ENERVEX MEC 18 Installation & Operating Manual

ENERVEX MEC 18 MECHANICAL EXHAUST CONTROL
3916010 06.16 Installation & Operating Manual
READ AND SAVE THESE INSTRUCTIONS!
ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA
3916010 06.16
The MEC 18 Mechanical Exhaust Control is ETL Listed in the U.S. and Canada: under file #302882A
Symbol Legend
The following terms are used throughout this manual to bring attention to the presence of potential hazards, or to important information concerning the product.
DANGER: Indicates an imminent hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING: Indicates an imminent hazardous situation which, if not avoided, may result in personal injury or property damage.
How to use this manual
This installation manual does not contain any system design documentation. System design documentation is available from any authorized ENERVEX representative. Accessories, fans, and variable frequency drives are not covered by this manual. Please refer to these component’s individual
manuals.
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
1. Use this unit in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed on the front of the manual.
2. Before servicing or cleaning the unit, switch off at service panel and lock service panel to prevent power from being switched on accidentally.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with applicable codes and standards.
4. Follow the appliance manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. This unit must be grounded.
2
Content
1. PRODUCT INFORMATION
1.1 Function ................................................................. 4
1.2 Shipping ................................................................ 4
1.3 Warranty ................................................................ 4
2. SPECIFICATIONS AND DIMENSIONS
2.1 Dimensions and Capacities .................................... 5
3. MECHANICAL INSTALLATION
3.1 Location................................................................. 6
3.2 Mounting of Control ............................................... 6
3.3 Mounting of Transducer ......................................... 7
3.4 Mounting of Duct Probe ......................................... 7
3.5 Connecting Transducer to Duct Probe ................... 7
4. ELECTRICAL INSTALLATION
4.1 General .................................................................. 8
4.2 Continuous Fan Operation ..................................... 9
4.3 Intermittent Fan Operation .......................................... 10
4.4 Connection to a Variable Frequency Drive ..................12
4.5 Integrated with External PDS ...................................... 13
5. STARTUP AND CONFIGURATION
5.1 General .................................................................. 14
5.2 Setting Operatuing Pressure .................................. 15
6. MAINTENANCE AND TROUBLESHOOTING
6.1 Troubleshooting ..................................................... 16
3916010 06.16
3
3916010 06.16
1. PRODUCT INFORMATION
1.1 FUNCTION
The ENERVEX MEC 18 is a Mechanical Exhaust Control used to monitor and maintain a constant pressure in a duct system. This is achieved by modulating the speed of a fan or ventilator. The MEC 18 can be used with ENERVEX Models EFH, RSV, BESB and BESF. It can control the fan speed directly or via a Variable Frequency Drive (VFD). It is a component in the MDVS, Mechanical Dryer Venting
TM
System
The MEC 18 is typically used to control the pressure in duct systems serving clothes dryers, bathrooms, kitchen hoods and other building venting applications. The control monitors the pressure in a duct system via connection
to a pressure sensor (XTP2) , and maintains the pressure by modulating the fan speed.
The control has an integrated safety system that assures the appliance shuts down in the event of fan and/or control failure.
The use of the MEC 18 is not restricted to any type of duct or venting application. When the appliance is activated, the control
sends maximum voltage to the fan or VFD. Once the specified pressure is achieved, the control regulates the voltage to the fan or VFD to manintain the specified pressure (the value can be viewed on the display).
If desired, the control can be interlocked with an appliance. When the appliance is activated, the control sends maximum voltage to
the fan or VFD. Once the specified pressure is achieved, the control releases the appliance for operation and continues to regulate the voltage to the fan or VFD to maintain the specified pressure (the value can be viewed in the display). In the event of insufficient pressure, the control assures the appliance(s) shuts down after 15 seconds. When the appliance shuts down, the control turns off the fan.
The control can be used in one of two ways:
• Interlocked with the appliance to pre-purge the duct prior to appliance start-up and post-purge the duct for 3 minutes after appliance shut down, or,
• Set to run the fan continuously.
In most cases, local codes will require continuous fan operation.
The control has an integrated safety function. It can be operated with a manual reset function (reset button) or an automatic reset function. All terminal connections are monitored by LED’s for easy service and troubleshooting.
ENERVEX’s MEC 18 is tested and listed to the Standard for Indus­trial Control Equipment, UL Standard 508, 16th Ed. and CSA C22.2 No. 14-95 as well as UL378, Standard for Pressure Equipment. It is also tested and listed as a part of an ETL listed MDVS System (ETL Report J99*18091-004) for exhausting of lint-laden air from single or multiple type I and type II residential and commercial clothes dryers whether electric or gas-fired.
and the MBES, Modulating Building Exhaust SystemTM.
1.2 SHIPPING
Standard packing list
The MEC 18 contains the following:
• MEC 18 control unit
• Pressure transducer (XTP)
• Silicone tubing
• Duct probe
• Jumpers If other components are shipped, these will appear as separate
items on the shipment packing list.
1.3 WARRANTY
2-Year Factory Warranty. Complete warranty conditions are available from ENERVEX, Inc.
4
2. SPECIFICATIONS
2.1 DIMENSIONS AND CAPACITIES
Specifications
MEC 18 Control
Power supply V 1x120VAC
Amperage A 6.3
Operating temperature °F/°C -4 to 122 / -20 to 50
Range of operation inWC / Pa 0-0.6 / 0-150
Tolerance inWC / Pa 0.01 / 3 +/-10%
Output Current mA max. 10
Max. Load 120 VAC / 8A
Real-time PID Control Method Infinitely variable
Real-time PID Signal Stability +/- 0.5%
Ramp Up/Down Time Seconds max 20
Output VAC 10-120
VDC 0-10
Dimensions A in / mm 7.17 / 182
B in / mm 7.09 / 180
C in / mm 4.37 / 111
Weight lbs/kg 3.0 / 1.5
EMC standard Emission EN50 081-1
Immunity EN50 082-2
XTP Sensor
Power supply VDC 12-36
Amperage mA <20
Output VDC 0-10
Operating temperature °F / °C 0 to 160 / -18 to 71
Accuracy +/- 0.08%
Dimensions D in / mm 3.70 / 94
E in / mm 5.12 / 130
F in / mm 6.18 / 157
G in / mm 3.13 / 80
Weight lbs / kg .6 / .3
Stack Probe
Dimensions H in / mm 4.25 / 108
I in / mm 3.50 / 89
3916010 06.16
MEC 18
FB
E
C
D
A
I
Symbols:
Fig. 1-A Fuse holder Fig. 1-B Alarm-red LED Fig. 1-C Reset button Fig. 1-D Set point button Fig. 1-E Potentiometer for pressure
setting Fig. 1-F Display Fig. 1-G LEDs (yellow) showing
increasing/decreasing speed Fig. 1-H Dipswitch block Fig. 1-I LEDs (green) showing ON/OFF
status
H
G
MEC 18
EXHAUST CONTROL
>
__
+24V
+24V
COM-0
COM
+24V-+
0-10V-
+0-10V
5
3916010 06.16
3. MECHANICAL INSTALLATION
3.1 LOCATION
The control and transducer must be installed indoors. The control does not need to be installed in an enclosure. See Fig. 2 for component connections.
The transducer cannot be mounted inside an airtight enclosure. It uses the atmoshpheric pressure as reference pressure.
XTP Sensor
3.2 MOUNTING OF CONTROL
The control can be mounted directly to a wall or similar. Remove the cover. The mounting holes are located under the plastic screws that hold the cover in place. See Fig. 3.
The distance between the control and the transducer should not exceed three hundred (300) feet.
Max. 300 feet
Fig. 2
Fig. 2a
MEC 18
EXHAUST CONTROL
Fig. 3
6