The numerical value of gas concentration and other information is displayed.
Audio Alarm(Horn)Audio alarm (105 dB at 30cm/12in). The audio alarm is on when the unit is in alarm.
Visual Indicators and
Alarms
LED indicators:
Power / Fault Indicator LED, Green / Red
Alarm (3) Indicator LED, Red
Membrane Switches2 Pushbutton Switches on front panel control the instrument maintenance functions. The
pushbutton switch locations are indicated by:
M
ENU
↓: Advances the instrument display through operation information and maintenance
menus
S
ELECT
: Disables audio alarm temporally and
Selects the maintenance menu operations such as, Zero, Span, Exit menu or sets
proper calibration values for Zero or Span
See Section 4.0 and 5.0 for operational and maintenance flow charts.
FlowmeterA flow indicator located at the output of the sample flow stream, which indicates
quantitatively the flow of sample air or calibration gas through the instrument.
Three alarm points are preprogrammed into the PID-G
UARD
. At each alarm point, an LED on the front panel is activated.
These internal alarm settings are independent of the 4-20mA output alarm values that can be set at a controller. An optional
relay board is available that will activate 0.5 Amp relay contacts at each alarm point, plus a fault relay.
2
PID-G
Regulator
¼“ NPT
Input Port
Strain Relief
Power/Fault
Menu
UARD
ENMET Corporation
Visual Indicator
Flowmeter
Select
Figure 1: External PID-G
UARD
Visual Indicators:
Alarm1, Alarm2, Alarm3
Output Port
Pushbutton Switches
Audio Alarm
Front Cover
Retaining Screws
4 places
Features
Figure 1a: Optional R
Female Quick Release
Fitting to Inlet Port
EGULATOR AND SAMPLE AIR HOSE
3
PID-G
PCB/Sensor Manifold
4-20mA Output
UARD
ENMET Corporation
2.3 Circuit Board Features
The Display Panel is attached by a cable and is released by unscrewing the 4 screws located in the corners. After releasing the
panel, it is swung upward, exposing the interior of the enclosure. The Circuit Board is mounted at the back surface of the
enclosure interior. Features are shown in Figure 2.
FeatureDescriptionRelay TerminalsThis group of terminals is located on the Circuit Board.
For the contacts for each of three alarm relays, and for the contacts of a fault relay.
See Section 3.2.2
Output TerminalsFor the 4-20 mA output.PCB/Sensor ManifoldThe PCB/Sensor manifold. The photoionization sensor located under this housing.
Terminal J12
External Power
Figure 2: PID-G
UARD
Circuit Board Features
Relay Terminals
J14, J15, J16, J17
Relays
K1, K2, K3, K4
4
PID-G
Right Side View
UARD
3.0 Installation
The PID-G
being used. The PID-G
UARD
should be located near the pipe or tank containing the air to be monitored, and upstream from where the air is
ENMET Corporation
UARD
must be installed such that it samples the compressed air before it reaches the users.
3.1 Mounting PID-G
Mount the PID-G
UARD
UARD
instrument on an appropriate vertical surface, leaving room for lid to be opened, using the mounting
holes provided. Avoid areas with excessive vibration or temperature extremes. The holes in the bottom of the enclosure are
0.18 inch in diameter and form a 6.44″ x 4.47″ rectangle. See Figure 3
It is recommended to use #8 drywall anchors and screws for mounting the PID-G
UARD
to a drywall/sheetrock surface.
Cover Inside View
Opened Upward
Attached to Base
Dimensions are in inches.
Figure 3: Mounting PID-G
5
UARD
PID-G
UARD
3.2 Wiring the PID-G
UARD
ENMET Corporation
The electrical installation should conform to appropriate electrical codes, such as the National Electrical Code in the United
States.
W
ARNING
:
The compliance of the installation to appropriate codes is not ENMET’s responsibility.
The PID-G
UARD
should be powered through circuit breakers provided for this purpose.
3.2.1 Air Supply
Tap the pipe or tank containing the air and use appropriate fittings to connect the sample input hose. The instrument is
designed to operate from an air supply pressure 55
PSIG
. The sample input hose length should be as short as possible.
3.2.2 Power Supply
The input power can vary from 100 to 240 VAC, 50/60 Hz. Power should be connected to the Power Input Terminal TB1 and
the Ground screw. See Figure 4 for location.
W
ARNING
:
Continuous gas detection and alarm systems (110VAC/220VAC / 24VDC/12VDC powered) become inoperative
upon loss of primary power. Contact factory for specifications and pricing of backup battery systems.
Upon supplying air and power to the PID-G
UARD
:
The green power on LED is lit.
The display backlight is lit, and instrument will step through a start-up sequence: unit serial number and software revision
may be shown on the display.
The instrument may go into alarm briefly, but the sensors stabilize quickly. If the instrument persists in alarm, acknowledge the
alarm by pressing the S
ELECT
button. If alarm persists longer than 30 minutes, call ENMET customer service personnel.
For DC wiring 24Vdc may be wired to J12, (J12-1)position 1 + with ground connected to (J12-2)position 2.
AC Power Supply Terminal: TB1
Label on PCBFunction
110V
AC
Ground
TB1 ACNNeutral
TB1 ACLLine
AC GND
Cover Inside View
Opened Upward
Attached to Base
Screw
220V
AC
TB1 ACNNeutral
OptionalTB1 ACLLine
Ground
AC GND
Screw
DC Power Supply Terminal: J12
PositionFunction
1 +24 V
2GND
34 - 20 mA out
DC
power
Figure 4: Power Terminal Connections PID-G
UARD
6
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.