ENERVEX GSV 200, GSV 450, GSV 315, GSV 400, GSV 250 Installation & Operating Manual

ENERVEX GSV 200-450 GREASE FAN
3001391 12.16 Installation & Operating Manual
READ AND SAVE THESE INSTRUCTIONS!
ENERVEX Inc. 1685 Bluegrass Lakes Parkway Alpharetta, GA 30004 USA
3001391 12.16
!
The GSV 200-450 Grease Fan is ETL Listed in the U.S. and Canada.
Symbol Legend
The following terms are used throughout this manual to bring attention to the presence of potential hazards, or to important information concerning the product.
DANGER: Indicates an imminent hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING: Indicates an imminent hazardous situation which, if not avoided, may result in personal injury or property damage.
How to use this manual
This installation manual does not contain any system design documentation. System design documentation is available from any authorized ENERVEX representative. Accessories, fans, and variable frequency drives are not covered by this manual. Please refer to these component’s individual manuals.
TO REDUCE THE RISK OF FIRE, ELECTRICAL SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A CHIMNEY FIRE, OBSERVE THE FOLLOWING:
1. Immediately close all dampers and/or air entrance openings to the cooking appliance. This includes doors.
2. Alert your patrons to the possible danger.
3. Inspect your cooking appliance and chimney surroundings for possible fire. If in doubt, alert your fire department.
4. Do not continue to use your appliance until it and your chimney have been throroughly inspected. Overheating can cause metal parts to expand, buckle and crack. If you are not certain, have a certified chimney sweep disas­semble all parts so they can be inspected and cleaned.
5. Do not use salt or water on the fire in the cooking appli­ance. Salt is corrosive and water will cause a dangerous steam explosion. You might be able to control the fire by using ashes, sand or baking soda, since baking soda is an ingredient used for dry chemical fire extinguishers.
6. After a chimney fire, when it is safe to do so, check inter­nal locations such as an attic and under the roof and keep watching for two or three hours. There may be delayed smoldering and subsequent ignition, even if the fire inside the chimney has been controlled.
1. Use this unit in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the address or telephone number listed on the front of the manual.
2. Before servicing or cleaning the unit, switch off at service panel and lock service panel to prevent power from being switched on accidentally.
3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with applicable codes and standards.
4. Follow the appliance manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
5. This unit must be grounded.
TO REDUCE THE RISK OF A CHIMNEY FIRE:
1. Keep chimney and grease fan clean.
2. Always turn ON fan when using the cooking appliance.
3. Do not leave cooking appliance unattended when in use.
CAUTION
Please read specification label on product for further information and requirements.
2
Content
1. PRODUCT INFORMATION
1.1 Function ............................................................4
1.2 Components .....................................................4
1.3 Shipping ...........................................................5
1.4 Warranty ...........................................................5
2. SPECIFICATIONS AND DIMENSIONS
2.1 Dimensions and Capacities ...............................6
3. MECHANICAL INSTALLATION
3.1 Positioning ........................................................7
3.2 Installation on Steel Duct ...................................7
3.3 Installation on Roof Curb ...................................7
3.4 Installation on Venting System ...........................8
3.5 Installation on Side Wall ....................................8
3.6 High Temperature Applications ..........................8
4. ELECTRICAL INSTALLATION
4.1 Electrical Requirements .....................................9
4.2 Wiring Diagram for GSV 250-315 ...................... 9
4.3 Wiring Diagram for GSV 400-450 ...................... 10
4.4 Dual Voltage Wiring ...........................................11
5. STARTUP AND CONFIGURATION
5.1 Start-up ............................................................12
5.2 Adjusting the Fan Speed ...................................12
6. MAINTENANCE AND TROUBLESHOOTING
6.1 Maintenance Intervals .......................................13
6.2 Cleaning ...........................................................13
6.3 Spare Parts Ordering ........................................14
3001391 12.16
3
3001391 12.16
1. PRODUCT INFORMATION
1.1 FUNCTION
ENERVEX Model GSV Grease Fan is designed to provide a large exhaust volume at a high discharge velocity. It is intended for use as a part of a restaurant kitchen exhaust system and grease applications according to NFPA 96.The use of the ENERVEX Grease Fan is not restricted to any type of chimney or grease duct. However, always follow the exhaust-hood manufacturer’s instructions regarding the venting.
The fan housing is made of heavy cast aluminum and can be opened for easy cleaning. The impeller is of the backward inclined type. It is made of cast aluminum and has permanently attached balancing weights.
The motor is a direct-drive, variable speed, class H insulated, high temperature motor. It has permanently lubricated and sealed ball bearings and is maintenance free.
Installations must conform to the requirements of the authority having jurisdiction. Where required by the authority having jurisdiction, the installation must also conform to the NFPA 96. All electrical wiring must be in accordance with the requirements of authority having jurisdiction or, in absence of such requirements, with the National Electrical Code, NFPA
70.
ENERVEX Model GSV is tested and listed to UL Standard 705 for Power Ventilators and UL Standard 762 for Power Ventilators for Restaurant Exhaust Ventilators.
The model is also tested and listed to ULC-S645-93, Standard for Power Roof Ventilators for Commercial and Institutional Kitchen Exhaust Systems.
1.2 COMPONENTS
The GSV Grease Fan consists of the following components
a. Top section b. Bottom section c. Motor d. Centrifugal Impeller e. Inlet for impeller f. Locking hinge g. Bird screen h. Carrying handle h. Wiring conduit
Max. 575°F (300°C)
Fig 1
4
1.3 SHIPPING
!
The fan is shipped in a corrugated cardboard box. If a transport securing device is attached (GSV 400 and GSV 450 only) to the bottom of the fan to hold the motor and impeller in place, do not remove it when unpacking the fan.
Do not remove the transport securing device until the fan is being installed on the duct or the roof curb. The motor shaft could be damaged.
NOTE: All single phase fans are shipped with a capacitor and junction box connected via conduit. The capacitor is located INSIDE the junction box. Please do not discard.
1.4 WARRANTY
2-Year Factory Warranty. Complete warranty conditions are available from ENERVEX, Inc.