Energy Tech Laboratories New Yorker CL, Riello 40, New Yorker F5, New Yorker F3 User Manual

Page 1
INSTALLATION, OPERATING
nonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
rebmuNledoMrelioB rebmuNlaireSrelioB etaDnoitallatsnI
LC
rotcartnoCgnitaeH rebmuNenohP
sserddA
AND SERVICE INSTRUCTIONS
CL™ SERIES
CAST IRON OIL-FIRED BOILER
As an ENERGY STAR® Partner, New Yorker Boiler Co., Inc. has determined that the CL3-091, CL3-105, CL4-126 and CL5-168 water boilers meet the ENERGY STAR guidelines for Energy
efciency established by the
United States Environmental Protection Agency (EPA).
®
100825-01R5-10/08
Price - $3.00
Page 2
IMPORTANT INFORMATION - PLEASE READ THIS PAGE CAREFULLY
1. Read and understand all instructions, including all those contained in component manufacturers manuals which are provided with the appliance before installing, starting-up, operating, maintaining or servicing this appliance. Keep this manual and literature in legible condition and posted near appliance for reference by owner and service technician.
2. All heating systems should be designed by competent contractors and only persons knowledgeable in the layout and installation of hydronic heating systems should attempt installation of any boiler.
3. All boilers must be installed in accordance with National, State and Local Plumbing, Heating and Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may differ from this instruction manual. Authorities having jurisdiction should be consulted before installations are made.
In all cases, reference should be made to the following Standards:
USA BOILERS
A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil Burning Equipment”, for
recommended installation practices.
Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces, Vents, and Solid Fuel
B.
Burning Appliances”, For Venting requirements.
C.
Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for
Automatically Fired Boilers”, for assembly and operations of controls and safety devices.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or
D.
Local Regulations.
CANADIAN BOILERS
A.
Current Edition of Canadian Standards Association CSA B139, “Installation Code for Oil Burning Equipment”,
for recommended Installation Practices.
B. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or
Local Regulations.
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. The warranty for this boiler is valid only if the boiler has been installed, maintained and operated in accordance
with these instructions.
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other
appliance.
2
Page 3
WARNING
This boiler is suitable for installation on combustible ooring. Do not install boiler on carpeting.
Installation is not complete unless a pressure relief valve is installed into the tapping located on top left corner of rear section - See Piping and Trim Sections of this manual for details.
This boiler is designed to burn No. 2 fuel oil only. Do not use gasoline, crankcase drainings, or any oil containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e.
wood, coal). Do not convert to any gaseous fuel (i.e. natural gas, LP). All ammable debris, rags, paper,
wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of
re hazards. This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air. This boiler must be connected to an approved chimney in good condition. Serious property damage
could result if the boiler is connected to a dirty or inadequate chimney. The interior of the chimney ue
must be inspected and cleaned before the start of the heating season for any obstructions. A clean and
unobstructed chimney ue is necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler's efciency.
Inspect ueways at least once a year - preferably at the start of the heating season. The inside of the combustion chamber, the vent system and boiler ueways should be cleaned if soot or scale has
accumulated. When cleaning this boiler, do not damage combustion chamber liner and/or rear target wall. If damaged, combustion chamber insulation must be replaced immediately.
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained in this manual. Installation, maintenance, and service must be performed only by an experienced, skilled
and knowledgeable installer or service agency. It is the responsibility of the installing contractor to see that all controls are correctly installed and
are operating properly when the installation is completed. Do not tamper with or alter the boiler or controls.
Do not operate unit if any control, switch, component, or device has been subject to water. When cleaning this boiler, do not damage combustion chamber liner and/or rear target wall. If damaged, combustion chamber insulation must be replaced immediately.
Oil Burner and Controls must be checked at least once a year or as may be necessitated.
All boilers equipped with burner swing door have a potential hazard which if ignored can cause severe property damage, personal injury or loss of life. Before opening swing door, turn off service switch to boiler to prevent accidental ring of burner outside the combustion chamber. Be sure to tighten swing
door fastener completely when service is completed. Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy
metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when
servicing or working nearby the appliance.
High water temperatures increase the risk of scalding injury. If this boiler is equipped with a tankless heater for domestic water supply, a ow regulator and automatic mixing valve must be installed properly
in tankless heater piping. See Piping and Trim Sections of the manual for details.
3
Page 4
Table of Contents
I. General Information ....................................4
II. Installation Instructions ..............................8
III.
Indirect Water Heater Piping ....................23
IV. Operating & Service Instructions ............24
V. Maintenance and Service Instructions. ...30
VI. Boiler Cleaning ..........................................
34
I. General Information
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. ALL EQUIPMENT is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition.
2. ANY CLAIMS for damage or shortage in shipment
must be led immediately against the carrier by
the consignee. No claims for variances from, or shortage in orders, will be allowed by the manufacturer unless presented within sixty (60) days after receipt of goods.
B. LOCATE BOILER in front of nal position before
removing crate. See Figures 1A thru 1D.
1. LOCATE so that smoke pipe connection to chimney will be short and direct. BOILER IS SUITABLE FOR INSTALLATION ON COMBUSTIBLE FLOOR. Boiler cannot be installed on carpeting.
Trouble Shooting
Carlin 40200 .............................................36
Riello 40 Series .......................................36
VII. Repair Parts .............................................37
VIII. Appendix
Low Water Cut Off ..................................45
Burner Specications ............................46
2. FOR BASEMENT INSTALLATION, provide a
solid base, such as a concrete pad, if oor is not level, or if water may be encountered on oor
around boiler.
PROVIDE SERVICE CLEARANCE of at least 24”
3.
on top of boiler for cleaning ueways. Provide at
least 24" on right side of boiler for removal of rear tankless heater. Provide at least 24” clearance from front jacket panel for servicing.
4. For minimum clearances to combustible materials. See Figure 2.
C. PROVIDE AIR SUPPLY AND VENTILATION to
accommodate proper combustion. If natural ventilation is inadequate, provide a screened opening or duct from the boiler room to the outside. The opening or duct must be sized so the boiler input will not exceed 4,000 BTUH/Sq. In. of free area. If other air consuming appliances are near the boiler, the air inlet should be larger. Consult respective manufacturers.
4
Page 5
Figure 1A: CL3 Thru CL5 Water Boiler Less Tankless Heater
Figure 1B: CL3 Thru CL5 Water Boiler With Tankless Heater
5
Page 6
Figure 1C: CL3 Thru CL5 Steam Boiler with or without Tankless Heater
Figure 1D: CL3 thru CL5 Steam Boiler with McDonnell & Miller PS-801 Low Water Cut-Off, Riello Burner
TABLE 1: DIMENSIONAL DATA (SEE FIGURES 1A THRU 1C)
Boiler
Model
CL3 17-3/8" 8-1/4" 5-7/8" 8" x 8" x 15' 6" x 15' 16 14.33 CL4 22-3/8" 10-7/8" 6-7/8" 8" x 8" x 15' 7" x 15' 20 20.90 CL5 27-3/8" 13-3/8" 7-7/8" 8" x 8" x 15' 8" x 15' 24 27.46
Maximum Working Pressure: Steam: 15 PSI; Water: 30 PSI Shipped Standard from Factory, 50 PSI Optional
Dimensions Minimum Chimney Size
"A" "B" "C" Rectangular Round
Approx. Water
Content - Gallons
Heat Transfer Surface
Area - Sq. Ft.
6
Page 7
TABLE 2: RATING DATA
Burner
Boiler Model
Capacity
No. *
GPH MBH
CL3-091(W) 0.65 91 80 --- 70 --- --- 6 8 x 8 15 86.0 ---
CL3-091(S) 0.65 91 --- 78 --- 56 233 6 8 x 8 15 --- 84.1
CL3-105(W) 0.75 105 91 --- 79 --- --- 6 8 x 8 15 85.1 ---
CL3-105(S) 0.75 105 --- 90 --- 68 283 6 8 x 8 15 --- 83.8
CL3-140(W) 1.00 140 120 --- 104 --- --- 6 8 x 8 15 83.6 ---
CL3-140(S) 1.00 140 --- 119 --- 89 370 6 8 x 8 15 --- 82.7
CL4-126(W) 0.90 126 111 --- 97 --- --- 7 8 x 8 15 85.8 ---
CL4-126(S) 0.90 126 --- 108 --- 81 338 7 8 x 8 15 --- 84.1
CL4-175(W) 1.25 175 152 --- 132 --- --- 7 8 x 8 15 84.2 ---
CL4-175(S) 1.25 175 --- 149 --- 112 467 7 8 x 8 15 --- 83.5
CL4-210(W) 1.50 210 179 --- 156 --- --- 7 8 x 8 15 83.1 ---
CL4-210(S) 1.50 210 --- 177 --- 133 554 7 8 x 8 15 --- 82.6
CL5-168(W) 1.20 168 147 --- 128 --- --- 8 8 x 8 15 85.7 ---
CL5-168(S) 1.20 168 --- 144 --- 108 450 8 8 x 8 15 --- 83.7
CL5-245(W) 1.75 245 210 --- 183 --- --- 8 8 x 8 15 83.0 ---
CL5-245(S) 1.75 245 --- 207 --- 155 646 8 8 x 8 15 --- 82.5
CL5-280(W) 2.00 280 238 --- 207 --- --- 8 8 x 8 15 82.5 ---
CL5-280(S) 2.00 280 --- 235 --- 176 733 8 8 x 8 15 --- 82.3
* Boiler Model Sufx: (W) = Water, (S) = Steam
DOE Heating
Capacity
Water
MBH
Steam
MBH
I=B=R NET Ratings
Water
MBH
Steam
MBH
Steam Sq. Ft.
Minimum Chimney
Requirements
Round
In. Dia.
Rectangle
In. x In.
Height
Ft.
AFUE %
Water Steam
Figure 2: Minimum Installation Clearances To Combustible Materials (Inches)
C
A
Above
6 24 18 6 6
NOTE 1: Listed clearances comply with American National Standard NFPA 31, Standard for the Installation of Oil Burn­ing Equipment.
B
Front
Chimney
Connector
D
Rear
E
Sides
NOTE 2: CL Series boilers can be installed in rooms with clearances from combustible material as listed above. Listed clearances cannot be reduced for alcove or closet installa­tions.
NOTE 3: For reduced clearances to combustible material, protection must be provided as described in the ANSI/NFPA 31 standard.
7
Page 8
II. Installation Instructions
A. REMOVE CRATE
1. Remove all fasteners at crate skid.
2. Lift outside container and remove all other inside protective spacers and bracing. Remove miscellaneous steam or water trim carton.
Using hand truck or pipe rollers under skid, move
3. boiler into position along side installation site.
B. REMOVAL OF BOILER FROM SKID
1. Boiler is secured to base with 4 carriage bolts, 2 on left side and 2 on right side. See Figure 3. Remove all bolts.
Figure 3: Removal of Boiler From Skid
2. Tilt boiler to right and to rear. Using right rear leg as pivot, rotate boiler 90° in a clockwise direction,
and lower left side of boiler to oor. Tilt boiler
and remove crate skid. Care should be exercised to prevent damage to jacket or burner.
C. MOVE BOILER TO PERMANENT POSITION by
sliding or walking.
D. INSPECT COMBUSTION TARGET WALL AND
COMBUSTION CHAMBER LINER
1. OPEN FLAME OBSERVATION DOOR AND/ OR BURNER SWING DOOR on front of boiler.
Use ashlight to inspect target wall secured to
rear section with silastic sealant. Inspect ceramic
ber blanket secured to oor of boiler with water
glass adhesive. If either is damaged they must be replaced.
E. INSPECT NOZZLE, ELECTRODES INSERTION
DEPTH AND TURBULATOR SETTING/CHANGE FIRING RATE: Refer also to Model F3 & F5
Installation Manual, Riello 40 Series Residential Oil Burners (C6501010) or Model F10 Installation Manual, Riello 40 Series Residential Oil Burners (2902554).
1. PACKAGED CL™ Series boilers are shipped with the highest input oil nozzle installed in the burner.
Oil nozzles for lower ring rates are shipped
loose for the CL3 through CL5 models, attached to the burner. Select the proper oil nozzle for the installation. The lower input nozzle will provide
greater boiler efciency. However, boiler output will be reduced. Refer to Table 2 for ring rates.
If the higher rate is desired, inspect the installed nozzle and assure that the nozzle is the correct size
and type as specied in Tables 9 and 9A of this
manual.
If a lower input is desired, remove the nozzle
which was factory installed. Locate the lower ring rate nozzle that is supplied loose. Conrm the nozzle is the proper size and type for the lower ring rate as specied in Tables 9 and 9A of this manual.
Install the proper nozzle in the burner nozzle adaptor.
2.
On the Beckett AFG Burner, use the following
procedure to complete the inspection, check the settings
and to change the nozzle to a lower ring rate:
a. Loosen two (2) igniter latching screws, rotate
tabs and swing open igniter about hinge.
b.
Loosen knurled nut and disconnect copper
connector tube. c. Remove nozzle line electrode assembly. d. If high ring rate is desired, conrm the nozzle
is the proper size and type, refer to Table 9, then
proceed to Item i. below.
If a lower input is desired, remove the nozzle
e.
that was factory installed. f. Remove Beckett MD(V1) or MB(L1) head. g. Locate the desired nozzle. Refer to Table 9 for
proper nozzle. The nozzle must be securely
installed to assure leak free joints between the
nozzle and adapter. When installing the nozzle,
be careful not to bump or move the burner
electrodes. NOTE: On the CL3-091 (0.65 GPH) burner
application, a low ring rate bafe is required.
Bafe is shipped loose with nozzles. Install
bafe per Beckett Instruction included with
bafe.
h. Reinstall Beckett MD(V1) or MB(L1) Head. i. Inspect and measure burner electrodes. Refer
to Figure 25 for the proper electrode setting.
Readjust electrode setting to the proper
dimensions if necessary. Refer to Figure 25. j. Reinstall nozzle line electrode assembly. k. Connect copper connector tube.
8
Page 9
l. Inspect Beckett head setting on left side of
burner by insuring the blue line MD(V1) or the line on the label MB(L1) are aligned, readjust if
necessary. m. Tighten knurled nut. n. Swing igniter closed, rotate tabs and tighten two
(2) igniter screws. o. Replace burner cover and tighten burner cover
knobs.
3. On the Carlin EZ-PH Burner, use the following procedure to complete the inspection, check the
settings and to change the nozzle to a lower ring
rate: a. Loosen two (2) igniter latching screws, rotate
tabs and swing open igniter about hinge.
b. Loosen knurled nut and disconnect copper
connector tube.
c. Remove nozzle line electrode assembly from
burner.
d.
If high ring rate is desired, conrm the nozzle
is the proper size and type, refer to Table 9, then proceed to Item i. below.
e. If a lower input is desired, remove the ame
retention head and then remove the nozzle that was factory installed.
Locate the desired nozzle, refer to Table 9 for
f.
proper nozzle. The nozzle must be securely installed to assure leak free joints between the nozzle and adapter. When installing the nozzle, be careful not to bump or move the burner electrodes.
g.
Reinstall Flame Retention Head on Nozzle Line
Electrode Assembly. Make sure the clamp is fully sated against the shoulder on the nozzle adapter before securing.
h. Loosen and remove the retaining nut and factory
installed head bar from side of burner housing. Install the proper head bar that corresponds
to the desired ring rate, refer to Table 9, and
tighten retaining nut.
i. Readjust air band to preliminary setting that
corresponds to the lower ring rate nozzle
installed, refer to Table 9.
j. Inspect and measure burner electrodes. Refer
to Figure 25A for proper electrode setting. Readjust electrode setting to the proper
dimensions if necessary. k. Reinstall nozzle line electrode assembly. l. Reconnect copper connector tube. m. Tighten knurled nut. n. Close igniter, rotate and tighten two (2) igniter
latching screws.
On the Riello 40 Series Oil Burner, use the
4. following procedure to complete the inspection,
check the settings and to change the nozzle to a
lower ring rate:
a. Installation/Removal of Drawer Assembly,
refer to Figure 4.
Figure 4: Installation/Removal of Drawer Assembly
i. Removal:
• Disconnect oil delivery tube nut from pump.
• Loosen SCREW (3), and then unplug PRIMARY CONTROL (1) by carefully pulling it back and then up.
• Remove the AIR TUBE COVER PLATE (5) by loosening the retaining SCREW (4) (Two SCREWS-Model F5).
• Loosen SCREW (2), and then slide the complete drawer assembly out of the combustion head as shown.
ii. Installation:
To insert drawer assembly, reverse the
procedure in Step i above.
b. Nozzle Replacement, refer to Figure 5.
Figure 5: Nozzle Replacement
i. Remove the NOZZLE ADAPTER (2) from
the DRAWER ASSEMBLY by loosening the SCREW (1).
9
Page 10
ii. Remove existing nozzle from nozzle adapter.
Insert the proper NOZZLE into NOZZLE
iii.
ADAPTER and tighten securely (Do not cover tighten).
iv. Replace adapter, with nozzle installed, into
drawer assembly and secure with screw (1).
c.
Inspect and measure burner electrodes. Refer
to Figure 6 for the proper electrode settings.
Figure 6: Electrode Setting
d. Re-install Drawer
Head per Step 4a above.
e. Insertion Depth, verify the distance between
the tip of the end cone is equal to the distance
specied in Table 9A.
f. Turbulator Setting, refer to Figure 7.
Assembly into Combustion
This burner is shipped with the oil pump set
to operate on a single line system. To operate on a two-line system the bypass plug must be installed.
WARNING: Do not operate a single line
system with the by-pass plug installed. Operating a single line system with the by-pass plug installed will result in damage to the pump shaft seal.
NOTE: Pump pressure was factory pre-set but
must be checked at time of burner start-up. A pressure gauge is attached to the PRESSURE/ BLEEDER PORT (7) for pressure readings. Two PIPE CONNECTORS (4) are supplied with the burner for connection to either a single or two-line system. Also supplied are two ADAPTORS (3), two female ¼” NPT to adapt oil lines to burner pipe connectors. All pump port threads are British Parallel Thread design. Direct connection of NPT threads to the pump will damage the pump body.
Riello manometers and vacuum gauges do not
require any adapters, and can be safely connected to the pump ports. An NPT x metric adapter must be used when connecting other gauge models.
h. Replace Burner Cover and Tighten Burner
Cover Screws.
Figure 7: Turbulator Setting
g. Pump Connections and Port Identication,
refer to Figure 8.
F. INSTALL WATER BOILER TRIM AND CONTROLS,
(see Figures 1A and 1B)
1. Install return piping supplied with boiler. Apply
Teon or Sealant to all joints prior to assembly.
Thread 1½" NPT x 5" Lg. return nipple into 1½" NPT tapping located in lower left corner of front section. Thread 1½" x ¾" x 1½" NPT tee onto 5" nipple. Thread ¾" drain valve into ¾" NPT connection on tee. Tighten all joints with wrench until water tight and 1½" NPT return connection on tee is facing away from boiler horizontally to allow for proper burner swing door clearance, see Figures 1A, 1B and Figure 9.
10
Figure 8: Pump Connections and Port Identication
Page 11
Figure 9: Recommended Boiler Piping for Series Loop Hot Water System
NOTE: Vertical piping will prevent door from opening
fully for service and cleaning of boiler.
2. Thread relief valve onto factory installed ¾" NPT x 7¼" nipple located in left rear corner on top of boiler as shown in Figures 1A and 1B. Valve spindle must be in vertical position. Tighten with wrench. Pipe discharge as shown in Figure 9. Installation of the relief valve must be consistent with ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
3. On boilers with rear tankless heater, factory wired L7224C Control Relay was not installed in heater. Locate ¾" NPT Immersion Well, apply sealant and thread into ¾" NPT tapping on heater. Apply heat transfer paste (not furnished) to control bulb and insert bulb into immersion well. Tighten clamp screws to secure control to immersion well. Secure
control conduit to jacket right side panel with 5/8" cable clamp provided, refer to Figure 1B.
4.
CONNECT FIELD WIRING
a. Water boilers without tankless heater and with
front tankless heater. Connect the eld wiring
from the circulator to the aquastat control and from the control to the burner. Make the wiring connections as shown on Figures 16B.
b. Water boilers with rear tankless heater. Connect
the eld wiring from a standard junction box to
the circulator, aquastat control and burner. Make the wiring connections as shown on Figure 17B.
G. INSTALL STEAM BOILER TRIM AND CONTROLS,
(see Figures 1C and 1D).
1. Thread ¾" MPT safety valve and ¾" NPT coupling onto factory installed ¾" NPT x 7¼" nipple located
11
Page 12
Figure 10: Recommended Piping for Combination
Heating & Cooling (Refrigeration) Systems
in left rear corner on top of boiler as shown in Figure 1C. Tighten with wrench. Pipe discharge as shown in Figure 11. Installation of the relief valve must be consistent with ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
2. Install ¾" drain valve in wet return piping as shown in Figure 11.
3.
On boilers with rear tankless heater, factory wired
L4006A Aquastat Heater Control was not installed in heater. Locate ¾" NPT Immersion Well, apply sealant and thread into ¾" NPT tapping on heater. Apply heat transfer paste (not furnished) to control bulb and insert bulb into immersion well. Tighten clamping screws to secure control to immersion well. Secure 18/2 Control Cable Wire to jacket right side panel with 5/16" cable clamp provided, refer to Figure 1C.
4. CONNECT FIELD WIRING
a. Connect the eld wiring to the pressure limit,
the R8239C Control Center, the LWCO and the burner primary control. If equipped with
tankless heater, connect eld wiring from the
aquastat control to the R8239C Control Center's "R-G" terminals. Make the wiring connections as shown in Figure 19B.
H. CONNECT SUPPLY AND RETURN PIPING TO
HEATING SYSTEM.
1. CLEARANCES — Steam and hot water pipes shall have clearances of at least ½” from all combustible construction.
12
Figure 11: Recommended Boiler Piping For Gravity Return Steam Boiler
Page 13
2. WATER BOILER a. For Forced Circulation HOT WATER HEATING.
See Figure 9. Consult I=B=R Installation and Piping Guide No. 200.
b.
Use a boiler water bypass if the boiler is to be
operated in a system which has a large volume or excessive radiation where low boiler water temperature may be encountered (i.e. converted gravity circulation system, etc.).
Install a pipe tee between the circulator and
boiler return along with a second tee in the supply piping as shown in Figure 9. The bypass should be the same size as the supply and return lines. Locate valves in the bypass and supply outlet as illustrated in Figure 9 for regulation
of water ow to maintain higher boiler water
temperature.
Set the by-pass and boiler supply valves to a half
throttle position to start. Operate boiler until the system water temperature is a normal operating range.
Adjust the valves to provide 180° to 200°F
supply water temperature. Opening the boiler supply valves will raise the system temperature, while opening the bypass valve will lower the system supply temperature.
c. If this boiler is connected to heating coils located
in air handling units where they may be exposed to refrigerated air the boiler piping must be
equipped with ow control valves to prevent
gravity circulation of boiler water during the operation of the cooling system.
d. If this boiler is used in connection with
refrigeration systems, the boiler must be installed so that the chilled medium is piped in parallel with the heating boiler using appropriate valves to prevent the chilled medium from entering the boiler, see Figure 10. Also consult I=B=R Installation and Piping Guides.
e. A hot water boiler installed above radiation level
must be provided with a low water cutoff device as part of the installation. See Section VIII, Low Water Cut-Off for additional details.
3. STEAM BOILER a. For Recommended STEAM BOILER PIPING
refer to Figure 11. Also, consult I=B=R Installation and Piping Guides.
b. Evaluate the Existing Steam System. The single most important factor in determining
the expected life cycle of a steam boiler, is the amount of fresh water added to the boiler during operation. Fresh water brings minerals and oxygen into the boiler. These contaminants greatly accelerate corrosion of the cast iron boiler sections.
i. Assure that all system radiators, piping and
vents are absolutely leak tight.
• When a steam boiler is installed in an existing system, ALL air vents should be replaced at the same time. This assures that the new boiler will not be compromised by existing system leaks.
• If the system contains hidden supply or return piping (hidden behind walls, buried in concrete, etc.) pressure test this piping to assure there are no leaks.
ii. Repair any leaks in the system. iii. Install accurate water meter on the fresh
water supply to the boiler.
NOTICE
Do not use softened water in steam boilers. Accelerated boiler corrosion will result. Tie in fresh water supply to the boiler upstream of a water softener.
4. OXYGEN CONTAMINATION: a. There are many possible causes of oxygen
contamination such as: i. Addition of excessive make-up water as a
result of system leaks.
ii. Absorption through open tanks and ttings. iii. Oxygen permeable materials in the
distribution system.
In order to insure long product life, oxygen
b.
sources should be eliminated. This can be accomplished by taking the following measures:
i. Repairing system leaks to eliminate the need
for addition of make-up water.
ii. Eliminating open tanks from the system. iii. Eliminating and/or repairing ttings which
allow oxygen absorption.
iv. Use of non-permeable materials in the
distribution system.
v. Isolating the boiler from the system water by
installing a heat exchanger.
See Section V, Paragraph B, Step 3 for additional
details.
CAUTION
Oxygen contamination of the boiler water
will cause corrosion of iron and steel boiler components, and can lead to boiler failure. New Yorker's Standard Warranty does not cover
problems caused by oxygen contamination of
boiler water or scale (lime) build-up caused by
frequent addition of water.
13
Page 14
I. CONNECT TANKLESS HEATER PIPING AS
SHOWN IN Figure 12. See Table 3 for Tankless Heater Ratings.
addition, savings of hot water will be achieved since the user will not waste as much hot water while seeking water temperature to his liking. Higher temperature hot water required by dishwashers and automatic washers is possible by piping the hot water from the heater prior to entering the mixing valve. The mixing valve should be “trapped” by installing it below the cold water inlet to heater to prevent lime formation in the valve.
WARNING
Install automatic mixing valve at tankless heater
outlet to avoid risk of burns or scalding due to
excessively hot water at xtures. Adjust and maintain the mixing valve in accordance with the
manufacturer's instructions.
Figure 12: Schematic Tankless Heater Piping
TABLE 3: TANKLESS HEATER DATA
Boiler
Model
CL3-091 2.25 2.75 2.3 3.9 CL3-105 2.25 3.00 2.3 4.7 CL3-140 2.50 3.25 3.1 5.6 CL4-126 2.50 3.25 3.1 5.6 CL4-175 2.75 3.75 3.9 7.2 CL4-210 3.00 4.00 4.7 8.0 CL5-168 2.75 3.50 3.9 6.4 CL5-245 3.25 4.25 5.6 8.8 CL5-280 3.50 4.75 6.4 9.6
THE FOLLOWING GUIDELINES SHOULD BE FOL­LOWED WHEN PIPING THE TANKLESS HEATER:
1.
FLOW REGULATION — If ow through the heater
2. TEMPERING OF HOT WATER — Installation
Rating (Gal/Min)
Steam Water Steam Water
is greater than its rating, the supply of adequate hot water may not be able to keep up with the demand.
For this reason a ow regulator matching the heater
rating should be installed in the cold water line to
the heater. The ow regulator should preferably be
located below the inlet to the heater and a minimum of 3’ away from the inlet so that the regulator is not subjected to excess temperatures that may occur during “off” periods when it is possible for heat to be conducted back through the supply line. The
ow regulator also limits the ow of supply water
regardless of inlet pressure variations in the range of 20 to 125 psi.
of an automatic mixing valve will lengthen the delivery of the available hot water by mixing some cold water with the hot. This prevents excessive
and possibly scalding hot water at the xtures. In
Pressure Drop
(PSI)
14
3. FLUSHING OF HEATER — All water contains some sediment which settles on the inside of the coil. Consequently, the heater should be periodically backwashed. This is accomplished by installing hose bibs as illustrated and allowing water at city pressure to run into hose bib A, through the heater, and out hose bib B until the discharge is clear. The tees in which the hose bibs are located should be the same size as heater connections to minimize pressure drop.
HARD WATER — A water analysis is necessary to
4. determine the hardness of your potable water. This is applicable to some city water and particularly to well water. An appropriate water softener should be installed based on the analysis and dealer’s
recommendation. This is not only benecial to the tankless heater but to piping and xtures plus the many other benets derived from soft water.
J. INSTALL SMOKEPIPE — The CL Series boiler
should be vented into a reclay tile-lined masonry
chimney or chimney constructed from type L vent or a factory built chimney that complies with the type HT requirements of UL103. The chimney and vent
pipe shall have a sufcient draft at all times, to assure
safe proper operation of the boiler. See Figure 13 for recommended installation.
1. Install a draft regulator (supplied by installer) following the instructions furnished with the regulator. See Figure 14 for draft regulator locations.
2. Consider the chimney overall. Chimneys that have a high heat loss may become less suitable as the
heat loss of the home goes down and the efciency
of the boiler installed goes up. Most homes have a chimney appropriate for the fuel and the era in which the home was built. That may have been a
coal red or an inefcient oil red boiler built into
a home without insulation or storm windows. With increasing fuel prices that home probably has been
insulated and tted with storm windows so that
Page 15
Figure 13 Recommended Smokepipe Arrangement
and Chimney Requirements
the heat loss of the home has been reduced. This requires less fuel to be burned and sends less heat up the chimney.
A new boiler probably has a higher efciency than
the boiler being replaced. That probably means that the stack temperature from the new boiler will be lower than that from the old boiler and with less room air being drawn up the chimney to dilute the stack gases. The combination of a large uninsulated
chimney, reduced ring rate, reduced ring time,
lower stack temperature and less dilution air can,
in some cases, contribute to the condensing of small amounts of water vapor in the chimney. Such condensation, when it occurs, can cause chimney deterioration. In extreme cases, condensed water may be visible on the outside of the breeching or chimney. In those extreme cases, the chimney may have to be lined to insulate the chimney and thus prevent the condensation. The addition of dilution air into the chimney may assist in drying the chimney interior surfaces.
A massive chimney on a cold, or exposed outside
wall may have produced adequate draft when it
was red with a higher input and greater volumes
of heated gases. With reduced input and volume, the draft may be severely affected. In one instance research showed a new chimney of adequate sizing produced only .035" W.C. after 30 minutes
of continuous ring at 13.0% CO2. Outside wall
chimneys take longer to heat up and can have .00" W.C. draft at burner startup. You may have to
consider a special alloy chimney ue liner with
insulation around it and a stabilizing draft cap or even a draft inducing fan in severe cases.
3. For the same reasons as in 2. above, heat extractors mounted into the breeching are not recommended.
IMPORTANT
Single-pipe installations must be absolutely airtight or leaks or loss of prime may result. Bleed line and fuel unit completely.
Figure 14: Proper and Improper Locations of Draft Regulator
15
Page 16
K. FUEL UNITS AND OIL LINES
SINGLE-PIPE OIL LINES Standard burners are
provided with single-stage 3450 rpm fuel units with the by-pass plug removed for single-pipe installations.
The single-stage fuel unit may be installed single-pipe
with gravity feed or lift. Maximum allowable lift is 8 feet. See Figure 15.
TWO-PIPE OIL LINES For two-pipe systems
where more lift is required, the two-stage fuel unit is recommended. Table 4 (single-stage) and Table 5 (two­stage) show allowable lift and lengths of 3/8-inch and 1/2-inch OD tubing for both suction and return lines. Refer to Figure 16.
Be sure that all oil line connections are absolutely
airtight. Check all connections and joints. Flared
ttings are recommended. Do not use compression ttings.
Open the air-bleed valve and start the burner. For clean
bleed, slip a 3/16" ID hose over the end of the bleed valve and bleed into a container. Continue to bleed for 15 seconds after oil is free of air bubbles. Stop burner and close valve.
Figure 15
TABLE 4: SINGLE STAGE UNITS (3450 RPM) TWO PIPE SYSTEMS
Maximum Length of Tubing
Lift "H"
(See Figure)
0' 84' 100' 1' 78' 100' 2' 73' 100' 3' 68' 100' 4' 63' 100' 5' 57' 100' 6' 52' 100' 7' 47' 100' 8' 42' 100'
9' 36' 100' 10' 31' 100' 11' 26' 100' 12' 21' 83' 13' --- 62' 14' --- 41'
"H" + "R" (See Figure)
3/8" OD
Tubing (3 GPH)
1/2" OD
Tubing (3 GPH)
Figure 16
TABLE 5: TWO-STAGE UNITS (3450 RPM) TWO-PIPE SYSTEMS
Maximum Length of Tubing
Lift "H"
(See Figure)
0' 93' 100' 2' 85' 100' 4' 77' 100' 6' 69' 100'
8' 60' 100' 10' 52' 100' 12' 44' 100' 14' 36' 100' 16' 27' 100' 18' --- 76'
"H" + "R" (See Figure)
3/8" OD
Tubing (3 GPH)
1/2" OD
Tubing (3 GPH)
16
Page 17
L. INSTALL ELECTRIC WIRING in accordance with
National Electrical Code and local regulations. A separate electrical circuit must be run from the main electrical service with an over-current device/disconnect
in the circuit. A service switch is recommended and may be required by some local jurisdictions. Wiring should conform to Figures 17 thru 19B.
Figure 17: Wiring Diagram for Water Boilers With Beckett AFG Burner and
Split Controls Less Tankless Heater
SEQUENCE OF OPERATION
A call for heat by the thermostat energizes the L7248C control which in turn energizes the primary control. The burner will initiate ignition after completing a 15 second pre-purge cycle. If burner ignites within approximately 45 seconds
and the cad cell sees ame, the burner will continue to operate until the call for heat is satised or the setting of the
high limit is reached. The circulator will operate as long as the thermostat is calling for heat. If the thermostat is not
satised and the high limit is reached, the circulator will continue to operate, and the burner will stop until the high limit
is closed by a drop in boiler water temperature.
17
Page 18
Figure 17A: Wiring Diagram for Water Boilers With Carlin EZ-HP Burner and
Split Controls Less Tankless Heater
18
Figure 17B: Wiring Diagram, Water without Tankless Heater, Riello Burner
Page 19
Figure 18: Wiring Diagram for Water Boilers with Beckett AFG Burner and
Split Controls with Tankless Heater
SEQUENCE OF OPERATION
A call for heat by the thermostat energizes the L7224C control which in turn energizes the primary control. The burner will initiate ignition after completing a 15 second pre-purge cycle. If burner ignites within approximately 45 seconds
and the cad cell sees ame the burner will continue to operate until the call for heat is satised. The circulator will also
operate when the thermostat calls for heat if the boiler water temperature is up to the setting of the low limit in the L7224C control. If boiler water temperature is below the low limit setting the burner will operate but the circulator will not, giving preference to the domestic hot water demand.
On call for heat by the thermostat the burner will continue to operate until the thermostat is satised or the setting of the high limit is reached. If the thermostat is not satised when the high limit is reached the burner will stop but the circulator will continue to operate until the thermostat is satised.
Any time the boiler water temperature drops below the setting of the low limit the burner will be energized in order to maintain domestic water temperature.
19
Page 20
Figure 18A: Wiring Diagram for Water Boilers with Carlin EZ-PH Burner and
Split Controls with Tankless Heater
20
Figure 18B: Wiring Diagram, Water with Rear Tankless Heater, Riello Burner
Page 21
Figure 19: Wiring Diagram, Steam Boilers With or Without Tankless Heater,
McDonnell & Miller PS-801 Probe LWCO, Beckett AFG Burner
SEQUENCE OF OPERATION
When the thermostat calls for heat, it energizes the cad cell primary control. The burner will initiate ignition after com-
pleting 15 second pre-purge cycle. The burner will operate until the thermostat is satised or the limit setting on the
high limit is reached. When the high limit control restores the circuit on a drop in pressure, the burner will start if the thermostat is still calling for heat. The low water cut off will shut down the burner if the water level in the boiler drops too low. The control resets and restarts the burner with a call for heat a few seconds after the water is returned to its normal level. The McDonnell Miller low water cut off incorporates a 10 second delay to prevent nuisance burner cut-off due to rapid
water level uctuations. The LWCO also has a time delay of 15 seconds which allows additional ll time after water
touches the probe. Red LED indicates a low water condition.
On burner start, if the cad cell does not see ame within approximately 45 seconds, primary control will lock out on
safety and must be reset before burner can be restarted. When there is no demand for heat, the operating control will maintain the boiler water temperature at the selected set­ting for proper operation of the domestic water heater, if equipped with optional tankless heater.
21
Page 22
Figure 19A: Wiring Diagram, Steam Boilers With or Without Tankless Heater,
McDonnell & Miller PS-801 Probe LWCO, Carlin EZ-HP Burner
22
Figure 19B: Wiring Diagram, Steam with or without Tankless Heater,
Optional McDonnell & Miller PS-801 Probe LWCO, Riello Burner
Page 23
III. Indirect Water Heater Piping
A. CONNECT Alliance™ or other Indirect Water Heater Piping as shown in Figures 15 and 16. Refer to Alliance™ or other
Indirect Water Heater Instruction Manual for additional installation information.
Figure 20: Indirect Water Heater Piping on CL Series Water Boiler
1.
CL SERIES WATER BOILER - Figure 20 shows indirect water heater piping on typical hot water heating system. Boiler
piping is the same as for any two-zone system. Figure 20 shows circulator zoning, which is usually preferred for indirect
water heaters. Size the circulator and indirect water heater piping to obtain the boiler water ow through the indirect
water heater called for by the indirect water heater manufacturer. Refer to the indirect water heater instruction manual for additional details.
Figure 21: Indirect Water Heater Piping on CL Series Steam Boiler
CL SERIES STEAM BOILER - All CL Series steam boilers are equipped with tappings to permit the connect of an
2. Alliance™ or other indirect water heater. In this type of system, hot boiler water is drawn from below the water line and passed through the heat exchanger in the indirect water heater. This section describes boiler-side piping only. Refer to the indirect water heater instruction manual for additional details.
23
Page 24
IV. Operating and Service Instructions
A. ALWAYS INSPECT INSTALLATION BEFORE
STARTING BURNER.
B. FILL HEATING SYSTEM WITH WATER.
1. Hot Water Boilers: Fill entire Heating System with water and vent air from system. Use the following procedure on a Series Loop System installed as per Figure 9:
Close all but one zone valve.
a. b. Open drain valve on boiler.
c. Open ll valve.
d. Close purge valve. e. Open relief valve on boiler. f. Allow water to run out of drain valve until zone
has been purged of air and lled with water.
g.
Open zone valve to the second zone to be
purged, then close the rst. Repeat this step until
all zones have been purged but always have one
zone open. At completion open all zone valves. h. Close drain valve. i. When water discharges from relief valve, release
the lever on the top of the relief valve, allowing
it to close.
j. Continue lling the system until the pressure
gauge reads 12 psi. Close ll valve.
C. CHECK CONTROLS, WIRING AND BURNER to be
sure that all connections are tight and burner is rigid, that all electrical connections have been completed and
fuses installed, and that oil tank is lled and oil lines
have been tested.
D. LUBRICATION
1. Follow instruction on burner and circulator label to lubricate, if oil lubricated. Most motors currently used on residential type burners employ permanently lubricated bearings and thus do not
require any eld lubrication. Water lubricated circulators do not need eld lubrication.
2. Do not over-lubricate. This can cause as much trouble as no lubrication at all.
3. On WATER BOILERS WITH TANKLESS
HEATERS equipped with L7224 electronic aquastat controller, set operating control (low limit [LL]) at 190°F and high limit (HL) at 210°F. Operating control (low limit) setting must be a minimum of 20°F below high limit setting.
L7224 controller has the High Limit adjustment
range from 130°F to 240°F (55°C to 116°C), and the Low Limit adjustment range from 110°F to 220°F (43°C to 104°C). High Limit Differential is
xed at 10°F (6°C), and Low Limit Differential has
adjustment range from 10°F (6°C) to 25°F (14°C).
ADJUSTING AQUASTAT CONTROLLER
4. SETTINGS. To discourage unauthorized changing of Aquastat settings, a procedure to enter the
ADJUSTMENT mode is required. To enter the ADJUSTMENT mode, press the UP, DOWN, and I buttons (refer to Figure 22) simultaneously for
three seconds. Press the I button until the feature requiring adjustment is displayed:
• HL_ High Limit.
• LL_ Low Limit.
• Ldf Low Limit Differential.
• °F °C.
Then, press the UP and/or DOWN buttons to
move the set point to the desired value. After 60 seconds without any button inputs, the control will automatically return to the RUN mode.
Note that L7224 Aquastat Controller will display all
four (4) above-listed adjustment features, but L7248 Aquastat Controller will not display Low Limit and Low Limit Differential adjustment features.
5. DISPLAY READOUT
In the RUN mode, the Aquastat will ash "bt"
(boiler temp) followed by the temperature (i.e.,
220), followed by °F or °C.
E. ADJUST CONTROL SETTINGS with burner
service switch turned “ON”.
1. SET ROOM THERMOSTAT about 10°F below room temperature.
2. On WATER BOILERS WITHOUT TANKLESS HEATERS equipped with L7248 electronic aquastat controller, set High Limit (HL) at 180°F. This temperature can be varied to suit installation requirements. L7248 controller has the High Limit adjustment range from 180°F to 240°F (82°C to
116°C). High Limit Differential is xed at 15°F
(8°C).
24
Figure 22: L7248/L7224 Circuit Board Layout -
Horizontal Mount
Page 25
To read boiler settings, press the I key to read the
parameter of interest. For example, press I High Limit (HL) is displayed, followed by a three-digit number, i.e., 220, followed by °F or °C. Pressing the I button again (on L7224 models) will display the Low Limit (LL) followed by a three-digit number and the corresponding degree designator. See Display Readout, Figure 23.
After approximately 60 seconds without any key
presses, the display will enter a dim display mode. To return to the bright display mode, simply press any key.
d. Error: The controller has detected an error
condition (e.g., open sensor) and has shut down the burner output. The ZC output is energized. The controller continues to monitor the system and automatically restarts if the error condition clears. Refer to Table 6. Refer to Table 8 for Trouble Shooting Guide.
TABLE 6: LED ERROR CODES
Error
Code
Err1 Sensor fault; check sensor. Err2 ECOM fault; check EnviraCOM™ wiring. Err3 Hardware fault; replace control. Err4 B1 fault; check B1 wiring/voltage. Err5 Low Line; check L1-L2, 110 Vac. Err6 Fuse; check ECOM wires, replace fuse.
Err7
Err8
EEPROM, HL, LL, Hdf, Ldf; reset to default
values. Restore desired settings.
Repeated B1 fault (voltage present at B1 when
output is turned off); check B1 wiring/voltage.
Cause / Action
The operating sequence for the L7224/L7248 is
shown in Table 7.
Figure 23: Display Readout Denitions
6. OPERATION The L7224 model can be in any of four operational
states - Normal, High Limit, Low Limit and Error. The controller moves back and forth from High Limit to Normal to Low Limit state as part of normal operation.
The L7248 model is restricted to three operational
states - Normal, High Limit and Error. The controller moves back and forth from High Limit to Normal state as part of normal operation.
For both models, the controller will enter the Error
state when there is an abnormal condition. The operating states are:
a. Normal: Boiler temperature went below the
High Limit setting (minus the Differential) and has not exceeded the High Limit setting; or the boiler temperature went above the Low Limit setting and has not gone below the Low Limit setting (minus the Differential).
b. High Limit: Boiler temperature went above the
High Limit setting and has not dropped below the High Limit setting (minus the Differential).
c. Low Limit: Boiler temperature went below
the Low Limit setting (minus the Low Limit Differential) and has not gone above the Low Limit setting.
TABLE 7: L7248/L7224 CONTROLLER
OPERATING SEQUENCE
Action System Response
Thermostat
calls for heat.
Boiler
exceeds the
High Limit.
Thermostat is
satised.
Error
condition 1-5.
Error
condition 6.
Error
condition 7.
Error
condition 8.
Circulator starts when water temperature is above Low Limit setting (if applicable).
Boiler temperature is checked. Burner
starts when water temperature is below
High Limit setting.
Burner is turned off. Burner restarts when
the water temperature drops below the
High Limit setting minus the Differential.
Circulator and burner turn off.
If an error condition is detected, all outputs
except ZC are shut down. Burner is off.
Control continues to function and restarts
when error is corrected.
During the error check sequence, the
system checks for drift in the sensor and
corrosion in the connections.
EnviraCOM communication is not
available.
The control has reset the High Limit, Low
Limit and Differential setting to a default
setting and will continue to run at those
settings.
Performance of the system will be
degraded.
If the error condition is detected, all
outputs except ZC are shut down. Burner
is off. Control continues to function and
restarts when all three user keys have
been pressed longer than 60 seconds.
25
Page 26
TABLE 8: TROUBLE SHOOTING GUIDE
System Condition Diagnostic Condition Check Action
Boiler is cold, house is
cold.
Boiler is hot, house is
cold.
Display is OFF. 120 Vac System power. Turn system power on.
Display is ON. 24 Vac T-T No 24 V; replace control.
24 V present; disconnect
thermostat, short T-T.
120 Vac at B1-B2 • If no, replace control.
Refer to Err on display. -----
Display is ON. 120 Vac at C1-C2 • 120 Vac at C1-C2, check wiring
Boiler below the Low Limit
temperature, wait for boiler to go
above Low Limit temperature.
Boiler above LL? If yes, check
for 120 Vac between ZC and L2.
Boiler starts, check wiring and thermostat.
• If yes, check burner and wiring.
to pump.
• Wiring OK, is pump running?
• If not, replace the pump.
• If pump is running, check for
trapped air or closed zone valves
• If no 120 Vac , replace control.
• If yes, check zone relays, circulators and wiring.
-----
7. HIGH LIMIT CONTROLLER The High Limit opens and turns off the burner
when the water temperature reaches the setpoint. The High Limit automatically resets after the water temperature drops past the setpoint and through the Differential. The L7248 models have High Limit Differential presets of 15°F (8°C). The L7224 models have High Limit Differential presets of 10°F (6°C).
8.
LOW LIMIT AND CIRCULATOR CONTROLLER
On a temperature rise, with the adjustable
Differential at the default setting of 10°F (6°C), the burner circuit breaks and the circulator circuit makes (assuming no call for heat is present) at the Low Limit setpoint. On a temperature drop of 10°F (6°C) below the Low Limit setpoint, the burner circuit makes and the circulator circuit breaks. See Figure 24.
F. REMOVE GUN ASSEMBLY
1. CL Series boilers are equipped with Beckett AFG burners. Items to be checked are nozzle size, head size, gun setting, and positioning of electrodes. This information is shown in Figure 25 and Table 9 at rear of manual.
2. CL Series boilers are equipped with Carlin EZ-HP burners. Items to be checked are nozzle size, head bar size, gun setting, and positioning of electrodes. This information is shown in Figure 25A and Table 9 at rear of manual.
3. Reinstall gun assembly.
26
Figure 24: Setpoints and Differentials
Figure 25: "L1" and "V1" Head Electrode
Positioning and Gun Setting (Beckett AFG)
Page 27
Figure 25A: Electrode Settings (Carlin EZ-HP)
G. ADJUST OIL BURNER BEFORE STARTING.
1. SET BURNER AIR BAND AND AIR SHUTTER, see Table 9 at rear of manual.
2. Inspect Beckett head setting on left side of burner by insuring the blue line MD(V1) or the line on the label MB(L1) are aligned, readjust if necessary. Refer to Figure 25.
3. Inspect Carlin head setting on left side of burner to ensure that the proper head positioning bar matches the nozzle that is installed in drawer assembly.
Replace bar if necessary. Carlin burners for boiler models CL3-140 and
CL4-210 have the higher ring rate nozzle installed
and two (2) loose nozzles with a head positioning bar kit attached to the nozzle line. Refer to Table 9 for proper nozzle size, air settings and fuel pump
pressure setting based on desired ring rate.
If the desired ring rate is the lower GPH:
a. replace the factory installed high ring rate
nozzle with one of the loose lower ring rate
nozzles.
b. replace the factory installed head positioning bar
with the corresponding head bar that matches the lower GPH nozzle installed, see Table 9.
c. change the factory air settings according to Table
9 and,
d. check the oil pump pressure and adjust if
necessary to the setting specied in Table 9, refer
to Paragraph H, Step 5 for details.
4. INSPECT RIELLO BURNER AIR DAMPER AND TURBULATOR SETTING, readjust if necessary, see Table 9a.
a. Remove pressure port/bleeder plug from fuel
pump and install Riello Combination Pressure Gauge and Bleeder Valve Assembly.
5. OPEN ALL OIL LINE VALVES.
6. ATTACH A PLASTIC HOSE TO FUEL PUMP VENT FITTING and provide a pan to catch the oil.
7. OPEN FLAME OBSERVATION DOOR on front of boiler.
H. START OIL BURNER.
1. Open vent tting on fuel pump.
2. TURN ‘ON’ BURNER service switch and allow
burner to run until oil ows from vent tting
in a SOLID stream without air bubbles for approximately 10 seconds.
3. Close vent tting and burner ame should start
immediately after pre-purge is complete. Pre-purge
prevents burner ame until 15 seconds has elapsed
after initial power is applied to burner. During pre-purge, the motor and ignitor will operate but the oil valve will remain closed. Refer to Oil Primary Control Instructions for more details.
Figure 26: Adjusting Fuel Pump Pressure
ADJUST OIL PRESSURE for Beckett AFG burners
4. (shut the burner off).
When checking a fuel unit's operating pressure, a
a.
reliable pressure gauge may be installed in either the bleeder port or the nozzle port. See Figure
26.
b. Locate oil pressure adjusting screw and turn
screw for appropriate pump pressure, refer to Table 9 at rear of manual.
c. To check the cutoff pressure, deadhead a reliable
pressure gauge onto the copper connector tube attached to the nozzle port. Run the burner for a short period of time. Shut the burner off. The pressure should drop and hold.
d. Remove the gauge and install bleeder port and/or
reconnect the nozzle port line.
5. VERIFY/ADJUST FUEL PUMP PRESSURE for Carlin EZ-HP burners.
a. Turn “off” burner service switch.
27
Page 28
Figure 26A: Adjusting Fuel Pump Pressure
b. When checking a fuel pump’s operating pressure,
a reliable pressure gauge may be installed in either the gauge port or the bleeder port. See Figure 26A.
a. CL3 through CL5 Move the turbulator setting forward or back one
position at a time to optimize the smoke and CO2 readings.
4. Turn “OFF” burner and remove Riello Combination Pressure Gauge and Bleeder Valve Assembly. Install pressure port/bleeder plug and tighten. Start burner again.
5. FLAME FAILURE
The CL Series boiler controls operate the burner
automatically. If for unknown reasons the burner
ceases to re and the reset button on the primary
control has tripped, the burner has experienced ignition failure. Before pressing the reset button call your heating contractor immediately.
WARNING
Do not attempt to start the burner when excess oil
has accumulated, when the unit is full of vapor, or when the combustion chamber is very hot.
7. CAD CELL LOCATION AND SERVICE
The burner is supplied with a cadmium sulde ame
detector mounted at the factory, mounted on the bottom of the electronic ignitor. See Figure 27. To service cad cell or to replace the plug in portion, swing open the ignitor. After service is complete, be sure to fasten down the ignitor.
6. VERIFY/ADJUST OIL PRESSURE for Riello 40 burner.
Adjust oil pressure. Locate oil pressure adjusting
screw and turn screw to obtain proper pump pressure, refer to Figure 8 and Table 9A.
I. ADJUST OIL BURNER WHILE OPERATING.
(ame present)
1. ADJUST DRAFT REGULATOR for a draft of
-0.02” (water gauge) over the re after chimney has
reached operating temperature and while burner is running.
2. READJUST THE AIR DAMPER SETTING on the
burner for a light orange colored ame while the draft over the re is -0.02”. Use a smoke tester and
adjust air for minimum smoke (not to exceed #1)
with a minimum of excess air. Make nal check
using suitable instrumentation to obtain a CO2 of
11.5 to 12.5% with draft of -0.02” (water gauge) in re box. These settings will assure a safe and efcient operating condition. If the ame appears stringy instead of a solid re, try another nozzle of
the same type. Flame should be solid and compact. After all adjustments are made recheck for a draft of
-0.02” over the re.
3. READJUST THE TURBULATOR SETTING only if necessary.
28
Figure 27: Cad Cell Location
J. CHECK FOR CLEAN CUT OFF OF BURNER.
1. AIR IN THE OIL LINE between fuel unit and nozzle will compress when burner is on and will expand when burner stops, causing oil to squirt from nozzle at low pressure as burner slows down and causing nozzle to drip after burner stops. Usually cycling the burner operation about 5 to 10 times will rid oil line of this air.
2. IF NOZZLE CONTINUES TO DRIP, repeat Paragraph J, Step 1. If this does not stop the dripping, remove cutoff valve and seat, and wipe both with a clean cloth until clean, then replace
Page 29
and readjust oil pressure. If dripping or after burn persist replace fuel pump.
K. TEST CONTROLS.
WARNING
Before installation of the boiler is considered complete, the operation of all boiler controls must be checked, particularly the primary control and high limit control.
1. CHECK THERMOSTAT OPERATION. Raise and lower thermostat setting as required to start and stop burner.
VERIFY PRIMARY CONTROL SAFETY
2. FEATURES using procedures outlined in Instructions furnished with control or instructions as follows:
CHECKOUT PROCEDURE
a. Check wiring connections. Close line switch.
Check power at control. PRIMARY RELAY TEST b. Disconnect cad cell leads from quick connects
on underside at primary control. Reset safety
switch. c.
Set controller to call for heat. Burner should
start. d. Jumper the quick connect terminals within 15 to
30 seconds. Burner should run. e. Remove the quick connect terminals jumper.
Burner shuts down in approximately 15 to 60
seconds.
f. If burner operates as described, relay is good. If
not, install new relay. CAD CELL TEST (see Figure 27) g. Open line switch. Clean cell face and see that
cell is securely in socket. Reconnect leads. Reset
safety switch. h. Close line switch. If burner starts and runs
beyond safety switch cut-out time, cell is good.
If not, install new cell.
3. WARNING — Check High Limit Control — Jumper Thermostat Terminals. Allow burner to operate until shut-down by limit. Installation is not considered complete until this check has been made.
REMOVE JUMPER.
4. Check low water cut off control with water level at normal water line (see Figures 1C and 1D). Raise thermostat setting to allow burner to operate. Open boiler drain to allow water level to drop to bottom of sight glass until burner operation is shut-down by low water cut-off.
Close boiler drain and rell to normal water line.
Burner should automatically restart during ll.
Lower thermostat setting.
CHECK OPERATING CONTROL on boiler
5. equipped with tankless heaters. With burner off, draw hot water until burner starts, then turn off hot water and check burner shut-down.
IF CONTROLS DO NOT MEET REQUIREMENTS
AS OUTLINED ABOVE, REPLACE CONTROL AND REPEAT CHECK-OUT PROCEDURES.
29
Page 30
V. Maintenance and Service Instructions
A. MAINTENANCE OF LOW WATER CUT-
OFF DEVICES
WARNING
Probe and oat type low water cut-off devices require annual inspection and maintenance.
1. Although these devices are solid state in their operation, the probe is exposed to possible contamination in the boiler water and subject to fouling.
It is important to physically remove the probe from
2. the boiler tapping annually and inspect that probe for accumulation of scale or sediment.
3. Follow these steps to inspect, clean and/or replace the probe: a. Turn off electric service to the boiler.
b. Drain boiler water to a level below the tapping
for the probe.
DANGER
Assure that the boiler is at zero pressure before
removing the LWCO probe. Do not rely on the pressure gauge to indicate that the boiler is at
zero pressure. Open the safety valve to relieve
all internal pressure prior to proceeding. Safety valve discharge piping must be piped such that the potential for burns is eliminated.
c. Disconnect wiring connections between the low
water cut-off control and the probe.
d.
Remove the low water cut-off control from the
probe.
e. Unscrew the probe from the boiler tapping. f. Inspect that portion of the probe that is exposed
to the boiler water for a scale or sediment buildup.
g. Light deposits may be removed by wiping the
probe with a damp cloth. Wiping the probe with a cloth soaked in vinegar will remove more tenacious lime deposits. The most stubborn deposits may be removed from the probe by using a diluted amount, 3 parts of water to 1 part of phosphoric acid (H2PO4).
CAUTION
Exercise caution when handling phosphoric acid
and follow the instruction label on its container.
h. Clean the pipe threads of the probe to remove
old, hardened pipe dope and other foreign matter.
Apply a moderate amount of good quality pipe
i.
dope to the pipe threads on the probe, leaving the
two end threads bare. Do not use PTFE (Teon)
tape. j. Screw the probe into the boiler tapping. k. Mount the low water cut-off control on the
probe.
Reconnect the control to probe wiring.
l. m. Fill the boiler to its normal waterline. n. Add boiler water treatment compound as needed
(refer to Paragraph B.). o. Restore electric service to the boiler. p. Fire burner to bring the water in the boiler to a
boil to drive off free oxygen. q.
WARNING — BEFORE RETURNING
BOILER TO SERVICE: Follow the low water
cut-off check out procedure in Section IV.
Operating & Service Instructions.
B. BOILER AND SYSTEM CLEANING
INSTRUCTIONS FOR TROUBLE FREE OPERATION.
1. STEAM BOILERS: a. Oil, greases & sediments which accumulate in a
new boiler and piping must be removed from the system in order to prevent an unsteady water line and carry over of the water into the supply main above boiler.
Operate the boiler with steam in the entire
system for a few days allowing the condensate to return to the boiler. If the condensate can temporarily be wasted, operate boiler only for the length of time it takes for condensate to run clear. If the latter cannot be achieved or if the condensate is returned to the boiler, boil out the boiler using the SURFACE BLOW-OFF connection.
i. Drain boiler until 1” of water is visible in
gauge glass. Run temporary 1½” NPT pipe line from the surface blow-off connection to an open drain or some other location where hot water may be discharged safely. Do not install valve in this line.
ii.
Drain about 5 gallons of hot water from
boiler into a container and dissolve into it an appropriate amount of recommended boil out compound. Remove safety valve & add solution to boiler water thru exposed tapping using a funnel.
30
Page 31
NOTICE
Check with local authorities or consult local water treatment services for acceptable chemical cleaning compounds.
Start burner and operate sufciently to boil
iii.
the water without producing steam pressure. Boil for about 5 hours. Open boiler feed
pipe sufciently to permit a steady trickle
of water from the surface blow-off pipe. Continue this slow boiling and trickle of
overow for several hours until the water coming from the overow is clear.
iv.
Stop burner and drain boiler in a manner
and to a location that hot water can be discharged with safety.
Rell boiler to normal water line. If water
v.
in gauge glass does not appear to be clear, repeat steps (i. thru iii.) and boil out the boiler for a longer time.
b. Low pressure steam boilers such as the CL
Series should be maintained with appropriate water treatment compounds. Add suitable water treatment compounds as recommended by your
qualied water treatment company.
c. Remove temporary surface blow-off piping, plug
tapping and reinstall safety valve. Boil or bring water temperature to 180°F promptly in order to drive off the dissolved gases in the fresh water.
d. If unsteady water line, foaming or priming
persist, install gate valve in Hartford Loop and drain valves in return main and at boiler as shown in Figure 9 and proceed as follows:
i Connect hoses from drain valves to oor
drain. Close gate valve in Hartford Loop and open drain valve in return main. Fill boiler to normal water level, turn on oil burner and operate boiler at this water level for at least 30 minutes after the condensate begins to run hot, then turn off burner.
Close all radiator valves. Remove all supply
main air valves and plug the openings in supply main.
ii. Draw about 5 gallons of hot water from
boiler into a container and dissolve into it the appropriate amount of a recommended boilout compound. Remove safety valve from boiler and pour this solution into boiler, then reinstall safety valve.
iii. Turn on oil burner and keep operating while
feeding water to boiler slowly. This will raise water level in boiler slowly so that water will be boiling hot and will rise slowly into supply main and back through return
main, owing from drain hose at about
180°F. Continue until water runs clear from drain hose for at least 30 minutes.
iv. Stop feeding water to boiler but continue
operating oil burner until excess water in
boiler ows out through supply main and
water lowers (by steaming) until it reaches normal level in boiler. Turn off oil burner. Drain boiler. Open all radiator valves. Reinstall all supply main air valves. Open gate valve in Hartford Loop.
v. When boiler has cooled down sufciently
(crown sheet of sections are not too hot to touch), close the drain valves at boiler and in return main and feed water slowly up to normal level in boiler. Turn on oil burner and allow boiler to steam for 10 minutes, then turn off burner. Draw off one quart of
water from bottom gauge glass tting and
discard. Draw off another quart sample and if this sample is not clear, repeat the cycle of draining the boiler and return main and
relling the boiler until sample is clear.
vi. If the boiler water becomes dirty again
at a later date due to additional sediment loosened up in the piping, close gate valve in Hartford Loop, open drain valve in return main, turn on oil burner and allow
Condensate to ow to drain until it has run
clear for at least 30 minutes while feeding water to boiler so as to maintain normal water level. Turn off oil burner, drain boiler, open gate valve in Hartford Loop, then repeat the full "Boiler and System Cleaning" procedure outlined in Paragraph B starting
on Page 30. e. Make pH or Alkalinity Test. After boiler and system have been cleaned and
relled as previously described, test the pH of
the water in the system. This can easily be done by drawing a small sample of boiler water and testing with hydrion paper which is used in the same manner as litmus paper, except it gives
specic readings. A color chart on the side of the
small hydrion dispenser gives the reading in pH. Hydrion paper is inexpensive and obtainable from any chemical supply house or through your local druggist. The pH should be higher than 7, but lower than 11. Add some of the washout chemical (caustic soda), if necessary, to bring the
pH within the specied range.
f. Boiler is now ready to be put into service.
2. WATER BOILERS: a. Filling of boiler and system. GENERAL — In a hot water heating system,
the boiler and entire system (other than the expansion tank) must be full of water for satisfactory operation. Water should be added to the system until the boiler pressure gauge registers 12 psi. To insure that the system is full,
31
Page 32
water should come out of all air vents when opened.
b. BOILING OUT OF BOILER AND SYSTEM.
The oil and grease which accumulate in a new hot water boiler can be washed out in the following manner:
i. Remove relief valve using extreme care to
avoid damaging it.
ii. Add an appropriate amount of recommended
boil out compound.
iii. Replace relief valve. iv. Fill the entire system with water. v. Start ring the boiler. vi. Circulate the water through the entire
system.
vii. Vent the system, including the radiation. viii. Allow boiler water to reach operating
temperature, if possible.
ix. Continue to circulate the water for a few
hours.
x. Stop ring the boiler. xi. Drain the system in a manner and to a
location that hot water can be discharged with safety.
xii. Remove plugs from all available returns
and wash the water side of the boiler as thoroughly as possible, using a high­pressure water stream.
xiii. Rell the system with fresh water.
c. Add appropriate boiler water treatment
compounds as recommended by your qualied
water treatment company.
d. Make pH or Alkalinity Test. After boiler and system have been cleaned and
relled as previously described, test the pH of
the water in the system. This can easily be done by drawing a small sample of boiler water and testing with hydrion paper which is used in the same manner as litmus paper, except it gives
specic readings. A color chart on the side of the
small hydrion dispenser gives the reading pH. Hydrion paper is inexpensive and obtainable from any chemical supply house or through your local druggist. The pH should be higher than 7 but lower than 11. Add some of the washout chemical (caustic soda), if necessary, to bring the
PH within the specied range.
e. Boiler is now ready to be put into service.
3. EXCESSIVE MAKE-UP WATER A leaky system will increase the volume of make-up
water supplied to the boiler, which can signicantly
shorten the life of the boiler. Entrained in make­up water are dissolved minerals, salts and oxygen. When the fresh, cool make-up water is heated in the boiler, the minerals fall out as sediment, the salts
32
IMPORTANT
IF, DURING NORMAL OPERATION, IT IS NECESSARY TO ADD MORE WATER THAN INDICATED BELOW, CONSULT A QUALIFIED SERVICE TECHNICIAN TO CHECK YOUR SYSTEM FOR LEAKS.
Model No.
CL3 0.3 4
4 0.4 5
CL CL5 0.5 6
coat the inside of the boiler, and the oxygen escapes as a gas. The accumulation of sediment eventually isolates the water from contacting the cast iron. When this happens the cast iron in that area gets extremely hot and eventually cracks. The presence of free oxygen or chloride salts in the boiler corrodes the cast iron from the inside. More make­up water and higher concentrations of contaminants damage the boiler sooner. Our warranty does not cover corrosion and sediment-related damage. Clearly it is in everyone’s best interest to prevent this type of failure. You can do your part by ensuring that your system is leak-free, keeping leakage to less than 2 percent of the total water volume each month.
Gallons Per
Month
C. HINTS ON COMBUSTION
1. NOZZLES — Although the nozzle is a relatively inexpensive device, its function is critical to the successful operation of the oil burner. The selection of the nozzle supplied with the CL boiler is the
result of extensive testing to obtain the best ame shape and efcient combustion. Other brands of the
same spray angle and spray pattern may be used but may not perform at the expected level of CO2 and smoke. Nozzles are delicate and should be protected from dirt and abuse. Nozzles are mass-produced and can vary from sample to sample. For all of those reasons a spare nozzle is a desirable item for a serviceman to have.
2. FUEL LEAKS — Any fuel leak between the pump and the nozzle will be detrimental to good combustion results. Look for wet surfaces in the air tube, under the ignitor, and around the air inlet. Any such leaks should be repaired as they may cause erratic burning of the fuel and in the extreme case
may become a re hazard.
3. AIR LEAKS — Any such leaks should be repaired, as they may cause erratic burning of the fuel and in
extreme cases may become a re hazard.
SUCTION LINE LEAKS ­ Whatever it takes, The Oil Must Be Free of Air. This
can be a tough problem , but it must be resolved. Try
Gallons Per
Year
Page 33
bleeding the pump through a clear tube. There must be no froth visible. There are various test kits available to enable you to look at the oil through clear tube. There must be no froth visible. There are various test kits available to enable you to look at the oil through clear
tubing adapted to the supply line at the pump tting.
Air eliminators are on the market that have potential. Also, electronic sight glasses are being used with good success. At times, new tubing must be run to the tank
or new ttings put on. Just make sure you get the air
out before you leave.
Any air leaks in the fuel line will cause an unstable
ame and may cause delayed ignition noises. Use only are ttings in the fuel lines.
4. GASKET LEAKS — If 11.5 to 12.5% CO2 with a
#1 smoke cannot be obtained in the breeching, look for air leaks around the burner mounting gasket, observation door, and canopy gasket. Such air leaks will cause a lower CO2 reading in the breeching. The
smaller the ring rate the greater effect an air leak
can have on CO2 readings.
5. DIRT — A fuel lter is a good investment.
Accidental accumulation of dirt in the fuel system can clog the nozzle or nozzle strainer and produce a poor spray pattern from the nozzle. The smaller the
ring rate, the smaller the slots become in the nozzle
and the more prone to plugging it becomes with the same amount of dirt.
6. WATER — Water in the fuel in large amounts will stall the fuel pump. Water in the fuel in smaller amounts will cause excessive wear on the pump, but more importantly water doesn’t burn. It chills
the ame and causes smoke and unburned fuel to
pass out of the combustion chamber and clog the
ueways of the boiler.
7. COLD OIL — If the oil temperature approaching the fuel pump is 40°F or lower poor combustion or delayed ignition may result. Cold oil is harder to atomize at the nozzle. Thus, the spray droplets get
larger and the ame shape gets longer. An outside
fuel tank that is above grade or has fuel lines in a shallow bury is a good candidate for cold oil. The best solution is to bury the tank and lines deep enough to keep the oil above 40°F.
8. FLAME SHAPE — Looking into the combustion
chamber through the observation door, the ame
should appear straight with no sparklers rolling up
toward the crown of the chamber. If the ame drags
to the right or left, sends sparklers upward or makes wet spots on the target wall, the nozzle should be replaced. If the condition persists look for fuel leaks, air leaks, water or dirt in the fuel as described above.
9. HIGH ALTITUDE INSTALLATIONS
Air settings must be increased at high altitudes. Use
instruments and set for 11.5 to 12.5% CO2.
10. START-UP NOISE — Late ignition is the cause of start-up noises. If it occurs recheck for electrode
settings, ame shape, air or water in the fuel lines.
11. SHUT DOWN NOISE — If the ame runs out of air
before it runs out of fuel, an after burn with noise may occur. That may be the result of a faulty cut-off valve in the fuel pump, or it may be air
trapped in the nozzle line. It may take several ring
cycles for that air to be fully vented through the
nozzle. Water in the fuel or poor ame shape can also
cause shut down noises.
NOTICE
CHECK TEST PROCEDURE. A very good test for isolating fuel side problems is to disconnect the fuel system and with a short length of tubing,
re out of an auxiliary ve gallon pail of clean,
fresh, warm #2 oil from another source. If the burner runs successfully when drawing out of the
auxiliary pail then the problem is isolated to the fuel or fuel lines being used on the jobsite.
D. ATTENTION TO BOILER WHILE NOT IN
OPERATION
1. IMPORTANT IF BOILER IS NOT USED DURING WINTER
TIME, IT MUST BE FULLY DRAINED TO PREVENT FREEZE DAMAGE.
2. Spray inside surfaces with light lubricating or crankcase oil using gun with extended stem so as to reach all corners.
3. With steam boilers, at end of season add sufcient water to ll boiler to top of water column and leave
it that way until fall when water should be drained again to proper level. If, at this time, boiler water
is dirty, drain water, ush out boiler, and rell with
clean water to prescribed water level.
4. Always keep the manual fuel supply valve shut off if the burner is shut down for an extended period of time.
5. To recondition the heating system in the fall season after a prolonged shut down, follow the instructions outlined in Section IV, Paragraphs A through K.
WARNING
This boiler contains controls which may cause the boiler to shut down and not restart without service.
If damage due to frozen pipes is a possibility, the
heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
33
Page 34
VI. Boiler Cleaning
WARNING
All boiler cleaning must be completed with burner service switch turned off.
A. CLEAN THE FLUEWAYS (See Figure 28).
1. Disconnect oil line(s) and remove burner and burner mounting plate. See Figures 1A thru 1D.
2. Lay protective cloth or plastic over combustion chamber blanket.
3. Remove the smokepipe as necessary to gain access to the boiler canopy.
4. Remove the jacket top panels.
5. Remove the canopy being careful not to damage the cerafelt gasket.
6. Usinga1¼”diameterwireorbrebristlebrush (30”handle)cleantheueways.Brushfromthetop
using diagonal strokes for best results. DO NOT allow brush to strike the target wall or liner in the chamber.
B. CLEANTOPOFBOILERSECTIONS.
1. Brushandvacuumthetopsoftheboilersections.
C. CLEANTHEFIREBOX.
1. Usingwireorbrebristlebrush,cleancrown
of boiler and inside of water legs. DO NOT allow brush to strike target wall or blanket in the combustion chamber.
D. AFTERCLEANING,removeprotectiveclothwith
debrisandvacuumasnecessary,butbecarefulnot todamageblanket.Inspecttargetwall,combustion
chamber blanket and burner mounting plate insulation
forsignsofdamage.Ifdamaged,replaceasneeded.
E. REASSEMBLEBOILER.
CAUTION: Donotstarttheburnerunlesscanopy,
smokepipe and burner swing door are secured in place.
1. Installthecanopytakingcaretoalignthegaskets withoutblockingtheueways.Ifgasketisdamaged,
replace as needed.
2. Close and secure burner swing door to front section with fasteners.
3. Reconnect oil line(s).
4. Reinstall Top Panels and secure with sheet metal screws.
5. Reinstall smokepipe on canopy and secure to collar with sheet metal screws.
Figure 28: Cleaning of Boiler Flueways
WARNING
The boiler must be connected to an approved chimney in good condition. Serious property damage could result if the boiler is connected to a dirty or inadequate chimney. The interior of
the chimney ue must be inspected and cleaned
before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and
unobstructed chimney ue is necessary to allow
noxious fumes that could cause injury or loss of life to vent safely and will contribute toward
maintaining the boiler's efciency.
34
Page 35
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
The Repair Parts list designates parts that contain refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to temperatures about 1805°F, such as during direct flame contact, RCF changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures: Do not remove or replace RCF parts or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United States and Canada.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
35
Page 36
TROUBLE SHOOTING CARLIN 40200 OIL PRIMARy CONTROL
CARLIN 40200 OIL PRIMARy CONTROL Also refer to Model EZ-1/2/3 Oil Burner - Instruction
Manual (Form #MNEZ123) for additional information.
1. Burner (control) will not come on. a. No power to control. b. Control is in lockout. Press reset button for one
(1) second.
c.
CAD cell seeing light. d. CAD assembly defective. e. Control motor relay is stuck closed (see note
below).
2. Burner (control) will light, then shut down after a short time, then restart after one (1) minute.
CAD cell is defective.
a.
b. Air leaking into oil line causing ame out. c. Defective nozzle causing ame to be erratic. d. Excessive airow or draft causing ame to be
erratic.
e.
Excessive back pressure causing ame to be
erratic.
Control locks out after Trial For Ignition (TFI).
3. a. No oil to burner. b. Shorted electrodes. c. Nozzle clogged.
d. Airow too high.
e. Ignitor module defective. f. CAD cell defective. g. Oil valve stuck open or closed. Note: The Safety Monitoring Circuit (SMC) is
designed to provide lockout in the event of a stuck or welded motor relay.
NOTICE
If ame is not established within 15 seconds
of oil valve actuation (known as Trial For Ignition [TFI]) lockout will occur. Lockout is indicated by a red LED solid-on located on the oil primary control.
Latch-up will occur if the control locks-out three ( indicated by red and amber LED's solid-on.
3) times during a call for heat. This is
CARLIN OIL BURNER PART NUMBERS FOR CL SERIES BOILERS
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Refer to Carlin Model EZ-1/2/3 Oil Burner-Instruction Manual (Form #MNEZ123) for an exploded view of the burner and a
list of spare parts.
For replacement Carlin oil burner parts, contact your wholesaler or the burner manufacturer:
CCT, Carlin Combustion Technology, Inc.
70 Maple Street
East Longmeadow, MA 01028
Telephone: (413) 525-7700 Facsimile: (413) 525-8306
TROUBLE SHOOTING RIELLO 40 SERIES
Not Applicable to Riello 40 Series Burner, refer
to Models F3 and F5 Installation Manual, Riello 40
Series Residential Oil Burners (C6501010 or Model
F10 Installation Manual, Riello 40 Series Residential Oil Burners (2902554) or contact burner manufacturer.
36
Page 37
VII. Repair Parts
All CL™ Series repair parts may be ordered through New Yorker Boiler Co., Inc., or its authorized distributors. Should you require assistance in locating a New Yorker Distributor in your area, or have questions regarding the availability of
New Yorker products or repair parts, please contact: New Yorker Boiler Co., Inc., P.O. Box 10, Hateld, PA 19440-0010, Phone:
(215) 855-8055 Attn: Customer Service Department
37
Page 38
38
Bare Boiler Assembly (Exploded View)
Page 39
Item
No.
Description
Boiler Size / Quantity
Part No.
CL3 CL4 CL5
Bare Boiler Assembly
Front Section (Non-Htr.), Machined Water
1
---(OR)--­Front Section (Non-Htr.), Machined Steam
2 Center Section 1 2 3 71720301
Rear Section (Non-Htr.), Machined Water
---(OR)--­Rear Section (Non-Htr.), Machined Steam
3
Rear Heater Section, Machined Water
---(OR)---
Rear Heater Section, Machined Steam 4 5" Cast Iron Slip Nipple 2 3 4 7066003 5 Slip Nipple, 22-B Steel 2 3 4 806600375 6 Rear Target Wall Insulation 1 1 1 82020002
Tie Rod, 3/8"-16 x 12-1/2" Lg. 2 --- --- 80861010 7
Tie Rod, 3/8"-16 x 17-3/4" Lg. --- 2 --- 80861032
Tie Rod, 3/8"-16 x 23" Lg. --- --- 2 80861049 8 3/8" Flat Washer 4 4 4 80860600 9 3/8"-16 Heavy Hex Nut 4 4 4 80860423
Combustion Chamber Liner, 1/2" x 19-1/2" x 9-3/4" 1 --- --- 82020031
10
Combustion Chamber Liner, 1/2" x 19-1/2" x 14-3/4" --- 1 --- 82020041
Combustion Chamber Liner, 1/2" x 19-1/2" x 19-3/4" --- --- 1 82020051
11 BSD Hinge Loop Bracket 2 2 2 100795-02 12 5/16" Flat Washer - Plated 4 4 4 80860611 13 5/16-18 x 1" Lg. Cap Screw, Plated 2 2 2 80861341 14 5/16-18 x 1-1/2" Lg. Cap Screw, Plated 2 2 2 80861349 15 Burner Swing Door (only) 1 1 1 100793-01 16 Burner Swing Door Insulation 1 1 1 82020001 17 Observation Port Cover 1 1 1 71728004 18 5/16-18 x 3/4" Lg. Cap Screw, Plated 1 1 1 80861340 19 Canopy Sealing Strip (1/2" x 1 x 10') 1 1 1 6206001
Canopy Assembly - 3 Section 1 --- --- 100827-03
20
Canopy Assembly - 4 Section --- 1 --- 100827-04
Canopy Assembly - 5 Section --- --- 1 100827-05
21 1/4"-20 x 3" Lg. Carriage Bolt, Plated 2 2 2 80860119 22 1/4"-20 x 3-1/2" Lg. Carriage Bolt, Plated 2 2 2 100838-01 23 1/4" Flat Washer - Plated 4 4 4 80860603 24 1/4"-20 Wing Nut - Plated 4 4 4 80860910 25 Heater Cover Plate Gasket - Rear Heater 1 1 1 8036058 26 V1-2 Heater Carton (WR[T] & SR[T]) Rear Heater 1 1 1 6036031 27 5/16" Flat Washer - Plated 8 8 8 80860611
3/8"-16 x 7/8" Lg. Cap Screw, Plated, ASME Grade
28
SA307B
1 1 1
1 1 1
8 8 8 80861337
71720103 71720104
71720201 71720202 71720203 71720204
39
Page 40
Jacket Assembly (Exploded View)
Item
No.
Description
Boiler Size / Quantity
Part No.
CL3 CL4 CL5
Jacket Components -- Items 1 thru 6 Include Insulation as Part of Assembly
1 Jacket Front Panel Assembly 1 1 1 100819-01 2 Jacket Rear Panel Assembly 1 1 1 100820-01
2 --- --- 100821-03
Non-Heater Build
Jacket Reversible Side
3
Panel Assembly
With Heater Build
Jacket Left Side Heater Panel Assembly
4
(with Heater Build)
5 Jacket Split Front Top Panel Assembly 1 1 1 100823-01
6 Jacket Split Rear Top Panel Assembly
--- 2 --- 100821-04
--- --- 2 100821-05 1 --- --- 100821-03
--- 1 --- 100821-04
--- --- 1 100821-05 1 --- --- 100824-03
--- 1 --- 100824-04
--- --- 1 100824-05
1 --- --- 100822-03
--- 1 --- 100822-04
--- --- 1 100822-05
40
Page 41
CL3 Thru CL5 Water Boilers - Trim and Controls
Item
No.
Description
Boiler Size / Quantity
Part No.
CL3 CL4 CL5
CL3 Thru CL5 Water Boilers - Trim and Controls
1 Beckett R7184B Oil Primary Control 1 1 1 100136-01
Honeywell L7248C1014 Hi Limit, Circ. Relay
2
--- (OR)---
L7224C1004 Hi & Lo Limit, Circ. Relay 3 ¾" NPT x 1½" Immersion Well, Honeywell 123870A 1 1 1 80160426 4 2½" Temperature / Pressure Gauge 1 1 1 8056169 5 ¾" NPT x 7¼" Lg. Nipple, SCH 80, Black 1 1 1 100839-01 6 Relief Valve, #10-407-05 1 1 1 81660319 7 1½" NPT x 5" Lg. Nipple, Black 1 1 1 806600060 8 1½" x ¾" x 1½" NPT Tee, Black 1 1 1 806601003 9 ¾" Drain Valve 1 1 1 806603061
10 Taco 007 Circulator 1 1 1 8056007 11 1½" Circulator Flange 2 2 2 806602014 12 Taco Flange Gasket 2 2 2 806602006
1 1 1
100059-01 100862-01
41
Page 42
CL3 Thru CL5 Steam Boilers - Trim and Controls
Item
No.
Description
Boiler Size / Quantity
Part No.
CL3 CL4 CL5
CL3 Thru CL5 Steam Boilers - Trim and Controls
1 Beckett R7184B Oil Primary Control 1 1 1 100136-01 2 McDonnell & Miller PS801 LWCO With Probe 1 1 1 80160723
3 Honeywell PA404A1009 Pressuretrol 1 1 1 80160300 3A ¼" x 90° Syphon, 2½" Equal Leg 1 1 1 806603006 3B ¾" x ¼" NPT Bushing, Black 1 1 1 806600508
4 Honeywell L4006A2015 Aquastat 1 1 1 80160400
5 #123871A Immersion Well ¾" NPT 1 1 1 80160426
6 2½" Dia. Steam Gauge 1 1 1 8056010
7 10¼" Gauge Glass Set, Conbraco #22-171-10 1 1 1 100854-01 7A ½" Male x ½" Female NPT Brass Extension Piece 1 1 1 100853-01 7B ½" NPT Brass Street Elbow 1 1 1 100852-01
8 ¾" NPT x 7¼" Lg. Nipple, SCH 80, Black 1 1 1 100839-01
9 ¾" NPT, M/F, 15 PSI Safety Valve Conbraco #13-511-08 1 1 1 81660530 10 ¾" NPT Coupling 1 1 1 806602561
11 ¾" NPT Drain Valve, Conbraco #35-302-03 1 1 1 806603061
42
Page 43
BECKETT OIL BURNER PARTS LIST
MODEL AFG --- 60-Hz, 3450 RPM
P.O. BOX 1289
1-800-645-2876
ELYRIA, OHIO 44036
R. W. BECKETT CORP.
FOR REPLACEMENT OIL BURNER PARTS, CONTACT
YOUR WHOLESALER OR THE BURNER MANUFACTURER:
Beckett AFG Burner
43
Page 44
BECKETT OIL BURNER PART NOS. FOR CL SERIES BOILERS
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Also provide the name of the part(s) and part number as listed below.
Boiler Model CL3-091, 105, 140 CL4-126 CL4-175, 210 CL5-168, 245 CL5-280 Air Tube Combination AFG70MBAS AFG70MBAS AFG70MDAS AFG70MDAS AFG70MLAS Beckett's Spec No. NY2701 NY2702 NY2703 NY2704 NY2705
Air Band 3492A 3492A 3492A 3492A 3492A Air Band Nut 4150 4150 4150 4150 4150 Air Band Screw 4198 4198 4198 4198 4198 Air Shutter 3709 3709 3709 3709 3709 Air Shutter Screw 4198 4198 4198 4198 4198 Blower Wheel 2999 2999 2999 2999 2999 Coupling 2454 2454 2454 2454 2454 Low Firing Rate Bafe 5880[1] ---- ---- ---- ---­Bulkhead Knurled Locknut 3-666 3-666 3-666 3-666 3-666 Connector Tube Assembly 5636 5636 5636 5636 5636 Electrode Clamp 1-49 1-49 1-49 1-49 1-49 Electrode Clamp Screw 4219 4219 4219 4219 4219 Electrode Insulator Assembly 5780 5780 5780 5780 5780 Spider Spacer Assembly 5653 5653 5653 5653 5653 Escutcheon Plate 3493 3493 ---- ---- ---­Adjusting Plate Assembly ---- ---- 5941 5941 5941 Head 5912 5912 5913 5913 5913 Head Screws 4221 4221 4221 4221 4221 Flange Gasket 3416 3416 3416 3416 3416 AFG Housing 5874BK 5874BK 5874BK 5874BK 5874BK Motor 21805 21805 21805 21805 21805 Nozzle Adapter 2-13 2-13 2-13 2-13 2-13 Nozzle Line Electrode Assembly NL70MB NL70MB NL70MD NL70MD NL70ML Oil Pump, Clean Cut (Single Stage) 2184404U 2184404U 2184404U 2184404U 2184404U Oil Pump, Clean Cut (Two Stage) 21941U 21941U 21941U 21941U 21941U Static Plate 3384 3384 3384 3384 Less Ignitor 51771U 51771U 51771U 51771U 51771U Ignitor Hinge Screw 4217 4217 4217 4217 4217 Ignitor Holding Screw 4292 4292 4292 4292 4292 Ignitor Gasket Kit 51304 51304 51304 51304 51304 Junction Box 5770 5770 5770 5770 5770 Flame Detector 7006 7006 7006 7006 7006 Oil Solenoid Valve Coil 21755 21755 21755 21755 21755 Oil Solenoid Valve Cord 21807 21807 21807 21807 21807
[1] 5880 used on CL3-091 ring rate only
44
Page 45
VIII. Low Water Cut Off (LWCO)
WARNING
DO NOT ATTEMPT to cut factory wires to install an aftermarket Low Water Cut Off (LWCO). Only use
connections specically identied for Low Water Cut Off.
In all cases, follow the Low Water Cut Off (LWCO) manufacturer's instructions.
When
A low water cutoff is required to protect a hot water
boiler when any connected heat distributor (radiation) is installed below the top of the hot water boiler (i.e.
baseboard on the same oor level as the boiler). In
addition, some jurisdictions require the use of a LWCO with a hot water boiler.
Where
The universal location for a LWCO on both gas and oil
hot water boilers is above the boiler, in either the supply or return piping. The minimum safe water level of a water boiler is at the uppermost top of the boiler; that is, it must be full of water to operate safely.
What Kind
Typically, in residential applications, a probe type
LWCO is used instead of a oat type, due to their
relative costs and the simplicity of piping for a probe LWCO.
How to Pipe
A “tee” is commonly used to connect the probe LWCO to the supply or return piping, as shown below.
manufacturers recommend an annual inspection of the probe.
How to Wire
LWCO’s are available in either 120 VAC or 24 VAC
congurations. The 120 VAC conguration can be
universally applied to both gas and oil boilers by wiring it in the line voltage service to the boiler (after the service switch, if so equipped).
The presence of water in a properly installed LWCO
will cause the normally open contact of the LWCO to close, thus providing continuity of the 120 VAC service to the boiler.
It is recommended to supply power to the probe LWCO
with the same line voltage boiler service as shown below.
LWCO Location
Select the appropriate size tee using the LWCO
manufacturer’s instructions. Often, the branch connection must have a minimum diameter to
prevent bridging between the probe and the tee. Also, the run of the tee must have a minimum diameter to prevent the end of the probe from touching or being located too close to the inside wall of the run of the tee.
Ideally, manual shutoff valves should be located
above the LWCO and the boiler to allow for servicing. This will allow probe removal for inspection without draining the heating system. Many probe LWCO
Wiring of Typical LWCO
A 24 VAC LWCO is used primarily for gas red
boilers where a 24 volt control circuit exists within the boiler. However, a 24 VAC LWCO can only be used if the boiler manufacturer has provided piping and wiring connections and instructions to allow for this application.
How to Test
Shut off fuel supply. Lower water level until water level is BELOW the LWCO. Generate a boiler demand by turning up thermostat. Boiler should not attempt to
operate. Increase the water level by lling the system.
The boiler should attempt to operate once the water level is above the LWCO.
45
Page 46
TABLE 9: BURNER SPECIFICATIONS
Beckett AFG
Boiler Model
1
CL3-091
CL3-105 0.75 L1 6 0 0.65 x 45B (Hago)
p CL3-140
CL4-126 0.90 L1 7 0 0.75 x 45B (Delavan) Installed 140
CL4-175 1.25 V1(0) 10 1 1.00 x 45B (Hago)
CL4-210
CL5-168 1.20 V1(2) 10 0 0.90 x 45B (Hago)
l CL5-245
CL5-280 2.00 V1(4) 10 3 1.50 x 45B (Hago) Installed 175
Firing Rate
GPH
Head
(Setting)
0.65 L1 8 0 0.55 x 70B (Delavan)
1.00 L1 10 1 0.85 x 45B (Hago) Installed 140
1.50 V1(0) 10 2 1.10 x 45B (Hago) Installed 175
1.75 V1(3) 7 3 1.35 x 45B (Hago) Installed 175
Air
Shutter
Air
Band
GPH x Angle Type
2
Shipped
p Loose
p Loose
Loose
l Loose
Settings Nozzle
3
Pump
Pressure
140
140
175
175
Carlin Burner
Boiler Model
CL3-091 0.65 CL3-105 0.75 0.60/0.65 0.60 0.60 x 60ES (Hago)
p CL3-140
CL4-126 0.90 0.75 0.75 0.75 x 60A (Delavan)
CL4-175 1.25 0.85/1.00 1.00-1.10 1.00 x 60A (Delavan)
CL4-210
CL5-168 1.20 0.85/1.00 0.90 1.00 x 60B (Hago) Installed 150
CL5-245 1.75 EZ-2HP 1.50 1.75 1.50 x 60A (Delavan) Installed 150
1
Beckett low ring rate bafe required on CL3-091 (0.65 GPH) application only; shipped loose with nozzle.
2
Nozzle(s) for alternate boiler model ring rate(s) are shipped loose in bag attached to the
burner designated by corresponding symbol, i.e. (p) = CL3-140.
3
Single stage fuel pump is standard, two stage fuel pump is optional. Burner manufacturer has preset
single stage fuel pump to settings shown in table above.
Firing Rate
GPH
1.00 0.85/1.00 0.75 0.85 x 60B (Hago) Installed 150
1.50 1.10/1.25 1.25-1.35 1.25 x 60B (Hago) Installed 150
Burner
Model
EZ-1HP
Head
Bar
0.50 0.55 0.55 x 70B (Delavan)
Air
Band
GPH x Angle Type
2
Shipped
p Loose p Loose
Loose
Loose
Settings Nozzle
3
Pump
Pressure
150 150
150
150
46
Page 47
RIELLO OIL BURNER PART NUMBERS FOR CL SERIES BOILERS
NOTE: When ordering parts always give the serial and model numbers shown on the boiler and burner. Refer to Models F3 & F5 Installation Manual, Riello 40 Series Residential Oil Burners (C6501010) or Model F10
Installation Manual, Riello 40 Series Residential Oil Burners (2902554) for an exploded view of the burner and a list of spare parts.
For replacement Riello oil burner parts, contact your wholesaler or the burner manufacturer:
Riello Corporation of America
35 Pond Park Road
Hingham, Massachusetts 02043
Telephone: (617) 749-8292
Facsimile: (617) 740-2069
Toll Free: (outside Massachusetts)
(800) 992-7637
TABLE 9A: RIELLO BURNER SPECIFICATIONS
Boiler
Model
CL3-105 0.75
CL3-140 1.00 2.85 2
CL4-175 1.25 40F5 4 4
CL4-210 1.50 40F10 3 1
CL5-245 1.75
CL5-280 2.00 3.8 2
Firing
Rate
GPM
Burner
Model
40F5
40F10
Air Shutter Turbulator
Settings Nozzle
2.60 0
3 1.5
GPH x Angle
Type
0.60 x 60A (Delavan)
0.85 x 60W (Delavan)
1.00 x 60A (Delavan)
1.25 x 60B (Delavan)
1.35 x 45B (Delavan)
1.65 x 45B (Delavan)
Riello Canada Inc.
2165 Meadowpine Blvd.
Mississauga, Ontario L5N 6H6
Telephone: (905) 542-0303
Facsimile: (905) 542-1525
Toll Free: (800) 387-3898
Pump
Shipped
Loose
Installed
Installed SBT 6.0” 2-3/8”
Installed SBT 5.0” 2-1/2”
Loose
Installed
Pressure
150
Combustion
Insertion
Head
SBT 6.0” 2-3/8”
SBT 5.0” 2-1/2”
Depth
47
Page 48
SERVICE RECORD
DATE SERVICE PERFORMED
48
Page 49
SERVICE RECORD
DATE SERVICE PERFORMED
49
Page 50
SERVICE RECORD
DATE SERVICE PERFORMED
50
Page 51
51
Page 52
NEW YORKER BOILER CO., INC.
Limited Warranties
For Residential Cast Iron Steam Boilers
By this Warranty Statement New Yorker Boiler Co., Inc. ("New Yorker") issues limited warranties subject to the terms and conditions stated below. These limited warranties apply to residential cast iron steam boilers labeled with the New Yorker® brand which are sold on or after March 1, 2004
ONE yEAR LIMITED WARRANTy
One Year Limited Warranty for Residential Cast Iron Steam Boilers
New Yorker warrants to the original consumer purchaser at the original installation address that its residential cast iron steam boilers will be free of defects in material and workmanship under normal usage for a period of one year from the date of original installation. In the event that any defect in material or workmanship is found during the one-year period following the date of installation, New Yorker will, at its option, repair the defective part or provide a replacement free of charge, F.O.B. its factory.
TEN yEAR LIMITED WARRANTy
Ten Year Pressure Vessel Limited Warranty for Residential Cast Iron Steam Boilers New Yorker warrants to the original consumer purchaser at the original installation address that the pressure vessel of its residential cast iron steam boilers will be free of defects in material and workmanship under normal usage for a period of 10 years from the date of original installation. In the event that any defect in material or workmanship is found during the ten year period following the date of installation, New Yorker will, at its option, repair the defective pressure vessel or provide a replacement free of charge, F.O.B. its factory.
EXCEPTIONS AND EXCLUSIONS
1.Components Manufactured by Others Following the expiration of the
foregoing one year limited warranty, all component parts of a boiler which are manufactured by others (such as burners, burner controls, circulator, tankless water heater, and New Yorker Link) shall be subject only to the manufacturer's warranty, if any.
2.Removal and Replacement Costs These warranties do not cover expenses
of removal or reinstallation. The consumer purchaser will be responsible for the cost of removing and replacing any defective part and all labor and related materials connected therewith. Replacement parts will be invoiced to the distributor in the usual manner and will be subject to adjustment upon proof of defect.
3.Proper Installation These warranties are conditioned upon the installation
of the boiler in strict compliance with New Yorker's Installation, Operating and Service Instructions. New Yorker specifically disclaims any liability of any kind which arises from or relates to improper installation.
4.Improper Use or Maintenance These warranties will not be applicable if
the boiler is used or operated over its rated capacity, is installed for uses other than home heating, or is not maintained in accordance with New Yorker Installation’s, Operating and Service Instructions and hydronics industry standards.
5.Improper Operation These warranties will not be applicable if the boi
has been damaged as a result of being improperly serviced or operated, including but not limited to the following: operated with insufficient wat allowed to freeze; subjected to flood conditions; or operated with water conditions and/or fuels or additives which cause un
ler
er;
usual deposits or corrosion
in or on the pressure vessel or associated controls.
6.Geographic Limitations These warranties apply only to boilers installed
within the 48 contiguous United States.
7.Installation Requirements In order for these warranties to be effective: a)The boiler must be installed in a single or two-family residential dw
This warranty does not apply to boilers installed in apart
elling.
ments or for
commercial or industrial applications.
b)The boiler must be installed in strict compliance with New Yorker's
Installation, Operating and Service Instructions, including the installation of a low water cut-off, by an installer regularly engaged in boiler installations.
c)Boiler sections must not have been damaged during shipment or
installation.
d)The boiler must be vented in accordance with chimney recommendations
set forth in New Yorker's Installation, Operating and Service Instructions.
8.Exclusive Remedy New Yorker's obligation in the event of any breach of
these warranties is expressly limited to the repair or replacement of any part found to be defective under conditions of normal use.
9.Limitation of Damages Under no circumstances will New Yorker be liable
for incidental, indirect, special or consequential damages of any kind under these warranties, including, without limitation, injury or damage to persons or property and damages for loss of use, inconvenience or loss of time. New Yorker's liability under these warranties shall under no circumstances exceed the purchase price paid for the boiler involved. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
10.Limitation of Warranty These limited warranties are given in lieu of all
other express warranties and set forth the entire obligation of New Yorker with respect to any defect in a residential cast iron steam boiler. New Yorke shall have no express obligations,
r
other
A
n
er
.
SO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO
STATE.
responsibilities or liabilities of any kind,
than those set forth herein.
ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDING ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR PARTICULAR PURPOSE, ARE EXPRESSLY LIMITED IN DURATION TO A PERIOD OF ONE YEAR, EXCEPT THAT IMPLIED WARRANTIES, IF ANY, APPLICABLE TO THE PRESSER VESSEL OF A RESIDENTIAL CAST IRON STEAM BOILER SHALL BE LIMITED IN DURATION TO THE LESSER OF THE DURATION OF SUCH IMPLIED WARRANTY OR A PERIOD OF TEN YEARS. Some states do not allow limitations on how long a i u.
PROCEDURE FOR OBTAINING WARRANTy SERVICE
Upon discovery of a condition believed to be related to a defect in material or workmanship covered by these warranties, the original consumer purchaser should notify the installer, who will in turn notify the distributor. If this action is not possible or does not produce a prompt response, the original consum purchaser should write to New Yorker Boiler Co., Inc. at P.O. Box 10,
mplied warranty lasts, so the above limitation may not apply to yo
Hatfield, PA 19440-0010, giving full particulars in support of the claim
The original consumer purchaser is required to make available for inspection by New Yorker or its representative the parts claimed to be defective and, if requested by New Yorker, to ship those parts prepaid to New Yorker at the above address for inspection or repair. In addition, the original consumer purchaser agrees to make all reasonable efforts to settle any disagreement arising in connection with any warranty claim before resorting to legal remedies in the courts. THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY AL
02/04
52
Loading...