1.2 Check Order ...................................................................................................................................... 1
1.3 Serial Numbers .................................................................................................................................. 1
2.0 F
EATURES OF THE
3.0 I
NSTALLATION OF THE
3.1 Mounting the EX-5100 Enclosure ..................................................................................................... 3
3.2 Wiring the EX-5100 to a Control Unit .............................................................................................. 4
4.0 O
PERATION OF THE
4.1 Start up .............................................................................................................................................. 6
4.1.1 Typical Start Up ...................................................................................................................... 6
4.1.2 Alternate Start Up ................................................................................................................... 6
4.2 Normal Display Mode ....................................................................................................................... 7
The ENMET EX-5100 sensor/transmitters (S/T) is, 3-wire, 24VDC 4-20 ma S/T for the detection of combustible gas.
The EX-5100 is meant to be used in conjunction with an appropriate power supply and controller. The ENMET EX-5100
sensor/transmitter is in an enclosure rated for use in a Class I, Div. 1, Groups B, C, D, classified area.
N
OTE
: All specifications stated in this manual may change without notice.
1.1 Unpack
Unpack the EX-5100 and examine it for shipping damage. If such damage is observed, notify both ENMET customer service
personnel and the commercial carrier involved immediately.
Regarding Damaged Shipments
N
OTE
: It is your responsibility to follow these instructions. If they are not followed, the carrier will not honor
any claims for damage.
This shipment was carefully inspected, verified and properly packaged at our company and delivered to the carrier in
good condition.
When it was picked up by the carrier at ENMET, it legally became your company’s property.
If your shipment arrives damaged:
•Keep the items, packing material, and carton “As Is.” Within 5 days of receipt, notify the carrier’s local office and
request immediate inspection of the carton and the contents.
•After the inspection and after you have received written acknowledgment of the damage from the carrier, contact
ENMET Customer Service for return authorization and further instructions. Have your Purchase Order and Sales
Order numbers available.
ENMET either repairs or replaces damaged equipment and invoices the carrier to the extent of the liability coverage,
usually $100.00. Repair or replacement charges above that value are your company’s responsibility.
The shipping company may offer optional insurance coverage. ENMET only insures shipments with the shipping
company when asked to do so in writing by our customer. If you need your shipments insured, please forward a written
request to ENMET Customer Service.
Regarding Shortages
If there are any shortages or questions regarding this shipment, please notify ENMET Customer Service within 5 days of
receipt at the following address:
ENMET Corporation
680 Fairfield Court
Ann Arbor, MI 48108
734-761-1270 734-761-3220 Fax
1.2 Check Order
Check, the contents of the shipment against the purchase order. Verify that the EX-5100 is received as ordered. [Each EX5100 is labeled with its target gas.] If there are accessories on the order, ascertain that they are present. Check the contents of
calibration kits. Notify ENMET customer service personnel of any discrepancy immediately.
1.3 Serial Numbers
Each EX-5100 is serialized. These numbers are on tags on the equipment and are on record in an ENMET database.
1
ENMET Corporation EX-5100 C
Power /Fault
M
S
Sensor
2.0 Features of the EX-5100
See Figure 1 for location of features:
Feature Description
Display
Gain Potentiometer
(POT)
Visual Alarms
Magnetic Switches
Sensor
LCD: Indicates the level of gas detected by sensor
POT 1: Display contrast adjustment
POT 2: Combustible Sensor Zero adjustment, See Sections 3.2 and 5.4
POT 3: Combustible Heater Do not adjust unless advised by ENMET
POT 4: Used with EX-5150-MOS (High Voltage) Do not adjust unless advised by ENMET
LED indicators:
Power / Fault Indicator LED, Green / Red
Alarm (3) Indicator LED, Red
M
ENU
: Advances the instrument display through menus (Zero, Span, Exit)
S
ELECT
: Selects the Zero, Span, Exit menu or sets proper calibration values for Zero or Span
For sensing LEL levels of gas, see Table 2 and 3 for sensor types
OMBUSTIBLE
Magnetic switches control the instrument maintenance functions. The switch locations are indicated by M
ENU
and S
magnetic field pulse is applied by momentarily putting the end of the magnet in proximity to the switch and then removing it.
Since the magnetic field penetrates the window, the enclosure cover is not removed in order to perform calibration.
Three alarm points are preprogrammed into the EX-5100 sensor/transmitters. At each alarm point, an LED on the front panel
is activated. These internal alarm settings are independent of the 4-20mA output alarm values that can be set at a controller.
An optional relay board is available that will activate 0.5 Amp relay contacts at each alarm point, plus a fault relay.
3 Alarm Indicators
POT 1
Indicator
Display
POT 3
MenuSelect
POT 4
ENU
Magnetic switch
POT 2
Note: POT 1, 3 & 4 shown
for reference only.
Do Not Adjust
Note: See Section 6.0
Replacement Parts for
sensor identification
ELECT
Magnetic switch
ELECT
. A
Internal PCB View External View
Figure 1: EX-5100 Features
2
EX-5100 C
Optional
Mounting Holes
Sensor/T
ransmitter
Sensor/Transmitter
OMBUSTIBLE
ENMET Corporation
3.0 Installation of the EX-5100
C
AUTION
C
AUTION
3.1 Mounting the EX-5100 Enclosure
C
AUTION
:
Area must be declassified during installation.
The ENMETEX-5100 gas sensor/transmitter (S/T) is a 3-wire, 24 VDC 4-20 mA S/T for the detection of combustible gas. The
S/T is meant to be used in conjunction with an appropriate power supply and controller. The ENMETEX-5100
sensor/transmitter is in an enclosure rated for use in a Class I, Div. 1, Groups B, C, D, classified area. Appropriate wiring,
conduit and fittings are required for proper installation in a explosion proof rated environment.
: Since the sensor/transmitter detects gas only at the sensor location, pay attention to the possible sources of gas, the
density of the gas, locations where the gas may be confined and locations where the gas may damage or injure
property or personnel, when choosing locations of sensor/transmitters.
Take into consideration environmental factors when deciding on S/T location. Avoid locations where the S/T may be damaged
by liquid immersion, excessive heat or other know hazards. Also, take precautions to insure condensation inside of the conduit
does not enter the S/T.
Mount the enclosure, using the two mounting holes provided see Figure 2. Pay particular attention to the source and density of
the gas being detected when choosing the location. Mount the S/T near the ceiling for lighter than air gases /vapors and near
the floor for heavier then air gas/vapors. Contact ENMET if you have questions regarding your application.
: Before connecting S/T to controller remove the power source to controller. Failure to do so may cause damage to
sensitive components.
Conduit fitting
Typically: ½″ NPT female
Sensor
½″ NPT female
Select
Menu
Enclosure Top View
Enclosure Side View
S
IDE VIEW
Sensor
Figure 2: EX-5100 Mounting Dimensions
2 places, 0.313″
T
OP VIEW
3
ENMET Corporation EX-5100 C
J4
J8
Wires to
To J8
Wires t
o
Sensor 03070
-
001
Sensor 03070
-
003
Relay Output Board
Optional Relay Output Board
OMBUSTIBLE
3.2 Wiring the EX-5100 to a Control Unit
C
AUTION
*
Contact ENMET for Modbus
Address information
:
Area must be declassified during installation.
Run conduit and 16
AWG
(1.5
2
MM
) wires to the enclosure from the power supply and controller. If the EX-5100 is installed in a
hazardous location as defined by the National Electrical Code, then ALL wiring must be in accordance with the National code
and any local governing codes.
Open the enclosure, and remove the 2 screws that retain the display overlay to the circuit board.
Use caution when removing the over lay. Do not damage the magnetic switches.
Remove the two overlay standoffs and remove the circuit board, exposing the terminal strips on the bottom of the circuit board.
Do not disconnect the circuit board wiring.
Connect the wires from the controller (power supply) to the supplied J4 plug then attach to J4 terminal.
Connect the wires from the sensor to the supplied J8 plug then attach to the J8 terminal.
See Figure 3 for locations
J4 P
LUG – TERMINAL TO CONTROLLER WIRING
Position Function
1 +
24 V
DC
power
2 GND
3 4 - 20 mA out
4* RS-485 D+
5* RS-485 D–
Controller
To J4
Plug J4
It is recommended that the auxiliary
alarm is powered separately.
Use 14 – 20
AWG
(2.5 – 0.5
MM
2
) wire.
When on power the relays are energized.
Relays are rated at 0.5 Amp continuous.
5
4
3
2
1
1 2 3
Sensor
Circuit Board Bottom View
J8 P
LUG – TERMINAL SENSOR WIRING
Position Function Catalytic Sensor
1 + Heater Red
2 Signal Yellow
3 – GND Blue
Position Function Catalytic Sensor
1 + Heater Red
2 Signal White
3 – GND Black
Plug J8
03070-001
03070-003
Bottom View
N
OTE
: Auxiliary alarms should be powered from an
independent power source separate form the
instrument power to avoid alarm failure due to
controller malfunction.
ALL wiring must be in accordance with the
National code and any local governing codes.
End View
End View
4
Loading...
+ 12 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.