This document is intended for everyone involved
in installation of Enervent ventilation units. The
equipment described in this manual must be installed
by skilled persons only, according to the instructions
given in this manual and local law and regulations.
Failure to comply with instructions in this manual voids
the warranty of the equipment, and possibly results in
harm to people or property.
The equipment described in this manual must not be
used by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been
given supervision or instruction concerning use of the
equipment by a person responsible for their safety.
Tables at the end of this manual list:
• Ventilation units introduced in this document
• Components included in the delivery.
NOTE: If your delivery does not include all
the components listed in the Models and
components table at the end of this manual,
check your order and contact your seller or
Enervent before starting installation.
The type plate is located near the main power switch or
inside the ventilation unit. Before you start reading,
check the type of the unit from the plate.
ilmanvaihtolaite
ventilation unit
TYYPPI/TYPE:
W/ V/ HZ / A:
SRJ. NRO/SERIAL NO:
www.enervent.com
IP 20
Type designation
The type designation contains three parts:
1. The rst part of the type designation indicates the
chassis of the ventilation unit, for instance LTR-3, or
Pandion.
2. The next letters indicate the type of automation
that the ventilation unit is equipped with, in this
case eWind.
3. The next letter of the type designation indicates
the type of supply air heater that the ventilation
unit is equipped with, E= electrical, W= water.
4. The next letters if any, indicate the type of preheater/pre-cooler or supply air cooler, CHG=
Cooling Heating Geo, CG=Cooling Geo.
Example: Pandion eWind-E-CHG.
6
SAFETY
General
DANGER: Before opening the service hatch,
always make sure that the unit’s supply voltage
is switched o.
WARNING: In case of malfunction, always nd
out the cause for it before restarting the unit.
WARNING: After switching o the unit
power, wait two (2) minutes before starting
maintenance work. Even though the power is
switched o, the fans continue spinning and the
after-heater coil remains hot for some time.
DANGER
WARNING
WARNING
Electrical
DANGER: Only a qualied electrician may
open the electrical box.
DANGER: Follow the local regulations for
electrical installations.
CAUTION: Make sure that the unit is fully
detached from the electrical network before
carrying out voltage tests, insulation resistance
measuring or other electrical work or measuring.
This kind of work can cause damage to sensitive
electronic equipment.
EN
DANGER
DANGER
CAUTION
CAUTION
CAUTION: All ventilation units that come with
a water coil must be equipped with dampers to
avoid freezing of the coil during possible power
failure.
CAUTION
CAUTION: Control equipment used in
ventilation units can cause leakage current.
This can aect the functionality of fault current
protection.
CAUTION
CAUTION: All ventilation units with a control
system must be equipped with over voltage
protection.
7Installation instructions
TERMINOLOGY
TermExplanation
CG (Cooling Geo) is cooling of the supply air using brine, which circulates in pipes under ground.
CG, CHG, AGH
after-heatingAfter-heating warms the supply air after the heat recovery wheel. It ensures that the incoming
click modelsNew ceiling installation method for models Pingvin and Pandion.
eWindControl panel for managing the ventilation unit.
exhaust air (waste air)Air removed from house after-heat recovery.
extract airOutbound air ow from rooms.
ModbusCommunication protocol that is used here for communication between ventilation unit and home
outside airOutside air supply to ventilation unit.
supply airInbound air ow to rooms.
%RHRelative humidity percent that is used here for determining whether ventilation should be
active coolingCooling created by a cooling unit included in some ventilation units.
cool recoveryIn the summer the rotating heat recovery wheel can cool the supply air, if the extract air is cooler
CHG (Cooling Heating Geo) is cooling or pre-heating using brine, which circulates in pipes under
ground.
AGH (Air Ground Heat exchanger) is cooling or pre-heating using air, which ows in ducts under
ground.
air is not too cold. After-heating can be realized with either an electrical or water coil. Suitable
temperature for the incoming air is 5°C less than the room temperature if no extra heating of the
room is desired.
automation systems (+ possible accessories).
boosted to remove excessive humidity.
than the outside air. The function is automatic.
8
BEFORE INSTALLATION
Selecting installation location
Before you start installing the ventilation unit, make
sure that the installation location is suitable for the
model you are installing.
Pinion, Pingvin, Pingvin XL, Pandion,
Pelican, Pegasos and Pegasos XL
Installation location:
• Make sure that you install re shuto valves if the
unit is placed in a separate re area.
• Install wall mounted units on a partition wall rather
than on an exterior wall.
• Consider the unit maintenance tasks when
installing the unit.
• Doors of the unit must be fully opened for
maintenance work.
• Leave minimum 15 mm space surrounding the
ventilation unit to the sides. Otherwise, the
service doors cannot be fully opened.
• Consider the space needed for duct coils (if
included).
EN
UnitInstalling location
Pinion, Pingvin, Pingvin
XL and Pandion
Pinion, Pingvin, Pingvin
XL and Pandion
Pandion, Pelican,
Pegasos and Pegasos XL
On the wall.
Hanging from the ceiling.
• Requires ceiling installation
plate, (sold as accessory).
On the oor
• On a suitable at plane.
Installation space:
UnitInstallation space
Pinion, Pingvin, Pingvin
XL, Pandion, Pelican,
Pegasos and Pegasos XL
Warm space (over +5°C).
• We recommend the unit is installed in a technical
space.
• Do not install the unit in spaces with high
temperature and high humidity level.
• In certain conditions these can cause
condensation on the unit’s outer shell.
• Consider the unit noise level when choosing the
installation location.
• If possible, install the unit on a soundproof
wall.
• Do not install the ventilation unit directly
outside a bedroom, since even though the
ventilation unit is quiet, it is never completely
silent.
• Install an insulating plate at the back of the
ventilation unit, or otherwise try to prevent
structure borne noise.
• Soft, foamed plastic sheets are recommended
for this (not included in the delivery).
• Make sure that it is possible to connect the
condensate water drain and water lock.
• Consider the space needed for the condensate
water connection.
LTR-2, LTR-3, LTR-4, LTR-6, LTR-7 and
LTR-7 XL
Installation location:
UnitInstalling location
All LTR-2, LTR-3 and
LTR-4
Standard LTR-6, LTR-7
units and LTR-7 XL
LTR-4, LTR-6, LTR-7
and LTR-7 XL
ventilation units
equipped with built in
cooling coil
Installation space:
UnitInstallation space
LTR-2, LTR-3, LTR-4,
LTR-6, LTR-7 and
LTR-7 XL
CAUTION: Do not install any LTR units so that
the maintenance hatch is facing downwards or
so that the unit is standing upright. Always make
sure that one of the condensate water drain is
downwards.
In two positions:
• Maintenance hatch up.
• Maintenance hatch on the side.
Maintenance hatch up.
• On request, units can be made
for installation with the hatch
on the side. This must be
mentioned when the unit is
ordered.
We recommend to order with the
maintenance hatch to the side.
• This will enable the
condensation formed in the
cooling coil to drain more easily.
Either warm or cold space.
• For example in a storage space
or attic.
CAUTION
9Installation instructions
• Consult the ventilation planner regarding possible
need for additional insulation of the unit if
mounted in a cold space.
• If you use solid (hard) insulation, make sure
that the insulation does not carry sound to the
frame of the house.
• Do not install the unit in spaces with high
temperature and high humidity level.
• In certain conditions these can cause
condensation on the unit’s outer shell.
• Consider the unit noise level when choosing the
installation location.
• Do not install the ventilation unit directly
outside a bedroom, since even though the
ventilation unit is quiet, it is never completely
silent.
• Set the unit on top of a soundproong 100 mm
insulation.
• Make sure that it is possible to connect the
condensate water drain and water lock.
• Consider the space needed for the condensate
water connection.
• Make sure that you install re shuto valves if the
unit is placed in a separate re area.
• Consider the unit maintenance tasks when
installing the unit.
• Make sure that there is enough space in front
of or above the maintenance hatch:
UnitFree space in front of the hatch
LTR-2 and LTR-3min. 50 cm
LTR-4 and LTR-6min. 60 cm
LTR-7 and LTR-7 XL min. 70 cm
• Make sure that the electrical connections can be
easily accessed.
• Take into account the space needed for opening
the maintenance hatch locking latches.
• Consider the space needed for duct coils (if
included).
BUILDING THE VENTILATION
SYSTEM
Designing the ventilation system must be done by a
professional ventilation designer. By following closely
the design plan when building the ventilation system,
you ensure the operation of the whole ventilation
system and customer satisfaction. Use the Enervent
Energy Optimizer calculation program at the Enervent
home page to calculate the performance and estimated
heating/cooling power of a particular ventilation unit.
• Use type-approved factory made materials when
building the ventilation system.
• Use valves that are suitable for mechanical
ventilation.
• Do not cover the outside air grating with mosquito
net.
• This would make it very dicult to keep clean.
• Prevent rain water and snow from entering the
outside air and exhaust air duct.
• Install enough inspection hatches in the
ventilation network to enable cleaning of the
ventilation ducts.
• To make it easier to nd the inspection
hatches, mark their location for example on
the rafters.
• Ventilation systems for dierent re areas must be
separate.
• For example garage is one re area whereas
living quarters are another re area, which
means that they cannot be connected to the
same ventilation system.
• Use an extractor hood with its own fan, above the
stove.
• The extractor hood must have its own extract
duct directly out.
• A motorless extractor hood can be connected
to the ventilation unit only if the ventilation
unit has an extractor hood connection.
• The extractor hood used must be equipped
with a grease lter and a timer controlled ap
that prevents any airow through the extractor
hood when not in use.
• A drying cabinet with its own fan can be indirectly
connected to the outlet valve using the connection
system of the drying cabinet.
• A part of the extract air is taken from the living
space and a part from the drying cabinet.
• The extract air must ow through the valve at
a speed of 12 litres / second minimum.
• Install silencers at least in the supply and extract
ducts.
10
• The amount of silencers must be considered
case by case.
• We recommend that automatically closing
dampers are installed in outside and exhaust air
ducts.
• In case of a power failure, the dampers will
close and block out cold air, preventing any
water coil from freezing.
• If cold air gets into ventilation ducts, it will
create condensate when mixing with warm air.
NOTE: The ventilation ducts must be blanked
o until the ventilation system is taken into use.
This is in order to keep warm air from owing
into the duct. Warm air causes condensation if
it meets cold outside air or surfaces in the duct.
Furthermore the plugging keeps dirt and other
unwanted particles from clogging the system.
Ventilation duct insulation
examples
EN
NOTE: Sound insulation is not taken into
account in these insulation instructions and
examples.
NOTE: Semi-warm space = +5°C - +15°C. A
semi-warm space refers also to dropped ceilings,
sub-oors, and casings.
Outside air duct (fresh air duct)
Cold spaces
Insulating ventilation ducts
Insulate the ventilation ducts appropriately. This is
especially important when the ventilation unit comes
with a cooling functionality.
Ventilation ducts must be thermally insulated to
prevent water from condensing to the inner or external
duct surfaces in any circumstances. Additionally, the air
temperature must not decrease or increase excessively
in the ducts because of external factors. The ventilation
engineer calculates the insulation requirements
depending on the placement of the ducts and the air
temperatures.
Ventilation duct thermal insulation in heating use
Supply air duct from
the ventilation unit to
the supply valve.
Extract air duct from
the extract valve to
the ventilation unit.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C.
• 100 mm of sheet, mat, or pipe-covering insulation
(plus the blown wool, when used).
Warm/semi-warm spaces, dropped ceilings, suboors, and casings
• Option 1
• 80 mm insulation with vapour-proof external
surface.
• Option 2
• 20 mm of cellular rubber insulation on the
duct surface and 50 mm insulation with
vapour-proof external surface.
The insulation must prevent water vapour from
condensing to the external duct surface and excessive
air temperature rise during summer.
Supply air duct
Cold/semi-warm spaces and also by dropped
ceilings, sub-oors, and casings:
Ventilation duct thermal insulation in cooling use
Supply air duct from
the ventilation unit
to the supply valve.
Extract air duct from
the extract valve to
the ventilation unit.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C. At least
19mm of cellular rubber insulation
on the duct surface.
The insulation must be designed
and implemented so that the
maximum air temperature change
in the duct is less than 1°C.
• In standard ventilation the insulation must be
designed and implemented so that the maximum
air temperature change in the duct is less than 1°C.
• For example, 100 mm of sheet, mat, or pipecovering insulation can be used (plus the blown
wool, when used).
Warm spaces
• Insulation is not required in standard ventilation.
In heating and cooling use see tables "Ventilation duct
thermal insulation in heating use" on page 11 and
"Ventilation duct thermal insulation in cooling use" on
page 11.
11Installation instructions
Extract air duct
Warm spaces
• Insulation is not required in standard ventilation.
Ventilation unit models equipped with duct coils for
after-heating or cooling (see table "Models with duct
coils" on page 36).
• These coils are installed in the supply air duct (after
the ventilation unit).
Cold/semi-warm spaces
• In standard ventilation the insulation must be
designed and implemented so that the maximum
air temperature change in the duct is less than 1°C.
• For example, 100 mm of sheet, mat, or pipe-
covering insulation can be used (plus the
blown wool, when used).
In heating and cooling use see tables "Ventilation duct
thermal insulation in heating use" on page 11 and
"Ventilation duct thermal insulation in cooling use" on
page 11.
Exhaust air duct
Cold spaces
• 100 mm of sheet, mat, or pipe-covering insulation.
Warm/semi-warm spaces
• Option 1
• 80 mm insulation with vapour proof external
surface.
• Option 2
• 20 mm of cellular rubber insulation on the
duct surface and 50 mm insulation with
vapour proof external surface.
The insulation must prevent water vapour from
condensing to the external and internal duct surfaces.
Extractor hood duct
• The extractor hood duct must be insulated and
constructed in accordance with local building and
re safety regulations.
Installing duct coils
Duct coils are used in several unit models both as preheaters, after-heaters and coolers. For information what
type of coils are used with your ventilation unit model,
refer to tables listing models with duct coils at the end
of this manual. For correct mounting of duct coils, refer
to the principal diagrams at the end of this manual.
Ventilation unit models equipped with pre-heating/precooling coils (see table "Pre-heating and pre-cooling
coils" on page 37).
• These coils are installed in the outside air duct
(before the ventilation unit).
• Duct coils must be accommodated in the
ventilation ducts.
• There must also be sucient room for
maintenance and draining of condensate water.
NOTE: For more technical details about the
coils, see the technical data table at the end of
this manual.
Duct coil for uids
When installing duct coils:
• Place the duct coil in the supply air duct after the
ventilation unit or in the outside air duct before
the ventilation unit depending on its function.
• Make sure that there is a lter before pre-heater
coils in the outside air duct to prevent dirt from
entering the coil.
• Do not install the coil too close to a fan outlet or a
bend in the ducting.
• This can result in lower eciency.
• Connect the coil so that the system is easy to
empty for maintenance.
• Install duct heaters in a horizontal or a vertical duct
with optional direction of airow.
• To facilitate venting of the coil, the unit
must be tted with the longitudinal tubes
horizontal.
• Install duct coolers in a horizontal duct with airow
in the direction of the arrow.
• Insulate the cooler externally to prevent the
formation of condensation.
• Connect the cooler to a condensate drain
and water trap and tilt it at an angle of 10-15
degrees to the horizontal in the direction of
the drain.
• Insert the coil into standard spiral ducting and
attach it to the ducting with screws.
• Support the weight of the coil.
• Connect the coil with clamping ring
connectors.
12
• Connect the water inlet to the lowest pipe
connector in order to facilitate venting of the coil.
• Consult the principal drawings at the end of
this manual on how to construct the hydronic
circulating system.
• Install a venting valve near the coil or at the
highest point in the system.
• Inspect the duct coil and its connections for leaks
immediately after the system has been lled with
liquid.
• Place the supply air temperature sensor (TE10) in
the duct after the coil.
• Place the water coil return water sensor (TE45)
on the return water pipe of the coil, if the coil is
mounted in the supply air duct.
• Place the outside air temperature sensor (TE01)
in the outside air duct before the coil, if the coil is
mounted in the outside air duct.
• Connect the sensor to the ventilation unit control
circuit board.
• Refer to the electrical schematics at the end of this
manual for correct connections.
Electrical duct coils
NOTE: The heater is designed for insertion
into standard spiral ducting and is xed to the
ducting with screws.
• The distance from (to) the heater to (from) a duct
bend, valve, lter, etc., must be at least twice the
duct diameter.
• Otherwise there is a risk that the airow
through the heater will be uneven which can
cause activation of the overheating cut-out.
• Insulate the duct heater in accordance with local
regulations for ventilation ducting.
• Make sure that the insulation is incombustible.
• Do not cover the lid with insulation, since the
rating plate must be visible and the lid must
be removable.
• Do not cover any heatsinks, nor the side of the
connection box where the SCR’s (Triac’s) are
mounted with insulation.
• The duct heater must be accessible for
replacement and inspection.
• Make sure that the distance from the heater metal
casing to any wood or other combustible material
is at least 30 mm.
• Install the duct sensor TE10 (delivered with the
heater) in the duct after the heater, if the heater is
mounted in the supply air duct.
• If the heater is mounted in the outside air duct,
install the temperature sensor (TE01) before
the heater in the outside air duct and connect
the sensor(s) to the ESC control circuit board.
NOTE: We recommend installing a safety switch
for the electric heater.
EN
NOTE: The air must ow through the heater in
the direction indicated by the arrow on the side
of the connection box.
To install:
• Install the heater in either horizontal or vertical
ducting.
• The heater must only be tted in ducts that
are made of incombustible and heat-and-cold
resistant material.
• The connection box can be freely placed
facing upwards or sideways to a maximum
angle of 90°.
CAUTION
CAUTION: Do not install the connection box
facing downwards.
Installing ventilation unit ceiling
installation plate (OPTIONAL)
NOTE: Ceiling installation plate is separately
sold extra equipment available for ventilation
unit models Pinion, Pingvin, Pingvin XL and
Pandion.
Before installation:
• Make sure that the ceiling is even so that the plate
will be stable and straight when installed.
• The gap between the plate and the back wall must
be at least 10 mm (recommendation) and at least
15 mm between the plate and the side walls.
• The ceiling installation plate top surface must
not be more than 15 mm above the ceiling inner
height.
• Otherwise you will not be able to hook
the ventilation unit front on to the ceiling
installation plate.
13Installation instructions
To install:
To install:
1. Prepare the holes in the ceiling for the ventilation
ducts.
2. Attach the plate on the ceiling using screws that
are suitable for the ceiling material.
3. Seal the ceiling installation plate against the
ceiling’s vapor barrier using for example duct tape.
4. Attach the ducts to the ceiling installation plate
with rivets.
• Make sure that there are no gaps between the
insulation and the ducts.
• Consider the unit’s weight when screwing the
plate to the ceiling.
• The ceiling installation plate must be
absolutely rigid.
• Weights for all units are found in the technical
table in the end of this manual.
Installing geo-cooling equipment
If a geothermal heat pump is in use, the cold brine in
the ground loop can be used in the summertime to
cool the incoming air.
The system can be implemented in two ways:
• In a standard delivery, a separate pump is used
(Option 1).
• Alternatively, the brine is circulated through the
geothermal pump (Option 2).
1. Install the cooling coil in the supply air duct (in
case of a duct coil).
2. Connect the condense water outlet.
3. Build a separate pump group with valve and
actuator for circulating cool brine adjacent to the
ventilation unit cooling coil.
4. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
• Follow the principal chart at the end of this
manual.
NOTE: The valve and actuator must be in the
same position when connected. When the valve
is in the open position, the actuator is turned
counter-clockwise before connecting, and
when the valve is closed, the actuator is turned
clockwise before connecting. Figure 1 on page
15 shows the valve and markings on valve
spindle in valve open (cooling/heating on max)
position.
5. Prepare / connect wiring between the ventilation
unit, the geothermal pump and the actuator, as
shown in the connection diagram at the end of
this manual.
Option 2
A geothermal heat pump is used for circulating brine
also in the supply air coil.
The cooling coil can be either built in the ventilation
unit or it can be a duct coil, depending on the model.
A duct coil is mounted in the supply air duct after the
ventilation device.
Detailed principal charts are found at the end of this
manual.
Option 1 (standard)
A separate pump is used for circulating brine in the
supply air coil.
The delivery includes:
• A relay for starting up the circulation pump for the
ventilation unit’s cooling coil.
• The relay is situated on the unit motherboard
connection DO8.
• A 3-way control valve (Belimo R3) needed for
cooling.
• An actuator (Belimo TR24-SR).
The temperature is controlled using the ventilation
unit’s own automatic control. The ventilation unit
controls the circulation pump and the 3-way valve.The
heat pump is not started up for ventilation cooling.
The delivery includes:
• A relay for starting up the brine pump.
• The relay is situated on the unit motherboard
connection DO8.
• A 3-way control valve (Termomix D32S) needed for
cooling.
• An actuator (Belimo NRYD24-SR-W + installation
set MS-NRE).
The temperature is controlled using the ventilation
unit’s own automatic control. The ventilation unit
controls the geothermal heat pump and the 3-way
valve.
To install:
1. Install the cooling coil horizontally in the supply air
duct (in case of a duct coil).
2. Isolate a separate loop for the cooling coil.
• Make sure to include the one-way valve.
• Follow the principal chart at the end of this
manual.
3. Connect the condense water outlet.
4. Install the 3-way valve and the actuator in the
ground collector’s piping.
14
• The actuator controls the brine ow to the
cooling coil as needed.
5. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
• For example in Helsinki, the brine must still
be functional at -26°C whereas in Lapland the
temperature value is -38°C.
It is also possible to use earth to air heat exchangers
(earth tubes) for pre-heating or pre-cooling. The earth
tube must be combined with a normal outside air
duct and a damper that switches the outside air ow
between the earth tube and the normal outside air
duct depending on the actual need for pre-cooling and
pre-heating. The damper can be controlled from the
same relay that controls the circulation pump for the
hydronic pre-cooler / heater.
The CHG pre-heating / pre-cooling system can be built
as a separate system (option 1) or as a part of the geothermal heat system (option 2).
Detailed principal charts are found at the end of this
manual.
Option 1
A ground loop is built for the pre-heating / cooling
coil. To avoid freezing of the system, brine in the
loop must meet the local rated temperature value.
The ventilation unit automatic control regulates the
system’s temperature. The ventilation unit controls the
circulation pump and the 3-way valve.
EN
Figure 1. Valve and actuator open counter-clockwise and
close clockwise. The gure shows the valve and actuator
in the fully open position. Also, shown is the allowed direction of the liquid ow.
NOTE: The valve and actuator must be in the
same position when connected. When the valve
is in the open position, the actuator is turned
counter-clockwise before connecting, and
when the valve is closed, the actuator is turned
clockwise before connecting. Figure 1 above
shows the valve and markings on valve spindle
in valve open (cooling/heating on max) position.
6. Prepare / connect the wiring between the
ventilation unit, the geothermal pump and the
actuator.
A geothermal pre-heating / pre-cooling coil for
improving the system energy eciency can be installed
in the ventilation system. A duct coil is always used
when a hydronic pre-heating coil is needed. The coil is
installed in the outdoor air duct before the ventilation
unit. The duct or the coil must have a lter to keep dirt
out of the coil.
To avoid freezing the coil, the brine used in the coil
system must meet the local rated temperature value.
To install:
1. Install the cooling / heating coil in the outside air
duct.
2. Connect the condense water outlet.
3. Build a separate pump group for circulating cool
brine adjacent to the ventilation unit cooling /
heating coil.
4. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
5. Prepare / connect wiring between the ventilation
unit, the circulation pump and the actuator.
6. Install and connect the outside air temperature
sensor (TE01) in the outside air duct before the
duct coil.
• Refer to the electrical connection diagrams at
the end of this manual.
Option 2
A separate loop is isolated from the geothermal pump
brine loop for the cooling coil. To avoid freezing the coil,
brine in the loop must meet the local rated temperature
value. In addition to this, a heat exchanger is installed
in the coil system to ensure the functionality of the
geothermal pump. For the pre-heating / pre-cooling
coil to yield any benets there must be some ow in the
collector of the geothermal pump.
15Installation instructions
Temperature is controlled using the ventilation unit’s
own automatic control. The ventilation unit controls the
circulation pump and the 3-way valve.
To install:
4. Isolate the pipes carefully with vapour proof
insulation to prevent condensation on the outside
of the pipes in warm and semi-warm spaces.
5. Install a heat exchanger in the coil system.
6. Install and connect the outside air temperature
1. Install the cooling coil in the outside air duct.
2. Connect the condense water outlet.
3. Build a separate pump group for circulating cool
brine adjacent to the ventilation unit cooling coil.
sensor (TE01) in the outside air duct before the
duct coil.
7. Prepare / connect wiring between the ventilation
unit, the geothermal pump and the actuator.
Refer to the electrical connection diagrams at the
end of this manual.
The functions and accessories listed in the following table may need external wiring or connecting to function:
eWind external connections
Connection/Functionality
AI NTC
TE01 Outside air temperatureTE013.3VDCQuick connector 5m
TE10 Supply air temperatureTE103.3VDCQuick connector 5m
TE45/TE46 Heating/cooling coil
return water temperature
Digital outputs DOPotential free contact
ON/OFF Control for heatingDO2Max 250VAC/50VDC
ON/OFF Control for dampersDO5Max 250VAC/50VDC
A alarm output (NO) (Default)
ON/OFF Control for preheating (CHG/AGH or electrical
pre-heater)
ON/OFF Control for cooling (CG)
Analog inputs AI
%RH or CO2 external transmitter AI1 (user
Analog Outputs AO
Control voltage for heating AO50-10VDC 10mAKLM 2x0.8Yes, if hydronic heating
Control voltage for pre-heater /
Control voltage for cooling
(CHG/CG)
Digital inputs DIPotential free NO
Emergency stopDI1 (xed)24VDCKLM 2x0.8Yes
Manual boost modeDI4 24VDCKLM 2x0.8Yes
Away modeDI5 24VDCKLM 2x0.8Yes
Overpressure modeDI6 24VDCKLM 2x0.8Yes
Miscellaneous connections
Operating panel connectorsOP1, OP210m cable supplied with
Modbus-RTUX26Instrumentation cable
Location
on eWind
controller card
TE453.3VDCQuick connector 5m
DO8Max 250VAC/50VDC
congurable)
AO60-10VDC 10mAKLM 2x0.8Yes, except built in
Voltage/currentCable (example)Wiring outside AHU
cable supplied with AHU
cable supplied with AHU
cable supplied with AHU
MMJ 3x1.5Yes, if hydronic heating
8A/2A inductive load
MMJ 3x1.5Yes
8A/2A inductive load
MMJ 3x1.5Yes, except built in pre-
8A/2A inductive load
0-10VDCKLM 4x0.8Yes
contact
AHU
2x2x0.5
Yes, if pre-heater/
preecooler (CHG/
AGH) or electrical duct
mounted pre-heater
Yes, if duct heater/
cooler coil
Yes, if duct heater/
cooling coil (W/E-CG)
(W)
heater coil
(W)
pre-heater
Yes
Yes
16
ELECTRICAL CONNECTIONS
DANGER
DANGER: Only an authorized electrician
is allowed to perform electrical work on the
ventilation units.
Refer to the electrical drawings at the end of this
manual.
Preparing for electrical
installations
Before you start the installation, make sure that:
• Appropriate power supply is available for the
ventilation unit.
• At least 30 mA fault current protection is installed.
• Because of this, no other electrical appliances
should be plugged into the same outlet.
• There is appropriate cabling between the unit and
the control panel wall mount.
• The cable must run inside a protective conduit
of at least Ø 20 mm.
• The cable included in the basic delivery is
10m. Optionally a 30 m cable is available.
• The cable heads are type RJ4P4C.
eWind card connections
eWind card connections
NTC sensors
InputUse
TE01Outdoor temperature measuring TE01.
TE05Supply air temperature after-heat recovery TE05.
TE10Supply air temperature TE10
TE32Exhaust air temperature TE32
TE02Pre-heated outside air temperature TE02 (CHG/
AGH)
TE45Return water temperature TE45 (W)
Return water temperature TE46 Option (CG).
Analog inputs AI 0-10V
Analog input AI1 for voltage range 0-10V
Functionality of this input is decided by user. (Parameter
c27)
InputUse
AI1 External CO2 or %RH transmitter
Analog inputs AI7 - AI8 for voltage range 0-5V
Functionality of these inputs are locked by software.
AI7 Extract air humidity RH30
AI8 Extract air temperature TE30
eWind card connections
Analog Outputs AO 0 - 10V
Output Use
AO1Control voltage for supply fan
AO2 Control voltage for extract fan
AO4 Control voltage for HRW
AO5 Control voltage for heating
AO6 Control voltage for electrical pre-heater. Control
Digital outputs DO relays, potential free normally open
contacts.
Output Use
DO2ON/OFF Control for heating
DO5ON/OFF Control for dampers
DO8A/AB alarm output NO (Default)
Digital inputs DI (buttons and indications).
Connection to GND only! No voltage allowed to be
connected to digital inputs.
InputUse
DI1Emergency stop
DI2 External electrical after-heater or pre-heater alarm
DI4 Manual boost
DI5 Away mode. Away mode is active as long as the
DI6Fireplace/extractor hood mode. The replace
DI11 Supply fan tacho input
DI12 Extract fan tacho input
Miscellaneous connections
OP1,
OP2
X26ModBus RTU
24VDC+24VDC
GNDGND
voltage for (CHG). Control voltage for cooler (CG)
ON/OFF control for pre-heating (optional)
ON/OFF control for cooling (CG/CHG/AGH)
(optional)
input is grounded.
switch is a momentary push-button switch.
Fireplace mode is active 10 minutes from when
input is grounded. If connected to a changeover
switch, the circuit must be cut for the mode to
reactivate. The extractor hood mode is active
as long as the input is grounded. The selection
between replace mode or extractor hood mode
is done in parameter c12.
Operating panel connections for eWind
EN
17Installation instructions
External sensors
Installing eWind control panel
It is possible that external sensors must be installed
depending on model of ventilation unit.
• The sensor element for duct mounted
temperature, RH and CO2 sensors must be
installed inside the duct.
• Most temperature sensors are supplied with a
readymade 5m long cable.
• RH and CO2 sensors need wiring on site.
To install:
1. Choose the place for the sensor according to the
unit of measurement that is to be measured.
Refer to the control diagram at the end of this
manual.
2. Place the sensor in the duct at a straight segment,
at least 2x the duct Ø before and after any duct
coil, bends or ttings.
3. Drill a suitable hole for the sensor and a rubber
grommet in the duct.
4. Push sensors attached to a cable trough the
rubber grommet so that the sensor element is a
few centimetres inside the duct.
The rubber grommet must be air tight, and tight
enough that the sensor cable cannot slip through
by itself.
• You can use a cable tie to lock the sensor in
place.
5. Install sensors with rigid pipe type sensor elements
through an adjustable ange mounted to the duct.
• Push the sensor element through the ange
and lock in place with a screw at suitable
depth.
• Conduct electrical connections according to
the electrical schematics at the end of this
manual.
• The functions and accessories listed in the
table "eWind external connections" on page
16 may need external wiring or connecting
to function:
• Make sure the cable grommets in the duct and
ventilation unit are absolutely air and water
tight. If in doubt, use an elastic sealer to seal
the grommets.
6. To select a CO2 sensor active the CO2 boosting
function must be selected "on" from parameter
c27.
For more information on electrical connections, see
the control and connection diagrams at the end of this
manual.
The eWind control panel (see chapter "Control system,
eWind operating panel" on page 26) is installed
in a wall mounted recessed junction box, or using
the supplied surface mounted junction box. One
ventilation unit can be controlled with the maximum of
2 panels.
Installing one control panel
To install:
1. Install the connection cable supplied with the unit.
2. Attach the connection cable to the connector on
the eWind control panel.
3. Install the eWind control panel to the wall junction
box.
4. Attach the connection cable to connector OP1 of
the eWind controller card.
• Make sure the cable grommets in the ventilation
unit are absolutely air and water tight.
• If in doubt, use an elastic sealer to seal the
grommets.
Installing two control panels
If the ventilation unit is controlled with two control
panels, each panel is attached to the eWind controller
card with its own cable.
To install:
1. Install the eWind control panels as instructed
above. Attach the connection cable of the rst
eWind panel to connector OP1 and cable of the
second eWind control panel to connector OP2 of
the eWind controller card.
2. Remove jumper J1 from the eWind controller card.
Installing with Modbus
The ventilation unit can also be controlled via Modbus
connector X26.
Specication of Modbus:
• Modbus address 1 (default)
• Communication standard RS485
• Modbus trac via Modbus connector X26 of
controller card
• Speed 9600, 19200 or 115200 bps
• 8 bit
• No parity or parity.
18
The order of Freeway connector’s pins is marked on the
controller card.
Additional installation materials
Modbus registers are available on Enervent webpage
www.enervent.
CAUTION
CAUTION: Do not connect the external bus to
the motherboard before the bus is programmed
and compatible with the unit control.
INSTALLATION
NOTE: Before you install the ventilation unit,
make sure that there are no foreign objects in
the ventilation unit and duct system.
• Refer to the model-specic dimensional drawings
in the back of this manual for your specic
ventilation unit type.
• Inspect the order of duct connections to avoid
cross connections.
• Do not start the ventilation unit when it is installed
until the building is taken into use.
• If the ventilation unit is started too early, the
ventilation system can be contaminated by
building dust.
• Make sure that the ventilation unit duct
connections are the same size as the duct.
• Use a circular duct tting to connect the unit
to the duct.
• Insulate the duct all the way to the unit casing.
MaterialDescription of use
ScrewsFor hanging the rear attachment
Sheet metal screwsFor attaching the rear attachment
Wall mounting boxFor installing eWind operating
CablesAs specied in chapter "Preparing
Duct tapeFor sealing.
Insulation sheets (soft foamed
plastic)
Insulation material (foamed
plastic and/ or wool,
depending on where the unit
will be installed)
RivetsFor attaching the ventilation
Spirit levelFor making sure that the unit is
Water pipeFor connecting duct coils and for
Water trapFor condensate water drain.
Reducing ttings for duct
connections
DampersTo keep cold air out.
SilencersTo reduce possible noise.
Suitable grommets for duct
mounted sensors
Shut-o valvesTo facilitate servicing of unit.
Hydronic balancing valvesTo properly adjust the water ow.
bracket and ventilation unit on
the wall (if applicable). Select
the screws according to the wall
material.
bracket onto the ventilation unit.
panel.
for electrical installations" on
page 17.
For preventing structure-borne
noise.
For retaining heat and coolness.
ducts onto the unit.
level.
disposing of condensate water.
For tting the ducts in the
ventilation system. NOTE: Always
use reducing ttings, if necessary.
• Make sure that the ventilation ducts are
insulated according to the instructions in
chapter "Insulating ventilation ducts" on page
11.
5. Make the applicable electrical and plumbing
connections according to the electrical and
principal diagram at the end of this manual.
Pinion, Pingvin, Pingvin XL and Pandion
To prepare:
1. Prepare the holes in the wall.
2. Bring in the ducts through the cross cut in the
vapor barrier to the height to which the unit will
be mounted.
3. Seal the gap between the duct and the vapor
barrier using for example duct tape.
4. Install an insulating plate at the back of the
ventilation unit or otherwise prevent the structure
borne noise.
• Soft foamed plastic sheets are recommended
(not included in the delivery).
5. Install an extra layer of insulation outside the
ventilation unit (for example foamed plastic), if the
unit is installed with its side against exterior wall
or if there is any other reason to suspect that the
outside of the unit will condensate.
• Condensation risk is present in areas where the
climate is cold.
• Installation varies for dierent models.
To install:
1. Install the rear attachment bracket at the desired
height.
2. Lift the unit on the bracket.
NOTE: Remove the heat exchanger before you
lift the unit. This will make the unit much lighter
to handle. Remove or secure the doors so that
they do not open during lifting.
Ceiling installation
Pinion, Pingvin, Pingvin XL and Pandion
The dimensional drawings for each of the models can
be found at the end of this manual.
To install:
1. Install the installation plate on the ceiling.
2. Install the supplied duct couplings and insulation
rings (Pingvin, Pingvin XL and Pandion), or
insulation sheet (Pinion) on top of the unit.
3. Unscrew the cover of the electrical cabinet.
• Prepare the lead-ins on unit for the cables
coming through the ceiling.
• Leave the electrical cabinet cover open.
4. Guide the unit power cable to run in front of the
hook to keep the cables from squashing between
the unit and the ceiling installation plate.
3. Attach the unit to the wall by the upper mounting
lugs.
• Make sure to install the rubber bushings for
the fastening screws. (Pingvin and Pandion
only).
4. Attach the rear attachment bracket to the unit’s
base using sheet metal screws.
NOTE: It is essential for the proper disposal of
condensate water that a Pingvin unit is installed
slightly tilted backwards. This must be veried
using a spirit level.
20
NOTE: Remove the heat exchanger before you
lift the unit. This will make the unit much lighter
to handle. Remove or secure the doors so that
they do not open during lifting.
• Make sure that there is enough space
underneath the ceiling plate to t the unit.
5. Lift the unit up.
6. Hook the unit to the front side of the ceiling
installation plate.
7. Connect the cable(s) coming through the ceiling
plate to the electrical enclosure box.
• Make sure that the unit is hanging straight,
directly in the middle of the ceiling plate.
8. Push the base of the unit upwards until it locks
onto the ceiling plate.
CLICK
NOTE: Make sure to leave the cables loose in
case the unit must be taken down for some
reason.
EN
NOTE: It is essential for the proper disposal
of condensate water that a Pingvin unit is
installed slightly tilted backwards. The unit
is automatically installed tilted in the ceiling
installation plate.
Taking down ceiling installed units
DANGER
DANGER: Before taking the unit down, make
sure that the unit’s supply voltage has been
switched o.
CAUTION
CAUTION: Make sure you are holding the unit
in its place when opening the locking plates.
When the locking plates are opened, the unit’s
back side disengages from the ceiling plate.
Make sure that you have enough space under
the unit for it to swing down.
9. Secure the unit in place by tightening the two
security screws on both sides of the ceiling plate.
• The locking screws for Pinion units are below
the ventilation unit.
10. Put the heat exchanger back in the unit and close
the electrical cabinet door.
11. Reinstall the doors if you removed them before the
lifting.
12. Make the applicable electrical and plumbing
connections according to the electrical and
principal diagram at the end of this manual.
To take down:
1. Open the security screws.
2. Open the electrical cabinet and disconnect the
cables coming from the ceiling.
3. Holding the unit securely in its place, twist both
of the locking plates open (towards you) using a
screwdriver.
4. Lift down the unit.
21Installation instructions
Floor installation
Pandion, Pelican, Pegasos and Pegasos XL
• Make sure that there is enough space left in
front of or above the maintenance hatch:
• Tilt the unit slightly in the direction of the
condensation drain.
Dimensional drawings for each of the models can be
found at the end of this manual.
To install:
1. Set the ventilation unit on the oor or on the
platform standing on its own rubber feet.
• Make sure there is at least a 10 mm gap all
around the unit.
• If the unit is installed with its side against a
wall, a 15 mm gap is required so the hatch can
be fully opened.
2. Note the space needed for disposing of
condensate water and the water trap under the
unit (if applicable).
• Make sure there is at least 95 cm of space in
front of the unit’s maintenance hatch and
that the electrical connections can be easily
accessed.
3. Connect the unit to a condensate water disposal
drain with water trap.
4. Connect the ducts to the ventilation unit using
rivets.
5. Insulate the ducts according to the instructions in
Insulating ventilation ducts section.
6. Make the applicable electrical and plumbing
connections according to the electrical and
principal diagram at the end of this manual.
Installing models LTR-2, LTR-3,
LTR-4, LTR-6, LTR-7 and LTR-7 XL
Dimensional drawings for each of the models can be
found at the end of this manual.
Consult the ventilation planner regarding possible
need for additional insulation of the unit if mounted in
a cold space.
UnitFree space
LTR-2 and LTR-3min. 50 cm
LTR-4 and LTR-6min. 60 cm
LTR-7 and LTR-7 XLmin. 70 cm
3. Note the space needed for opening the
maintenance hatch locks.
• Make sure the electrical connections can be
easily accessed.
4. Connect the ducts to the ventilation unit with
circular duct ttings using rivets.
5. Insulate the ducts according to the instructions
in chapter "Insulating ventilation ducts" on page
11.
6. Connect the unit to a condensate water disposal
drain with water trap.
• If the ventilation unit is equipped with a
built-in cooling coil it is recommended to
install the unit with the service hatch to the
side to enable the condensate water to drain
more easily.
• LTR-4 units with cooling coil have two optional
32mm condensation drains. One drain is
welded shut and the other is ready to use.
Depending on the way the LTR-4 unit is
installed, the drain that becomes lower is to
be used. If the lower drain is the welded one,
a short piece of the pipe is sawed o to open
the pipe, and the water trap is connected to
the pipe.
• The unused condensation drain must be
plugged.
7. Make the applicable electrical and plumbing
connections according to the electrical and
principal diagram at the end of this manual.
Installing model eWind W
If you are using solid (hard) insulation, avoid fastening
the isolation in a way that conducts sound and
vibration to the house frame.
To install:
1. Set the unit on top of an insulating plate.
• For example a chipboard covered with
100mm of hard insulating wool – above the
rafters in the attic or on a separate shelf in a
storage etc.
2. Note the space needed for disposal of condensate
water and the water trap.
22
Principal, control and wiring diagrams for each model
can be found at the end of this manual.
Check the principal charts for units with uid coil. Install
and connect the water pipes according to these charts.
To install:
1. Install the dampers and damper motors.
2. Install and connect the water pipes.
3. Install the valve and the valve actuator.
• Do not connect Modbus until all installation
and commissioning work is done.
7. Install over voltage protection to the unit.
8. Open the unit’s maintenance hatch and make sure
that:
• The unit is clean from the inside
• There are no unwanted objects inside
• The lters are in place and
• The condensate drain works.
9. Close the hatch carefully.
10. Connect the unit to an appropriate electric supply.
NOTE: The valve and actuator must be in the
same position when connected. When the
valve is in open position, the actuator is turned
counter-clockwise before connecting, and
when the valve is closed, the actuator is turned
clockwise before connecting. Figure 2 on page
23 shows the valve and markings on valve
spindle in valve open (cooling/heating on max)
position.
EN
Figure 2. Valve and actuator open counter-clockwise and
close clockwise. The gure shows the valve and actuator
in the fully open position. Also, shown is the allowed direction of the liquid ow.
NOTE: Do not install the actuator so that the
manual control faces downwards.
4. Connect the water.
• Do not connect to a point where the water
circulation ends for example during hot water
production.
5. Check the duct coil and its connections for leaks
immediately after the system has been lled with
water.
• The water heating coil needs a steady ow
of suciently warm water without large
temperature uctuations.
• Adjust the water ow in the heating coil
according to the technical features table at the
end of this manual.
• If the water is taken for instance from a ground
source heat pump, the heating coil needs its
own circulation pump.
• If the installation is done in wintertime it is
recommended not to let water in the coil until
the ventilation is running. This is in order to
prevent cold air from entering the ventilation
system and possibly freezing the coil.
6. Connect the external cables such as the cable
between the unit and the control panel, supply
sensor, actuator and pump.
Draining condensate water
All Enervent ventilation units must be drained. When
air cools down (condenses), condense water forms.
For example in winter time when humid inside air
meets cold heat recovery wheel, or when warm outside
air meets the cooling coil in the ventilation unit (if
applicable).
CAUTION
CAUTION: The condense water drain must not
be directly connected to a sewer pipe.
• The condensate water should be led in a falling, at
least Ø15 mm pipe, through a water trap to a oor
drain or such.
• The pipe must at all times lie lower than the
condensate water drip pan / condensate water
connection of the ventilation unit.
• There must not be any longer horizontal sections
on the pipe.
• The condensation drain pipe must be insulated if
mounted in spaces where freezing can occur.
• Only one water lock is allowed for each condensate
water drain.
• If the unit is equipped with more than one
condense water drains, each one must have a
water lock of its own.
• There is underpressure in the ventilation unit. We
recommend a height dierence of (A) 75 mm,
or at least the underpressure divided with 10 in
millimeters (i.e. 500 Pa under pressure -> 50 mm),
between the unit drain and the water lock drain.
23Installation instructions
• We recommend that the height of backwater
A
B
in the water lock (B) is 50 mm, or at least the
underpressure divided with 20 in millimeters
(i.e. 500 Pa under pressure -> 25 mm height of
backwater). The above also applies to duct coils for
cooling mounted in the outside air duct or extract
air duct.
• There are over pressure inside duct coils mounted
in the supply air duct. We recommend the height
dierence (A) between the duct coil drain and the
water lock drain is 25 mm. The water lock height of
backwater (B) must be 75 mm, or at least the over
pressure divided with 10 in millimeters (i.e. 500 Pa
under pressure -> 50 mm).
• The water lock must be lled with water before
starting up the unit. The water lock might dry up
if water is not accumulated in it. If this happens,
air might get into the pipe and hinder water from
entering the water lock, which might result in an
irritating ”bubbling” sound.
• The functionality of the water lock must be
checked every year before the heating season and
also in the spring if the ventilation unit is equipped
with cooling.
CONDENSATE WATER DRAIN TABLE
Unit
Pinion eWind (E)/(W)•
Pingvin eWind (E)/(W)•
Pingvin eWind E-CG/CHG••
Pingvin XL eWind (E)/(W)•
Pingvin XL eWind E-CG/CHG ••
Pandion eWind (E)/(W)••
Pandion eWind E-CG•••’
Pandion eWind E-CHG•••
Pelican eWind (E)/(W)••
Pelican eWind E-CG•••’
Pelican eWind E-CHG•••
Pegasos eWind (E)/(W)••
Pegasos eWind E-CG••
1/4”
(inner
thread)
DN32
G½”
(VEAB,
outer
thread)
Pegasos eWind E-CHG•••
Pegasos XL eWind (E)/(W)••
Pegasos XL eWind E-CG/CHG •••
LTR-2 eWind (E)/(W)••
LTR-2 eWind E-CHG•••
LTR-3 eWind (E)/(W)••
LTR-3 eWind E-CG/CHG•••
LTR-4 eWind (E)/(W)••
LTR-4 eWind E-CG•••••’
LTR-4 eWind E-CHG•••
LTR-6 eWind (E)/(W)••
LTR-6 eWind E-CG••••’
LTR-6 eWind E-CHG•••
LTR-7 eWind (E)/(W)••
LTR-7 eWind E-CG/CHG•••
24
LTR-7 XL eWind (E)/(W)••
LTR-7 XL eWind E-CG/CHG•••
• condensate drain
•• two condensate drains of the same size
•’ option
COMMISSIONING
Commissioning checklist
Requirements
For the ventilation unit to start running, it needs:
• Minimum +8 °C return water temperature (if
applicable)
• Supply and extract air below +55 °C.
For the ventilation unit to stay running, it needs:
• Minimum +10 °C measured extract air temperature
• Above +5 °C heat recovery supply air
• Above +10 °C supply air temperature
• All foreign objects removed from the ventilation
system.
• Both fans operating.
Calibrating airow
After the unit has been switched on, the airows must
be calibrated to the planned values.
• The airow calibration is performed at start-up of
the ventilation unit.
• The airow calibration is done separately for both
fans for each mode selection (=fan speed) of the
ventilation unit.
When calibrating, make sure that:
• All lters are clean
• All supply and extract air valves, the roof passthrough and the outside air grating are in place.
NOTE: Do not cover the grating with a
mosquito net.
To achieve optimal values during calibration the
airows must be measured at each duct opening. A
suitable measuring instrument is a thermo anemometer
or dierential pressure meter. With the help of
registered values, airow can be regulated to achieve
the projected values.
A correctly calibrated ventilation unit is quiet and gives
a good heat return and also upholds a small underpressure in the house. The underpressure prevents
humidity from entering the walls and ceiling.
ItemChecked Notes
The unit has been
installed in its
place according
to the installation
instructions provided
by the manufacturer.
Condensate water
disposal pipe has
been connected to
the drain’s water lock
and tested.
Silencers have been
installed in the
supply and extract
air ducts.
For models with
water coils: dampers
have been installed.
All liquid coils are
connected, the liquid
ow(s) adjusted, and
the connections are
checked for leaks
All external valves
and valve actuators
are connected and
checked for correct
operation.
For CHG model:
coil, control valve,
valve actuator and
temperature sensor
for outside air duct
have been installed
and connected,
checked for correct
operation, and the
brine ow adjusted.
The freezing point
of the brine liquid
checked to be
sucient.
Terminal devices
have been
connected to the
ventilation network.
Outside air grating
has been installed for
fresh air intake.
NOTE: Do not cover
the grating with a
mosquito net. It will
make it very dicult
to clean.
Unit is connected
to an appropriate
electric supply.
Control panel has
been connected.
All external
sensors have been
connected and
checked for correct
operation.
The ventilation
ducts are insulated
according to the
ventilation plan.
EN
25Installation instructions
Control system, eWind operating panel
1
4
2
3
1. Mode (in basic display)2. Temperature (in basic display)3. Mode button
4. Eco button5. Temperature button6. Cable connector
Important to know about control
5
6
Setting up fan speeds
system
The fan speed settings for each operating mode must
Factory settings are suitable for most installations.
The fan speed settings for dierent operating modes
are installation specic and must be specied and
set separately for each installation. Otherwise, do not
change the factory setting, unless otherwise specied
in the ventilation system plan.
Make sure that you have all the necessary information
at hand before starting the setup.
be specied and set separately for the installation. Refer
to the parameter table for settings
To set up:
1. Press the Eco and Temperature buttons
simultaneously three times.
2. Use the Mode and Eco buttons to select
parameters c1-c 32.
• Refer to "Parameter list" on page 27 for
meaning of each parameter.
3. Press the Temperature button for 3 seconds select
the parameter to adjust.
4. Use the Mode and Eco buttons to change the
parameter value.
5. Press the Temperature button to conrm the
value and return to selection of parameters
c1 - c32.
6. Press the Eco and Temperature buttons
simultaneously once to exit the setup.
26
Parameter list
Parameter Description
c1Extract fan speed, mode 1,
range: 20-100%, step: 1%
c2 Supply air fan speed, mode 1,
range: 20-100%, step: 1%
c3 Extract fan speed, mode 2,
range: 20-100%, step: 1%
c4Supply air fan speed, mode 2,
range: 20-100%, step: 1%
c5 Extract fan speed, mode 3
range: 20-100%, step: 1%
c6Supply air fan speed, mode 3
range: 20-100%, step: 1%
c7Extract fan speed, mode 4
range: 20-100%, step: 1%
c8Supply air fan speed, mode 4
range: 20-100%, step: 1%
c9Manual boost time limit (mode 4)
range: 1...4 h, step: 1 h
c10Extract fan speed, replace/extractor hood
mode range: 20-100%, step: 1%
Factory
setting
36%Away mode102
35%Away mode100
56%Home mode52
55%Home mode51
83%Maximum eect also
80%Maximum eect also
100%Manual boost mode68
100%Manual boost mode67
2 h66
30%Overpressure mode55
Remark
by RH ja CO2 boost
mode
by RH ja CO2 boost
mode
Modbus
registration
74
72
Field
setting
EN
c11Supply air fan speed, replace/extractor hood
mode range: 20-100%, step: 1%
c12Overpressure mode time limit
range: 5...15 min
step: 1 min
c13Heat recovery defrosting
on or oFF
c14Service reminder interval
4 or 6 months
c15CHG/AGH pre-heating and AGH pre-cooling,
on or oFF
c16CHG/AGH outside temperature TE01, below
which pre-heating is used
range: 0…10°C, step 1°C, (for pre-heating)
c17CHG/AGH pre-heating not in use when outside
air temperature (TE01) rises above value (c16)
+ (c17)
range: 1…5°C, step 1°C
c18CG cooling or CHG pre-cooling on/oFFonValid for CG and CHG
c19Outside temperature TE01, above which
cooling is allowed
c20AGH outside temperature above which earth
channel is used
range: 15…25°C, step 1°C, (for pre-cooling)
c21AGH pre-cooling not in use when outside air
temperature (TE01) drops below value (c20c21)
range: 1…5°C, step 1°C
c22Temperature setup for air temperature after
electric pre-heater
range: -10…-20°C, step: 1°C
c23Humidity boosting
on or oFF
50%Overpressure mode54
10 minExtractor hood mode
selected when set to 0
oFFCoil 55
4Register value in days 538
onCoil 58
5°C592
1°C593
heat exchangers
17°C164
20°C629
2°C630
-15°C591
onCoil 19
56
Coil 52
27Installation instructions
Parameter list
Parameter Description
c24Summer/winter temperature threshold,
range -10…+10 °C, step 1 °C
c25RH boosting threshold,
range 10…100 %RH, step 5%
c26Humidity boosting start threshold range:
5…30% RH exceeding 48h average, step 5%
c27CO2 boosting
on or oFF
c28CO2 boosting start threshold range:
600...1200 ppm, step: 100 ppm
c29Boosted dehumidication with HRW rotor
on or oFF
Factory
setting
4 °COutside air 24 h
45%In winter mode RH
15%In summer mode RH
oFFIf on congures AI1 for
1000 ppm76
oFFCoil 24
Remark
temperature average.
When over threshold,
RH boosting is in
summer mode, when
under threshold, in
winter mode.
boosting starts when
RH value exceeds the
threshold.
boosting starts, when
RH exceeds the 48 h
RH average by the
threshold value.
external CO2 sensor
Modbus
registration
137
69
70
Coil 21
Field
setting
c30Display dimmed in stand-by
on or oFF
c31eWind motherboard Modbus address
range: 1...99, step: 1
c32Modbus bus speed
1=9600, 2=19200, 3=115200
Information view
You can view the active functions from eWind Info list
shown in the information display.
eWind Info list
To open:
1. Press Eco and Temperature buttons
simultaneously once.
• A parameter (n1..nn) is shown in the display.
2. Browse the Info list with Mode and Eco buttons.
To return to the basic view:
1. Press the Eco and Temperature buttons
simultaneously once.
NOTE: Without input the menu closes after 5
minutes and the panel switches back to basic
display.
oFFPanel specic setting
oFF: display o in
stand-by,
on: dimmed display in
stand-by.
1640
219200bps733
eWind Info list
Designation Explanation
n0Basic mode in use
n1 Ventilation boosted by %RH
n2Ventilation boosted by CO2
n3Heat recovery in use
n4 After-heating by electrical or water coil in
use
n5 Outside air pre-heating by CHG/AGH or
electrical pre-heater in use
n6 Supply air cooling by CG, CHG or AGH in use
n7Cool recovery by rotating heat exchanger
in use
n8Ventilation manually boosted
n9 Away mode in use
n10Rotor dehumidication in use
n11 Defrosting in use
n12ECO mode in use
n13 Service reminder; Days remaining to next
lter change
n14Unit starting up
Internal
28
Measurements view
eWind Measurements list
You can follow the temperature, humidity, heat
recovery eciency among other measurements in the
eWind Measurements list shown in the measurements
display.
To open:
1. Press the Eco and Temperature buttons
simultaneously twice.
• A parameter (r1..rn) and the value of the
parameter are shown in the display.
•
2. Press the Mode or Eco buttons to scroll the
parameter list up or down.
To return to the basic view:
1. Press the Eco and Temperature buttons
simultaneously once.
eWind Measurements list
Designation in
Designation Explanation
r1Outside air temperature, °CTE01All models6
r2Supply air temperature after-heat
recovery, °C
r3Supply air temperature, °CTE10All models8
r4Extract air temperature, °CTE30All models10
r5Exhaust air temperature, °CTE32All models9
r6Return water temperature of water
heating coil, °C
r7Pre-heated outside air temperature
(CHG/AGH/electrical pre-heater), °C
r8Relative humidity of extract air, %RHRH30All models13
r9CO2 level, ppmWithout external CO2 sensor
r10External relative humidity
measurement, %RH
r11Supply air heat recovery temperature
eciency, %
r12Extract air heat recovery temperature
eciency, %
schematics and
connection on
eWind main board
TE05All models7
TE45W only. Other models show “0”12
TE02Only if equipped with CHG/
Note
AGH or electrical pre-heater)
(accessory) showing "--”
Without external %RH sensor
(accessory) showing "--”
All models
Calculated value
All models
Calculated value
EN
Modbusregister
32
23
23
29
30
Documenting commissioning
• Fill in the warranty.
• Mark down the possible changes you made to the
factory settings to the column Field settings in the
table "Parameter list" on page 27.
• Fill out the air amount measuring document. A
copy of the measuring document is provided at
the end of this manual.
NOTE: The warranty does not apply for units
with no documented air amount measuring.
NOTE: It is very important to write down all the
changes made to the parameters. This way the
information is backed up in case the automation
gets damaged (for example by a lightning).
29Installation instructions
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.