1.3 Serial Numbers ..........................................................................................................................................1
7.3 Power supply ...........................................................................................................................................15
7.6 Control functions .....................................................................................................................................17
The MX 42A C
located in a place to be monitored. The measurement from the detector is displayed on the MX 42A C
compared to alarm thresholds. Should alarm thresholds be exceeded, the MX 42A C
which can be used for the control of outside devices (horn, telephone call, exhaust fans, etc.).
N
OTE
: This instrument is also available as a 2 channel control.
ONTROL
ONTROL
is an apparatus for the detection and measurement of various combustible, toxic and oxygen-
has up to 4 independent measuring channels. Each channel is connected to a gas detector
ONTROL
ENMET Corporation
unit actuates relays
: All specifications stated in this manual may change without notice.
ONTROL
1.1 Unpack
Unpack the MX 42A and examine it for shipping damage. If such damage is observed, notify both ENMET customer
service personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
N
OTE
: It is your responsibility to follow these instructions. If they are not followed, the carrier will
not honor any claims for damage.
This shipment was carefully inspected, verified and properly packaged at our company and delivered to the
carrier in good condition.
When it was picked up by the carrier at ENMET, it legally became your company’s property.
If your shipment arrives damaged:
•Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local
office and request immediate inspection of the carton and the contents.
•After the inspection and after you have received written acknowledgment of the damage from the carrier,
contact ENMET Customer Service for return authorization and further instructions. Have your Purchase
Order and Sales Order numbers available.
ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability
coverage, usually $100.00. Repair or replacement charges above that value are your company’s responsibility.
The shipping company may offer optional insurance coverage. ENMET only insures shipments with the
shipping company when asked to do so in writing by our customer. If you need your shipments insured, please
forward a written request to ENMET Customer Service.
and
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days
of receipt at the following address:
ENMET Corporation
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 734-761-3220 Fax
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the MX 42A is received as ordered. If
there are accessories on the order, ascertain that they are present. Check the contents of calibration kits. Notify
ENMET customer service personnel of any discrepancy immediately.
1.3 Serial Numbers
Each MX 42A is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.
1
Page 6
ENMET CorporationMX42A C
Display
Visual Alarms
Terminals
Power Switch
10
pl
2.0 Features
2.0 Features
2.0 Features2.0 Features
See F
IGURE
1
FeatureDescription
EnclosureFor wall mounting made of PVC
(length: 13.38, height: 11.81, depth: 4.21 inches)
with internal coating for RFI protection.
ONTROL
Power Supply
Display
Inputs4, for 4-20mA sensor/transmitters which may have combustible, toxic or oxygen sensors.
Output
Audio Alarms
Visual Alarms
Relays
AC or DC
LCD display of the measurements
4-20 mA output per channel (< 1 mA for fault, 2 mA for maintenance)
Resettable buzzer for alarms or a fault conditions, a total of 3:
• 2 increasing or decreasing thresholds, with manual or automatic clearance.
• 1 increasing or decreasing threshold, automatic clearance.
5 LED per channel
A total of 10 relays distributed as follows:
• 2 relays per channel (NO or NC) for the first two alarm thresholds
• 1 relay common to the channels for the third alarm threshold (or the remote
transmission of the alarm on programming)
• 1 relay common to the channels for detector faults
Enclosure
Microswitches
1 set per channel
5 LED per channel
Power Supply
Mounting Holes 4 pl
Buzzer
Buzzer Jumper
See caution in Section 4.0
Relays, total of 10
Input / Output
Fuses
Cable glands
Figure 1: Interior View of MX42A
2
Page 7
MX42A C
3.0 Installation and Connection
3.0 Installation and Connection
3.0 Installation and Connection3.0 Installation and Connection
ONTROL
3.1 Installation
3.1.1 Placement of Control
The MX 42A C
ventilated place where it can be watched, such as a guard house, control room or security service area.
To mount the Control see F
4 mounting holes, with centers of 12.40 x 9.65 inches, use #10 or 5 mm screws.
C
AUTION
: There must be 12 inches of clearance above the MX 42A C
3.1.2 Placement of Sensor/Transmitters
Their location depends on three main factors:
♦ Density of gas to be detected: high for gases lighter than air and low for gases heavier than air
♦ Leak point: determination of the probable source of a leak
♦ In the flow of air in ventilated rooms.
ONTROL
maintenance.
can be installed in any place with an unclassified atmosphere. It should be put in a well
IGURE
2 mounting demotions:
ONTROL
so the cover can be opened for
ENMET Corporation
Front View
Bottom View
Figure 2: Mounting MX42A C
3
Front View with Lid Open
ONTROL
Page 8
ENMET CorporationMX42A C
3.2 Electrical Connection of the MX42A Control
Power supply: connect the power supply wires to the terminal blocks of the Control. Located on the PC Board at the
bottom of the enclosure.
N
OTE
: Before installation, turn off the MX 42A C
bottom left corner.
W
ARNING
:
Continuous gas detection and alarm systems (110VAC/220VAC / 24VDC/12VDC powered) become
inoperative upon loss of primary power. Contact factory for specifications and pricing of backup
battery systems.
See Figure 3 for the connection of the power terminals.
• AC, Ground labeled TERRE on the board
AC, High labeled PHASE on the board
AC, Neutral labeled NEUTRE on the board
terminals, 115 VAC (103 V to 122 V), 50/60 Hz, are protected by F1 and F3 with 1.25A time-delay fuses.
• + DC labeled + CONTINU on the board
– DC labeled – CONTINU on the board
terminals, 24 V (19 V to 32 V), DC is protected by F2 a 4A fuse.
• Optional: 230 VAC (207 V to 244 V), 50/60 Hz, is protected by F1 and F3 with 630mA time-delay fuses.
A label on the enclosure gives the power supply voltages.
OFF is up
ON is down
ONTROL
using the toggle switch, S2, located inside the unit in the
ONTROL
Switch S2
110VDC Or Optional
220VDC If Installed
Not Field Convertible
110V
VDC Connections
Note: Labeling on board will appear different then shown in this figure.
Figure 3: Connection of Power Terminal
4
Page 9
MX42A C
Channel 1
Channel 3
ONTROL
3.3 Connection of the MX42A Control to the Sensor/Transmitter
3.3.1 Type and Connection of Sensor/Transmitters
Various types of sensor/transmitters can be connected.
Two wire 4-20mA, toxic gas or oxygen detection sensor/transmitters. Such as, ENMET SDS and EN models.
Negative in, Signal (wire 1) and Positive in +24 VDC (wire 3) of each channel. See figure 4
Three wire 4-20mA combustible or toxic gas and oxygen sensor/transmitters. Such as, ENMET SDS-97D and
EX5000 models. Signal (wire 1), DC-GND (wire 2) and +24 VDC (wire 3). See figure 4
If used with other manufactures sensor/transmitters, follow installation instructions procedures supplied by the
sensor/transmitter manufacturer, or contact your ENMET representative or ENMETCorporation.
Specifications of cable:
• Using shielded cables is necessary for RFI protection.
• The shield of the cable must be connected to wire #2 (DC ground) of the C
ONTROL
ENMET Corporation
.
Example: 2 wire 4-20mA
Toxic Gas or Oxygen
Example: 3 wire 4-20mA
Combustible or Toxic Gas
DC-G
Signal ( – )
24VDC ( + )
Signal ( – )
ND
24VDC ( + )
Note: Labeling on board will appear different then shown in this figure.
Figure 4: Connection of Sensor/Transmitter Terminal
5
Page 10
ENMET CorporationMX42A C
3.4 Connection of the Control to External Devices
Auxiliary alarms should be powered from an independent power source separate form the instrument power to avoid
alarm failure due to controller malfunction.
3.4.1 Connection to Auxiliary Alarms
The MX 42A C
telephone callers, exhaust fans, etc.
The relays are assigned to functions as follows:
For Each Channel:
• one relay, RELAY 1, actuated by alarm 1
• one relay, RELAY 2, actuated by alarm 2
For All Channels:
• A common relay, CR RELAY, actuated by the high alarm of any channel
• One relay, FAULT RELAY, associated with faults detected on any channel such as: detector malfunctions, poor
electrical connections, signal current is 0mA or signal current is greater then 25mA.
An example of a connection is shown in Figure 5
• Example A: a light and horn, connected to RELAY 2 of channel 4
• Example B: a light and horn, connected to RELAY 2, of channels 1 – 4
N
OTE
: Contact rating of the MX42AC
must be added if the devices to be controlled require higher current requirements.
3.4.2 4-20mA Current Output
For each channel, the MX 42A C
a recorder or data logger. In a loop configuration, the maximum resistance is 600 ohms. The 4-20 mA outputs have
common ground connections.
ONTROL
has 10 relays that can be used to control external devices such as: horns, solenoid valves,
ONTROL
ONTROL
relays is 2 A for 85 V
AC
to 240 V
AC
or up to 30 VDC. External relays
has a 4-20 mA output which can be used for the transfer of measurements to
ONTROL
Power
Source
Light
Horn
Power
Source
Light
Horn
Example AExample B
Note: Labeling on board will appear different then shown in this figure.
Figure 5: Connection to External Devices
6
Page 11
MX42A C
4.0 Start-up and Operation
4.0 Start-up and Operation
4.0 Start-up and Operation4.0 Start-up and Operation
ONTROL
ENMET Corporation
Once the control has been installed and connected, turn it on with the toggle switch, S2, located on the inside bottom
left corner.
OFF is up
ON is down
When the MX42AC
the buzzer for about a minute. All alarms are inhibited during this test mode. Then, the MX 42A C
ONTROL
is turned on it initiates a test mode, checking the proper operation of the LEDs, LCD and
ONTROL
channel 1 for one minute before starting the normal display cycle of each channel.
2 cases can happen:
a) If: Channel 1 is in operation
The display indicates INIT and then displays the actual measurement value, and the green LED blinks indicating
the channel is in operation, the yellow LED is on steady indicating the channel on display.
b) If: Channel 1 is off
The display indicates STOP, the yellow LED is on steady the channel on display and the green LED is off
indicating the channel is not in operation.
During the normal display cycle of all channels, each channel is scanned by the MX 42A C
ONTROL
every 9 seconds,
and the measurement is displayed for 3 seconds.
On the front of the control F
IGURE
6, the switches 1, 2, 3 and 4 are used to display the respective channel
measurement for one minute on the display. After one minute, the display returns to normal display cycle.
The TEST switch triggers the lighting of all signal lamps, all segments of the LCD display and the functioning of the
buzzer.
The BUZZER switch resets the alarms and clears the buzzer alarm.
For each channel, there are 5 LEDs to indicate the status of the channel.
displays
LEDDescription
Display/Operation
[Lighting bolt on front panel ]
Paired yellow LED to the left and green LED to the right:
When the green LED is blinking the channel is in test mode.
When the green LED is on steady the channel is in operation.
When the yellow LED is on steady the channel is being displayed.
AL1 [ Bell on front panel ]Alarm 1 red LED when in alarm
AL2 [ Bell on front panel ]Alarm 2 red LED when in alarm
AL3 [ Bell on front panel ]Alarm 3 red LED when in alarm
Fault signal / Calibration signal
[ Wrench on front panel ]
Lower most yellow LED
When the yellow LED is on steady it indicates a malfunction on the line.
When the yellow LED is blinking the channel is in calibration mode.
In case of an alarm or fault, the audio alarm on the control panel latches, to clear press the BUZZER switch. The
LEDs will clear when the channel is no longer in alarm condition.
N
OTE
: The buzzer can be inhibited by moving the jumper on the top right corner of the display board to the OFF
position. See figure 1 for location of jumper.
C
AUTION
: There is no visual indication that the buzzer is in inhibited. Return jumper to ON position before normal
operation.
7
Page 12
ENMET CorporationMX42A C
MX42A
MX42AMX42A
MX42A
Fault/Calibration
Channel
4
3
1
2
DEF
123
4
Display/Operation
Yellow & Green LEDs
AL1
Alarm 1
AL2
ONTROL
Display
Alarm 2
Red LED
Alarm 3
Red LED
Yellow LED
N
OTE
: In some applications, slight electronic noise between the Sensor/Transmitter and the Control can cause
fluctuations in the display reading. These minor fluctuations are considered to be insignificant in terms of the
range, detection limit and alarm values of the gas being monitored.
AL3
Figure 6: Front View of MX42A Control
Switches
TEST
Test Switch
Buzzer Switch
8
Page 13
MX42A C
ONTROL
ENMET Corporation
4.1 Configuration of Alarms and Servocontrol
C
AUTION
: The procedures and adjustments described in the following sections must be performed by authorized
personal. Failure to follow instructions may jeopardize accurate measurements.
4.2 Characteristics of alarm triggering
There are three alarm thresholds associated with each channel:
Threshold 1 controls Alarm 1 LED and relay 1.
Threshold 2 controls Alarm 2 LED and relay 2.
Threshold 3 controls Alarm 3 LED and the CR relay (common relay).
N
OTE
: The CR relay is common to all channels.
For each channel, a block of microswitches is located on the display board and is used to program the characteristics of
alarm thresholds and operation of each channel. See F
1 23 45 67 89 10
Example of Microswitch in normal operation mode, grayed areas indicated position of each switch
•Microswitch position 1: Sets the triggering of alarms 2 & 3 by increasing or decreasing values.
D
OWN
is for increasing value and UP if for decreasing value. Down is normal
•Microswitch position 2: Is used to set alarm 3 on either delay time or averaging.
D
OWN
is delay time: See microswitches 9 & 10 for setting time delay
UP is averaging: Is set to time delay at the factory.
IGURE
7 and Table 1.
•Microswitch position 3: Is used to set clearance of audio Alarms 1 and 2 to latching or non-latching:
D
OWN
is latching/manual clearance:
When a threshold is reached, the LED and relay are activated.
When a threshold decreases, the signals are deactivated by manually pressing BUZZER button.
UP is non-latching/automatic clearance:
When a threshold is reached, the associated LED and relay are activated. When the threshold decreases, the
signals are automatically deactivated. This is the factory set position.
N
OTE
: Alarms 1 and 2 are set together to the same condition, alarm 3 has automatic clearance
•Microswitch position 4: Sets the triggering of alarms 1 by increasing or decreasing values.
D
OWN
is for increasing value and UP is for decreasing value. Down is normal
•Microswitch position 5: Is used for European parking garage regulations.
D
OWN
is normal operation and UP parking garage mode.
•Microswitch position 6: Is used to set control in adjustment or calibration mode.
D
OWN
is for adjustment of display settings and UP is for calibration of sensor/transmitter.
N
OTE
: microswitch 6 is disabled when microswitch 7 is in normal operation mode.
•Microswitch position 7: Is used to place the channel in normal operation or maintenance mode.
D
OWN
is maintenance mode and UP is normal operation.
•Microswitch position 8: Is used to place channel in operation or take it out of operation.
D
OWN
is in operation and UP is out of operation.
• Microswitch position 9 & 10: Are used to set the time delay of alarm 3rd relay common to the channels.
9
Page 14
ENMET CorporationMX42A C
ONTROL
Figure 7: Location of Microswitches
10
Page 15
MX42A C
ONTROL
4.3 Adjustment of alarm thresholds and averaging times of alarm 3
The alarms are adjusted at the factory. However, these adjustments can be changed.
N
OTE
: The fault lamp blinks to signal the channel is in maintenance mode. The maintenance mode lasts for 30
minutes. After which, the channel automatically changes over to fault.
Only one channel can be programmed at a time.
When a channel is in the maintenance mode, the 4-20 mA current output is set to 2 mA.
1 23 45 67 89 10
Example of Microswitch in Maintenance mode gray areas indicate position of each switch
For the selected channel, set the microswitches as follows:
In this mode, the pushbutton switches 1, 2, 3 and 4 have the following functions:
pushbutton switch 4 = to cycle through functions and ENTER
pushbutton switch 3 = to view setting of function
pushbutton switch 2 = to increase setting of function
pushbutton switch 1 = to decrease setting of function
The following is the cycle of functions:
AL1: alarm 1 threshold
AL2: alarm 2 threshold
AL3: alarm 3 threshold
T1: averaging time of alarm set at factory to 15 minutes.
PT: sets the position of the decimal point according to the sensor/transmitter measuring range. See S/T
manual for correct setting.
Example: To positioning alarm 3 at 150 for channel 2:
On the microswitch block of channel 2, position microswitch 7 to
LCD displays AL1.
Press pushbutton switch 4 twice. The LCD displays AL3.
Press pushbutton switch 3. The LCD displays the present value of the alarm 3 threshold.
Using pushbutton switches 1 and 2, to decrease or increase the setting, set the desired threshold.
Press the pushbutton switch 4 to ENTER. The threshold is now set.
Return Microswitch 7 to normal operation position.
Leave Microswitches 6 and 8 as above.
MAINTENANCE
ENMET Corporation
, 6 to
ADJUSTMENT
. The
11
Page 16
ENMET CorporationMX42A C
Jumpers
4.4 Outputs
4.4.1 Relays
With the position of jumpers S3 through S12, the contacts of the relays for each channel can be selected. The
contacts can be either open or closed during the alarm condition. see F
closed.
This selection is made by moving the corresponding jumper. The standard factory setting, relays (except for the fault
relay) are energized in the non-alarm condition.
4.4.2 4-20 mA Current Output
A 4-20 mA output is available on the terminal block for each channel. It serves to connect the MX 42A C
chart recorder or to any other data acquisition system (maximum load resistance is 600 ohms).
N
OTE
: The 4-20 mA output is preset in the factory: 4 mA corresponds to a display of 0 and 20 mA corresponds to a
full-scale value.
Potentiometers P5, P6, P7 and P8 (for channels 1, 2, 3 and 4 respectively) adjust the 4 mA.
Potentiometers P21, P22, P23 and P24 (for channels 1, 2, 3 and 4 respectively) adjust the 20 mA
IGURE
8. The factory set position is normally
ONTROL
ONTROL
to a
P21
P5
P22
P6
P23
P7
P24
P8
Figure 8: Relay Jumper and 4-20mA POT Location
12
Jumper position
for NC contact
Jumper position
for NO contact
S3 to S12
Page 17
MX42A C
5.0 Maintenance
5.0 Maintenance
5.0 Maintenance5.0 Maintenance
ONTROL
The MX 42A C
ONTROL
requires practically no servicing at all. Nevertheless, since it is a safety device, it is still
necessary to calibrate the detectors periodically.
C
AUTION
: The procedures and adjustments described in the following sections must be performed by authorized
personal. Failure to follow instructions may jeopardize accurate measurements.
ENMET Corporation
5.1 Adjustment of sensor/transmitter and the MX 42A C
ONTROL
unit
adjustment consists of calibrating the zero of the sensor/transmitter in clean air and the gain of the sensor/transmitter to
the reference gas.
For each channel, set the microswitches as follows
In the maintenance mode, the Control current output is set to 2 mA.
N
OTE
: If left in calibration mode, the channel automatically changes over to fault after 30 minutes.
1 23 45 67 89 10
Example of Microswitch in calibration mode
gray areas indicate position of each switch
Voltmeter readings are taken at test points of sensor/transmitter refer to S/T manual for location and across OUTPUT+, 4-20mA– terminal for each channel of the MX42AC
Adjustment of MX42A C
ONTROL
zero
ONTROL
. See F
IGURE
4, 9.
With the sensor/transmitter in clean air, set the output of the sensor/transmitter to zero (4mA). Then use MX42A
potentiometer: F
IGURE
9, Zero Adjust
P9 for channel 1
P12 for channel 2
P15 for channel 3
P18 for channel 4
to display 0000 on the channel in question. If the ambient air at S/T is not free of contamination, use air from a cylinder.
Adjustment MX42A C
ONTROL
gain
• Apply the correct calibration gas to the sensor/transmitter, and set the sensor/transmitter output to appropriate output
see S/T manual for proper setting.
•Adjust the
CONTROL
display to the value of the calibration gas using potentiometer: F
IGURE
9, Span Adjust
P11 for channel 1
P14 for channel 2
P17 for channel 3
P20 for channel 4
Remove Calibration Gas and return to the microswitch configuration to normal operation:
Microswitch 8 = in operation
Microswitch 7 = normal
Microswitch 6 = calibration
Terminal
Cannel 1
P11
P9
P14
P12
P17
P15
P20
P18
Figure 9: Potentiometer Location
13
Span Adjust
POTs
Zero Adjust
POTs
Page 18
ENMET CorporationMX42A C
6.0 Troubleshooting
6.0 Troubleshooting
6.0 Troubleshooting6.0 Troubleshooting
Fault messagePossible CauseCorrective action
ONTROL
Display off or no LED lighted fuse blown
power switch set to OFF
STOP displayedchannel out of serviceput the channel microswitch 8 to ON
INIT displayedbad detector electrical connections
defective detector
the type of detector does not
correspond to the configuration of
the channel
channel very badly adjusted
Fault signal lamp lighted and
DEF displayed
Fault signal lamp blinking
External alarm controlled in
opposite direction, in relation
to the tripping of the alarm
channel in maintenance mode for
more than 30 minutes
channel in maintenance position
bad choice of relay contactmove the jumper to use the correct contact
check power supply voltages and change the
fuses if necessary
set the power switch to ON
check the connections
change the detector
change the type of detector
Caution: The channel could have been damaged
adjust the channel
reset the channel microswitch 7 to NORMAL
reset the channel microswitch 7 to NORMAL
14
Page 19
MX42A C
0 to 100,
0 to 300,
0 to 1000,
0 to 2000;
preset at factory, not field convertible
7.0 Specifications
7.0 Specifications
7.0 Specifications7.0 Specifications
N
OTE
ONTROL
: All specifications stated in this manual may change without notice.
7.1 Physical
Enclosure
Operating temperature
Storage temperature
Relative humidity
Tightness
Dimensions
Weight
Positioning
Warranty
Function
Capacity
Measurement
Manufacturer
13.38x11.81x4.22 (340 x 300 x 107 mm, length x height x depth)
10.5 lb (4.75 kg)
wall-mounted
1 year
Control unit for gas detection
4 channels (2 optional)
continuous
OLDHAM FRANCE
7.2 Display
Display
Measuring scale
Signal lamps
Digital LCD
24 LEDs, see details in Section «ALARM»
ENMET Corporation
7.3 Power supply
Electrical supply accessible in enclosure:
103 V to 122 VAC, 50/60 Hz
207 V to 244 VAC, 50/60 Hz (option) Not field convertible
19 V to 32 V
43 to 60 VAC (option)
Fuses:
0.63 A, time-delayed, for 230 V and 110 V
4 A for 24 V
2 A, time-delayed, for 48 V
Power consumption: 85 VAC or 67 W
On/off switch inside enclosure
Earth terminal: yes
Cable outlet through 10 metallic cable glands, connected earth ground.
Maximum shielded cable diameter: 0.37 in. (10 mm)
DC
7.4 Measurement inputs
Line resistances (loop) in ohms between detector and Control
Sensor/transmitter detector of 4-20 mA type, 3 wires or 2 wires: 32 ohms (1 km long, cable 3 x 1.5mm²)
15
Page 20
ENMET CorporationMX42A C
7.5 Alarm
Visual alarms provided: for each channel
•fault signal lamp:
channel in service: green color
channel off or malfunction of microprocessor: off
disturbance on line: steady yellow color
calibration/adjustment mode: blinking yellow color
• alarm 1 signal lamp: red color when in alarm
• alarm 2 signal lamp: red color when in alarm
• alarm 3 signal lamp: red color when in alarm
Alarms 1 and 2
• activation after 5 seconds
• by increasing or decreasing value
• manual or automatic clearance
Alarm 3
• activation after elapsed delay time or on basis of average value
• automatic clearance
• by increasing or decreasing value
ONTROL
Disturbance
• complete check of short circuit or cut out of at least one wire (with just one detector)
• display per channel with yellow signal lamp
Buzzer
Triggered if:
microprocessor malfunction
anomaly of connecting cable or sensor/transmitter
alarm threshold level exceeded
maintenance time longer than 30 minutes
16
Page 21
MX42A C
ONTROL
7.6 Control functions
Accessible after removal of front panel
For each channel:
A set of 10 microswitches
Potentiometers for the adjustment of zero and sensitivity of detector
Programming by pushbutton switches of alarms thresholds, averaging time (alarm 2)
7.7 Relays
Relay contacts
2 relays per channel for alarm 1 and alarm 2 (positive safety)
1 common relay for alarm 3 (or on option for remote transmission of alarm) (positive safety)
1 common relay for fault (negative safety)
for each relay, choice of common closed contact or common open contact (by positioning jumpers S3 to S12)
characteristics of contact: 2A-250 VAC or 30 V
DC
ENMET Corporation
7.8 Output
4-20 mA current outputs per channel (common ground)
Load resistance (loop): maximum 600 ohms
In case of fault: output < 1 mA
In maintenance position: output = 2 mA
17
Page 22
ENMET CorporationMX42A C
8.0 WARRANTY
8.0 WARRANTY
8.0 WARRANTY8.0 WARRANTY
ENMET warrants new instruments to be free from defects in workmanship and material under normal use for a period
of one year from date of shipment from ENMET. The warranty covers both parts and labor excluding instrument
calibration and expendable parts such as calibration gas, filters, batteries, etc... Equipment believed to be defective
should be returned to ENMET within the warranty period (transportation prepaid) for inspection. If the evaluation byENMET confirms that the product is defective, it will be repaired or replaced at no charge, within the stated
limitations, and returned prepaid to any location in the United States by the most economical means, e.g. Surface
UPS/FedEx Ground. If an expedient means of transportation is requested during the warranty period, the customer is
responsible for the difference between the most economical means and the expedient mode. ENMET shall not be
liable for any loss or damage caused by the improper use of the product. The purchaser indemnifies and saves
harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of
this equipment.
This warranty is expressly given in lieu of all other warranties, either expressed or implied, including that of
merchantability, and all other obligations or liabilities of ENMET which may arise in connection with this equipment.
ENMET neither assumes nor authorizes any representative or other person to assume for it any obligation or liability
other than that which is set forth herein.
NOTE: When returning an instrument to the factory for service:
Be sure to include paperwork.
A purchase order, return address and telephone number will assist in the expedient repair and return of your unit.
Include any specific instructions.
For warranty service, include date of purchase
If you require an estimate, please contact ENMET Corporation.
ONTROL
There are Return for Repair Instructions and Form on the last pages of this manual. This Form can be copied or used
as needed.
Manual Part Number
80003-042
October 1999
MCN 229, 02/08/00
PO Box 979
680 Fairfield Court
Ann Arbor, Michigan 48106-0979
734.761.1270 Fax 734.761.3220
Returning an Instrument for Repair
ENMET instruments may be returned to the factory or any one of our Field Service Centers for regular
repair service or calibration. The ENMET Repair Department and Field Service Centers also perform
warranty service work.
When returning an instrument to the factory or service center for service, paperwork must be included
which contains the following information:
A purchase order number or reference number.
A contact name with return address, telephone and fax numbers
Specific instructions regarding desired service or description
of the problems being encountered.
Date of original purchase and copy of packing slip or invoice
for warranty consideration.
If a price estimate is required, please note it accordingly and be
sure to include a fax number.
Providing the above information assists in the expedient repair and return of your unit.
Failure to provide this information can result in processing delays.
ENMET charges a one hour minimum billing for all approved repairs with additional time billed to the
closest tenth of an hour. All instruments sent to ENMET are subject to a minimum $30 evaluation fee,
even if returned unrepaired. Unclaimed instruments that ENMET has received without appropriate
paperwork or attempts to advise repair costs that have been unanswered, after a period of 60 days,
may be disposed of or returned unrepaired COD with the evaluation fee.
Service centers may have different rates or terms. Be sure to contact them for this information.
Repaired instruments are returned by UPS/FedEx Ground and are not insured unless otherwise
specified. If expedited shipping methods or insurance is required, it must be stated in your
paperwork.
Note: Warranty of customer installed components.
If a component is purchased and installed in the field, and fails within the warranty term, it can
be returned to ENMET and will be replaced, free of charge, per ENMET’s returned goods
procedure.
If the entire instrument is returned to ENMET Corporation with the defective item installed, the
item will be replaced at no cost, but the instrument will be subject to labor charges at half of the
standard rate.
Page 24
Page 25
Repair Return Form
Mailing Address:
ENMET Corporation
PO Box 979
Ann Arbor, Michigan 48106
K UPS: K GroundK 3 Day SelectK Next Day Air K ND Air SaverK 2-Day Air
K Federal Express:K GroundK Express SaverK P-1 K Standard K 2-Day Air
K FedEx Account number: ________________________
Would you like ENMET to insure the return shipment?
K NoK YesInsurance Amount: $_________________
Page 26
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.