58 =575-3-60
EC = Single Input EconomizerDK = Dual Input Economizer
FD = Sing. Input Economizer w/ Power
Exhaust
BG =Motorized Outdoor Air Damper
N=NaturalGas
46 = 460-3-60
CF = Dual Input Economizer with Power
Exhaust
GENERAL
YORK Model DHG units are single package high efficiency
gas-fired central heating furnaces with cooling unit designed
for outdoor installation on a rooftop or a slab.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electrical wiring is factory installed and tested. The units require
electric power, gas connection, duct connections, installation
of combustion air inlet hood, flue gas outlet hoods and fixed
outdoor air intake damper (units without economizer or
motorized damper option only) at the point of installation.
The gas-fired heaters have aluminized-steel tubular heat
exchangers and spark ignition with provenpilot.
.
FOR YOUR SAFETY IF YOU SMELL GAS:
a.Open windows.
b.Don’t touch electrical switches; do not use any
phones inthe area ofthe gas leak.
SAFETY CONSIDERATIONS
Installer should pay particular attention to the words: NOTE,
CAUTION, and WARNING. Notes are intended to clarify or
make the installation easier. Cautions are given to prevent
equipment damage. Warnings are given to alert installer that
personal injury and/or equipment damage may result if installation procedure is not handled properly.
Due to system pressure, moving parts and electrical components, installation and servicing of air conditioning equipment
can be hazardous. Only qualified, trained, service personnel
should install, repair, maintain or service this equipment.
Observe all precautions in the literature, on labels and tags
accompanyingthe equipment whenever working on air conditioning equipment. Be sure to follow all other safety precautions thatapply.
Wear safety glasses and work gloves, and follow all safety
codes. Use a quenching cloth and have a fire extinguisher
available for all brazing operations.
c.Extinguish any open flame.
d.Immediately call your gas supplier from another
location. Follow your gas supplier’s instructions.
e.If you cannot reachyour gas supplier, call the fire
departments.
This product must be installed in strict compliance
with the enclosed installation instructions and any
applicable local, state, and national codes including, butnot limited to, building, electrical and
mechanical codes.
Unitary Products3
Page 4
INSTALLATION
LIMITATIONS
035-17233-000-C-0702
Improper installation may create a condition where
the operation of the product could causepersonal
injury orproperty damage.
REFERENCE
Additional information on the design, installation, operation
and service of this equipment is available in the following reference forms:
•44-320-10 - Barometric Relief Damper Accessory
•530.18-N6.1V - Propane Conversion Accessory(USA)
•530.18-N6.2V - High Altitude Accessory (Nat. Gas)
•530.18-N6.3V - High Altitude Accessory (Propane)
RENEWAL PARTS:
Refer to the Renewal Parts Manual for complete listing of
replacement parts on this equipment.
All forms referenced in this instruction may be ordered from:
Standard Re gister
2101 West Tecumseh Road
Norman, Oklahoma 73069
Toll Free Phone (877) 318-9675
Toll Free Fax: (877) 379-7920
AGENCY APPROVALS
Design certified by ETL as follows:
These units must be installed in accordance with the following national and local safety codes:
1.National Electrical Code ANSI/NFPA No. 70.
2.NationalFuel Gas Code Z223.1.
3.Gas-Fired Central Furnace StandardANSI Z21.47a.
4.Local gas utility requirements.
Refer to Table 2 for Unit Application Data and to Table 4 for
Gas HeatApplication Data.
TABLE 2: UNIT APPLICATION DATA
MODEL SIZE15 TON20 TON
VoltageVariation,
Min./Max
Supply Air CFM, Min./Max.4500/72006000/9400
Wet Bulb Temperature (°F) of a ir
on Outdoor CoilMin./Max.
Dry Bulb Temperature (°F) of air
on Outdoor CoilMin./Max.
1
2
1
Rated in accordance with ARI Standard110, utilization
range “A”.
A lowambient accessory is available for operation
downto0°F.
208/230-3-60187/253
460-3-60414/506
575-3-60518/630
57/72
2
25/120
1.For use as a forced air furnace with cooling unit.
2.For outdoor installationonly.
3.For installation on combustible material.
4.For use with natural gas or propane gas.
After installation, the unit must be adjusted to obtain a temperature rise within the range specified on the unit rating
plate.
If components are to be added to a unit to meet local codes,
they are to be installed at the dealer's and/or the customer's
expense.
INSPECTION
As soon as a unit is received,it shouldbe inspected for possible damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill. A
separate request for inspection by the carrier's agent should
be made in writing. Refer to Form 50.15-NM for additional
information.
4Unitary Products
Size ofunit for proposed installation should be based on heat
loss/heat gain calculation made according to the methods of
the Air Conditioning Contractorsof America (ACCA).
This furnace is not to be used for temporary heating of buildings orstructures under construction.
Page 5
035-17233-000-C-0702
LOCATION
Use the following guidelines to select a suitable location for
these units.
1.Unit is designed for outdoor installation only.
2.Condensercoils must have an unlimited supply of air.
Where a choice of location is possible, position the unit
on eithernorth or eastside of building.
Excessive exposure of this furnace to contaminated combustion air may result equipment damage or personal injury. Typical contaminates
include: permanent wave solutions, chlorinated
waxes and cleaners, chlorine based swimming
pool chemicals, water softening chemicals, carbon
tetrachloride, Halogen type refrigerants, cleaning
solvents (e.g. perchloroethylene), printing inks,
paint removers, varnishes, hydrochloric acid,
cements and glues, antistatic fabric softeners for
clothes dryers, masonry acid washing materials.
Length ofthe forks must be a minimum of 90”.
An adhesive backed label isprovided overthe outside of the combustion air inlet opening to prevent
moisture from entering the unit which could cause
damage to electrical components. Allow this closure label to remain in place until the combustion
air hoodis to be installed (refer to Figure 7).
3.For ground level installation, use a level concrete slab
with a minimum thickness of 4 inches.The length and
width should be at least 6 inchesgreater than the unit
base rails. Do not tie slabto the building foundation.
4.Roofstructures must beable to support the weightof the
unit andits options and/or accessories.Unit must be
installed on a solid level roof curb or appropriate angle
iron frame.
Ifaunitistobeinstalledonaroofcurborspecial
frame other than a YORK roof curb, gasketing
must be applied to all surfaces that come in contact with the unit underside.
5.Maintain leveltolerance to 1/2" maximum across the
entire length or width of the unit.
RIGGING AND HANDLING
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the round lifting
holes provided in the base rails. Spreaders, whose length
exceeds the largest dimension across the unit, MUST be
used across the top of the unit. Refer to Figure 1.
FIGURE 1: TYPICAL RIGGING
Refer to Table 6 for unit weights and to Figure 2 for approximate center of gravity.
FIGURE 2 : CENTER OF GRAVITY
CLEARANCES
Units may also be moved or lifted with a forklift, from the front
or rear only, providing that an accessory skidis used.
Unitary Products5
All units require certain clearances for proper operation and
service. Installer must make provisions for adequate
Page 6
combustion and ventilation air in accordance with Section
5.3, Air for Combustion and Ventilation of the National Fuel
Gas Code, ANSI Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or
7.4 of Gas Installation Codes CAN/CGA-B149.1 and .2 (in
Canada) and/or applicable provisions of the local building
codes. Refer to Table 8 for the clearances required for
combustible construction, servicing,and properunit
operation.
Do not permit overhanging structures or shrubs to
obstruct outdoor air discharge outlet, combustion
air inlet or vent outlets.
035-17233-000-C-0702
DUCTWORK
Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).
A closedreturn duct system shall be used. This shall not preclude use of economizers or outdoor fresh air intake. The
supply and return air duct connections at the unit should be
made with flexible joints to minimize noise.
The supply and return air duct s ystems should be designed
for the CFM and static requirements of the job. They should
NOT be sized to match the dimensions of the duct connec-
tions on the unit.
When fastening ductwork to side duct flanges on
unit, insert screws through duct flanges only. DO
NOT insert screwsthrough casing.
Outdoor ductwork must be insulated and waterproofed.
Refer to Figure 10 and12 for information concerning side and
bottom supply and return air duct openings.
FIGURE 3 : FIXED OUTDOOR AIR DAMPER
Gasketing and mounting screws are provided in a parts bag
attached to the hood assembly. Apply gasketing to the three
flange surfaces on the hood prior to installing the hood.
Extend gasketing 1/4" beyond the top and bottom of the two
side flanges to insure adequate sealing.
Adjusting the damper to the desired air flow may be done
before mounting the hood into position or (after installation)
by removing thefront hood panel or thescreen on the bottom
of the hood. Damper baffle in position 1 will allow approximately 10% recirculated air flow, position 2 approximately
15% and, to allow approximately 25%, remove the damper
baffle.
On units with bottom return air applications, install the
damper assembly over the opening in the side return air
access panel. Remove and discard the opening cover and
the covering over the hood mounting holes (used for shipping) before installing. Securewith the screws provided.
On units with side return air applications, install the damper
assembly on the return air ductwork as close to the unit as
possible.Cut anopening 16" high by 18" wide in the ductwork
to accommodate the damper. Using the holes in the hood
flanges as a template, drill 9/64" dia. (#26 drill) holes into the
ductwork and secure with the screws provided.
FIXED OUTDOOR AIR INTAKE DAMPER
This damper is shipped inside the return air compartment. It
is completely assembled and ready for installation. A damper
baffle inside of the hood is adjustable to provide variable
amounts of outdoor air intake on units that are not provided
with an economizer or a motorized damper option. Refer to
Figure 3.
6Unitary Products
If outdoor air intake will not be required on units
with bottom return air applications, the damper
assembly should still be mounted on the side
return airaccess panel, per theinstructions above,
to insure moisture is not drawn into the unit during
operation. The covering over the mounting holes
only need be removed. Do not remove theopening
cover.
Page 7
035-17233-000-C-0702
CONDENSATE DRAIN
Plumbing must conform to local codes. Use a sealing compound on male pipe threads. Install a condensate drain line
from the 1" NPT female connection on the unit to an open
drain.
FIGURE 4 : RECOMMENDED DRAIN PIPING
An alternate drain connection (1" NPT female coupling) is
provided inboard on the same centerline as the exterior location.
NOTE:
vide proper drainage.See Figure 4.
The condensate drain line MUST be trapped to pro-
•Side Supply & Return Air compartments (Two panels)
•Blower compartment (Three panels)
•Main control box
•Filter compartment
•Outdoor Air compartment (Two panels)
Refer toFigure 10 forlocation of these access panels.
Make sure that all screws and panel latches are
replaced and properly positioned on the unit to
maintain an air-tight seal.
THERMOSTAT
The room thermostat should be located on an inside wall
approximately 56" above the floor where it will not be subject
to drafts, sun exposure or heat from electrical fixtures or
appliances. Follow manufacturer's instructions enclosed with
thermostat for general installation procedure. Seven color
coded insulated wires (#18 AWG) should be used to connect
thermostat to unit.
POWER AND CONTROL WIRING
COMPRESSORS
Units are shipped with compressor mountings factoryadjusted and ready for operation.
Do Not loosen compressor mountingbolts.
FILTERS
Two-inch filters are supplied with each unit. Filters must
always be installed ahead of the evaporator coil and must be
keptcleanorreplacedwithsamesizeandtype.Dirtyfilters
will reduce the capacity of the unit and will result in frosted
coils or safety shutdown. Minimum filter area and required
sizes areshown in Table 6.
SERVICE ACCESS
Access to all serviceable components areprovided bythe following removable panels:
•Compressor compartment
•Gas Heatcompartment (Two panels)
Field wiring to the unit must conform to provisions of the
National Electrical Code, ANSI / NFPA No. 70 (latest edition)
and/or local ordinances. The unit must be electrically
grounded in accordance with N.E.C. and/or local codes. Voltage tolerances which must be maintained at the compressor
terminals during starting and running conditions are indicated
on the unit Rating Plate and Table 2.
The internal wiring harness furnished with this unit is an integral part of a ETL design certifiedunit. Field alterationto comply withelectrical codesshould not be required.
A fused disconnect switch should be field provided for the
unit. Theswitch must be separate from all othercircuits. Wire
entry at knockout openings require conduit fittings to comply
with NEC and/or local codes. Refer to Figure 10 for installation location. If any of the wire supplied with the unit must be
replaced, replacement wire must be of the type shown on the
wiring diagram and the same minimum gauge as the
replaced wire.
Electrical line must be sized properly to carry the load. Each
unit must be wired with a separate branch circuit fed directly
from themeter panel and properly fused.
Refer toFigure 5 for typical field wiringand to the appropriate
unit wiring diagram for control circuit and power wiring information.
Unitary Products7
Page 8
035-17233-000-C-0702
Typical supply piping arrangements are shown in Figures 6
and 7. All shaded items are field-supplied.
When connecting electrical power and control wiring to the unit, waterproof type connectors MUST
BE USED so that water or moisture cannot be
drawn into the unit during normal operation. The
above waterproofing conditions will also apply
when installing a field-supplied disconnect switch.
COMBUSTION DISCHARGE
The products of combustion are discharged horizontally
through two screened (hooded) openings on the upper gas
heat access panel.
TABLE 3: CONTROL WIRE SIZES
Wire Size
2220191816
40120150190305
Max. Wire Length3Feet
1
Total wire length is from unit to room thermostat, and
back tounit.
2
Solid, ClassII copper wire.
3
Total Wire length is from unitto room thermostat, and
back tounit.
1
2
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. National Fuel Gas Code Z223.1 should be followed in all cases unless superseded by local codes or gas
utility requirements. Refer to Table 5.
The heating value of the gas may differ with locality. The
value should be checked with the local gas utility.
NOTE:
There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units require a 1
inch pipeconnection at the entrance fitting.
GAS CONNECTION
The gas supply line can be routed through the knockouts
located on the front of the unit or through the opening providedintheunit'sbase.RefertoFigure10tolocatethese
access openings.
Two grommets are shipped in the blower compartment (in
parts bag taped to the blower housing) of every unit with gas
heat and should be used in the knockouts when the gas piping penetrates the front of the unit.
After the gas supply piping has been installed, the bottom
opening in the unit should be sealed to prevent water from
leaking into the building.
Gas piping recommendations:
1.A drip leg and a ground joint union must be installed in
the gaspiping.
2.When required by localcodes, a manual shut-off valve
may haveto be installed outside of the unit.
3.Usewrought iron orsteel pipe forall gas lines.Pipe dope
should be applied sparingly tomale threads only.
4.All piping shouldbe cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the
loose dirtand scale. Before initial start-up, besure that
all ofthe gas lines external tothe unit have been purged
of air.
5.Thegas supply should be aseparate line andinstalled in
accordance with all safety codes as prescribed under
Limitations.After the gas connections have been completed, open the main shut-off valve admitting normal
gas pressure tothe mains.Check alljoints forleaks with
soap solution orother material suitable for the purpose.
NEVER USE AFLAME.
6.Thefurnace and its individual manual shut-off valve must
be disconnected fromthe gas supply pipingsystem during anypressure testingof that system at test pressures
in excessof 1/2 psig (3.48kPa).
The furnace mustbe isolatedfrom the gas supply piping
system byclosing itsindividual manual shut-off valve
during anypressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig
(3.48kPa).
7.A1/8 inchNPTplugged tapping, accessiblefor testgage
connection, must be installed immediately upstream of
the gassupply connection to the furnace.
8Unitary Products
Page 9
035-17233-000-C-0702
p
C O O L I N G O N L Y ( 2 4 V O L T T H E R M O S T A T )
T H E R M O S T A T
T E R M I N A L S
R
Y 1
Y 2
G
1
2 4 V o l t T h e r m o s t a t 2 T H 0 4 7 0 1 2 2 4 o r 2 T H 0 4 7 0 1 5 2 4
( w i t h S u b b a s e 2 T B 0 4 7 0 0 2 2 4 ) .
T e r m i n a l b l o c k 1 T B - l o c a t e d o n r e l a y b o a r d i n 2 4 - v o l t s e c t i o n
o f t h e u n i t c o n t r o l b o x .
T H E R M O S T A T
T E R M I N A L S
A D D
J U M P E R
L E D 1
L E D 2
C O M
A D D
J U M P E R
1
E l e c t r o n i c p r o g r a m m a b l e t h e r m o s t a t 2 E T 0 4 7 0 0 2 2 4 ( i n c l u d e s s u b b a s e ) .
2
T e r m i n a l b l o c k 1 T B - l o c a t e d o n r e l a y b o a r d i n 2 4 - v o l t s e c t i o n o f t h e u n i t c o n t r o l b o x .
3
S e c o n d s t a g e h e a t i n g i s n o t r e q u i r e d o n u n i t s w i t h a s i n g l e s t a g e e l e c t r i c h e a t e r .
4
T e r m i n a l s A 1 a n d A 2 p r o v i d e a r e l a y o u t p u t t o c l o s e t h e o u t d o o r e c o n o m i z e r d a m p e r s
w h e n t h e t h e r m o s t a t s w i t c h e s t o t h e s e t - b a c k p o s i t i o n .
N O T E : F a n s s w i t c h m u s t b e i n " O N "
C O N T R O L WI R I N G
U N I T T E R M I N A L
1
C O O L I N G O N L Y ( 2 4 V O L T T H E R M O S T A T )
1
B L O C K 1 T B
R C
R H
Y 1
Y 2
W 1
W 2
G
B
N O T U S E D
A 1
A 2
T
T
T O R E M O T E S E N S O R
2 T H 0 4 7 0 2 2 2 4 I F U S E D
o s i t i o n f o r m i n i m u m v e n t i l a t i o n d u r i ng h e a t e r ope r a t i o n .
2
R
Y 1
Y 2
W 1
W 2
G
B
2 4 V O L T
X
T R A N S F O R M E R
A 1
A 2
U N I T T E R M I N A L
B L O C K 1 T B
3
4
4
R
Y 1
Y 2
W 1
W 2
G
B
X
2 4 V O L T
A 1
T R A N S F O R M E R
A 2
A D D
J U M P E R
2
C O O L I N G / H E A T I N G ( 2 4 V O L T T H E R M O S T A T )
T H E R M O S T A T
T E R M I N A L S
1
R H
R C
Y 1
Y 2
W 1
W 2
G
3
U N I T T E R M I N A L
B L O C K 1 T B
2
R
Y 1
Y 2
W 1
W 2
G
B
X
A 1
A 2
2 4 V O L T
T R A N S F O R M E R
Y 3
1
2 4 V o l t T h e r m o s t a t 2 T H 0 4 7 0 1 0 2 4 o r 2 T H 0 4 7 0 1 5 2 4
( w i t h S u b b a s e 2 T B 0 4 7 0 0 3 2 4 ) .
2
T e r m i n a l s t r i p 1 T B - l o c a t e d o n r e l a y b o a r d i n 2 4 - v o l t s e c t i o n
o f t h e u n i t c o n t r o l b o x .
3
S e c o n d s t a g e h e a t i n g i s n o t r e q u i r e d o n u n i t s w i t h a s i n g l e s t a g e
e l e c t r i c h e a t e r .
P O WE R WI R I N G
L I N E V O L T A G E
T E R M I N A L
B L O C K 2 T B
I N C O N T R O L B O X
G R O U N D L U G
L 1
L 2
L 3
R e f e r t o t h e
E L E C T R I C A L D A T A
t a b l e s t o s i z e t h e
p o w e r w i r i n g , t h e
f u s e s a n d t h e
d i s c o n n e c t s w i t c h .
Maximum capacity of pipein cubic feet ofgas per hour.
(Based upon a pressure drop of 0.3 inch water column
and 0.6 specificgravity gas.)
1
Nominal Iron Pipe Size
1in.1-1/4in.
FIGURE 7 : BOTTOM SUPPLY CONNECTION
EXTERNAL SHUT-OFF
L.P. UNITS, TANKS AND PIPING
All gas heat units are shipped from the factory equipped for
natural gas use only. The unit may be converted in the field
for use with L.P./propane gas with accessory kit model number 1NP0437.
FIGURE 6 : EXTERNAL SUPPLY CONNECTION
EXTERNAL SHUT-OFF
Natural gas may contain some propane. Propane,
being an excellentsolvent, willquickly dissolve
white leador most standard commercial compounds. Therefore, aspecial pipe compoundmust
be applied when wroughtironor steel pipe isused.
Shellac base compounds such as Gaskolacor
Stalastic, and compounds such as Rectorseal #5,
Cyde's or John Crane maybe used.
All L.P./propane gas equipment must conform to the safety
standards of the National Fire Protection Association.
For satisfactory operation, L.P./propane gas pressure must
be 8.8inch W.C atthe unit under full load. Maintaining proper
gas pressure depends on three main factors:
1.The vaporization ratewhich depends on(a) thetemperature of the liquid and (b) the wetted surface area of the
container or containers.
2.The proper pressure regulation. (Two-stage regulation is
recommended from the standpoint of both cost and efficiency.)
3.The pressure drop in the linesbetween regulators and
between the second stage regulatorand the appliance.
Pipe size required will depend on the length of the pipe
run and the total load of all appliances.
Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available
from most regulator manufacturers and L.P./propane gas
suppliers.
L.P./propane gas is an excellent solvent and special pipe
compound must be usedwhen assemblingpiping for this gas
as it will quickly dissolve white lead or most standard commercial compounds. Shellac base compounds such as Rectorseal #5 are satisfactory for this typeof gas.
10Unitary Products
Page 11
035-17233-000-C-0702
A
Check all connections for leaks when piping is completed,
using a soap solution. NEVER USE A FLAME.
VENT AND COMBUSTION AIR HOODS
Two vent hoods and a combustion air hood (with screens) are
shipped attached to the blower housing in the blower compartment. These hoods must be installed to assure proper
unit function. Allhoods must be fastened to the outside of the
gas heat access panel with the screws provided in the bag
also attached tothe blower housing.
The screen for the combustion air intake hood is secured as
shown on the label attached to the hood. The top flange of
this hood slips in under the top of the access panel opening
when installing. Refer to Figure 8.
Each vent hood is installed by inserting the top flange of the
hood into the slotted opening in the access panel and securing in place.
SLOTTED
VENT AIR
OUTLET
HOODS
OPENINGS IN
ACCESS PANEL
The outdoor and return air dampers, the damper actuator, the
damper linkage, the outdoor and return air divider baffles,
and all the control sensors are factory mounted as part of the
Factory installed economizer option.
ENTHALPY SET POINT ADJUSTMENT
Remove the economizer access panel from the unit to check
the following adjustments. Loosen but do not remove the two
panel latches.
Extreme care must be exercised in turning both
the setpoint and minimum position adjusting
screws to prevent twisting them off.
1.The enthalpy set pointmay now be set by selecting the
desired s etpoint shown in Figure 9. Adjust as follows:
•For a single enthalpy operation, carefully turn the set
point adjusting screw to the A, B, C or D setting corresponding to the lettered curve.
•For a dual enthalpy operation,carefully turn the set point
adjusting screw fully clockwise past the D setting.
2.To check that thedamper blades move smoothly without
binding, carefully turn theminimum positionadjusting
screw fully clockwise and then energize andde-energize
terminals R to G. With terminals Rto G energized,turn
the minimum positionscrew counterclockwise untilthe
desired minimum position has been attained.
3.Replacethe economizer access panel. Reposition the
two latches horizontally and retighten the screws.
COMBUSTION
IR INTAKE
HOOD
GAS HEAT
ACCESS
PANELS
POWER EXHAUST/BAROMETRIC RE LIEF DAMPER
AND RAIN HOOD OPTION
The instructions for the power exhaust/barometric relief
damper and rain hood can be found in form 44-320-10. The
exhaust fan, all supporting brackets, angles, and the wiring
FIGURE 8 : VENT AND COMBUSTION AIR
HOODS
are factory installed as part of thepower exhaust option.
All of the components, including the dampers, hardware, and
mounting instructions are shipped in a single package exter-
OPTIONAL ECONOMIZER/MOTORIZED DAMPER
RAIN HOOD
The instruction for the optional economizer/motorized
nal from the unit. The hood must be field assembled and
installed.
Power exhaust is not available as a field installed option.
damper rain hood can be found in form 44-320-2. Use these
instructions when field assembling an economizer rain hood
onto a unit.
Unitary Products11
Page 12
035-17233-000-C-0702
FIGURE 9 : ENTHALPY SETPOINT ADJUSTMENT
12Unitary Products
Page 13
035-17233-000-C-0702
TABLE 6: PHYSICAL DATA
MODELS
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
(Two Per Unit)
CONDENSER
COILS
(Two Per Unit)
COMPRESSOR
(Qty.Per Unit)
AIR
FILTERS
CHARGE
BASIC
UNIT
OPTIONS
ACCY.
1
This compressor will be energized first.
Centrifugal Blower (Dia. x Wd. in.)
Fan Motor HP
Rows Deep
Fins Per Inch
Face Area (Sq. Ft.
Propeller Dia. (in.)(Each)
Fan Motor Hp (Each)
Nom. CFM (Each)
Rows Deep (Each)
Fins PerInch (Each)
Face Area (Sq.Ft.) (Total)
10-Ton Tandem Hermetic Recip.
5-Ton Hermetic Recip.
Quantity Per Unit (16” X 20” X 2”)
Quantity Per Unit (16” X 25” X 2”)
Quantity Per Unit (18” X 24” X 2”)
TotalFaceArea(sq.ft.)
Refrigerant 22
(lbs./oz.)
DHG
(Gas/Electric)
Economizer (lbs)160
Economizer with
Power E xhaust (lbs)
Motorized Damper (lbs)150
Roof Curb (lbs)175185
Barometric Damper (lbs)4545
Wood Skid (lbs)220220
DHG
180240
15 x 15 18 x15
57.5
44
13.513.5
15.520.0
3030
11
57657000
33
1315
36.043.3
1
1
1-
-4
-4
5-
15.020.0
System #1
System #2
240Mbh (lbs)21002300
320Mbh (lbs)21402340
29/923
14/823/12
2
245
TABLE 7: DHG VOLTAGE LIMITATIONS
POWER SUPPLY
208/230-3-60
460-3-60
575-3-60
1
Utilization Range “A” in accordance with ARI Standard
MIN.MAX.
187253
414506
518506
110.
VOLTAGE
TABLE 8: MINIMUM CLEARANCES
LOCATIONCLEARANCE
Front
Back
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit
Above Unit
1
Units may be installed on combustible floors made
1
2
from woodor class A, B, or C roof covering material.
2
Units must be installedoutdoors. Overhanging structures orshrubs should not obstruct condenser air discharge outlet.
Although these sizes are based on copper conductors aluminum wire can be used. Refer to the national electriccode (inUSA) or
#1#2
RLALRARLALRA
MOTORS
(#1 & #2)
HP
(ea.)
FLA
(ea.)
the currentCanadian Electrical Code (in Canada) to determine the proper size.
Unitary Products13
SUPPLY AIR
BLOWER
MOTOR
HPFLA
MIN.
CIRCUIT
AMPACITY
(AMPS)
MAX. TIME
DELAYFUSE
SIZE (AMPS)
1
MIN.
WIRE
SIZE 75°C
Page 14
035-17233-000-C-0702
R
R
BLOWER
BLOWER MOTOR
ACCESS
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)
DOT PLUG
(For pressure
Drop Reading)
GAS HEAT
ACCESS
VENT AIR
OUTLET
HOODS
COMBUSTION
AIR INLET
HOOD
(C)
GAS SUPPLY
ENTRY
ACCESS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
125-1/4" (15 Ton)
136-1/4" (20 Ton)
CONTROL BOX
ACCESS
FRONT
VIEW
UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
(D)
GAS SUPPLY
ENTRY
6-3/8"
24-1/4" (15 Ton)
35-1/4" (20 Ton)
35"
11-1/8"
46-5/8"
21"
5"
7-1/8"
9-3/4"
5-7/8"
46-5/8"
RETURN
AIR
33"
2-3/4" 21-1/2"
12-1/2"
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
92"
11-1/2"
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
SUPPLY
AIR
8-1/8"
9-1/4"
9-3/4"
COMPRESSOR
ACCESS
OPTIONAL COIL
GUARD KIT
48-5/8" (15 Ton)
52-5/8" (20 Ton)
CONDENSER
COILS
(A)
CONTROL WIRING
ENTRY
(B)
POWER WIRING
ENTRY
3-3/4"
(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY
RETURN AIR
SUPPLY AIR
OUTDOOR AI
OUTDOOR AI
(Economizer)
All dimensions are in inches. They are
subject tochange without notice. Certified dimensionswill be provided upon
request.
FIGURE 10 : UNIT DIMENSIONS DHG180 & 240 (FRONT VIEW)
E C O N O M I Z E R
P O W E R
E X H A U S T
S U P P L Y A I R
C O M P A R T M E N T
R A I N
H O O D
R e t u r n A i r C o m p a r t m e n t )
( o n
R E A R V I E W
FIGURE 11 : UNIT DIMENSIONS DHE/DHG180 & 240 (RAINHOOD)
M O T O R I Z E D
D A M P E R
R A I N H O O D
( o n O u t d o o r A i r C o m p a r t m e n t )
3 6 "
6 6 - 1 / 2 "
E C O N O M I Z E R
P O W E R E X H A U S T R A I N H O O D S
A N D
3 4 - 1 / 4 "
5 "
2 "
3 6 - 1 / 4 "
D E T A I L " Y "
U N I T W I T H R A I N H O O D S
1 6 - 1 / 8 "
M O T O R I Z E D D A M P E R
/
F I X E D
O U T D O O R
I N T A K E
( l o c a t e d o n
R e t u r n A i r
C o m p a r t m e n t )
H O O D
A I R
L H V I E W
1 " C O N D E N S T A T E
D R A I N
( M u s t b e t r a p p e d )
9 2 "
14Unitary Products
Page 15
035-17233-000-C-0702
G A U G E L I N E
A C C E S S
C O M P R E S S O R
A C C E S S
C O N D E N S E R S E C T I O N
4 0 - 3 / 8 "
5 - 1 / 2 "
S U P P L Y A I R
A C C E S S
S U P P L Y
A I R
1 8 - 5 / 8 "
R E T U R N
A I R
O U T D O O R
A I R
R E A R
V I E W
2 7 - 3 / 4 "
R E T U R N A I R
A C C E S S
5 - 1 / 8 "
2 8 - 5 / 8 " ( 1 5 T o n s )
3 9 - 5 / 8 " ( 2 0 T o n s )
FIGURE 12 : UNIT DIMENSIONS DHE/DHG180 & 240 (REAR VIEW)
E V A P O R A T O R
S E C T I O N
4 0 - 1 / 2 "
O U T D O O R A I R
C O M P A R T M E N T
A C C E S S
D O T P L U G
( F o r p r e s s u r e
d r o p r e a d i n g )
F I L T E R
A C C E S S
1 " N P T F E M A L E
C O N D . D R A I N
C O N N E C T I O N
NOTE: A 1” clearance must be provided between any combustiblematerial and the supply air ductworkfor adistanceof
3 feet from the unit.
NOTE:
The products of combustion must not be allowedto
accumulate within a confinedspace and recirculate.
NOTE:
Locate unit so that the vent air outlet hood isat least:
•Three (3)feet above any force airinlet located within 10
horizontal feet (excluding those integral to the unit).
•Four (4) feet below, 4 horizontal feet from, or 1 foot
above anydoor or gravity air inlet into the building.
•Four (4)feet from electric andgas meters, regulators
and relief equipment
NOTE:
All entry holes should be field sealed to prevent rain
water entryinto building
Duct Covers - Units are shipped with the bottom duct open-
ings covered. An accessory flange kit is available for connectingsideducts.
For bottomduct applications:
1.Remove the side panels from the supply andreturn air
compartments.
2.Remove and discard the bottom duct covers. (Duct
openings are closed withsheet metal covers except
when the unit includes a power exhaust option. The covering consists of a heavy black paper composition.)
TABLE 10: UTILITIES ENTRY
HOLE
3.Replace the side supply and return air compartment pan-
For sideduct applications:
1.Replace the side panels on the supply and return air
2.Connect ductwork to theduct flanges on the rear of the
OPENING SIZE
(DIA.)
A
B
C
D
1
1” Gas Piping MPT Required.
2
Opening inthe bottom to the unit can be located by the
1-1/8” KO
3/4” NPS (Fem.)Bottom
3-5/8” KO
3” NPS (Fem.)Bottom
2-3/8” KO
1-11/16” Hole
Control Wiring
Power Wiring
USED FOR
Gas Piping (Front)
Gas Pipping (Bottom)
Front
Front
1
1,
side inthe insulation.
els.
compartments with the accessory flange kit panels.
unit.
2
Unitary Products15
Page 16
TABLE 11: DHG 15 TON SUPPLY AIR BLOWER PERFORMANCE
DHG180 - BOTTOM DUCT CONNECTIONS
BLOWER
SPEED,
(RPM)
MOTOR
PULLEY
(TURNS
OPEN)
45005250600067507200
4
ESP
BHPKW
3
208 VOLT AND STANDARD DRIVE
850
8705.5
9154.5
9653.5
9803.0
10102.0
10401.0
6.0
5
0.92.42.10.62.92.60.33.43.0------
1.02.52.20.73.02.70.43.53.1------
1.12.62.40.83.12.80.53.63.20.24.13.7---
1.22.72.50.93.22.90.63.73.30.44.43.90.25.04.5
1.32.92.61.03.43.00.73.83.40.54.54.00.35.14.6
1.43.02.71.13.63.20.84.03.60.64.74.20.45.44.8
1.63.22.91.33.83.41.04.43.90.85.04.50.65.65.0
1, 2
ESP
3
BHPKW
ESP
CFM
3
BHPKW
FIGURE 13 : 208 VOLT AND HIGH SPEED DRIVE ACCESSORY
9656.0
9805.5
10254.5
10653.5
11252.0
11701.0
230/460 VOLT AND STANDARD DRIVE
870
9155.0
9654.0
9803.5
10152.5
10501.5
10651.0
6.0
230/460 VOLT AND HIGH SPEED DRIVE ACCESSORY
9806.0
10454.5
10654.0
11252.5
11701.5
11901.0
1
Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filtersand a dry evaporator coil.
2
Refer to the Static Resistance table.
3
DO NOT close the pulley below one turn open.
4
ESP = External Static Pressure available for the supplyand return air duct system. All inter nal unit resistances have been
deducted from the total static pressure of the blower.
5
The factory setting.
1.22.72.50.93.22.90.63.73.30.44.43.90.25.04.5
1.32.92.61.03.43.00.73.83.40.54.54.00.35.14.6
1.43.12.81.23.63.20.94.13.70.74.84.30.45.54.9
1.63.43.01.43.93.51.14.54.00.95.14.6---
1.93.63.21.74.43.91.45.04.51.25.85.2---
2.13.93.51.94.74.21.65.54.9------
4
1.02.52.20.73.02.70.43.53.1------
1.12.62.40.83.12.80.53.63.20.24.13.7---
1.22.72.50.93.22.90.63.73.30.44.43.90.25.04.5
1.32.92.61.03.43.00.73.83.40.54.54.00.35.14.6
1.43.02.71.13.63.20.84.03.60.64.74.20.45.44.8
1.53.12.81.23.73.30.94.23.80.74.94.40.55.75.1
1.63.43.01.43.93.51.14.54.00.95.14.6---
1.32.92.61.03.43.00.73.83.40.54.54.00.35.14.6
1.63.22.91.33.83.41.04.43.90.85.04.50.65.65.0
1.73.43.01.43.93.51.14.54.00.95.14.6---
1.93.63.21.74.43.91.45.04.51.25.85.2---
2.13.93.51.84.74.21.65.54.9------
2.24.03.61.94.84.31.75.65.0------
ESP
3
BHPKW
035-17233-000-C-0702
3
BHPKW
ESP
16Unitary Products
Page 17
035-17233-000-C-0702
TABLE 12: DHG 20 TON SUPPLY AIR BLOWER PERFORMANCE
Blower performance includes a gas -fired heat exchanger, fixed outdoor air, 2” T/A filters and a dry evaporator coil.
2
Refer to the Static Resistance table.
3
DO NOT close the pulley below one turn open.
4
ESP = External Static Pressure available for the supplyand return air duct system. All inter nal unit resistances have been
deducted from the total static pressure of the blower.
5
The Factory Setting
1.74.23.61.35.14.30.86.05.10.26.95.8---
1.94.53.81.55.44.51.06.35.30.47.26.10.18.57.1
2.14.63.91.65.54.71.16.45.40.57.56.30.28.67.3
2.24.84.01.75.74.81.26.65.60.67.86.6---
2.34.94.11.85.84.91.36.75.70.78.06.7---
2.55.14.32.06.15.11.47.16.00.98.47.0---
2.65.34.42.16.35.31.57.36.21.08.67.2---
2.95.64.72.36.85.71.87.96.6------
3.15.84.92.57.05.91.98.36.9------
1, 2
ESP
4
BHPKW
ESP
CFM
4
BHPKW
ESP
4
BHPKW
ESP
4
BHPKW
Unitary Products17
Page 18
035-17233-000-C-0702
TABLE 13: STATIC RESISTANCES
DESCRIPTION
WET COIL
ECONOMIZER OPTION
HORIZONTALDUCT CONN.
1
Deduct these resistance values from the available unit ESP values listed in the respective blower per-
2
1
15 TON20 TON
450057657200600070009400
0.10.10.10.10.10.1
0.10.10.10.10.10.1
0.20.30.50.20.30.5
formance tableexcept for Horizontal Duct Connections.
2
Add thesevalues due to less airflow resistance.
TABLE 14: POWER EXHAUST PERFORMANCE
MOTOR
1
SPEED
2
HIGH
MEDIUM
LOW
1
Power exhaust motor is a 3/4 HP,PSC type with sleeve bearings, a 48 frame and inherent protection.
All motors havea nominal speed of 1800 RPM, a1.15 service factor and as olid base. They can operate tothe limit oftheir service
BLWR
RANGE
(RPM)
Std.850/1065
965/1190BK807.757.41BX68
Std.870/1025
950/1120BK11010.7510.41-3/16BX80
MOTOR
HP FRAME
5184T89.51VP565.35
7.5213T911VP686.75
EFF.
(%)
factor because they are located in the moving air, upstream of any heating device.
2
DO NOT close this pulley below 1 turn.
ADJ. MOTOR PULLEYFIXED BLOWER PULLEY
DESIGN-
NATION
O/D
(in.)
PITCH
DIA
(in.)
4.3-
5.3
5.5-
6.5
BELT
(NOTCHED)
PITCH
BORE
BORE
DESIGN-
(in.)
NATION
BK908.758.41BX70
1-1/8
2
BK12011.7511.41-3/16BX83
1-3/8
2
O/D
(in.)
DIA
(in.)
(in.)
DESIG-
NATION
PITCH
LNGTH.
(in.)
71.81
69.81
84.81
81.81
QTY.
18Unitary Products
Page 19
035-17233-000-C-0702
OPERATION
COOLING SYSTEM
The cooling section isa complete factory package utilizing an
air-cooled condenser. The system is factory-charged with
Refrigerant-22.
The compressors are hermetically sealed, internally sprung
and base-mounted withrubber-insulated hold-down bolts.
Compressorshave inherent (internal) protection. Ifthere is an
abnormal temperature rise in a compressor, the protector will
open toshut down the compressor.
PRELIMINARY OPERATION COOLING
After installation has been completed, energize the crankcase heaters for at least four hours before operating the unit.
After the initial installation, the compressors should be given
three false starts (energized just long enough to make a few
revolutions) with 5-7 minutes delay between each start,
before being put into full timeservice.
NOTE:
must be energized at least 8 hours before system is put into
operation.
COOLING SEQUENCE OF OPERATION
NO OUTDOOR AIR OPTIONS
When the room thermostat calls for first-stage cooling, the
low voltage control circuitfrom R toG and Y1 is completed to
energize compressor #1, condenser fan motor #1,condenser
fan motor #2 (if the ambient temperature is above 60F), and
the supply air blower motor (if the fan switch on the room
thermostat is set in the AUTO position).
When the thermostat calls for second-stage cooling, the low
voltage control circuit from R to Y2 is completed to energize
compressor #2.
After the thermostat is satisfied and opens, all components
will stop simultaneously. The blower motor will continue to
operate if the fan switch on the room thermostat is set in the
ON position.
ECONOMIZER WITH SINGLE ENTHALPY SENSOR
When the room thermostat calls for first-stage cooling, the
low voltage control circuit from R to G and Y1 is completed.
The R to G circuit energizes the blower motor (if the fan
switch on the room thermostat is set in the AUTO position)
and drives the economizer dampers from fully closed to their
minimum position. If the enthalpy of the outdoor air is below
thesetpointoftheenthalpycontroller(previously
determined), Y1 energizes the economizer. The dampers will
Prior to each cooling season, the crankcase heaters
modulate to maintain a c onstant supply air temperature as
monitored by the discharge air sensor. If the outdoor air
enthalpy is above the setpoint, Y1 energizes compressor #1,
condenser fan motor #1, and condenser fan motor #2 (if the
ambient temperature is above 60°F).
When the thermostat calls for second-stage cooling, the low
voltage control circuit from R to Y2 is completed. If the
enthalpy of the outdoor air is below the setpoint of the
enthalpy controller (i.e. first stage has energized the economizer), Y2 will energize compressor #1. If the outdoor air is
above thesetpoint, Y2 will energize compressor #2.
After the thermostat is satisfied and opens, all components
will stop simultaneously. The blower motor will continue to
operate if the fan switch on the room thermostat is set in the
ON position.
ECONOMIZER WITH DUAL ENTHALPY SENSORS
The operation with the dual enthalpy sensors is identical to
the single sensor except that a second enthalpy sensor is
mounted in the return air. This return air sensor allows the
economizer to choose between outdoor air and return air,
whichever has the lowest enthalpy value, to provide maximum operating efficiency.
ECONOMIZER (SINGLE OR DUAL) WITH POWER
EXHAUST
This system operates as specified above with one addition.
The power exhaust motor is energized whenever the economizer ischosen by the enthalpy sensor for first stage cooling,
Y1. As always, the R to G connection provides minimum
position but does not provide power exhaust operation.
MOTORIZED OUTDOOR AIR DAMPERS
This system operation is the same as the units with no outdoor air options with oneexception. When theR toG circuitis
complete,themotorizeddamperdrivesopentoapositionset
by the thumbwheel on the damper motor. When the R to G
circuit isopened, the damper spring returns fullyclosed.
CONTINUOUS BLOWER
Continuousblower operationis possible by closing the R toG
circuit on the thermostat.
SAFETY CONTROLS
1.A Suction LineFreezestat toprotect against low evaporator temperatures dueto a low air flow or a low return
air temperature. (Opens at26°F + 5°Fand resets at38°F
+ 5°F)
2.A High Pressure Cutout Switch to protect againstexcessive discharge pressures due to a blockedcondenser
coil ora condenser motor failure. (Opens at 380 psig +
10 and resets at 300 psig +10)
Unitary Products19
Page 20
035-17233-000-C-0702
3.A Low Pressure Switch/Loss Of Charge to protect
against loss of refrigerant charge. (Opens at 7 psig + 3
andresetsat22psig+5)
If either one of the above safety controls opens, that individual refrigerant system will be locked out.The otherrefrigerant
system will continue in operation unless it too is effected by
the same fault. The lock out of either system can be reset by
opening the 24V circuit eitherat the room thermostator atthe
unit disconnect.
HEATING SYSTEM
The following sequence describes the operation of the gas
heat section.
CONTINUOUS BLOWER
With the room thermostat switch set to ON, the supply air
blower will operatecontinuously. Thenormally closedcontact
K5-1 provides 24volt power to the M3 contactor.The M3-1, 2
& 3 power contactsclose and the blowermotor operates.
INTERMITTENT BLOWER
With the room thermostat system switch set to the AUTO or
HEAT position and the fan switch set to AUTO, the supply air
blower will operate after the room thermostat calls for heat
and the time delay relay closes.
The TH1 closes, the heat relay RW1 is energized. The RW11 power contact closes energizing the line voltage draft
motor. The RW1-2 contactis also closed. As the speed of the
draft motor reachesapproximately 2500 RPM, the centrifugal
switch contact located on the end of the draft motor shaft
closes topower the first stage ignitionmodule IC1.
REDUNDANT
VALVE
GAS MAIN
MAIN VALVE
Gas flows into each of the main burners and is ignited from
the carryovertube flame.
If IC1 fails to detect a pilot flame, it will continue to try for a
maximum of 85 seconds to ignite the pilot tube. If the pilot
flame isnot detected, thenIC1 will lock out first stage furnace
operation until 24V power is removed from the module either
at the unit or by resetting the room thermostat.
At the same time power was supplied to the RW1, a parallel
circuit activates ETD which closes the ETD contact after
approximately 35 seconds and energizes K5 which closes
K5-2 and starts the blower by energizingM3.
When TH2 closes, heat relay RW2 is energized. The RW2-1
contact is closed energizing thesecond stage ignition module
IC2. IC2will immediatelystart the second stage ignitor sparking and will open the redundant valve located inside the second stage main gas valve GV2 to allow a flow of gas to the
second stage carryover tube. See Figure 11. Only after the
pilot flame has been ignited and the presence of pilot flame
detected at IC2 by a signal sent back through the flame sensor is sparking terminatedand the main gas valve opened.
Gas flows into each of the second stage main burners and is
ignited fromthe carryover tube flame.
If IC2 fails to detect a pilot flame, it will continue to try for a
maximum of 85 seconds to ignite the pilot tube. If the pilot
flame isnot detected, thenIC2 will lock out first stage furnace
operation until 24V power is removed from the module either
at the unit or by resetting the room thermostat. Note that the
second stage furnace can operate even if first stage has
locked out.
When the heating cycle is complete, TH2 opens de-energizing the RW2 then TH1 opens de-energizing RW1 and ETD,
thus closing all gas valves. The blower motor will continue to
run (approximately 45 seconds after the furnace is shut
down) until ETD opens, de-energizing the K5 relay and M3
contactor.
SAFETY CONTROLS
GAS
VALVE
TO PILOT BURNER
FIGURE 14 : GAS VALVE PIPING
Ignition module IC1 will immediately start the first stage ignitor sparking and will open the redundant valve located inside
the first stage main gas valve GV1 to allow a flow of gas to
only the first stage carryover tube. See Figure 14. Only after
the pilot flame has been ignited and the presence of pilot
flame detected at the IC1 by a signal sent back through the
flame sensor is sparking terminated and the first stage main
gas valveopened.
TO MAIN
BURNER
The controlcircuit includesthe following safety controls:
1.Limit Control (LS). Thiscontrol is located inside the heat
exchanger compartment and is set to open at the temperature indicated inTable 16.It resets automatically.
The limitswitch operates when a high temperature condition, caused byinadequate supply airflow occurs, thus
shutting down the ignition control and closing the main
gas valves and energizing the blower.
2.CentrifugalSwitch (CS).If thedraft motor should fail, the
centrifugal switch attached to the shaft of the motorprevents the ignition controls and gas valves from being
energized.
20Unitary Products
Page 21
035-17233-000-C-0702
TABLE 16: LIMIT CONTROL SETTING
I G N . C O N T R O L # 2
I G N . C O N T R O L # 1
R O L L O U T S W .
S E N S O R # 1
I G N I T O R # 2
G V 2
G A S
V A L V E
G V 1
G A S
V A L V E
I G N I T O R # 1
S E N S O R # 2
B U R N E R C O M P A R T M E N T
FIGURE 15 : GAS VALVE AND CONTROLS
3.Redundant Gas Valve - There are twoseparate gas
valves in the furnace. Each valvecontains a main and a
redundant valve. The redundantvalves are located
upstream of the main gas valves. Should either or both
of the main gas valves fail in the open position theredundant valves serve as back-ups and shuts off the flow of
gas.
4.Flame Sensor Rod / 100% Ignition Control Lock-Out The flame rods and controls are located per Figure 15. If
an ignitioncontrol fails to detect a signal from the flame
sensor indicating the pilotflame is properly ignited,then
the maingas valve will not open. It will continue to try
and ignite the pilot for amaximum of 85 seconds, then if
the pilotflame is not detected, the ignition control will
lock outfurnace operationuntil 24V power is removed
from themodule either at the unit or by resetting the
room thermostat.
Units
(Tons)
15 & 20300240195
15 & 20400320195
Capacity, M BH
InputOutput
Limit
Control
Opens, °F
HEAT ANTICIPATOR SETPOINTS
It is important that the anticipator setpoint be correct. Too
high ofa setting will result in longer heat cycles and a greater
temperature swing in the conditioned space. Reducing the
value below the correct setpoint will give shorter ON cycles
and may result in the lowering of the temperature within the
conditioned space.
TABLE 17: HEAT ANTICIPATOR SETPOINT
Gas Valve1st Stage2nd Stage
Honeywell VR8440
White-Rodgers 36C68
0.30 amp0.11 amp
START UP
PRE-START CHECK LIST
Complete thefollowing checksbefore starting the unit.
1.Check the type of gas being supplied. Be sure that it is
the same as listed onthe unit nameplate.
2.Make sure that the vent and combustion airhoods have
been properly installed.
OPERATING INSTRUCTIONS
5.Rollout Switch - Thisswitch is located above themain
burners in the control compartment which in the event of
a sustained main burner rollout shuts off and locks out
both ignition controls closing both gas valves. The ignition controls lock out furnace operation until24V power
is removed from the controls either at the unit or by
This furnace is equipped with an intermittent pilot
and automatic re-ignitionsystem. DO NOT attempt
to manually light the pilot.
resettingthe roomthermostat. Note theauto reset rollout
switch must reset before allowing furnace operation.
6.Auxiliary limit switch (AUX) - This control is located
inside theheat exchangercompartment and is set to
open at190F. It is a manual reset switch. If AUX limit
trips, then the primary limit hasnot functioned correctly.
TO LIGHT PILOT AND MAIN BURNERS:
1.Turn off electric power to unit.
2.Turn room thermostat to lowest setting.
3.Turn gas valve knob to on position.
Replace the primary limit switch.
4.Turn on electric power to unit.
Unitary Products21
Page 22
035-17233-000-C-0702
5.Set room thermostat to desired temperature.(If thermostat set temperature is above room temperature, pilot
burner ignition willoccur and, after an intervalto prove
pilot flame, main burners will ignite).
TO SHUT DOWN:
1.Turn off electric power to unit.
2.Depressknob of gasvalve while turning to offposition.
POST-START CHECK LIST (GAS)
After the entire control circuit has been energized and the
heating section is operating,make the following checks:
1.Check for gas leaksin the unit piping as well asthe supply piping.
2.Checkfor correct manifold gas pressures.See Checking
Gas Input.
3.Check the supply gas pressure. Itmust be within the limits s hown on rating nameplate. Supply pressure should
be checked with all gas appliances inthe building at full
fire. At no time should the standby gas line pressure
exceed 13", nor the operating pressure dropbelow 5.0"
for natural gas units. If gaspressure is outside these limits, contact the local gas utilityfor corrective action.
MANIFOLD GAS PRESSURE ADJUSTMENT
Adjust as follows:
1.Remove the cap on the regulator. It's located next tothe
push-on electrical terminals.
2.To decrease the gas pressure, turn the adjusting screw
counterclockwise.
3.To increase the gas pressure, turn the adjustingscrew
clockwise.
The correct manifold pressure for these furnaces is
NOTE:
3.5 IWG0.3.
PILOT CHECKOUT
The pilot flame should envelope the end of the flame sensor.
Refer to Figure 16. To adjust pilot flame, (1) remove pilot
adjustment cover screw, (2) increase or decrease the clearance for air to the desired level, (3) be sure to replace cover
screw after adjustment to prevent possible gas leakage.
Put the system into operation and observe through complete
cycle to be sure all controls function properly.
B U R N E R A S S E M B L Y B R A C K E T
F L A M E S E N S O R B U L B
Small adjustments to the high-fire gas flow may be made by
turning the pressure regulator adjusting screw on the automatic gasvalve. Refer to Figure 16.
On-Off Control
Pilot Adj.
(Under Screw)
High F ire Adj.
(Under Screw)
FIGURE 16 : TYPICAL GAS VALVE
1 / 8 " G A P B E T W E E N C A R R Y - O V E R
T U B E A N D F L A M E S E N S O R B U L B
C A R R Y - O V E R T U B E
FIGURE 17 : PROPER FLAME ADJUSTMENT
BURNER INSTRUCTIONS
To check or change burners, pilot or orifices, CLOSE MAIN
MANUAL SHUT-OFF VAL VE AND SHUT OFF ALL ELECTRIC POWER TO THE UNIT.
1.Removethe screwsholding either endof themanifold to
the burner supports.
2.Open the union fitting in the gassupply line just
upstreamof the unit gas valve and downstream fromthe
main manual shut-off valve.
3.Remove the gas piping closurepanel.
4.Disconnect wiring to the gas valves and spark ignitors.
Remove the manifold-burner gasvalve assemblyby lifting up and pulling back.
Burners are now accessible for service.
22Unitary Products
Page 23
035-17233-000-C-0702
Reverse the above procedure to replace the assemblies.
Make sure that burners are level and seat at the rear of the
heat exchanger.
BURNER AIR SHUTTER ADJUSTMENT
Adjust burner shutters so no yellow flame is observed in the
heat exchanger tubes. Refer to Figure 17.
CHECKING SUPPLY AIR CFM
The RPMof the supply airblower will depend on therequired
CFM, the unit accessories or options and the static resistances of both the supply and the return air duct systems.
With this information, the RPM for the supply air blower and
the motor pulley adjustment (turns open) can be determined
from theblower performance data in Tables 11 and 12.
High speed drive accessories (containing a smaller blower
pulley and a shorterbelt) are available for applications requiring the supply air blower to produce higher CFM's and/or
higher static pressures. Use Model 1LD0416 for 15 ton units
and Model 1LD0417 for 20 ton units. Refer to Table 15 for
1.The supply air CFM must be within the limitations shown
in Table 2.
2. Pulleyscanbeadjustedinhalfturnincrements.
3.The tension on the belt should be adjusted as shown in
Figure 19.
Start the supply air blower motor. Adjust the resistances in
both the supply and the return air duct systems to balance
the air distribution throughout the conditioned space. The job
specifications may require that this balancing be done by
someone other than the equipment installer.
To check the supply air CFM after the initial balancing has
been completed:
1.Remove the two 5/16"dot plugs from the blower motor
and thefilter access panels shown in Figure 10.
FIGURE 19 : BELT ADJUSTMENT
2.Insert at least 8" of 1/4 inch tubing into eachof these
holes forsufficient penetration intothe air flowon both
sides ofthe indoor coil.
NOTE:
The tubes must be insertedand heldin aposition perpendicular to the air flow so that velocity pressure will not
affect the static pressure readings.
3.Using an inclined manometer,determine the pressure
drop across a dry evaporator coil. Since the moisture on
an evaporator coil may vary greatly, measuring the pressure dropacross a wetcoil under field conditions would
be inaccurate. To assure a dry coil, the compressors
should be deactivated while the test is beingrun.
4.Knowing the pressure dropacross a drycoil, the actual
CFM through the unit and clean 2" filters, can be determined fromthe curve in Figure 20.
After readings have been obtained, remove the tubes and
reinstall the two 5/16" dot plugs thatwere removed in Step 1.
Failure to properly adjust thetotal systemair quantity canresult in extensive blower damage.
NOTE:
De-energize the compressors before taking any test
measurements to assure a dry indoor coil.
Unitary Products23
Page 24
035-17233-000-C-0702
2.Withthe furnace turned on,measure the timeneeded for
one revolution ofthe hand onthe smallest dial on the
meter. A typical gas meter usually has a 1/2 or a 1 cubic
foot testdial.
3.Usingthe number of secondsfor each revolutionand the
size ofthe test dialincrement, find the cubic feetof gas
consumed per hour from Table18.
If the actual input is not within 5% of the furnace rating (with
allowance being made for the permissible range of the regulator setting), replace the orifice spuds with spuds of the
proper size.
To find the Btu input, multiply the number of cubic feet
NOTE:
of gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)
FIGURE 20 : PRESSURE DROP ACROSS A DRY
INDOOR COIL VS. SUPPLY AIR CFM
ADJUSTMENT OF TEMPERATURE RISE
The temperature rise (or temperature difference between the
return air and the heated air from the furnace) must lie within
the range shown on the ETL ratingplate andthe data in Table
2.
After the temperature rise has been determined, the cfm can
be calculated as follows:
BtuhbInput0.8×
CFM
After about 20 minutes of operation, determine the furnace
temperature rise. Take readings of both the return airand the
heated air in the ducts(about sixfeet fromthe furnace) where
they will not be affected by radiant heat. Increase the blower
cfm to decrease the temperature rise; decrease the blower
cfm to increase the rise. Refer to Table 11 for blower motor
and drive data.
BELT DRIVE BLOWER
All units have belt drive single-speed blower motors. The variable pitch pulley on the blower motor can be adjusted to
obtain the desired supply air CFM. Tighten belts enough to
prevent slipping. but do not over tighten. Belt deflection
should be between 1/4" and 1/2" per foot. Refer to Table 15
for blower motor and drive data.
Example: By actual measurement, it takes 13 seconds
for the hand on the 1-cubic foot dial to make a rev olution with just a 300,000 Btuh furnace running. Read
across to the column in the table above, headed “1
Cubic Foot”,where you will see that 278 cubic feet of
gas per hourare consumed bythe furnace atthat rate.
Multiply 278 X 1050 (the Btu rating of the gasobtained
from the local gas company). The result is 292,425
Btuh, which is close to the 3000,000 Btuh rating of the
furnace.
SIZE OF TESTDIAL
1/2 Cu. Ft.1 Cu. Ft.
SECURE OWNER’S APPROVAL
1
CHECKING GAS INPUT
NATURAL GAS
1.Turn off all other gas appliances connected to the gas
meter.
When system is functioning properly, secure the owner’s
approval. Show him the location of all disconnect switches
and the thermostat. Teach him how to start and stop the unit
and how to adjust temperature settings within the limitations
of the system.
24Unitary Products
Page 25
035-17233-000-C-0702
MAINTENANCE
NORMAL MAINTENANCE
Prior to any of the following maintenance procedures, shut off all electric power to the unit to prevent personal injury.
Periodic maintenance normally consists of changing or cleaning filters and (under some conditions) cleaning the main
burners
FILTERS
Inspect once a month. Replace disposable or clean permanent type as necessary. DO NOT replace permanent type
with disposable. The dimensional size of the replacement filter mustbe the same as the replaced filter.
MOTORS
Outdoor fan motors are permanently lubricated and require
no maintenance.
If desired, every three years remove both pipe plugs at each
end shell and clean out any hardened grease or foreign matter.Replace one plug on each end with a cleangrease fitting.
Using a low pressure grease gun, pump grease (Chevron
SRI-2 or equivalent) into the bearing cavity until new grease
shows at the open port. Do not over lubricate. Run the motor
for ten minutes until excess grease is purged from the cavity.
Replace the plugs.
On 20 ton only, units are supplied with blower shaft bearings
that do not require maintenance but may be relubricated if
desired. Every three years, using a low pressure grease gun,
pump grease into the bearing grease fitting until grease just
begins to show at the seals. Do not over lubricate. Use any
lithium base grease recommended for ball bearing service.
OUTDOOR COIL
Dirt should not be allowed to accumulate on the outdoor coil
surface or other parts in the air circuit. Cleaning should be as
often as necessary to keep coil clean. Use a brush, vacuum
cleaner attachment, or other suitable means. If water is used
to clean coil, be sure electric power to the unit is shut off prior
to cleaning.
Exercise care when cleaning the coil so that the coil
NOTE:
fins arenot damaged.
Ventor motor is factory lubricated for an estimated 10 year
life.
Indoor Blower Motorand Drive- Theindoor blower motor features ball bearings that do not require periodic lubrication.
Periodic lubrication of the motor and bearings can extend the
life of components butis optional.
Damage can occur if the bearings are overlubricated. Use grease sparingly.
Perform all maintenance operations on the blower
motor with electric power disconnected from the
unit. Do not attempt to lubricate bearings with the
unit inoperation.
On an annual basis, check the motor for accumulations of
dust, etc. that may block the cooling slots in the motor shell.
Check for loose, damaged or misaligned drive components.
Check that all mounting bolts are tight. Replace defective
parts as required.
Do not permit the hot condenser air discharge to be
NOTE:
obstructed by overhanging structures of shrubs.
BURNER & PILOT
Periodically (at least annually at the beginning of each heating season) make a visual check of the pilot and main burner
flame. If necessary, adjust mainburner primaryair shutters to
give adistinct, sharp blueflame as explained underBURNER
AIR SHUTTER ADJUSTMENT. If it is not possible to adjust
for the proper flame, the burners may need cleaning.
TO CLEAN BURNERS
Remove them from the furnace as explained in Burner
Instructions. Clean burners with hot water applied along top
of the burner.
COMBUSTION AIR DISCHARGE
Visually inspect discharge outlet periodically to make sure
that the buildup of soot and dirt isnot excessive. Ifnecessary,
clean tomaintain adequate combustion air discharge.
CLEANING FLUE PASSAGES AND HEATING ELEMENTS
With proper combustion adjustment the heating element of a
gas fired furnace will seldom need cleaning. If the element
should become sooted, itcan be cleaned as follows:
Unitary Products25
Page 26
1.Remove the burner assembly as outlined in BURNER
INSTRUCTIONS.
2.Remove the roof over the gas heatsection.
3.Atthe topplate from thetop draftblower housingand the
top draftblower wheel.
4.Remove the screws holding thetop of the flue collector
box. Carefully removethe top of the flue collector box
without ripping the adjacentinsulation. Then removethe
center divider plateseparating the upper and lowerflue
boxes.
5.On the insideof the fluecollector box, remove the flue
baffles from the tube interiors. Note the last bend of the
baffle fits tightly against the tube forcing the endof the
baffle to lock into the tube collar. This collar isformed
when the tube is expanded into the end sheet. To
remove, move the end of the baffle toward the center of
the tubereleasing theend of the baffle from the tube collar,then pull straight out of the tube. Referto Figure 20.
6.Using a wire brush on a flexible wand, brush out the
inside of each heat exchanger from the burner inlet and
flue outlet ends.
7.Brush out the inside of theflue collectorbox andthe flue
baffles.
035-17233-000-C-0702
FIGURE 21 : TYPICAL FLUE BAFFLE INSTALLA-
TION
TROUBLESHOOTING
Label all wires prior to disconnection when servicing controls. Wiring errors cancause improperand
dangerous operation. Verify proper operation after
servicing.
8.Run the wire brush down the vent hoods from the flue
collector end.
9.Ifsoot build-up is particularly bad, removethe vent motor
and cleanthe wheel and housings. Run the wire brush
down theflue extensionsat the outlet of the vent housings.
10. Afterbrushing is complete, blow all brushed areas with
air or nitrogen. Vacuum as needed.
11. Replace parts in the orderthey were removed in Steps 1
through 4.
12. When replacing the center and topof the flue collector
box, be careful not to tear the adjoining insulation.
13. Ensurethat all seamson thevent side ofthe combustion
system are air tight. Apply a high temperature (+500°F)
sealing compound where needed.
Troubleshootingofcomponentsnecessarily
requires opening the electrical control box with the
power connected to the unit. Use extreme care
when working with live circuits! Check the unit
nameplate for the correct line voltage and set the
volt meter to the correct range before making any
connections with line terminals.
Prior to any of the following maintenance procedures, shut off all electric power to the unit to prevent personal injury.
NOTE: To find the Btu input, multiply thenumber ofcubic feet
of gas consumed per hour by the Btu content of the gas in
your particular locality (contact your gas company for this
information - it varies widely from city to city.)
26Unitary Products
Page 27
035-17233-000-C-0702
1.The indoor blower motor is a non-inherently protected
three-phasemotor.Protectionis provided by anoverload
relay forovercurrent and fuses for short circuit. If the
motor fails to run, check the line voltagecircuit and control voltage circuitper the following procedure:
a.If the Indoor Blower Motor does not operate, check
visually that contactor M3 is pulled in. If so, check
for line voltage between all three phases at the line
terminals of the Blower Overload Relay (BOR). If
line voltage is found, check the leads to the blower
motor for open circuit. If line voltage is found at the
motor leads (inside the conduit box on the motor
shell), disconnect the motor and check for open
windings per the motor wiring diagram. Ifopen windings are found, replace the motor. If line voltage is
not found at the BOR, trace the leads back to the
field supply terminal block, checking for an open circuit or blown fuses.
b.If the contactor M3 is not pulled in, check for control
voltage (24V) at the M3 coil. If voltage is found,
replace the contactor. If control voltage is not found
at M3, check for voltage across terminals 95 & 96 of
the BOR.If voltage exists, the BOR is openon overload. The BOR should be set to the auto reset position. The BOR must cool down in order to reset. If
theBORwillnotreset,replacetheBOR.IftheBOR
resets and M3 pulls in, but the indoor blower motor
will still not run, refer to para. (a) for troubleshooting
the line voltage supply circuit. If control voltage is
not found at the BOR, trace the circuit back to the
relay board and thermostat per the unit wiring diagram. Replace anydefective components.
2.Draft motor operates and furnace lights but supply air
blower does not start after a short timedelay with room
thermostat fan switch set to AUTO.
a.Set fan switch to ON. If blower motor runs, go to
Step f. If it does not, check to see if line voltage is
being supplied to the contacts of the contactor (M3),
and if the contactor is pulled in. Check for loose wiring.
b.If contactor (M3) is pulled in, proceed with the trou-
bleshooting steps indicated in Step 1 above.
c.If (M3) is pulled in and the blower motor still does
not run, replace the blower motor.
d.If (M3) is not pulled in, check for 24 volts at the (M3)
coil. If 24 volts is present, replace the (M3) contactor.
e.If 24 volts is not present at the (M3) coil, check for
loose 24 volt wiring back to the relay board. Check
control wiring to the room thermostat. If all is fine,
replace therelay board.
f.If the blower motor runs with the fan switch in the
ON position but does not run soon after the furnace
has ignited withthe fan switch in the AUTO position,
check for loose 24 volt wiring between the relay
board in the main control box, the Mate-N-Lok connector in the partition between the evaporator and
gas heatsections and the time delayrelay (ETD).
g.If all control wiring is fine, check for 24 volts at the
relay board. If 24 volts is present, replace the relay
board. If 24 volts is not present, replace the (ETD)
relay.
The furnace may s hut itself down on a high tempera-
NOTE:
ture condition during the procedure, but this will not effect the
test if it is donewithin 5 minutes of furnace shut-down.
3.The supply air bloweroperates but the draft motordoes
not when the room thermostat is set to call for heat and
the fan switch in the ON position.
a.The draft motor has inherent protection. If the motor
shell is hot to the touch, wait for the internal overload to reset.
b.If the m otor shell is cold with the room thermostat
calling for heat, check for line voltage at the motor's
Mate-N-Lok connector attached to the evaporator
partition. If line voltage is present, replace the draft
motor.
c.If linevoltage isnot present, check forline voltage at
the heat relay (RW1) contacts in the main control
box andcheck to see if the (RW1) is pulled in.
d.If the (RW1) relay is pulled in, check for a loose line
voltage connection.
e.If the (RW1) relay is not pulled in, check for 24 volts
at the (RW1) coil. If 24 volts is present, replace the
(RW1) relay. If 24 volts is not present, check for a
loose 24volt connection backto the relay board and
check the connections from the room thermostat to
the relay board. If all connections are correct,
replace therelay board.
4.The draft motor runs but the furnace does not light and
the sparker doesnot spark.
a.The ignition c ontrol (IC1, IC2) may be locked out
due to either a flame roll out or 100% shut off. These
safety features are described above. If lock-out has
occurred, 24V must be removed from the ignition
controls. This is done at the unit or by resetting the
room thermostat. After resetting 24V, check for
proper furnace operation. If lock-out continues to
occur, locate the source of the problem andcorrect.
b.Check all 24 volt connections from the relay board
to and in the gas heat section. Check low voltage
connections to the (ETD) located in thecontrol box.
c.If the furnace is hot, it may be out on an over-tem-
perature condition, wait for limit reset.
Unitary Products27
Page 28
d.If the furnace is cold, check for 24 volts at wire 241
attached to the time delay relay (ETD) located in the
main control box.If 24 volts is not found,replace the
ETD relay.
e.If 24 volts is found at wire 241, remove the wires
attachedtothe(ETD)andwithaVOM,checkfor
continuity across contacts 1 and 2. If none is found,
the (ETD) is open and must be replaced. If there is
continuity, re-attach the wires.With the draft motor
running, check for 24 volts at terminal 4 of (RW1-2)
and (RW2-1). If 24 volts is not present, the centrifugal switch (CS) has not closed or has gone bad.
Check the line voltage to the unit - if it is correct,
replace the draft motor. If line voltage is low, call the
power company.
f.Check for 24V at terminal 2 of (RW1-2 and RW2-1).
If 24V is not present, check for 24V at (RW1 and
RW2) relay coils. If these relays are pulled in, then
check for a loose connectionat terminal 2and terminal 4 of each relay. If no problem is found, then
replace (RW1 and/or RW2) as required.
g.If 24 volts is present at the ignitor controls, check all
control wiring at the ignitor controls and the high tension wire to the ignitors. Check that the ground wires
from the ignitor controls, the gas valves and pilot
burners are all intact and making good electrical
connection. Check to make sure that the ceramic
insulator on the pilot ignitors or sensors is not broken or cracked, if all are intact, replace the ignition
control IC1 or IC2.
5.The draft motor runs and the sparker sparks at the pilot
burner but the pilot does notignite and agas odor is not
detected atthe draft motor outlet.
a.Check to make sure gas is being supplied to the
unit. Make sure that the gas pressure to the unit is
within the proper limits as described in the POST
START CHECK LIST and that the pilot adjust screw
is allowing some flow of gas as described in PILOT
CHECKOUT.
b.Check all wiring between the ignitor control and the
gas valve. Check to make sure the ground connections areintact.
c.If the wiring is intact, check for 24volts across termi-
nals PV and COMMON on the ignitor control. If 24
volts is not present, replace the ignitor control.
d.If 24 volts is present, remove the pilot burner and
remove the pilotorifice fromthe pilotburner. Theorifice is removed in the direction opposite the flow of
gas. Inspect the orifice for obstruction. If it is clear,
replace the main gas valve.
6.The sparker sparks at the pilot burner but the pilot does
not igniteand a gasodor is detected at the draft motor
outlet.
a.Adjust the pilot adjust screw on the gas valve as
para. 5d. Clean as needed but the problem should
not be the gas valve.
7.The pilot burner ignites but the sparker continues to
spark and the main burners donot ignite.
a.Make the same checks and adjustment as
described in para. 6.
b.Make sure that the pilot burner is not bent or dam-
aged.
c.Make sure that the ground connections at the pilot
burner, gas valve and ignitor control are intact.
Check the high tension wire for good electrical connection. If all are intact, replace the ignitor module.
8.The pilot burner lights and the spark stops but themain
burners donot light.
a.Check electrical c onnections between the ignitor
control and the gas valve. If intact, check for 24 volts
across terminals MV and COMMON terminals. If no
voltage detected, replace ignitor control. If voltage is
present, replace gas valve.
9.Furnace lights with roll-out or one burner has delayed
ignition.
a.Make sure that the pilot burner is aligned properly
with the carryover as described in PILOT CHECKOUT.
b.Make sure that the carry overs on adjoining burners
are screwed fast and are level with respect to one
another.
10. Main burners light butexhibit erratic flame characteristics.
a.Adjust air shutters as described in BURNER AIR
SHUTTER ADJUSTMENT.
b.Check the main burner orifices for obstruction and
alignment. Removal procedure is described in
BURNER INSTRUCTIONS. Clean or replace burner
orifices and burners as needed.