EnerSys SBS 8, SBS 60, SBS 40, SBS 300, SBS 110 Instruction Sheet

...
PowerSafe®SBS batteries are supplied in a charged condition, and are capable of extremely high short circuit currents. Take care to avoid short-circuiting terminals of opposite polarity.
1. Receiving
Upon receipt of a shipment, check that the items delivered are undamaged and match the carrier’s Bill of Lading. Report any damage or shortages to the carrier. EnerSys
®
is not responsible for shipment damage or shortages that the receiver does not report to the carrier.
1.2 Shipment Damage or Shortages
Open the shipping containers and check the contents for damage and against the packing slip. Immediately inform EnerSys of any damaged or missing items.
EnerSys is not responsible for damaged or missing items after a shipment has been in storage.
2. Storage
2.1 Storage Conditions and Time
If a battery cannot be immediately installed it should be stored in a clean, cool, dry area.
During storage batteries lose capacity through self-discharge.
High temperature increases the rate of self-discharge and reduces the storage life.
The chart below shows the relationship between open-circuit voltage (OCV) and storage time at various temperatures.
The maximum storage times before a freshening charge is required and recommended open circuit voltage audit intervals are:
Monoblocs must be given a freshening charge when bloc voltages approach the equivalent of 2.10 Volts per cell or when the maximum storage time is reached, whichever occurs first.
2.2 Commissioning Charge
Before conducting a capacity discharge or fully loaded duty cycle test, the battery must be given a commissioning charge. The commissioning charge shall consist of 7 continuous days of float charge at the recommended float voltage (2.29Vpc at 20°C) with no load connected to the battery.
2.3 Freshening Charge
Charge the monoblocs, or strings at a constant voltage equivalent to 2.29 - 2.4Vpc with 10% of the C
10 current
available for a period of 24 hours.
3. Battery Location
The battery compartment/room must have adequate ventilation to limit hydrogen accumulation to a maximum of 1% by volume of free air.
4. Installation
Each monobloc is supplied with the terminal/connector fasteners.
On each monobloc the positive terminal is identified by a “+” symbol. Install the batteries in accordance with the instructions and/or layout drawing, taking care to ensure correct terminal location and polarity.
Connect the blocs with the connectors and fasteners provided. The fastener torque value is:
Instruction Sheet
Temperature Storage Time OCV Audit Interval
(°C / °F) (Months) (Months)
+10 / +50 48 6 +15 / +59 34 6 +20 / +68 24 4 +25 / +77 17 4 +30 / +86 12 3 +35 / +95 8.5 2 +40 / +104 6 2
Battery Fastener Torque
Type Size Nm / lbf in
SBS 8 M4 1.0 / 9 SBS 15-60 M6 3.9 / 35 SBS 110-390 M8 5.0 / 44 SBS J types M6 6.8 / 60 SBS B8, B10 M8 5.0 / 44 SBS B8F, B10F M6 5.0 / 44
No smoking, no naked flames, no sparks
Electrolyte is corrosive
Electrical hazard
Shield eyes
Clean all acid splash in eyes or on skin with plenty of clean water. Then seek medical help. Acid on clothing is to be washed with water
Danger
Read instructions
Re-cycle scrap batteries. Contains lead
California Proposition 65 Warning – Battery posts, terminals and related accessories contain lead and lead compounds, chemicals known to the State of California to cause cancer and reproductive harm. Wash hands after handling.
Warning: Risk of fire, explosion, or burns. Do not disassemble, heat above 60ºC, or incinerate.
Avoid any short circuit. Metallic parts under voltage on the battery, do not place tools or items on top of the battery
2.17
2.16
2.15
2.14
2.13
2.12
2.11
+40°C +30°C +25°C +20°C +10°C
2.10
Open Circuit Voltage per Cell
0 6 12 18 24 30 36 42 48
Months
Approx. % State of Charge
100
96
91
87
83
79
74
70
Publication No. EN-SBS-IS-008 - February 2012 - Subject to revisions without prior notice. E.&O.E.
Place the insulating covers in position immediately after tightening the fasteners.
5. Operation
Constant voltage chargers are recommended. The charging voltage should be set at the equivalent of 2.29Vpc at 20°C/68°F or 2.27Vpc at 25°C/77°F. The minimum charging voltage, at any temperature, is 2.21Vpc. The recommended float voltage temperature compensation is:
Disconnecting the battery from the load when the recommended end voltage is reached will eliminate the risk of over-discharge. We recommend that the charge voltage is reapplied within 24 hours, up to a maximum of 7 days, of any discharge.
6. Maintenance
In practice, the user usually specifies the maintenance schedule based on site criticality, location and manpower.
The following is a suggested maintenance schedule.
• Monthly (record all readings)
Measure the battery string voltage. If necessary, adjust the
float voltage to the correct value.
• Every six months (record all readings)
Measure the battery string voltage. If necessary, adjust the float voltage to the correct value.
Measure individual bloc voltages. The blocs should be within 5% of the average.
Inspect for contamination by dust, loose or corroded connections. If necessary isolate the string/bloc and clean with a damp soft cloth. Warning - Do NOT use any type of oil, solvent, detergent, petroleum-based solvent or ammonia solution to clean the battery containers or lids. These materials will cause permanent damage to the battery container and lid and will invalidate the warranty.
Contact EnerSys
®
if you have any questions regarding
maintenance.
7. Disposal
PowerSafe®SBS batteries are recyclable. Scrap batteries must be packaged and transported in accordance with prevailing transportation rules and regulations.
Scrap batteries must be disposed of in compliance with local and national laws by a licensed or certified lead acid battery recycler.
SBS 8 2205-8982 2205-8981
SBS 15 2205-9851 2205-9850
SBS 30, 40 2205-4090 2205-4215
SBS 60 2205-4090 2205-4260
SBS 110 - 300 2205-9887 2205-8865
SBS 390 2205-9759 x 2 N/A
Battery Type
Connector Part No.
A B
Temperature (°C / °F)
10/50 15/59 20/68 25/77 30/86 35/95 40/104 Recommended 2.33 2.31 2.29 2.27 2.25 2.23 2.21 Minimum 2.31 2.29 2.27 2.25 2.23 2.21 2.21
www.enersys-emea.com
Battery Type
Connector Part No.
A B
SBS J13, J16 2205-9851 2205-9850
SBS J30, J40 2205-4090 2205-4260
SBS J70 2205-4090 2205-4420
SBS B8, B10 2205-8919 N/A
SBS B8F, B10F 2205-8891 N/A
Contact:
© 2012 EnerSys. All rights reserved.
Trademarks and logos are the property of
EnerSys and its affiliates unless otherwise noted.
8. Connectors
EnerSys
2366 Bernville Road Reading, PA 19605 USA Tel: +1-610-208-1991
+1-800-538-3627
Fax: +1-610-372-8613
EnerSys Ltd.
Oak Court Clifton Business Park Wynne Avenue, Swinton Manchester M27 8FF UK Tel: +44 (0)161 794 4611 Fax: +44 (0)161 727 3809
EnerSys Europe
EH Europe GmbH Löwenstrasse 32 8001 Zurich, Switzerland
EnerSys Asia
152 Beach Road Gateway East Building, Level 11 189721 Singapore Tel: +65 6508 1780
SBS 8-60, J13, J16, J70