ENMET MX-42A User Manual

Page 1
ENMET
ENMET Corporation
ENMETENMET
PO Box 979 Ann Arbor, MI 48106-0979
E
O
NGUARD
MX42A C
PERATION
M
& M
ANUAL
ONTROL
AINTENANCE
Manual Part Number 80003-042 October 1999 MCN-358, 12/06/06
Page 2
Page 3
T
ABLE OF CONTENTS
1.0 I
NTRODUCTION
.................................................................................................................................... 1
1.1 Unpack ......................................................................................................................................................1
1.2 Check Order...............................................................................................................................................1
1.3 Serial Numbers ..........................................................................................................................................1
2.0 F
EATURES
3.0 I
NSTALLATION AND CONNECTION
.......................................................................................................................................... 2
.......................................................................................................... 3
3.1 Installation.................................................................................................................................................3
3.1.1 Placement of Control........................................................................................................................3
3.1.2 Placement of Sensor/Transmitters.....................................................................................................3
3.2 Electrical Connection of the MX42A Control .............................................................................................4
3.3 Connection of the MX42A Control to the Sensor/Transmitter .....................................................................5
3.3.1 Type and Connection of Sensor/Transmitters ....................................................................................5
3.4 Connection of the Control to External Devices............................................................................................6
3.4.1 Connection to Auxiliary Alarms........................................................................................................6
3.4.2 4-20mA Current Output....................................................................................................................6
4.0 S
TART-UP AND OPERATION
.................................................................................................................. 7
4.1 Configuration of Alarms and Servocontrol..................................................................................................9
4.2 Characteristics of alarm triggering..............................................................................................................9
4.3 Adjustment of alarm thresholds and averaging times of alarm 3 ................................................................11
4.4 Outputs....................................................................................................................................................12
4.4.1 Relays ............................................................................................................................................12
4.4.2 4-20 mA Current Output.................................................................................................................12
5.0 M
AINTENANCE
5.1 Adjustment of sensor/transmitter and the MX 42A C
6.0 T
ROUBLESHOOTING
7.0 S
PECIFICATIONS
...................................................................................................................................13
ONTROL
unit.............................................................13
............................................................................................................................14
.................................................................................................................................15
7.1 Physical...................................................................................................................................................15
7.2 Display ....................................................................................................................................................15
7.3 Power supply ...........................................................................................................................................15
7.4 Measurement inputs.................................................................................................................................15
7.5 Alarm ......................................................................................................................................................16
7.6 Control functions .....................................................................................................................................17
7.7 Relays......................................................................................................................................................17
7.8 Output......................................................................................................................................................17
8.0 WARRANTY....................................................................................................................................18
F
IGURE
F
IGURE
F
IGURE
F
IGURE
F
IGURE
F
IGURE
F
IGURE
F
IGURE
F
IGURE
L
IST OF ILLUSTRATIONS
1: I
NTERIOR VIEW OF
2: M
OUNTING
3: C
ONNECTION OF POWER TERMINAL
4: C
ONNECTION OF SENSOR/TRANSMITTER TERMINAL
5: C
ONNECTION TO EXTERNAL DEVICES
6: F
RONT VIEW OF
7: L
OCATION OF MICROSWITCHES
8: R
ELAY JUMPER AND
9: P
OTENTIOMETER LOCATION
MX42A C
MX42A......................................................................................................... 2
ONTROL
.................................................................................................... 3
............................................................................................ 4
.......................................................................................... 6
MX42A C
ONTROL
............................................................................................. 8
..................................................................................................10
4-20MA POT L
OCATION
......................................................................................................13
...................................................................... 5
............................................................................12
Page 4
Page 5
MX42A C
1.0 Introduction
1.0 Introduction
1.0 Introduction1.0 Introduction
N
OTE
ONTROL
The MX 42A C carrying gases.
The MX 42A C located in a place to be monitored. The measurement from the detector is displayed on the MX 42A C compared to alarm thresholds. Should alarm thresholds be exceeded, the MX 42A C which can be used for the control of outside devices (horn, telephone call, exhaust fans, etc.).
N
OTE
: This instrument is also available as a 2 channel control.
ONTROL
ONTROL
is an apparatus for the detection and measurement of various combustible, toxic and oxygen-
has up to 4 independent measuring channels. Each channel is connected to a gas detector
ONTROL
ENMET Corporation
unit actuates relays
: All specifications stated in this manual may change without notice.
ONTROL
1.1 Unpack
Unpack the MX 42A and examine it for shipping damage. If such damage is observed, notify both ENMET customer service personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
N
OTE
: It is your responsibility to follow these instructions. If they are not followed, the carrier will
not honor any claims for damage.
This shipment was carefully inspected, verified and properly packaged at our company and delivered to the carrier in good condition.
When it was picked up by the carrier at ENMET, it legally became your company’s property.
If your shipment arrives damaged:
Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local
office and request immediate inspection of the carton and the contents.
After the inspection and after you have received written acknowledgment of the damage from the carrier,
contact ENMET Customer Service for return authorization and further instructions. Have your Purchase Order and Sales Order numbers available.
ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage, usually $100.00. Repair or replacement charges above that value are your company’s responsibility.
The shipping company may offer optional insurance coverage. ENMET only insures shipments with the shipping company when asked to do so in writing by our customer. If you need your shipments insured, please forward a written request to ENMET Customer Service.
and
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days of receipt at the following address:
ENMET Corporation
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 734-761-3220 Fax
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the MX 42A is received as ordered. If there are accessories on the order, ascertain that they are present. Check the contents of calibration kits. Notify ENMET customer service personnel of any discrepancy immediately.
1.3 Serial Numbers
Each MX 42A is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.
1
Page 6
ENMET Corporation MX42A C
Display
Visual Alarms
Terminals
Power Switch
10
pl
2.0 Features
2.0 Features
2.0 Features2.0 Features
See F
IGURE
1
Feature Description
Enclosure For wall mounting made of PVC
(length: 13.38, height: 11.81, depth: 4.21 inches) with internal coating for RFI protection.
ONTROL
Power Supply Display Inputs 4, for 4-20mA sensor/transmitters which may have combustible, toxic or oxygen sensors. Output Audio Alarms
Visual Alarms Relays
AC or DC LCD display of the measurements
4-20 mA output per channel (< 1 mA for fault, 2 mA for maintenance) Resettable buzzer for alarms or a fault conditions, a total of 3:
2 increasing or decreasing thresholds, with manual or automatic clearance.
1 increasing or decreasing threshold, automatic clearance.
5 LED per channel A total of 10 relays distributed as follows:
2 relays per channel (NO or NC) for the first two alarm thresholds
1 relay common to the channels for the third alarm threshold (or the remote
transmission of the alarm on programming)
1 relay common to the channels for detector faults
Enclosure
Microswitches
1 set per channel
5 LED per channel
Power Supply
Mounting Holes 4 pl
Buzzer
Buzzer Jumper See caution in Section 4.0
Relays, total of 10
Input / Output
Fuses
Cable glands
Figure 1: Interior View of MX42A
2
Page 7
MX42A C
3.0 Installation and Connection
3.0 Installation and Connection
3.0 Installation and Connection3.0 Installation and Connection
ONTROL
3.1 Installation
3.1.1 Placement of Control
The MX 42A C ventilated place where it can be watched, such as a guard house, control room or security service area.
To mount the Control see F 4 mounting holes, with centers of 12.40 x 9.65 inches, use #10 or 5 mm screws.
C
AUTION
: There must be 12 inches of clearance above the MX 42A C
3.1.2 Placement of Sensor/Transmitters
Their location depends on three main factors:
Density of gas to be detected: high for gases lighter than air and low for gases heavier than air Leak point: determination of the probable source of a leakIn the flow of air in ventilated rooms.
ONTROL
maintenance.
can be installed in any place with an unclassified atmosphere. It should be put in a well
IGURE
2 mounting demotions:
ONTROL
so the cover can be opened for
ENMET Corporation
Front View
Bottom View
Figure 2: Mounting MX42A C
3
Front View with Lid Open
ONTROL
Page 8
ENMET Corporation MX42A C
3.2 Electrical Connection of the MX42A Control
Power supply: connect the power supply wires to the terminal blocks of the Control. Located on the PC Board at the bottom of the enclosure.
N
OTE
: Before installation, turn off the MX 42A C
bottom left corner.
W
ARNING
:
Continuous gas detection and alarm systems (110VAC/220VAC / 24VDC/12VDC powered) become
inoperative upon loss of primary power. Contact factory for specifications and pricing of backup battery systems.
See Figure 3 for the connection of the power terminals.
AC, Ground labeled TERRE on the board AC, High labeled PHASE on the board AC, Neutral labeled NEUTRE on the board terminals, 115 VAC (103 V to 122 V), 50/60 Hz, are protected by F1 and F3 with 1.25A time-delay fuses.
+ DC labeled + CONTINU on the board – DC labeled – CONTINU on the board terminals, 24 V (19 V to 32 V), DC is protected by F2 a 4A fuse.
Optional: 230 VAC (207 V to 244 V), 50/60 Hz, is protected by F1 and F3 with 630mA time-delay fuses.
A label on the enclosure gives the power supply voltages.
OFF is up ON is down
ONTROL
using the toggle switch, S2, located inside the unit in the
ONTROL
Switch S2
110VDC Or Optional
220VDC If Installed
Not Field Convertible
110V
VDC Connections
Note: Labeling on board will appear different then shown in this figure.
Figure 3: Connection of Power Terminal
4
Page 9
MX42A C
Channel 1
Channel 3
ONTROL
3.3 Connection of the MX42A Control to the Sensor/Transmitter
3.3.1 Type and Connection of Sensor/Transmitters
Various types of sensor/transmitters can be connected.
Two wire 4-20mA, toxic gas or oxygen detection sensor/transmitters. Such as, ENMET SDS and EN models.
Negative in, Signal (wire 1) and Positive in +24 VDC (wire 3) of each channel. See figure 4
Three wire 4-20mA combustible or toxic gas and oxygen sensor/transmitters. Such as, ENMET SDS-97D and
EX5000 models. Signal (wire 1), DC-GND (wire 2) and +24 VDC (wire 3). See figure 4
If used with other manufactures sensor/transmitters, follow installation instructions procedures supplied by the
sensor/transmitter manufacturer, or contact your ENMET representative or ENMET Corporation.
Specifications of cable:
Using shielded cables is necessary for RFI protection.
The shield of the cable must be connected to wire #2 (DC ground) of the C
ONTROL
ENMET Corporation
.
Example: 2 wire 4-20mA
Toxic Gas or Oxygen
Example: 3 wire 4-20mA
Combustible or Toxic Gas
DC-G
Signal ( – )
24VDC ( + )
Signal ( – )
ND
24VDC ( + )
Note: Labeling on board will appear different then shown in this figure.
Figure 4: Connection of Sensor/Transmitter Terminal
5
Page 10
ENMET Corporation MX42A C
3.4 Connection of the Control to External Devices
Auxiliary alarms should be powered from an independent power source separate form the instrument power to avoid alarm failure due to controller malfunction.
3.4.1 Connection to Auxiliary Alarms
The MX 42A C telephone callers, exhaust fans, etc.
The relays are assigned to functions as follows:
For Each Channel:
one relay, RELAY 1, actuated by alarm 1
one relay, RELAY 2, actuated by alarm 2
For All Channels:
A common relay, CR RELAY, actuated by the high alarm of any channel
One relay, FAULT RELAY, associated with faults detected on any channel such as: detector malfunctions, poor
electrical connections, signal current is 0mA or signal current is greater then 25mA.
An example of a connection is shown in Figure 5
Example A: a light and horn, connected to RELAY 2 of channel 4
Example B: a light and horn, connected to RELAY 2, of channels 1 – 4
N
OTE
: Contact rating of the MX42A C
must be added if the devices to be controlled require higher current requirements.
3.4.2 4-20mA Current Output
For each channel, the MX 42A C a recorder or data logger. In a loop configuration, the maximum resistance is 600 ohms. The 4-20 mA outputs have common ground connections.
ONTROL
has 10 relays that can be used to control external devices such as: horns, solenoid valves,
ONTROL
ONTROL
relays is 2 A for 85 V
AC
to 240 V
AC
or up to 30 VDC. External relays
has a 4-20 mA output which can be used for the transfer of measurements to
ONTROL
Power
Source
Light
Horn
Power
Source
Light
Horn
Example A Example B
Note: Labeling on board will appear different then shown in this figure.
Figure 5: Connection to External Devices
6
Page 11
MX42A C
4.0 Start-up and Operation
4.0 Start-up and Operation
4.0 Start-up and Operation4.0 Start-up and Operation
ONTROL
ENMET Corporation
Once the control has been installed and connected, turn it on with the toggle switch, S2, located on the inside bottom left corner.
OFF is up ON is down
When the MX42A C the buzzer for about a minute. All alarms are inhibited during this test mode. Then, the MX 42A C
ONTROL
is turned on it initiates a test mode, checking the proper operation of the LEDs, LCD and
ONTROL
channel 1 for one minute before starting the normal display cycle of each channel.
2 cases can happen:
a) If: Channel 1 is in operation
The display indicates INIT and then displays the actual measurement value, and the green LED blinks indicating the channel is in operation, the yellow LED is on steady indicating the channel on display.
b) If: Channel 1 is off
The display indicates STOP, the yellow LED is on steady the channel on display and the green LED is off indicating the channel is not in operation.
During the normal display cycle of all channels, each channel is scanned by the MX 42A C
ONTROL
every 9 seconds,
and the measurement is displayed for 3 seconds. On the front of the control F
IGURE
6, the switches 1, 2, 3 and 4 are used to display the respective channel
measurement for one minute on the display. After one minute, the display returns to normal display cycle. The TEST switch triggers the lighting of all signal lamps, all segments of the LCD display and the functioning of the
buzzer. The BUZZER switch resets the alarms and clears the buzzer alarm.
For each channel, there are 5 LEDs to indicate the status of the channel.
displays
LED Description
Display/Operation
[ Lighting bolt on front panel ]
Paired yellow LED to the left and green LED to the right:
When the green LED is blinking the channel is in test mode.When the green LED is on steady the channel is in operation.When the yellow LED is on steady the channel is being displayed.
AL1 [ Bell on front panel ] Alarm 1 red LED when in alarm AL2 [ Bell on front panel ] Alarm 2 red LED when in alarm AL3 [ Bell on front panel ] Alarm 3 red LED when in alarm Fault signal / Calibration signal
[ Wrench on front panel ]
Lower most yellow LED
When the yellow LED is on steady it indicates a malfunction on the line.When the yellow LED is blinking the channel is in calibration mode.
In case of an alarm or fault, the audio alarm on the control panel latches, to clear press the BUZZER switch. The LEDs will clear when the channel is no longer in alarm condition.
N
OTE
: The buzzer can be inhibited by moving the jumper on the top right corner of the display board to the OFF
position. See figure 1 for location of jumper.
C
AUTION
: There is no visual indication that the buzzer is in inhibited. Return jumper to ON position before normal
operation.
7
Page 12
ENMET Corporation MX42A C
MX42A
MX42AMX42A
MX42A
Fault/Calibration
Channel
4
3
1
2
DEF

123
4
Display/Operation Yellow & Green LEDs
AL1

Alarm 1
AL2

ONTROL
Display
Alarm 2 Red LED
Alarm 3 Red LED
Yellow LED
N
OTE
: In some applications, slight electronic noise between the Sensor/Transmitter and the Control can cause
fluctuations in the display reading. These minor fluctuations are considered to be insignificant in terms of the range, detection limit and alarm values of the gas being monitored.
AL3

Figure 6: Front View of MX42A Control
Switches
TEST
Test Switch
Buzzer Switch
8
Page 13
MX42A C
ONTROL
ENMET Corporation
4.1 Configuration of Alarms and Servocontrol
C
AUTION
: The procedures and adjustments described in the following sections must be performed by authorized
personal. Failure to follow instructions may jeopardize accurate measurements.
4.2 Characteristics of alarm triggering
There are three alarm thresholds associated with each channel:
Threshold 1 controls Alarm 1 LED and relay 1.Threshold 2 controls Alarm 2 LED and relay 2.Threshold 3 controls Alarm 3 LED and the CR relay (common relay).
N
OTE
: The CR relay is common to all channels.
For each channel, a block of microswitches is located on the display board and is used to program the characteristics of alarm thresholds and operation of each channel. See F
1 2 3 4 5 6 7 8 9 10
Example of Microswitch in normal operation mode, grayed areas indicated position of each switch
Microswitch position 1: Sets the triggering of alarms 2 & 3 by increasing or decreasing values. D
OWN
is for increasing value and UP if for decreasing value. Down is normal
Microswitch position 2: Is used to set alarm 3 on either delay time or averaging. D
OWN
is delay time: See microswitches 9 & 10 for setting time delay
UP is averaging: Is set to time delay at the factory.
IGURE
7 and Table 1.
Microswitch position 3: Is used to set clearance of audio Alarms 1 and 2 to latching or non-latching:
D
OWN
is latching/manual clearance:
When a threshold is reached, the LED and relay are activated. When a threshold decreases, the signals are deactivated by manually pressing BUZZER button.
UP is non-latching/automatic clearance:
When a threshold is reached, the associated LED and relay are activated. When the threshold decreases, the signals are automatically deactivated. This is the factory set position.
N
OTE
: Alarms 1 and 2 are set together to the same condition, alarm 3 has automatic clearance
Microswitch position 4: Sets the triggering of alarms 1 by increasing or decreasing values. D
OWN
is for increasing value and UP is for decreasing value. Down is normal
Microswitch position 5: Is used for European parking garage regulations. D
OWN
is normal operation and UP parking garage mode.
Microswitch position 6: Is used to set control in adjustment or calibration mode. D
OWN
is for adjustment of display settings and UP is for calibration of sensor/transmitter.
N
OTE
: microswitch 6 is disabled when microswitch 7 is in normal operation mode.
Microswitch position 7: Is used to place the channel in normal operation or maintenance mode. D
OWN
is maintenance mode and UP is normal operation.
Microswitch position 8: Is used to place channel in operation or take it out of operation. D
OWN
is in operation and UP is out of operation.
Microswitch position 9 & 10: Are used to set the time delay of alarm 3rd relay common to the channels.
9
Page 14
ENMET Corporation MX42A C
ONTROL
Figure 7: Location of Microswitches
10
Page 15
MX42A C
ONTROL
4.3 Adjustment of alarm thresholds and averaging times of alarm 3
The alarms are adjusted at the factory. However, these adjustments can be changed.
N
OTE
: The fault lamp blinks to signal the channel is in maintenance mode. The maintenance mode lasts for 30
minutes. After which, the channel automatically changes over to fault. Only one channel can be programmed at a time. When a channel is in the maintenance mode, the 4-20 mA current output is set to 2 mA.
1 2 3 4 5 6 7 8 9 10
Example of Microswitch in Maintenance mode gray areas indicate position of each switch
For the selected channel, set the microswitches as follows:
Microswitch 8: in operationMicroswitch 7: maintenanceMicroswitch 6: adjustment
In this mode, the pushbutton switches 1, 2, 3 and 4 have the following functions:
pushbutton switch 4 = to cycle through functions and ENTERpushbutton switch 3 = to view setting of functionpushbutton switch 2 = to increase setting of functionpushbutton switch 1 = to decrease setting of function
The following is the cycle of functions:
AL1: alarm 1 thresholdAL2: alarm 2 thresholdAL3: alarm 3 thresholdT1: averaging time of alarm set at factory to 15 minutes.PT: sets the position of the decimal point according to the sensor/transmitter measuring range. See S/T
manual for correct setting.
Example: To positioning alarm 3 at 150 for channel 2:
On the microswitch block of channel 2, position microswitch 7 to
LCD displays AL1.
Press pushbutton switch 4 twice. The LCD displays AL3.Press pushbutton switch 3. The LCD displays the present value of the alarm 3 threshold.Using pushbutton switches 1 and 2, to decrease or increase the setting, set the desired threshold.Press the pushbutton switch 4 to ENTER. The threshold is now set.Return Microswitch 7 to normal operation position.Leave Microswitches 6 and 8 as above.
MAINTENANCE
ENMET Corporation
, 6 to
ADJUSTMENT
. The
11
Page 16
ENMET Corporation MX42A C
Jumpers
4.4 Outputs
4.4.1 Relays
With the position of jumpers S3 through S12, the contacts of the relays for each channel can be selected. The contacts can be either open or closed during the alarm condition. see F closed.
This selection is made by moving the corresponding jumper. The standard factory setting, relays (except for the fault relay) are energized in the non-alarm condition.
4.4.2 4-20 mA Current Output
A 4-20 mA output is available on the terminal block for each channel. It serves to connect the MX 42A C chart recorder or to any other data acquisition system (maximum load resistance is 600 ohms).
N
OTE
: The 4-20 mA output is preset in the factory: 4 mA corresponds to a display of 0 and 20 mA corresponds to a
full-scale value. Potentiometers P5, P6, P7 and P8 (for channels 1, 2, 3 and 4 respectively) adjust the 4 mA. Potentiometers P21, P22, P23 and P24 (for channels 1, 2, 3 and 4 respectively) adjust the 20 mA
IGURE
8. The factory set position is normally
ONTROL
ONTROL
to a
P21
P5
P22
P6
P23
P7
P24
P8
Figure 8: Relay Jumper and 4-20mA POT Location
12
Jumper position for NC contact
Jumper position for NO contact
S3 to S12
Page 17
MX42A C
5.0 Maintenance
5.0 Maintenance
5.0 Maintenance5.0 Maintenance
ONTROL
The MX 42A C
ONTROL
requires practically no servicing at all. Nevertheless, since it is a safety device, it is still
necessary to calibrate the detectors periodically.
C
AUTION
: The procedures and adjustments described in the following sections must be performed by authorized
personal. Failure to follow instructions may jeopardize accurate measurements.
ENMET Corporation
5.1 Adjustment of sensor/transmitter and the MX 42A C
ONTROL
unit
adjustment consists of calibrating the zero of the sensor/transmitter in clean air and the gain of the sensor/transmitter to the reference gas.
For each channel, set the microswitches as follows
Microswitch 8 = in operationMicroswitch 7 = maintenanceMicroswitch 6 = calibration
In the maintenance mode, the Control current output is set to 2 mA.
N
OTE
: If left in calibration mode, the channel automatically changes over to fault after 30 minutes.
1 2 3 4 5 6 7 8 9 10
Example of Microswitch in calibration mode
gray areas indicate position of each switch
Voltmeter readings are taken at test points of sensor/transmitter refer to S/T manual for location and across OUTPUT+ , 4-20mA– terminal for each channel of the MX42A C
Adjustment of MX42A C
ONTROL
zero
ONTROL
. See F
IGURE
4, 9.
With the sensor/transmitter in clean air, set the output of the sensor/transmitter to zero (4mA). Then use MX42A potentiometer: F
IGURE
9, Zero Adjust
P9 for channel 1P12 for channel 2P15 for channel 3P18 for channel 4
to display 0000 on the channel in question. If the ambient air at S/T is not free of contamination, use air from a cylinder.
Adjustment MX42A C
ONTROL
gain
Apply the correct calibration gas to the sensor/transmitter, and set the sensor/transmitter output to appropriate output
see S/T manual for proper setting.
Adjust the
CONTROL
display to the value of the calibration gas using potentiometer: F
IGURE
9, Span Adjust
P11 for channel 1P14 for channel 2P17 for channel 3P20 for channel 4
Remove Calibration Gas and return to the microswitch configuration to normal operation:
Microswitch 8 = in operationMicroswitch 7 = normalMicroswitch 6 = calibration
Terminal Cannel 1
P11
P9
P14
P12
P17
P15
P20
P18
Figure 9: Potentiometer Location
13
Span Adjust POTs
Zero Adjust POTs
Page 18
ENMET Corporation MX42A C
6.0 Troubleshooting
6.0 Troubleshooting
6.0 Troubleshooting6.0 Troubleshooting
Fault message Possible Cause Corrective action
ONTROL
Display off or no LED lighted fuse blown
power switch set to OFF
STOP displayed channel out of service put the channel microswitch 8 to ON INIT displayed bad detector electrical connections
defective detectorthe type of detector does not
correspond to the configuration of the channel
channel very badly adjusted
Fault signal lamp lighted and DEF displayed
Fault signal lamp blinking
External alarm controlled in opposite direction, in relation to the tripping of the alarm
channel in maintenance mode for more than 30 minutes
channel in maintenance position
bad choice of relay contact move the jumper to use the correct contact
check power supply voltages and change the
fuses if necessary
set the power switch to ON
check the connectionschange the detectorchange the type of detector
Caution: The channel could have been damaged
adjust the channel
reset the channel microswitch 7 to NORMAL
reset the channel microswitch 7 to NORMAL
14
Page 19
MX42A C
0 to 100,
0 to 300,
0 to 1000,
0 to 2000;
preset at factory, not field convertible
7.0 Specifications
7.0 Specifications
7.0 Specifications7.0 Specifications
N
OTE
ONTROL
: All specifications stated in this manual may change without notice.
7.1 Physical
Enclosure Operating temperature Storage temperature Relative humidity Tightness Dimensions Weight Positioning Warranty Function Capacity Measurement Manufacturer
PVC (polyvinyl chloride), completely shielded inside
-10°C to +40°C
-20°C to +55°C 0 to 95%, noncondensing IP54
13.38x11.81x4.22 (340 x 300 x 107 mm, length x height x depth)
10.5 lb (4.75 kg) wall-mounted 1 year Control unit for gas detection 4 channels (2 optional) continuous OLDHAM FRANCE
7.2 Display
Display Measuring scale Signal lamps
Digital LCD
24 LEDs, see details in Section «ALARM»
ENMET Corporation
7.3 Power supply
Electrical supply accessible in enclosure:
103 V to 122 VAC, 50/60 Hz  207 V to 244 VAC, 50/60 Hz (option) Not field convertible19 V to 32 V43 to 60 VAC (option)
Fuses:
0.63 A, time-delayed, for 230 V and 110 V4 A for 24 V2 A, time-delayed, for 48 V
Power consumption: 85 VAC or 67 W On/off switch inside enclosure Earth terminal: yes Cable outlet through 10 metallic cable glands, connected earth ground. Maximum shielded cable diameter: 0.37 in. (10 mm)
DC
7.4 Measurement inputs
Line resistances (loop) in ohms between detector and Control Sensor/transmitter detector of 4-20 mA type, 3 wires or 2 wires: 32 ohms (1 km long, cable 3 x 1.5mm²)
15
Page 20
ENMET Corporation MX42A C
7.5 Alarm
Visual alarms provided: for each channel
fault signal lamp:
channel in service: green colorchannel off or malfunction of microprocessor: offdisturbance on line: steady yellow colorcalibration/adjustment mode: blinking yellow color
alarm 1 signal lamp: red color when in alarm
alarm 2 signal lamp: red color when in alarm
alarm 3 signal lamp: red color when in alarm
Alarms 1 and 2
activation after 5 seconds
by increasing or decreasing value
manual or automatic clearance
Alarm 3
activation after elapsed delay time or on basis of average value
automatic clearance
by increasing or decreasing value
ONTROL
Disturbance
complete check of short circuit or cut out of at least one wire (with just one detector)
display per channel with yellow signal lamp
Buzzer
Triggered if:
microprocessor malfunctionanomaly of connecting cable or sensor/transmitteralarm threshold level exceededmaintenance time longer than 30 minutes
16
Page 21
MX42A C
ONTROL
7.6 Control functions
Accessible after removal of front panel For each channel: A set of 10 microswitches
Microswitch no. 8: on/offMicroswitch no. 7: maintenance/normalMicroswitch no. 6: “adjustment/calibration”
displays displays alarm settings / loop signal
Microswitch no. 5: normal/parking garage (alarm 1 and 2) used for European regulationsMicroswitch no. 4: increase/decrease (alarm 1)Microswitch no. 3: “manual/auto” (alarm 1 and 2)
latching / non-latching
Microswitch no. 2: time delay/average (alarm 3)Microswitch no. 1: increase/decrease (alarm 2 and 3)Microswitch no. 9: time delay coding (alarm 3)Microswitch no. 10:time delay coding (alarm 3)
Potentiometers for the adjustment of zero and sensitivity of detector Programming by pushbutton switches of alarms thresholds, averaging time (alarm 2)
7.7 Relays
Relay contacts
2 relays per channel for alarm 1 and alarm 2 (positive safety)1 common relay for alarm 3 (or on option for remote transmission of alarm) (positive safety)1 common relay for fault (negative safety)for each relay, choice of common closed contact or common open contact (by positioning jumpers S3 to S12)characteristics of contact: 2A-250 VAC or 30 V
DC
ENMET Corporation
7.8 Output
4-20 mA current outputs per channel (common ground)Load resistance (loop): maximum 600 ohmsIn case of fault: output < 1 mAIn maintenance position: output = 2 mA
17
Page 22
ENMET Corporation MX42A C
8.0 WARRANTY
8.0 WARRANTY
8.0 WARRANTY8.0 WARRANTY
ENMET warrants new instruments to be free from defects in workmanship and material under normal use for a period of one year from date of shipment from ENMET. The warranty covers both parts and labor excluding instrument calibration and expendable parts such as calibration gas, filters, batteries, etc... Equipment believed to be defective should be returned to ENMET within the warranty period (transportation prepaid) for inspection. If the evaluation by ENMET confirms that the product is defective, it will be repaired or replaced at no charge, within the stated limitations, and returned prepaid to any location in the United States by the most economical means, e.g. Surface UPS/FedEx Ground. If an expedient means of transportation is requested during the warranty period, the customer is responsible for the difference between the most economical means and the expedient mode. ENMET shall not be liable for any loss or damage caused by the improper use of the product. The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of this equipment.
This warranty is expressly given in lieu of all other warranties, either expressed or implied, including that of merchantability, and all other obligations or liabilities of ENMET which may arise in connection with this equipment. ENMET neither assumes nor authorizes any representative or other person to assume for it any obligation or liability other than that which is set forth herein.
NOTE: When returning an instrument to the factory for service:
Be sure to include paperwork.A purchase order, return address and telephone number will assist in the expedient repair and return of your unit.Include any specific instructions.For warranty service, include date of purchaseIf you require an estimate, please contact ENMET Corporation.
ONTROL
There are Return for Repair Instructions and Form on the last pages of this manual. This Form can be copied or used as needed.
Manual Part Number 80003-042 October 1999 MCN 229, 02/08/00
MCN-286, 11/25/02 MCN-296, 11/12/03 MCN-358, 12/06/06
18
Page 23
PO Box 979 680 Fairfield Court Ann Arbor, Michigan 48106-0979
734.761.1270 Fax 734.761.3220
Returning an Instrument for Repair
ENMET instruments may be returned to the factory or any one of our Field Service Centers for regular repair service or calibration. The ENMET Repair Department and Field Service Centers also perform warranty service work.
When returning an instrument to the factory or service center for service, paperwork must be included which contains the following information:
A purchase order number or reference number.  A contact name with return address, telephone and fax numbers  Specific instructions regarding desired service or description
of the problems being encountered.
Date of original purchase and copy of packing slip or invoice
for warranty consideration.
If a price estimate is required, please note it accordingly and be
sure to include a fax number.
Providing the above information assists in the expedient repair and return of your unit.
Failure to provide this information can result in processing delays.
ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the closest tenth of an hour. All instruments sent to ENMET are subject to a minimum $30 evaluation fee, even if returned unrepaired. Unclaimed instruments that ENMET has received without appropriate paperwork or attempts to advise repair costs that have been unanswered, after a period of 60 days, may be disposed of or returned unrepaired COD with the evaluation fee.
Service centers may have different rates or terms. Be sure to contact them for this information.
Repaired instruments are returned by UPS/FedEx Ground and are not insured unless otherwise specified. If expedited shipping methods or insurance is required, it must be stated in your paperwork.
Note: Warranty of customer installed components.
If a component is purchased and installed in the field, and fails within the warranty term, it can be returned to ENMET and will be replaced, free of charge, per ENMETs returned goods procedure.
If the entire instrument is returned to ENMET Corporation with the defective item installed, the item will be replaced at no cost, but the instrument will be subject to labor charges at half of the standard rate.
Page 24
Page 25
Repair Return Form
Mailing Address:
ENMET Corporation PO Box 979 Ann Arbor, Michigan 48106
Phone Number: 734.761.1270 FAX Number: 734.761.3220
Your Mailing Address: Your Shipping Address:
Contact Name: __________________________ Your Phone: _______________________ Your PO/Reference Number: _______________ Your FAX: _______________________
Shipping Address:
ENMET Corporation Attn: Repair Department 680 Fairfield Court Ann Arbor, Michigan 48108
Payment Terms: K COD
(Check one) K VISA / MasterCard______________________ ________
Card number Expiration
Return Shipping Method:
K UPS: K Ground K 3 Day Select K Next Day Air K ND Air Saver K 2-Day Air K Federal Express: K Ground K Express Saver K P-1 K Standard K 2-Day Air K FedEx Account number: ________________________
Would you like ENMET to insure the return shipment?
K No K Yes Insurance Amount: $_________________
Page 26
Loading...