Energy Tech Laboratories EDP70 User Manual

EDP70 PLUS
UNINTERRUPTIBLE POWER SYSTEM
24/36/50/80kVA –
3 phase input / 3 phase output
USER HANDBOOK
PART NUMBER 10H52152PU9C rev.1
IMPORTANT SAFETY INSTRUCTIONS READ BEFORE INSTALLING
1) SAVE THESE INSTRUCTIONS
This manual contains important instructions for the EDP70 PLUS which should be followed during installation and maintenance of the UPS and associated batteries.
2) The installation must be inspected by trained technicians.
The instructions must be followed.
3) When external batteries are provided by the Customer and not Chloride, reference must be made
to the installation instructions provided by the battery supplier.
WARNINGS
1) The AC and DC supplies to the EDP70 PLUS UPS and the AC output from the UPS MUST be fed
through suitably rated circuit breakers or fuses and isolating switches suitable for branch circuit operation.
2) Any external battery cabinet connected to the UPS MUST be provided with an over-current
protection device per UL1778 Par. No. 10.4
3) To reduce the risk of fire or electric shock, the equipment must be installed indoors, in a humidity
and temperature controlled environment which is free from conductive contaminants.
SAFETY
1) DO NOT REMOVE COVERS DURING NORMAL OPERATION. The panels will be removed
during installation, however this should only be undertaken by qualified technicians. It should be ensured that the UPS is switched off and that all power sources are disconnected (A.C. mains and Battery) before either the rear or side panels are removed.
2) FOREIGN OBJECTS MUST NOT BE INTRODUCED INTO THE VENTILLATION GRILLES.
HAZARDOUS VOLTAGES are present within the EDP70 PLUS even when it is switched off.
3) Fuses must ONLY be replaced with the same type and rating.
4) The EDP70 PLUS contains a battery which can be DANGEROUS if interfered with. Contact the
supplier for replacement.
5) The UPS and/or its components must be disposed of as notifiable waste in accordance with local
pollution control (special waste) regulations.
page 2 -- MI00/10056 rev.1--05/2001
WARNING
The UPS contains hazardous voltages, even when all switches are open.
In case of fire in the installation area, do not use water to extinguish fire.
ELECTRICAL PRECAUTIONS:
If the UPS is in By-pass mode and the Output switch is closed, no indications will be displayed; fans will however function, and hazardous voltages are present downline
from the static switches.
EMERGENCY PROCEDURE
In the case of an emergency, the load supply can be interrupted by switching off all the switches fitted in the UPS.
ELECTRIC SHOCK
Switch off power; use dry insulating material for protection when pulling the injured person clear of conductors. NEVER TOUCH THE INJURED PERSON WITH BARE HANDS UNTIL CLEAR OF CONDUCTORS. SEEK QUALIFIED ASSISTANCE IMMEDIATELY.
INJURIES CAUSED BY CONTACT WITH CORROSIVE LIQUIDS
In normal conditions, installed batteries are sealed. A damaged battery container may however leak electrolyte, or cause the latter to come into contact with battery parts. In the event of electrolyte contact with the eyes, rinse eyes thoroughly with a saline solution or fresh water for at least 10 minutes. In the event of electrolyte contact with skin, rinse the affected area with abundant water. Remove contaminated clothing. Cover affected area with dry gauze.
If electrolyte is swallowed, do not induce vomiting. Administer large quantities of
milk or water.
IN ALL CASES, SEEK MEDICAL ATTENTION IMMEDIATELY
MI00/10056 rev.1--05/2001-- page 3
Contents
1.0 INTRODUCTION................................................................................................................6
1.1 Summary of the manual................................................................................................6
1.2 Summary of the equipment ..........................................................................................6
1.3 Block diagram................................................................................................................6
1.4 Functions.......................................................................................................................8
1.5 Operational modes........................................................................................................9
2.0 SAFETY...........................................................................................................................11
2.1 General safety..............................................................................................................11
2.2 Symbols .......................................................................................................................11
2.3 Electrical precautions ................................................................................................. 12
2.4 Battery precautions.....................................................................................................12
2.5 Battery safety equipment............................................................................................12
3.0 STORAGE .......................................................................................................................13
4.0 INSTALLATION...............................................................................................................13
4.1 Mechanical characteristics.........................................................................................13
4.2 Installation ...................................................................................................................21
Recommended wire sizes....................................................................................................22
4.4 Ventilation.................................................................................................................... 24
5.0 CONNECTION.................................................................................................................25
5.1 Electrical connections.................................................................................................28
5.2 24 – 12/18/24kVA..........................................................................................................29
5.3 36 – 24/30/36kVA..........................................................................................................32
5.3 EDP70 PLUS 50/80kVA................................................................................................35
5.4 Signal connections......................................................................................................38
6.0 CONTROLS.....................................................................................................................39
6.1 User Controls...............................................................................................................39
6.2 Control Panel...............................................................................................................40
7.0 START UP .......................................................................................................................41
page 4 -- MI00/10056 rev.1--05/2001
Figures
Figure 1 – Block diagrams – 24/36kVA....................................................................................7
Figure 2 – Block diagram – 50/80kVA......................................................................................8
Figure 3 – Normal operation.....................................................................................................9
Figure 4 – Utility Supply failure................................................................................................9
Figure 5 – Re-establishing the Utility Supply........................................................................10
Figure 6 – Transferring the Load onto the Reserve Supply.................................................10
Figure 7 – 24 Footprint and cabinet dimensions ..................................................................14
Figure 8 – 36 Footprint and cabinet dimensions ..................................................................15
Figure 9 – 50/80 Footprint and cabinet dimensions .............................................................16
Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings..........................................17
Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings..........................................18
Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings..........................................19
Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings..........................................20
Figure 14 – UPS Ratings.........................................................................................................21
Figure 15 – Connection diagrams..........................................................................................25
Figure 16 - 24 – 12/18/24kVA: Switches and Breakers .........................................................29
Figure 17 - 24 – 12/18/24kVA: Switches.................................................................................30
Figure 18 - 24 – 12/18/24kVA: Cable Connections................................................................31
Figure 19 - 36 – 24/30/36kVA: Switches and Breakers .........................................................32
Figure 20 - 36 – 24/30/36kVA: Connections...........................................................................33
Figure 21 - 36 – 24/30/36kVA: Cable Connections................................................................34
Figure 22 – 50/80kVA: Switches and Breakers .....................................................................35
Figure 23 – 50/80kVA: Connections.......................................................................................36
Figure 24 – 50/80kVA: Cable Connections............................................................................37
Figure 25 – Control panel .......................................................................................................39
MI00/10056 rev.1--05/2001-- page 5
1.0 INTRODUCTION
1.1 Summary of the manual
This handbook provides for the safe installation, startup and use of the EDP70 PLUS Uninterruptible Power System (UPS). The Company recommends that the equipment be installed and regularly maintained by a Chloride Authorized personnel.
DO: - read the User Handbook before operating the EDP70 PLUS UPS.
- keep a log of all incidents.
- protect the batteries from damage. Batteries leak acid; avoid contact with skin, clothes or eyes.
DO NOT: - operate the control switches.
- operate the EDP70 PLUS UPS with any covers removed.
- obstruct the ventilation grilles.
1.2 Summary of the equipment
The EDP70 PLUS Uninterruptible Power System (UPS) totally isolates the load from voltage drops, spikes, transients frequency variations in the utility supply.
In the event of failure or brownout of the AC utility supply, an internal audible alarm sounds and an LED on the control panel illuminates, the EDP70 PLUS UPS will continue to provide safe, clean continuous power, without interruption, from the battery, for a duration dependent on battery capacity and output load.
The audible alarm alerts the user to start a safe orderly shutdown of the load. When the AC utility supply returns to normal, the EDP70 PLUS UPS automatically recharges the battery ready for any future power failure.
The microprocessor display panel provides access to very detailed information regarding the status of the supplies and EDP70 PLUS UPS. Refer to current publication for detailed specification.
The block diagram, shows the main functional sub-assemblies of the EDP70 PLUS UPS. The AC three phase utility supply is rectified to provide direct current, which maintains the battery in a fully charged state and also supplies the inverter, which provides the three phase output via an electronic static switch.
Normally the supply of the reserve line is taken from the AC utility input, but special units, with a separate reserve input supply, are available. This allows the inputs to be supplied from independent three phase sources.
Provided the reserve supply is within limits, the inverter will match the output frequency with the reserve supply frequency. The inverter has its own internal crystal control to stabilize the output frequency if the reserve supply frequency is out of limits. The electronic static switch switches the output from the inverter to the reserve supply, without interruption, to meet any load current surges, or to supply the load if the battery is discharged during an AC utility supply failure.
Maintenance and testing can be carried out on the EDP70 PLUS UPS without interrupting the output, by switching the load from the reserve supply to the maintenance bypass circuit. This work should only be carried out by Chloride-trained personnel.
1.3 Block diagram
page 6 -- MI00/10056 rev.1--05/2001
24kVA - STANDARD CONFIGURATION
S3
Reserve Supply
208Y/120V
S2
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE
SUPPLY THE RESRVE IS DERIVED FROM THE
AC UTILITY INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Reserve Supply
208Y
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE
SUPPLY THE RESRVE IS DERIVED FROM THE
AC UTILITY INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Maintenance By-pass
290
3
Battery Contactor
208150
1
5
4
144 Cells (Internal)
2
36kVA - STANDARD CONFIGURATION
480
208Y
S2
S3
Battery Contactor
250
1
3
Maintenance By-pass
5
208Y
4
240 Cells (External)
2
S4
S4
Reserve Supply
480V
S1
AC Supply
IN THE ABSENCE OF A SEPARATE RESERVE SUPPLY THE RESRVE IS DERIVED FROM THE AC UTILITY INPUT WITH THE JUMPER CONNECTED AS INDICATED
Figure 1 – Block diagrams – 24/36kVA
36kVA - 480V/208V CONFIGURATION
480
208Y
S2
S3
Battery Contactor
250
1
Maintenance By-pass
3
208Y
240 Cells (External)
5
4
2
MI00/10056 rev.1--05/2001-- page 7
S4
S3
Maintenance Bypass
Reserve Supply
480V
AC Supply
S2
S1
IN THE ABSENCE OF A SEPARATE
RESERVE SUPPLY THE RESERVE IS
DERIVED FROM THE AC UTILITY
INPUT WITH THE JUMPER
CONNECTED AS INDICATED
Battery Contactor
240 Cells (External)
3
1
2
S5
5
S4
4
480Y/277V
208Y/120V
Figure 2 – Block diagram – 50/80kVA
The uninterruptible power system consists of the following:
1 - RECTIFIER/INVERTER S1 = Equipment ON/OFF switch 2 - BATTERY S2 = Equipment Reserve switch 3 - BACKFEED PROTECTION S3 = Equipment By-pass switch 4 - INVERTER STATIC SWITCH S4 = Equipment OUTPUT switch 5 - RESERVE STATIC SWITCH (INVERTER OUTPUT switch for 50/80kVA only)
S5 = RESERVE OUTPUT switch for 50/80kVA only
1.4 Functions RECTIFIER / BATTERY CHARGER
The rectifier/battery charger transforms the alternating current of the mains supply to direct voltage to maintain the battery in a fully charged state and also supply the inverter.
BATTERY
The battery is an energy reserve that is used by the inverter and the load whenever the mains supply fails.
INVERTER
The inverter changes the direct voltage from the rectifier or from the battery into a three phase sinusoidal alternating voltage for the external supply.
ELECTRONIC STATIC SWITCH
The function of the electronic static switch is to select one of the two sources of alternating voltage and to supply it to the external load. The two sources of voltage supplied to the static switch are the output of the inverter and the reserve supply. In normal working conditions, the static switch supplies the load from the inverter.
SWITCHES
The switches permits maintenance and repair of the UPS, without interrupting the supply to the load.
page 8 -- MI00/10056 rev.1--05/2001
1.5 Operational modes
S3
S2
Maintenance By-pass
AC Supply
AC Supply
S1
Battery Contactor
S3
S2
S1
Battery Contactor
24/36kVA Ratings
Maintenance By-pass
50/80kVA Ratings
LOAD
S4
S5
S4
480Y/277V
LOAD
208Y/120V
Figure 3 – Normal operation
During normal operation the load is supplied by the mains through the rectifier and inverter. The rectifier also supplies the current for recharging and maintaining the battery in a fully charged state.
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
24/36kVA Ratings
S4
LOAD
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
S5
S4
50/80kVA Ratings
480Y/277V
LOAD
208Y/120V
Figure 4 – Utility Supply failure
When the utility supply voltage is absent or outside the allowed tolerances, the battery supplies the inverter. This will be indicated on the UPS front panel display and the Remote Alarm Unit (if fitted). The standby time available depends both on the capacity of the battery and on the size of load. It is possible to extend autonomy by reducing the output power by disconnecting non-important loads. In all cases, the alphanumerical display shows the residual autonomy.
MI00/10056 rev.1--05/2001-- page 9
Reserve Supply
S3
S2
Maintenance By-pass
S4
S5
S4
480Y/277V
208Y/120V
AC Supply
Reserve Supply
AC Supply
S1
Battery Contactor
S3
S2
S1
Battery Contactor
24/36kVA Ratings
Maintenance By-pass
50/80kVA Ratings
Figure 5 – Re-establishing the Utility Supply
When the utility supply returns within acceptable limits, the UPS returns automatically to normal operation mode as previously described. The rectifier now starts to recharge the battery. However, until recharge has been completed, any further mains failure will result in reduced standby times.
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
S4
24/36kVA Ratings
Reserve Supply
AC Supply
S3
S2
S1
Battery Contactor
Maintenance By-pass
50/80kVA Ratings
S5
S4
480Y/277V
208Y/120V
Figure 6 – Transferring the Load onto the Reserve Supply
Transfer onto the reserve line is caused by two conditions: a) inverter stop b) overload In both instances the load is transferred onto the reserve without interruption. If the overload is temporary, the system will re-transfer from reserve to inverter as soon as the it ceases. This allows for the initial start-up of loads with high or excessive switch-on currents.
page 10 -- MI00/10056 rev.1--05/2001
2.0 SAFETY
Read all instructions carefully before installing or operating the equipment.
2.1 General safety
The procedure described in these instructions is intended for use by persons experienced in the operation of Uninterruptible Power Systems and ancillary equipment. Persons unfamiliar with this type of equipment should seek guidance from experienced personnel. The EDP70 PLUS UPS is designed to be operated in accordance with existing safe operating procedures. These instructions are not intended to replace existing safety practices. If there are any questions regarding the safe operation of the system, contact a Chloride service representative.
This equipment is designed and built for safe operation when used to supply its rated load, providing it is installed as specified by qualified, licensed and competent electricians. Electrical energy can be supplied by the equipment and the battery.
2.2 Symbols
The following symbols appear in this book and in the unit:
Warning - Hazardous voltages are present. If the instructions are not heeded, there is a
risk of electrical shock and danger to personal safety.
DIRECT CURRENT SUPPLY
ALTERNATING CURRENT SUPPLY
ON position of the switches
OFF position of the switches
Inverter Start Up
Inverter Shutdown
Audible Alarm Cancel Switch
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
For explanation see Para. 6.2. of this manual
MI00/10056 rev.1--05/2001-- page 11
Page Right Control For explanation see Para. 6.2. of this
manual
Record Up For explanation see Para. 6.2. of this
manual
Record Down For explanation see Para. 6.2. of this
manual
2.3 Electrical precautions
Never handle a component or assembly without first confirming that no voltage is applied or present. Remove only those protective covers that are essential to perform the repairs or adjustment currently required, and replace them as soon as possible.
. Use only insulated tools. . Place a rubber insulating mat in front of all equipment doors. . Keep all door closed and locked at all times during normal operation.
2.4 Battery precautions
Always isolate the load before connecting or disconnecting the batteries or battery cells. Ensure that batteries are fully isolated by disconnecting the battery connectors, opening circuit breakers, or both. Remove all jewellery from hands, wrists and neck before working on batteries or battery cells. Before leaning over batteries, remove any metal object that could fall out of pockets. Do not place tools or other conductive objects on the batteries.
2.5 Battery safety equipment
When working on or handling batteries, ensure that the following items are worn:
. Eye goggles . Rubber gloves . Rubber apron . Rubber boots
When batteries are being moved or worked on, ensure the following items are available in the immediate vicinity:
. An eye bath, eyewash station or equivalent . A clean water source to wash spilled acids . Absorbent materials to soak up spilled acids . Disposal for contaminated materials.
page 12 -- MI00/10056 rev.1--05/2001
3.0 STORAGE
If the EDP70 PLUS UPS cannot be installed within sixty days of delivery, there is a danger of the integral battery becoming discharged thereby sustaining permanent damage and affecting the standby period available and battery life. The date the battery was last recharged and the date the battery is due for its next recharge are both stamped on the packaging accompanying the unit. If you intend to store the unit, please refer to the recharge date. When the EDP70 PLUS is due to be recharged, refer to the Installation instructions and connect the EDP70 PLUS UPS to a temporary AC supply. The battery MUST be recharged for at least 24 hours every 3 months.
4.0 INSTALLATION
4.1 Mechanical characteristics
- Ambient temperature 18°F[-10°C] to 104°F [+40°C ]
- Relative Humidity (w/out condensing @ 68°F[20°C]) < 90%
- Max altitude (w/out derating) 3300 feet [1000 m] above sea-level
- Protection degree (panel fitted)
- Input cables bottom
- Air inlet bottom
- Air outlet rear
UPS model
Description
Size width
depth
height
u.m.
In
[mm]
24 36 50 80
27.5 [700]
28.7 [730] 56 [1420]
27.5 [700]
28.7 [730] 56 [1420]
35.4 [900]
28.7 [730] 63 [1600]
35.4 [900]
28.7 [730] 63 [1600]
Total Weight (UPS +
Battery)
Floor Area
Floor
Loading
(UPS +
Battery)
Acoustic Noise
100% Linear Load
Air-Flow
w/out cells 25 Ah cells 30 Ah cells 35 Ah cells
w/out cells 25 Ah cells 30 Ah cells 35 Ah cells
Lbs [kg]
In2[m2] 789 [0.511] 789 [0.511] 1019 [0.657] 1019 [0.657]
2
Lbs/in
[kg/m2]
cfm
[mc/h]
dBA 52 55
Notes: 1) n.a. = not applicable
2) Longer autonomies, and battery for EDP above 20 kVA are available with external
battery cubicles.
880 [400] 1342 [610] 1456 [662] 1526 [694]
1.12 [782]
1.70 [1194]
1.85 [1296]
1.93 [1358] 235
[400]
1300 [590]
n.a. n.a. n.a.
1.65 [1155] n.a. n.a. n.a.
647
[1100]
1342 [610]
n.a. n.a. n.a.
1.32 [930] n.a.
n.a. n.a.
MI00/10056 rev.1--05/2001-- page 13
1800 [818]
n.a. n.a. n.a.
1.77 [1245] n.a.
n.a. n.a.
1417,0
(26.77)
680,0
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
700,0 (27.56)
(55.79)
645,0
(25.39)
30,0 (1.18)
726,0 (28.58)
58,0 (2.28)
NR 4 X
260 (10.24) X 66 (2.6)
CABLE ENTRY
ø 8
(
ø 0
,
3
1
)
(2.64)
67,0
728,0 (28.66)
600,0
Figure 7 – 24 Footprint and cabinet dimensions
page 14 -- MI00/10056 rev.1--05/2001
(23.62)
63,0 (2.48)
ALL MEASUREMENTS ARE IN
(26.77)
680,0
MILLIMETERS (AND INCHES)
700,0 (27.56)
1417,0
(55.79)
NR 4 X
ø 8
(
ø 0
,
3
1
)
645,0
30,0
(25.39)
(1.18)
125,0
(4.92)
88,0 (3.46)
CABLE ENTRY
500 (19.68) X 110 (4.33)
(28.66)728,0
600,0
(23.62)
50,0
(1.97)
Figure 8 – 36 Footprint and cabinet dimensions
MI00/10056 rev.1--05/2001-- page 15
ALL MEASUREMENTS ARE IN MILLIMETERS (AND INCHES)
900,0 (35.43)
1600
(63.0)
NR 4 X
ø 8
(
ø 0
,
3
1
)
645,0
(25.39)
30,0 (1.18)
100,0
800,0
(3.94)
(31.5)
Figure 9 – 50/80 Footprint and cabinet dimensions
page 16 -- MI00/10056 rev.1--05/2001
68,0 (2.68)
700 (27.56) X 110 (4.33)
CABLE ENTRY
50,0
(1.97)
740,0 (29.13)
Figure 10 – “A” Battery Cabinet Drawing for 24/36kVA Ratings
MI00/10056 rev.1--05/2001-- page 17
Figure 11 – “B” Battery Cabinet Drawing for 24/36kVA Ratings
page 18 -- MI00/10056 rev.1--05/2001
Figure 12 – “E” Battery Cabinet Drawing for 50/80kVA Ratings
MI00/10056 rev.1--05/2001-- page 19
Figure 13 – “F” Battery Cabinet Drawing for 50/80kVA Ratings
page 20 -- MI00/10056 rev.1--05/2001
Loading...
+ 45 hidden pages