The Enforcer is the first two way wireless high security wireless system on the market. It can only be
compared to an addressable wired system, but instead of using a wired data bus it uses a wireless one.
The Enforcer 32-WE supports 32 wireless and 34 wired inputs, 2 wireless external sirens, 32 keyfobs, 75
user codes or tags, 19 programmable and automation outputs and a large variety of wireless accessories.
All devices can cover a wireless range of open space up to 1.6km.
*EN50131 compliance labeling should be removed if non-compliant configurations are used.
*Please note that technical functions for example fire, gas and flooding are not security graded as they are
outside the scope of EN50131-1 and EN50131-3.
NOTE: All messages are given equal priority and are dealt with on a “first in” basis.
4x Wired Input Expanders
16 x (1 x Wired Output Exp)
12 x (4 x Wired Input Exp)
3 x (Keypads/Readers)
4294967295 encrypted
Time and Date
rolling code
Page: 3
3. Initial Power Up
NOTE 1: It is recommended that the Engineer menu is accessed prior to opening a powered Enforcer 32-
WE.
NOTE 2: If any new peripheral is installed (i.e. Modem, I/O board, Expander) it is recommended that the
Enforcer 32-WE is powered down (mains and battery).
1. Slightly unscrew the two
screws located at the bottom.
NOTE: Do not fully unscrew -as
these can be used as a 'hanger'
to the rear casing as shown in
Step 3.
2. Unhinge the Enforcer 32-WE
from the top and pull down to
disconnect.
NOTE: Take extra care when
removing the front of the Enforcer
32-WE as modems, I/O boards
etc may be connected to the
front.
3. Rotate the front of the
Enforcer 32-WE 180 degrees and
hang it on the opening screws if
required.
3.1 Mains and Earth Wiring
It is important that the electrical earth connection is connected when connecting the 230V mains
supply to the Enforcer.
NOTE 1: Do not locate the mains cables next to internal cabling.
NOTE 2: Ensure that the Enforcer 32-WE is not mounted on any metal surfaces.
NOTE 3: Mains cables should not be internally 'looped' or tightly bundled as this may interfere with
the wireless antennas. Where possible it is recommended that all mains cables should be installed
through the area nearest the mains terminals as shown above.
Page: 4
3.2 Inside of the Enforcer 32-WE: Rear
1. Terminals for Earth and Mains Supply. See page: 4.
2. If a modem is required (DIGI-GPRS, DIGI-LAN or
DIGI-1200/PSTN) then this space is used to install
them. See page: 19
3. The transformer is situated in a housing, this
shouldn’t need to be removed.
4. The rear tamper adjustment screw is used if the
tamper from the front of the Enforcer 32-WE isn't sitting
flush to the back plate - this may happen if the Enforcer
32-WE is installed on an uneven surface.
5. If an I/O board is installed, then this space is used to
install it. See page: 9.
3.3 Inside of the Enforcer 32-WE: Front
1. RS232 connection for Up/downloading to the
InSite software. See page: 17
2. The location of the control panel battery.
See page 6 for replacement procedure.
3. The power connection for a DIGI-GPRS if
connected (Note that this port is labeled ‘GSM
MODEM’). See page: 19
4. The connection for an I/O board if
connected. See page: 9.
5: The connection for the modem installed
(DIGI-GPRS, DIGI-LAN or DIGI-1200/PSTN).
See page: 19
6: The power connection (+12V DC) for the
Enforcer 32-WE.
Page: 5
3.4 Connecting / Replacing the Control Panel Battery
1. Unscrew the battery
compartment
2. Connect the batteries 3. Close the battery
compartment masking sure no
battery cable is trapped
underneath.
NOTE: The Enforcer 32-WE back up battery must be replaced by the
manufacturer’s recommendation. The part code for this battery is BATT9V6/2Ah1WE.
The battery is a NiMH 8 cell 2200mAh rechargeable.
Install the batteries in the space provided and connect the battery connector to the
two pins as shown above. Reinstall the battery holder cover
Dispose of the batteries in accordance with the local regulations.
3.5 Important Installation Notes
Ensure wiring is done to the national wiring regulations in the country where the installation is
taking place. In the UK, this is ‘BS 7671 -Requirements for electrical installations; IET Wiring
Regulations (17th edition)’. If in doubt, consult a qualified local electrician.
Ensure that a readily accessible disconnect device is incorporated in the premises installation wiring
and is provided external to the equipment with a contact separation of at least 3,0mm and
connected as closely as possible to the supply.
Ensure that the Input and Output Board (I/O Board) used to connect wired keypads, readers,
inputs and outputs to the Enforcer 32-WE, is only connected to circuits operating at SELV voltage.
When securing external wires, ensure that means are provided in the installation to prevent the
SELV or signal circuits from coming into contact with live parts of the power supply circuit. Wires
should be fixed near their terminal blocks.
The end of the stranded conductor shall not be consolidated by soft soldering at places where the
conductor is subjected to contact pressure.
On completion of wiring use tie-wraps to prevent any loose wires causing a safety hazard (material
of cables ties shall be rated at least HB or better).
Cables ties and hoses shall be separate for power supply cable and SELV wirings.
Size of protective bonding conductors: minimum section 1.5mm².
Page: 6
4. Technical Specification
Enforcer 32-WE Mains Inputs
European rated
voltage
European rated
current
Capable operating
voltage
Current 22 - 75 mA
Rated Frequency 50 / 60Hz
Input Fuse Rating T 2A (non replaceable)
PSU Type A
Radio Frequency 868MHz, FM Transceiver
Physical Dims 220 x 160 x 50mm
Weight 1025g
Environmental
Operating Temp -10°C to +40°C
Storage Temp -20°C to +60°C
I/O Board (If Connected)
Belgium installations: To guarantee compliance
with the standard T014A no load shall be
connected to the I/O board.
Output Voltage 9-16VDC (12V nom.)
Max Current Output 0.07A allowed
PGM/BELL/STB
Outputs
BELL / Aux Fuses 500mA, Quick Blow
Electrical (Keyfob, PIR & Contact)
Operating Voltage 3.0V nominal
Current
(Communicating)
40-80-mA 250mA Continuous
Comms Time 40mS + 40ms
Battery Type (KF) BATT-CR1/3N(KF4
Battery Type (PIR) BATT-CR123A
Battery Type (UT) BATT-CR2
230V AC -15/+10%
63mA
90 - 264V AC
Narrow Band
250mA Continuous
Load
Consumption:
Load
MK2)
Environment: All Devices
Nominal operating
temperature
Certified operating
temperature
Storage temp. -40°C to +80°C
Enforcer Battery
Output instant voltage 12.71V (with no mains
Peak to peak ripple
voltage
Battery low voltage
value
Type NiMH 8 cell 2200mAh
CIE current when
operating on battery
backup
Systems Analysis: Inputs
On Board 32 Wireless
I/O Board 2 Wired
If wired connection is used one zone shall be
program as “Fault”.
All Enforcer peripherals; LCD keypads, readers, expanders etc. are connected via the D1-, D2+,D3 and D4 terminals. This is an example of what a typical Enforcer busmay look like.
General Principles:
NOTE 1: No alarm system
cable should be run with other cables carrying AC or digital signals.
NOTE 2: The cables should be protected by the use of grommets where appropriate.
NOTE: For greater than 1000m range a standard isolated RS485 repeater is required.
IMPORTANT NOTE: If an expansion module with a power supply on board is connected, the
D2+ terminal MUST NOT be connected between the main bus and module.
Page: 8
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.