Enlighted SU4S Users Manual

Page 5 Page 6
93-01663-01 Rev01 Page 1
Copyright © 2016 Enlighted Inc. All rights reserved.
All other brand or product names are trademarks of
their respective companies or organizations.
Technical Support
For questions regarding the installation or operation of
Technical Support: support@enlightedinc.com
Company Contact Information
Location: 930 Benecia Ave, Sunnyvale, CA 94085 Phone: +1.650.964.1094 Web: enlightedinc.com
FCC and Industry Canada Compliance Information
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
This device complies with Part 15 of the FCC Rules and Industry
Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
this device may not cause harmful interference, AND
this device must accept any interference received, including
interference that may cause undesired operation. Changes or modifications not expressly approved by Enlighted Inc. could void the user's authority to operate the equipment.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes:
l'appareil ne doit pas produire de brouillage, ET
l'utilisateur de l'appareil doit accepter tout brouillage
radioélectrique subi, même si le brouillage est susceptible d'en
compromettre le fonctionnement.
CE
This device complies with the essential requirements and other relevant requirements of the R&TTE Directive (1999/5/EC). The equipment is Class 1 radio equipment which can be placed on the market and be put into service without restrictions in accordance with article 1(3) of Commission Decision 2000/299/EC (Version July
2014).
Ruggedized Sensor
(SU-4S)
Installation Instructions
Model: SU-4S FCC ID: AQQ-SU4S
IC: 10138A-SU4S
Ruggedized Sensor (front and back)
Applicable For:
SU-4S-LRW; SU-4S-LRB SU-4S-HRW; SU-4S-HRB
Shipped Components
Enlighted Ruggedized Sensor Unit ½ inch Lock Nut
Tools you may Need
½ inch Knock out tool
Items you will Need
½ inch LB Conduit Body ½ inch Chase Nipple
Page 2
Page 3
Page 4
Installation
Figure 7
The Ruggedized sensor is shipped with the cable attached to the sensor. Figure 1.
Figure 1
Figure 6
LED Status Description/Solution
LED not on Check power and wiring
Purple solid All LEDs are on during boot time for 5-6
seconds
Green blinking Sensor commissioned and working
Red blinking Incompatibility between LED driver and sensor
– Replace LED driver and if not resolved,
replace sensor.
Red solid Faulty sensor – replace sensor
Green solid Sensor installed, initialized, and
uncommissioned – waiting for discovery.
Blue solid Image being upgraded.
LED Description
Caution
Installation and maintenance must be performed by a qualified electrician in accordance with local, state, and national electrical codes (NEC) and requirements.
Step 1: Turn off all power to the light fixture by switching off the circuit breaker.
Step 2: Mount the Control Unit (CU) in a UL approved
enclosure. Refer to the Control Unit Installation Guide. See Figure 7 for detailed wiring connections from the CU.
Step 3: Remove the cover plate of the ½ inch LB conduit body by removing the two screws. Figure 2.
Figure 2
Step 4: Thread the Ruggedized sensor onto LB conduit body. Figure 3.
Figure 4
Step 6: Knock out a ½ inch hole on the end of the light fixture. Using the ½ inch chase nipple, connect the LB conduit to the fixture. See Figure 5.
Step 5: Replace the cover and two screws on the LB conduit body. Figure 4.
Figure 3
Figure 5
Chase Nipple
Step 7: Pull the Ruggedized sensor cable through the chase nipple into the fixture and connect it to the Control Unit. See Figure 6. For wiring connections to the CU, see Figure 7.
Step 8: If the ruggedized senor cable is not long enough to reach the Control Unit, use an RJ12 coupling to connect
the rugged sensor cable to an Enlighted 7ft Sensor cable.
(CBL-2-7F)
Step 9: Switch on the circuit breaker to turn the power on.