Energy Tech Laboratories LB480, LB600, LB300, LB360 User Manual

INSTALLATION MANUAL
SPLIT-SYSTEM
(AIR COOLED)
EVAPORATOR BLOWER
CONTENTS
GENERAL....................................4
REPLACEMENTPARTS........................4
INSPECTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
INDOOR PRODUCT NOMENCLATURE . . . . . . . . . . . . 5
UNITINSTALLATION..........................11
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
See the following page for a complete Table of Contents.
MODELS: LB300
LB360 LB480 LB600
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION, and WARNING. Notes clarify or makethe installation easier. Cautions prevent equipment damage. Warnings installer that personal injury and/or equipment damage may result if installation procedure is not handled properly.
CAUTION: READ ALL SAFETY GUIDES BEFORE YOU
BEGIN TO INSTALL YOUR UNIT.
SAVE THIS MANUAL
are intended to
are given to
are given to alert
035-18496-000-C-1102
TABLE OF CONTENTS
035-18496-000-C-1102
GENERAL ......................................4
NOTES, CAUTIONS AND WARNINGS . . . . . . . . . . . . . . . .4
REPLACEMENTPARTS...........................4
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
LIMITATIONS..................................4
INDOOR PRODUCT NOMENCLATURE . . . . . . . . . . . . . . .5
BLOWERMOTORMOUNTINGLOCATIONS.........7
LA300/LB360/LB480MOTORMOUNTING............7
LB600MOTORMOUNTING .......................7
MOTORMOUNTARRANGEMENTS ...............8
LA300/LB360/LB480 MOTOR ARRANGEMENTS . . . . . . 8
ADDITIONAL M OTOR ARRANGMENTS FOR
LA300/LB360/LB480 ............................8
LB600MOTORARRANGEMENTS..................9
RE-LOCATING THE LB600 MOTOR MOUNT ING PLATE 9
ALTERNATEPOSITIONONE......................9
ALTERNATEPOSITIONTWO .....................9
ALTERNATEPOSITIONTHREE ...................9
AIRDISCHARGECONVERSION ..................9
LA360/LB360/LB480 AIRDISCHARGE ..............9
LB600AIRDISCHARGE .........................11
UNITINSTALLATION ............................11
LOCATION...................................11
RIGGING ....................................11
CLEARANCES................................11
MOUNTING ..................................12
DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . .15
INSULATION ..................................15
SUPPLY AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . .15
RETURN AIR DUCT ANGLES . . . . . . . . . . . . . . . . . . . . 16
DRAINCONNECTIONS .........................16
REFRIGERANTMAINS.........................16
EVAPORATORSECTIONPIPING .................17
EXPANSION VALVE BULB INSTALLATION . . . . . . . . .17
LA300........................................17
LB360/LB480/LB600 ............................17
LIQUIDLINESOLENOIDS .......................17
PUMPOUT ...................................18
BEARING ALIGNMENT: LB600 . . . . . . . . . . . . . . . . . . .18
AIR SYSTEM ADJUSTMENT . . . . . . . . . . . . . . . . . . . .18
TWINBELTDRIVEADJUSTMENT................18
ELECTRICALCONNECTIONS ...................19
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
LIST OF FIGURES
Fig.# Pg.# 1 LA300 AND LB360/LB480 FACTORY MOTOR
MOUNTINGPOSITION ........................7
2 LB600 FACTORY MOTOR MOUNTING POSITION . .7
3 LB600MOTORMOUNTPLATE..................7
4 LA300/LB360/LB480MOTOR LOCATION A . . . . . . . . 8
5 LA300/LB360/LB480MOTOR ARRANGEMENTS . . . .8
6 VERTICAL AIRFLOW ARRANGEMENTS . . . . . . . . . 10
7 HORIZONTAL AIRFLOW ARRANGEMENTS . . . . . .10
8 LB600AIRFLOWARRANGEMENTS.............11
9 DETAILS FOR SECURING BOTTOM MOUNTING
SUPPORTS ................................13
10 LA300/LB480/LB360 WEIGHT DISTRIBUTION . . . .13
11 LB600 WEIGHT DISTRIBUTION WITH SUSPENSION
APPLICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
12 DETAILS FOR SECURING SUSPENSION
CHANNELS ................................15
13 SUGGESTED METHOD FOR CONNECTING
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
14 RECOMMENDEDDRAINPIPING ...............16
15 LB600 CENTER BEARING . . . . . . . . . . . . . . . . . . . . . 18
16 DOUBLEGROOVEPULLEY ...................18
17 UNIT DIMENSIONS - LA300, LB360, LB480 . . . . . . .22
18 25TONLIQUIDLINESOLENOIDWIRING ........22
19 30, 40 & 50 TON LIQUID LINE SOLENOID
WIRING....................................22
20 LA300PIPINGCONNECTIONS.................23
21 LB360PIPINGCONNECTIONS.................23
22 LB480PIPINGCONNECTIONS.................23
23 UNITDIMENSIONS ..........................24
24 LB600 PIPING CONNECTIONS - END PANEL
DETAIL ....................................24
25 HOLE LOCATION FOR PRESSURE DROP
READING ..................................25
26 25-TON PRESSURE DROP VS. CFM ACROSS
INDOORCOIL ..............................26
27 30-TON - PRESSURE DROP VS. CFM ACROSS
INDOORCOIL ..............................26
28 40 TON - PRESSURE DROP VS. CFM ACROSS
INDOORCOIL(DOMESTIC) ...................27
29 50 TON - PRESSURE DROP VS. CFM ACROSS
INDOORCOIL ..............................27
30 INDOOR UNIT WIRING DIAGRAM LB360,
480&600 ..................................28
31 INDOORWIRINGDIAGRAMLA300 .............29
2 UnitaryProductsGroup
035-18496-000-C-1102
LIST OF TABLES
Tbl.# Pg.#
1 UNIT APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . 5
2 PHYSICALDATA .............................6
3 UNITMOUNTINGDIMENSIONS ................12
4 CORNERWEIGHTS..........................12
5 ACCESSORY OPERATING WEIGHT DISTRIBUTION
(LBS)......................................12
6 ELECTRICALDATA ..........................19
7 MOTOROVERLOADELEMENTS ...............19
8 UNITDRIVEDATA...........................20
Tbl.#
9 UNITBLOWERMOTORDATA .................20
10 FANPEFORMANCEDATA-25TON ............21
11 FANPEFORMANCEDATA-30TON ............21
12 FANPERFORMANCEDATA-40TON...........21
13 FANPERFORMANCEDATA-50TON...........21
14 UNIT DIMENSIONS - LA300, LB360, LB480 . . . . . . . 22
15 UNITCONNECTIONSIZES....................23
Pg.#
Unitary Products Group 3
035-18496-000-C-1102
GENERAL
The LA and LB evaporator units are designedfor use with the HA/HB Series condensing units.Units are designed to match up with LA/LB series Evaporator Blowers to meet ASHRAE
90.1 standards. Each unit consists of a coil section and a blower section that
are factory assembled and shipped as shown in figures 3 and
4. These sections may be rearranged in the field for other air discharge patterns. See figures 7, 8 and 9.
The LA and LB evaporator units have 24 volt normally closed solenoid valves to match the 24-volt control circuits of the
Simplicity HB360, HB480 and HB600 condensing units.
TM
control board in the HA300 as well as the
NOTES, CAUTIONS AND WARNINGS
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes make installation easier. Cautions equipment damage. Warnings personal injury and/or equipment damage may result if instal­lation procedure is not handled properly.
are intended to clarify or
are given to prevent
are given to alert installer that
REPLACEMENT PARTS
Refer to parts manual for complete listing of replacement parts on this equipment. The above forms and all other forms referenced on this instruction may be ordered from;
Standard Register 2101 W. Tecumseh Road Norman, OK 73069 Telephone : (877) 318-9675 Toll Free Fax: (877) 379-7920
INSPECTION
As soon as a unit is received, it should be inspected for possi­ble damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's freight bill. A separate request for inspection by the carrier's agent should be made in writing.
LIMITATIONS
This unit must be installed in accordance with all national and local safety codes. If no local codes apply, installation must conform to the appropriate national code. The unit is designed to meet National Safety Code Standards. If components are to be added to a unit to meet local codes, they are to be installed at the dealer's and/or the customer's expense. See Table1 for unit application data.
4 UnitaryProductsGroup
035-18496-000-C-1102
INDOOR PRODUCT NOMENCLATURE
L A 300 C 00 A 6 A AA 1
Model #
300
AA Additional Options AA = None
Model Number Description
Options
L Product Category L = Air Handling Unit A Product Identifier
Nominal Cooling Capacity MBH
A = R-22 Standard Efficiency 2-Pipe B = R-22 Standard Efficiency 4-Pipe
300 = 25 Ton 360 = 30 Ton 480 = 40 Ton 600 = 50 Ton
C Heat Type C = Cooling Only
Nominal Heating
00
Capacity
00 = No Heat Installed
A Airflow Options A=None 6 Voltage 5 = 575-3-60 6 = 208/230-460-3-60 A Installation Options A=None
1 Product Generation 1 = First Generation 2 = Second Generation
NOTE: LB600 Indoor Unit matches with both HB480
and HB600 Outdoor Condensing Units for maximum efficiency.
TABLE 1: UNIT APPLICATION DATA
Entering Air Temperature Degrees °F
Model Power Supply Voltage
208/230-3-60 187 253 8,000 12,000 65/57 95/72 40 77
LA300
LB360
LB480
LB600
*.
Heating Min/Max temperatures apply to steam and hot water coils. NOTE: Do not apply steam to hot water coils.
460-3-60 414 506 8,000 12,000 65/57 95/72 40 77 575-3-60 540 630 8,000 12,000 65/57 95/72 40 77
208/230-3-60 187 253 10,000 14, 000 65/57 95/72 40 77
460-3-60 414 506 10,000 14,000 65/57 95/72 40 77 575-3-60 540 630 10,000 14,000 65/57 95/72 40 77
208/230-3-60 187 253 12,800 19, 200 65/57 95/72 40 77
460-3-60 414 506 12,800 19,200 65/57 95/72 40 77 575-3-60 540 630 12,800 19,200 65/57 95/72 40 77
208/230-3-60 187 253 16,000 24, 000 65/57 95/72 40 77
460-3-60 414 506 16,000 24,000 65/57 95/72 40 77 575-3-60 540 630 16,000 24,000 65/57 95/72 40 77
VoltageVariation Supply Air Range CFM
Min. Max. Min. Max. Min. Max. Min. Max.
Cooling DB/WB
Heating DB
*
Unitary Products Group 5
TABLE 2: PHYSICAL DATA
DESCRIPTION
Rows Deep X Rows High 4 x 40 4 x 40 4 x 50 4 x 62 Finned Length, Inches 93 93 96 96
EVAPORATOR
COIL
CENTRIFUGAL
BLOWERS (2 PER UNIT)
FILTERS (THROWAWAY)
OPERATING CHARGE
(LBS R-22)
DRAINABLE HOT WATER
COIL ACCESSORY
NON-FREEZE, STEAM
DISTRIBUTING COIL
ACCESSORY
COMPONENT WEIGHT
Face Area, Feet Tube (copper) OD, Inches 3/8 3/8 3/8 3/8 Fins (Aluminum) per 1 inch 16 16 16 16
Piping Connections, Inches
Diameter X Width, Inches (Forward Curved) 18 x 18 20 x 18
Size and Quantity Per Model, Inches
Total Face A rea / feet System 1 49.65 30.08 37.83 46.59 System 2 - 30.08 37.83 46.59 Tube (copper) OD, Inches 1/2 1/2 1/2 Rows Deep 2 2 2 Fins (Aluminum) per 1 inch 12 12 8
Face Area, Feet Connections (Supply & Return), Inches 1 3/8 OD (Copper) 1 5/8 OD (Copper) Tube (copper) OD, inches 1 (Outside) 5/8 (Inside) Rows Deep 1 Fins (Aluminum) per 1 inch 8
Face Area, feet Connection, (Brass )
Inches (NPTE) Basic Unit (Less Motor & Drive) 980 980 1260 1474
Shipping Weight (lbs) 1180 1180 1510 ­Operating Weight (lbs) 1125 1146 1426 1640
Accessories
Blower Motor (1750 RPM)
035-18496-000-C-1102
MODEL
LA300 LB360 LB480 LB600
2
Liquid, Inches 7/8 7/8 7/8 7/8 Suction, Inches 2 1/8 1 1/8 1 3/8 2 1/8
16 x 20 x 2 - 6 ­20 x 20 x 2 - 3 ­20 x 22 x 2 - - ­16 x 25 x 2 - - 6 20 x 25 x 2 10 6 3 25 x 25 x 2 - - 6
2
2
2
Inlet 2 Outlet 1-1/2
Hot Water C oil 150 150 190 190 Steam Coil 160 160 - -
25.8 25.8 33.3 41.3
34.7 42.6 53.1
21.2 27.2 27.2
18.2
N/A
117(5hp) 117 (5hp) - -
120 (7.5hp) 120 (7.5hp) 120 (7.5hp) 141 (10hp)
- 141 (10hp) 141 (10hp) 217 (15hp)
6 UnitaryProductsGroup
035-18496-000-C-1102
a
BLOWER MOTOR MOUNTING LOCATIONS
Unitsareshippedfrom the factory less motor and drives. The blower motor and drive packages are ordered and shipped separatelyfor field mounting. However, the units are shipped with the motor mounting assembly installed as shown in 1 for the LA300, LB360, LB480 and 2 for the LB600.
MOTOR MOUNTING CHANNELS AND MOUNTING PLATE ARE ALWAYS SHIPPED IN THIS LOCATION.
FIGURE 1 - LA300 AN LB360/LB480 FACTORY
MOTOR MOUNTING POSITION
NOTE: The 5HP motors are not inherently protected.
A lte rn a tiv e P o s itio n 1 F o r P iv o t B o lts
Alternate Position 3 F o r P iv o t B o lts
A lte rn a tiv e P o s itio n 2 F o r P iv o t B o lts
LA300/LB360/LB480 MOTOR MOUNTING
The LA300, LB360 and LB480 ship from the factory with a motor mounting adapter plate for use with the 7.5 and 10 HP motors. If a 5 HP motor is used,the adapter is not necessary and should be removed and discarded.
LB600 MOTOR MOUNTING
The motor mounting plate will accommodate a 10 or 15 HP motor. One set of boltholes is provided on each end of the motor mounting plate for either motor. The motor mounting plate can be raised or lowered to any position on the adjust­ment screws to adjust the belt tension for the various pulley settings to cover the complete range of blower speeds.
The physical size of the 15HP motor reducesthe adjustment range of the motor mounting plate. To maximize this amount of adjustment, one set of boltholesis provided near the adjustment screws on each end of the motor mounting plate (refer to 4).
For some motor/blower wheel arrangements,however, the motor cannot be mounted in these bolt holes because the motor terminal box would interfere with one of the blower sec­tion panels. To make these motor/blower wheel arrange­ments possible, a second set of boltholes is provided near the pivot bolts on each end of the motor mounting plate.
15 H P
10 H P
15 H P
15 H P
Adjustm ent S c re w (2 )
M otor M ounting P late (S tandard Location
s Shipped)
P iv o t B o lt (2 )
FIGURE 2 - LB600 FACTORY MOTOR MOUNTING
POSITION
Adjustm ent Screw Holes
15 H P
15 H P
15 H P
10 H P
FIGURE 3 - LB600 MOTOR MOUNT PLATE
The motors used withthe evaporator blower are 3-phaseand can drive the blower wheels from either end of the blower section. Reversing the direction of rotation can be accom­plished by changing the connection of the power supply wir­ing at the motor terminal box.
NOTE: The 7.5-15 HP blower motors have solid bases
and are not inherently protected. For proper operation, these motors require overload heater elements. Please see curent product price pages for overloads.
Unitary Products Group 7
The 15 HP drive package requires two different lengths of belts to vary the blower wheel RPM over the complete range of rated conditions. When the motor is mounted near the adjustment screws, the two lengths of belt are interchange­able except for the higher and lower limits of blower wheel RPM. When the m otor is mounted near the pivot bolts, the shorter length of belt is recommended for the higher blower wheel Rpm's and the longer length of belt is recommended for the lower blower wheel Rpm's. See Page 7 for the recom­mended blower motor locations.
035-18496-000-C-1102
MOTOR MOUNT ARRANGEMENTS
The motor mounting arrangement can be changed to allow motor access based on the airflow arrangement required. The recommended motor location for each blower arrange­ment is as follows.
LA300/LB360/LB480 MOTOR ARRANGEMENTS
The LA300, LB360 and LB480 units are shipped with the motor mount in locationA as shownin 4. If this is the desired position, the motor mounting assembly is already in the cor­rect position and the motor and drive package can be installedwithout modifications.
ADDITIONAL MOTOR ARRANGMENTS FOR LA300/ LB360/LB480
Move the entire motor amounting assembly (both the mount­ing plate and the channels) so that the mountingplate will be in the correct location.
1. Rotate the motor mounting plate 180 degrees on the mountingchannels.(For locations B, andD only! Do not rotate the plate for location C or E.)
MOTOR
MOTOR
MOTOR MOUNTING
MOUNTING CHANNELS
PLATE
FIGURE 4 - LA300/LB360/LB480 MOTOR
LOCATION A
2. Install the motor and drive package.
NOTE: The blower section must be lifted off the evap-
orator section to gain access to the mounting channel fasteners. Since these sections have to be repositioned for the arrangements 2 through 10 and 12 of 6, the motor mounting assembly should be relocated before the two sectionsare rejoined.
ARRANGEMENT 1, 4, 8 OR 11
B
A
SEE NOTES
ARRANGEMENT 3, 5 OR 10
SEE NOTES
E
NOTE: Since the motor mounting assembly cannot be secured to the panel with the blower openings, the motor cannot be installed in either of the normally recommended bottom positions.
FIGURE 5 - LA300/LB360/LB480 MOTOR ARRANGEMENTS
ARRANGEMENT 2, 6 OR 7
D
C
ARRANGEMENT 9 OR 12
C
SEE NOTES
SEE NOTES
8 UnitaryProductsGroup
035-18496-000-C-1102
LB600 MOTOR ARRANGEMENTS
The LB600 unit is shipped with the motor mount in the stan­dard location as shown in 2.
If this is the desired position, the motor mounting assembly is already in the correct position and the motor and drive pack­age can be installed without modifications.
RE-LOCATING THE LB600 MOTOR MOUNTING PLATE
The motor mounting plate can bere-locatedin three alternate positions:
ALTERNATE POSITION ONE
For locating motor mounting plate in alternate position one, see 3 and re-locate as follows:
1. Remove pivot bolts from the mounting plate.
2. Remove the mounting plate from the adjustment screws.
3. Rotate mounting plate 180.
4. With pivot bolts removed in Step 1 fasten the mounting plate to alternate position No. one.
5. Fasten mounting plate to the adjustment screws.
ALTERNATE POSITION TWO
The motor mounting plate, the pivot bolts and the adjustment screws can be m oved intoa position similar to the one shown as standard in 3 but under the other blower scroll. The frame­work under each blower scroll has the same bolthole arrangement.
ALTERNATE POSITION THREE
The motor mounting plate, the pivot bolts and the adjustment screws can be moved into a position similar to the one detailed in alternate position one but behind the other blower scroll. The framework behind each blower scroll has the same bolthole arrangement.
AIR DISCHARGE CONVERSION
LA360/LB360/LB480 AIR DISCHARGE
The LA300 LB360 and LB480 units are shipped for upflow operation, but may be converted for any of the illustrated air discharge patterns shown in 7 and 8. C onvert as follows:
1. Remove the panels from the blower section.
2. Remove the Phillips machine screws located inside cas­ing corner angles that hold the coil and blower sections together.
3. Rotate the blower section for the desired air discharge pattern.
NOTE: Before proceeding to step 4, see the section
on the blower motor mounting locations and mount the blower motor in the desired position.
4. If accessory heating coils are used, mount heating coil between cooling coil and blower sections. Screw fasten­ing locations are the same for all sections and heating accessories. If heating coils are not used, fasten coil section to blower section with machine screws removed in step 2.
5. Before replacingpanels, see duct connectionsand drain connections.
6. Replace panels.
Unitary Products Group 9
035-18496-000-C-1102
1
BLOWER
AIR
AIR
EVAPORATOR COIL
AIR
2
AIR
**
AIR
AIR
4
AIR
AIR
5
**
FIGURE 6 - VERTICAL AIRFLOW ARRANGEMENTS
78
VERTICAL ARRANGEMENTS
AIR
AIR
AIR
3
AIR
*
6
* IF REQUIRED, SOME AIR CAN BE BROUGHT THROUGH THE BOTTOM OF THE EVAPORATOR SECTION.
AIR
*
9
AIR
AIR
AIR
10
AIR
AIR
FIGURE 7 - HORIZONTAL AIRFLOW ARRANGEMENTS
AIR
11
AIR
AIR
AIR
12
AIR
AIR
10 UnitaryProductsGroup