Energy Saving Products Hi-Velocity RCM-I Series, Hi-Velocity RCM-I-70, Hi-Velocity RCM-I-100 Installation Manual

Small Duct High Velocity Heating, Cooling and Home Comfort Systems
RCM-I Refrigerant Module
Installation Manual
For use with HVS-36 & HVS-60 Variable Speed Heat Pumps
Includes:
L-Mounting Brackets
Double Sided Mounting Tape
Carry-Over Screen
RCM-I-70 (2.5-3 Tons)
RCM-I-100 (3.5-5 Tons)
Manufactured By
Module-RCM-I-Refrigerant-Module-Installation-050519
www.hi-velocity.com
Module RCM-I
RCM-I Installation
Refrigerant Modules (RCM-I)
The RCM-I cooling coil comes as a module and must be installed in the horizontal position on the return air side of the fan coil. RCM-I modules come with two L mounting brackets, two access ports, carry-over screen and additional components for air sealing.
RCM-I modules can be used on any R-410A condenser if R-410A refrigerant components are used. All Energy Saving Products R-Series modules come standard with R-410A refrigerant components.
This module is for use with HVS-36 and HVS-60 Inverter Heat Pump Condensing Units. It does not come with thermal expansion valve, as there are internal EXVs inside the Heat Pump. When installing the RCM-I Modules, DO NOT INSTALL
WITH TXVs.
The module will come with access ports that will need to be installed to read refrigerant pressures/temperatures at the Evaporator (RCM-I). Fig. 01 shows approximate installation locations for these components.
RCM-I Modules were designed to be used with the HVS­36 and HVS-60 Heat Pumps but can be used on any R-410A Condensing Unit, as long as a TXV is installed as well. All Energy Saving Products cooling modules come standard with R-410A refrigerant components.
Mounting Brackets
Mounting the cooling coil to the fan coil can be done with the L brackets supplied (Fig. 02), ensure that no screws puncture the drain pan or coil. Page 8 has the dimensions of the cooling modules.
Fig. 02 - Mounting brackets
Fig. 01 - Coil Assembly
1) Liquid line
2) High side access port
3) Refrigerant distributor
4) Distributor tubes
4
3
7
7
5) Suction line
6) Low side access port
7) Suction line temperature port
8) Middle coil temperature port
2
6
5
Access Ports
When refrigerant lines are connected to the RCM-I coil, high and low side access ports must be connected as well. (Fig. 01 ­reference 2 & 6) With the use of a tee and reducer this process is
simplied. The access ports are required for system startup and
for future trouble shooting or service. When reading refrigerant pressures/temperatures, always read them at the evaporator
1
access ports.
Note: 7 & 8 coil temperature ports are explained in Module HVS - Heat Pump Manual
Module RCM-I - RCM-I Coil Installation (2/8)
www.hi-velocity.com
Module RCM-I
RCM-I Installation
P - Trap
The condensate drain must have a minimum 3” P-Trap
installed (Fig. 03), and run at a slope of ¼” per foot in the
direction of the drain. All RCM-I modules come with a ¾” male CPVC primary outlet and a ¾” secondary outlet. When installing the P-Trap it must be installed on the primary outlet. It is good practice to install a tee and a cap right above the P-Trap to act as a clean out, in the event of the drain line being plugged. If a vent is to be installed, it must be on the drain side of the P-Trap, and
must comply with all local building code requirements. If code requires a secondary drain line, run the secondary line using the
same method. Otherwise, having it drain into a secondary drain
pan is acceptable. If the coil is located above a nished area, a secondary drain pan must be installed. An equipment stand/riser or rubber equipment mat may be necessary to elevate the module o of the ground to allow for the P-Trap.
Secondary Drain
Vent
Clean Out
Primary Drain
Pipe Sizing
Refer to charts below and Module HVS - Variable Speed Heat Pump Manual for pipe sizing.
Piping the RCM-I
Only refrigerant grade pipe and ttings are to be used with the RCM-I Module. Plumbing ttings may contain wax or other
contaminants which are detrimental to the proper operation of the system. Insulate the suction line with a minumum of 3/8” insulation. For inverter heat pump applications, insulating both
suction and liquid lines is mandatory. In high heat areas, a
minimum of 1/2” insulation may be needed. Support the pipe every 5 feet, or whatever local code states.
Run the pipes in the most direct route possible, taking into account structural integrity, building details and local building codes. Minimum refrigerant pipe length is 16ft (6m). If going less than 16 ft, coil the additional copper pipe up in horizontal loops to ensure proper oil return. If the evaporator is located above the condenser, slope any horizontal runs toward the condenser. If the condenser is located above the evaporator, a P-trap must be installed at the bottom of the vertical riser. For long vertical risers, additional P-traps must be installed for every twenty feet. Lines running over 213’ (65m) are not recommended.
Secondary Drain Pan
Table 02 - Minimum pipe sizes (up to 98’), factory charge and additional refrigerant required
P-Trap
Important: Return Air must be ltered
before entering the cooling module.
Fig. 03 - P-Trap, Secondary Drain Pan
Pipe Sizing
Table 01 - Minimum pipe sizes, maximum length and maximum lift
Model Liquid Line Suction Line Maximum Length Maximum Lift
HVS-36 3/8” (9.5 mm) 5/8” (15.9 mm) 213.25’ (65 m) 98.4’ (30 m)
HVS-60 3/8” (9.5 mm) 3/4” (19 mm) 213.25’ (65 m) 98.4’ (30 m)
The HVS Variable Speed Heat Pump comes with a factory charge. Additional charge will only be needed on line sets longer than 49 ft. (See Table 02 below)
Add extra refrigerant
Model Liquid Line Suction Line Factory Charge (kg)
HVS-36 3/8” (9.5 mm) 5/8” (15.9 mm) 6.75 lbs (3.06 kg) 1 oz/ 3.3 ft
HVS-60 3/8” (9.5 mm) 3/4” (19 mm) 10.15 lbs (4.6 kg) 1 oz/ 3.3 ft
for line sets
over 49 ft (15 m)
Module RCM-I - RCM-I Coil Installation (3/8)
Loading...
+ 5 hidden pages